Advent XT Warden Call FIRE ALARM TONE NOT OPERATING ON ADVENT XT SYSTEM Is Fire Alarm Tone issue from ALL Speech Units or only on MINORITY? FIRE ALARM ISSUE ON MINORITY/1-3 UNITS Check Voltages are greater than 18v in Quiescent State & during audio on Intercom Units THEN Check PA1 & PA2 connection on Intercom Units are secure/ok THEN PA2 PA1 24v 0v

Upload: others

Post on 10-Feb-2022

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Addvveenntt eXXTT lWWaarrddenn CCaalll

AAddvveenntt XXTT WWaarrddeenn CCaallll

FFIIRREE AALLAARRMM TTOONNEE NNOOTT OOPPEERRAATTIINNGG OONN AADDVVEENNTT XXTT SSYYSSTTEEMM

Is Fire Alarm Tone issue from ALL Speech Units or only on MINORITY?

FFIIRREE AALLAARRMM IISSSSUUEE OONN MMIINNOORRIITTYY//11--33 UUNNIITTSS Check Voltages are greater than 18v in Quiescent State & during audio on Intercom Units

THEN Check PA1 & PA2 connection on Intercom Units are secure/ok

THEN

PA2

PA1

24v 0v

Page 2: Addvveenntt eXXTT lWWaarrddenn CCaalll

Are problematic Intercom’s ZXT205 model type (Intercom Speech Unit + PA)?

(ZXT205 Advent XT Intercom c/w PA)

YES continue NO replace units for ZXT205 Intercom + PA Model type Make sure A.C voltages across PA1 & PA2 on Intercoms equal voltages across Network PA1 & PA2 of that on A00381 Termination Board in quiescent state & during Fire Alarm Tone Mode

PA1 & PA2 Quiescent state = around 0v AC

PA1 & PA2 during ALL CALL Tones state = around 70-75v AC

THEN

PA1 Terminal 11

PA2 Terminal 12

PA1 Terminal 11

PA2 Terminal 12

ZXT205 Has Transformer Device Soldered onboard

Page 3: Addvveenntt eXXTT lWWaarrddenn CCaalll

Check Intercom PA, Audio & Data Cabling is using balanced pairs (examples below)

Data Cable ARE Balanced (Whi/Blu & Blu/Whi pair)

Audio Cables ARE Balanced (Whi/Grn & Grn/Whi pair)

Data Cable NOT Balanced (should be Whi/Blu & Blu/Whi pair)

Audio Cables NOT Balanced (should be Whi/Grn & Grn/Whi pair)

PA Cables ARE Balanced (Pink & Red pair)

Page 4: Addvveenntt eXXTT lWWaarrddenn CCaalll

Cable up the MINORITY of Intercoms reporting FIRE ALARM issues locally at the Advent XT CCU A00381 Termination Board individually (with all other system wiring removed) & test.

If FIRE ALARM Tone is then found to be fine, then possible wiring/device fault in Flat/Intercom location. Possible Intercom Unit Failures - Replace Speech Units for known working units

Page 5: Addvveenntt eXXTT lWWaarrddenn CCaalll

FFIIRREE AALLAARRMM IISSSSUUEE OONN AALLLL UUNNIITTSS

Is FIRE TONE enabled in system ‘General Set Up’ programming?

YES continue NO enable FIRE TONE in programming

Mimic Fire Alarm activation by placing link between IP4 of ‘Input’ Terminals on XT A00381 Termination Board and 0v?

Does FIRE ALARM TONE activate?

YES possible issue with cabling from Fire Panel or issue with Fire Panel itself. Does N/O contact on Fire Panel close on alarm? NO continue

Page 6: Addvveenntt eXXTT lWWaarrddenn CCaalll

Are all Intercom’s ZXT205 model type (Intercom Speech Unit + PA)?

(ZXT205 Advent XT Intercom c/w PA)

YES continue NO replace for ZXT205 Intercom + PA Model type

Are system Network PA1 & PA2 cabling from Main CCU occupying Terminals 11 & 12 in all Intercom’s?

YES continue NO terminate PA1 & PA2 cables as instructed in manual

ZXT205 Has Transformer Device Soldered onboard

A00381 Main CCU Termination Board

Intercom Termination Board

Page 7: Addvveenntt eXXTT lWWaarrddenn CCaalll

What is the Total Number of PA Intercom Units that are installed on the system Network? <80 Units continue >=80 Units 1 x ZXT155 All Call Amp/PSU should be installed for every 80 x ZXT205 PA Intercom Units on system. Check that correct number of ZXT155 All Call Amp/PSU’s are installed to allow total number of ZXT205 PA Intercom Units to operate during Fire Alarm.

If you Cable up a PA Model Intercom locally at the Advent XT CCU A00381 Termination Board individually (with all other system wiring removed), does FIRE ALARM TONE work when tested?

YES possible problem on system Network cabling or Network Devices (Data, Audio, Power). Possible that cabling or some Network devices are dragging down system audio. Break down system Network Leg cabling one at a time until audio issue is found/resolved. NO continue.

Page 8: Addvveenntt eXXTT lWWaarrddenn CCaalll

During FIRE ALARM Tone mode is 70-75vAC present across Terminal 11 (PA1) & Terminal 12 (PA2) on Intercom Units?

NO continue YES possible issue with Devices/Units/Cabling/Power on Network Break down system Network leg cabling individually, until FIRE ALARM Tone issue is found.

During FIRE ALARM Tone mode is there 70-75vAC present across system Network PA1 & PA2 Terminals on XT Main CCU A00381 Termination Board?

YES possible Network PA1 & PA2 wiring issue from Main CCU A00381 Termination Board to Intercom Units NO continue

During FIRE ALARM Tone mode is there 70-75vAC present across ‘PA Amplifier’ PA1 & PA2 Terminals on XT Main CCU A00381 Termination Board (below)?

YES possible A00381 Termination Board failure NO continue

PA1 Terminal 11

PA2 Terminal 12

Network PA2

A00381 Main CCU Termination Board

Network PA1

‘PA Amplifier’ PA1

‘PA Amplifier’ PA2

Page 9: Addvveenntt eXXTT lWWaarrddenn CCaalll

In Quiescent state does voltage across 0v & EN of ‘PA Amplifier’ terminals on XT Main CCU A00381 Termination Board = 13.7vDC

YES possible A00381 NO continue

During FIRE ALARM Tone mode does voltage across 0v & EN of ‘PA Amplifier’ terminals on XT Main CCU A00381 Termination Board switch too = 0.1vDC

YES possible A00381 NO continue

‘PA Amplifier’ EN

‘PA Amplifier’ 0v

‘PA Amplifier’ EN

‘PA Amplifier’ 0v

Page 10: Addvveenntt eXXTT lWWaarrddenn CCaalll

Does ZXT155 All Call Amp/PSU have power?

YES continue NO check mains to PSU, Possible ZXT155 All Call Amp/PSU fault

Check ZXT155 PSU Voltages at -27vDC, +27vDC, 12vDC, reference to 0v, on A00415 PA Amp/PSU Board inside ZXT155. Are they correct?

YES continue NO possible ZXT155 PSU failure

-27v (Blue Cable) on A00415 ZXT155 PSU Board

0v (Black Cable) on A00415 ZXT155 PSU Board

0v (Black Cable) on A00415 ZXT155 PSU Board

+27v (Pink Cable) on A00415 ZXT155 PSU Board

0v (Black Cable) on A00415 ZXT155 PSU Board

12v (Red Cable) on A00415 ZXT155 PSU Board

Page 11: Addvveenntt eXXTT lWWaarrddenn CCaalll

Check Voltage at RS485 TX+ & TX-, reference to 0v, on A00415 PA Amp/PSU Board inside ZXT155. Are they correct?

0v &RS485 TX+ in quiescent state = around 2.4v DC 0v &RS485 TX- in quiescent state = around 1.49v DC YES continue NO possible Data/cabling issue from Main A00381 Termination Board to Data on ZXT155 All Call Amp/PSU

Is Data Receive LED1 illuminated on A00415 All Call PSU?

YES continue NO possible Data/cabling issue from Main A00381 Termination Board to Data on ZXT155 All Call Amp/PSU

0v on A00415 ZXT155 PSU Board

RS485 TX+ on A00415 ZXT155 PSU Board

0v on A00415 ZXT155 PSU Board

RS485 TX- on A00415 ZXT155 PSU Board

RS485 DATA Receive LED1 on A00415 ZXT155 PSU Board

Page 12: Addvveenntt eXXTT lWWaarrddenn CCaalll

Is VR1 FIRE TONE Volume Level Pot on A00415 All Call PSU/Amp Board Set correctly? (i.e not turned fully anticlockwise = Lowest Tone Level)

YES continue NO turn VR1 Audio Level Pot on A00415 All Call PSU/Amp Board to correct level

During FIRE ALARM Tone mode is there 70-75vAC present across PA1 & PA2 Terminals on 100v Transformer inside ZXT155 All Call Amp/PSU (below)?

YES possible cabling issue from ZXT155 100v Transformer to XT A00381 Termination Board NO continue

Page 13: Addvveenntt eXXTT lWWaarrddenn CCaalll

Does voltage across 0v & EN of ‘Audio In’ terminals on A00415 ZXT155 All Call PSU/Amp Board switch from 13.7vAC (Quiescent State) to 0.1vAC (FIRE ALARM Tone Active Mode)?

Quiescent State = 13.7vAC All Call Audio & Tone Active Mode = 0.1vAC

NO possible A00415 ZXT155 All Call PSU/Amp Board failure

If you are still experiencing problems please contact our Technical Support Line on 01670 352371

0v on A00415 ZXT155 PSU Board

EN on A00415 ZXT155 PSU Board

0v on A00415 ZXT155 PSU Board

EN on A00415 ZXT155 PSU Board