ADDRESSSING THE ISSUE OF HIGH VOLTAGE. Action taken to control High Voltage. Closing of Bus and Line Reactors Changing of Transformation Tap Position Export to WR/ER Region Optimisation of HVDC Set Points Var absorption by Generators Switching – off of Capacitors. ISSUES OF CONCERN. - PowerPoint PPT PresentationTRANSCRIPT
Action taken to control High Voltage
• Closing of Bus and Line Reactors
• Changing of Transformation Tap Position
• Export to WR/ER Region
• Optimisation of HVDC Set Points
• Var absorption by Generators
• Switching – off of Capacitors
ISSUES OF CONCERN
STILL HIGH VOLTAGES IN SOME
AREAS
HIGH VOLTAGE PROBLEMWESTERN PART OF KARNATAKA
1. ONE CKT OF 400KV TALAGUPPA-NELAMANGALA LINE
OPENED OUT ON REGULAR BASIS TO CONTAIN OVER
VOLTAGE.
2. 400/220 KV TALAGUPPA ICT TAP POSITION AT 9 RESULTING IN
• 400KV BUS VOLTAGE @ TALAGUPPA IS AT 431KV WHILE
220KV BUS VOLTAGE @ SHARAVATHY IS AT 219KV
3. OPENING OF ONE CKT OF 400KV TALAGUPPA-NELAMANGALA
DROPS THE 400KV VOLTAGE BY 7 – 9 KV.
4. CHANGING THE TAP TO 11 WOULD BRING DOWN 400KV
VOLTAGE BY 4 – 6 KV & CORRESPONDINGLY 220KV VOLTAGE
WOULD ALSO RISE.
Map KarGRAPH kAIGA