ADDENDUM NUMBER ONE
To the Drawings
Dated: 23 May 2016
Entitled:
GRADY
Atlanta, Georgia
Minor Renovations Projects- Cardiology Expansion
Prepared By:
BSA LIFESTRUCTURES
3348 Peachtree Road NE Suite 1460
Atlanta, GA 30326
__________________________________
Joseph I. Mynhier
Georgia Certificate No. 013741
Addendum Dated: 23 May 2016
Project Number: 17220004
GRADY ADDENDUM NUMBER ONE
Atlanta, Georgia
Cardiology Expansion
BSA LifeStructures #17220004 Page 1
CHANGES TO DRAWINGS
1. DRAWING A 100:
a. A cubicle curtain specification section was added.
2. DRAWING A 101:
a. A note on Detail 3 has changed.
b. Elevation 5 – Casework Rm 2E307 has changed.
c. The Second Floor Architectural Plan has changed to show the sink at a new location.
END OF ADDENDUM NUMBER ONE
Attachments:
A100, A101
Newcomb and Boyd Addendum One
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
80 JESSE HILL JR DRIVE SEATLANTA, GA 30303
ISSUE FORCONSTRUCTIONFEB 21 201617220004
CONSTRUCTION DOCUMENTS
CARDIOLOGY EXPANSION
01 - ARCHITECTURE
A100 LOCATION PLAN/ SPECS
A 101 ARCH PLAN / ELEVATIONS / DETAILS/ FINISHES
DRAWING INDEX - BP1
05 - PLUMBING
P001 PLUMBING SPECIFICATIONS AND LEGEND
P101 PLUMBING SECOND FLOOR PLAN
06 - ELECTRICAL
E101 ELECTRICAL POWER SECOND FLOOR PLAN
PF # F 2015 010
GRADY PROJECT MANAGER:
TYRONE WILLIAMSFACILITIES DEVELOPMENTTel: 404 616 9650Cell: 404 717 0882Email: [email protected]
ROOF
ROOF
LIGHT WELL
LIGHT WELL
LIGHT WELL
LIGHT WELL
LOCKER
ROOM
SUPPLIES
2A01
4
2A01
5
2A01
7
TOILET
2A01
9A
E262
E261
E263
E257
E231
E232
E233
E234 E235 E236 E237 E238
E272E271E269E267E266E264
E253
E254
E250
E241
2E038
2E037
E223
E224
E222
E229
E228
E221 E219 E218
E227-1
E212 E214E216 E215
E227
E230
E286E282
E283
E286-1
E287
E281
E288
2E100
E280E278-1 E278 E275 E274 E273E203
EXAM 1
ALCOVE
EXAM 2 EXAM 3 EXAM 4 EXAM 5
EQUIP
RR
SUPPLY
STATION
ATTENDING EXAM 6
NURSES
EXAM 7
ALCOVE
SUPPLY
EXAM 8 EXAM 9 EXAM 10 EXAM 11 EXAM 12
EQUIP
REGISTRATION REGISTRATION
WAITING ROOM
CARDIACCARDIAC CARDIAC CARDIAC CARDIAC
CARDIAC
CARDIACCARDIACCARDIACCARDIACCARDIAC
CARDIAC ENTRYEXIT
ROOMCONFERENCE
REHABILITATIONCARDIAC
(FUTURE)
E220
OFFICEMANAGER
OFFICEPHYSICIAN
LOCKER ROOMSTAFF
EXAM 13HOLDINGCLEAN
HOLDINGSOILED
FILE ROOMCARDIAC
ROOM
OFFICE
FAX
FAX
FILE
COPY/
COPY/
CARDIAC
EKG
ATTENDING OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ECHO TECH EXAM 2EXAM 1
WORKROOM
EXAM 1EKG
EXAM 2EKG
OFFICE
EQUIPMENT
SUPPLY
EDIT/
OFFICE
LOCKERSSTAFF
GARAGECART
EXAM 14CLASSROOMOFFICE & SUPPLYEDUCATION PATIENT EDU CARDIAC ECHO ECHO
HOLTER
P13
ALLSPICE CA F E
2B044
2B046
2B047
2B045
2B043
2B042
2E027
2B054
2B075
2B076
2B073
2B074
2B049
2B048
2B051
2B050
2B052
2B071
2B068
2B077
2B069
2B067
2B066
2B064
2B065
2B063
2B056
2B055
2B057
2E106
2B058
2B062
2A002
2B061
2A006
2A000
2A010
2A004
2A003
2A005
2A009
2A007
2A008
2E108
2E011
2E012
2E107
2E104
2E008
2E014
2E006
2E013
2E015
2E114
2E017
2E016 2E021
2E018
2E023
2E004
2E005
2E003
2E025
2E024
2E022
2E026
2A013
E297
MECH (AC #12)
E255
CORRIDOR
CORRIDOR
E217
MECH
2E088
MECH
FE
FE
J.C
COMM
ASSIST.
SPEC.
DIR.
DEV.
P.R.
ROOM
WORK
DIR.
P.R.
P.R.
SPEC.
CLOTHING
VOLUNTEERS'
STORAGE
ELEC.
CLOSET
ADMINISTRATIVE OFFICES
COPY/FAX
STORAGE
STORAGE
VISITOR
ELEVATOR
LOBBY
ELEC.
COMM
P.R.
ASSIST.
P.R.
SEC'Y
SEC'Y
DIR.
VOL.
DIRECTOR
SEC'Y.
CORRIDOR
DRG. STOR.
DRG. STAFF
WKRM.
ENTRY/
P-16
ELEV
DRG.
E.A.N.
DRG. MGR
DRG. STAFF
OFFICE
SEC'Y
ASSIST.
ASSIST.
VOL.
DIR.
VOL.
TLT.
EXIST. P.S.
MECH
ELEV
ELEV
P-1
P-2
LOBBY
ELEVATOR
SERVING
CAFETERIA
CAFETERIA
SERVING
CREDIT UNION
SPACE
PIPE
CORRIDOR
SE-3
ELEV
VENT SHAFT ELEC. ROOM
SE-4
ELEV
DIRECTOR
OFFICE
ROOM
CONFERENCE
COSTELLO
ELEVATORS
STORAGE
VISITOR
LOBBY
HSKG
ELEVATOR
VISITOR
P-19
STORAGE
ELEV
P-4
ELEV
P-3
STORAGE
TLT
EXIST. P.S.
CORRIDOR
COMM.
ELEC
CLINICAL SPEC.
STAFF DEV/
PROJ. (1) &
SPECIAL
(2)
DISHWASHING
CLOSET
COMMUN.
PAPER
STORES
PARK
DISH
VEST SUPR.
OFFICE
CASHIER
OFFICE
AND SVR
WALK-IN
REF.
SPACE
PIPE
MGR'S
KITCHEN
OFFICE
PREP
AREA
VENDOR
WAITING
OFFICE
ASSIST.
MGR.
P.S.
TOILET
ROOM
ELEV.
SE-4
SE-3
VENT SHAFT ELEV.
E-CORRIDOR
2E027
MEDICAL RECORDS
CLO.
ROOM
COMMUN
TRASH RM
STAIR #4
NURSING DIVISION OFFICES-
SE5/T1
STAIR-6
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PROCEDURAL
WAITING
2A01
9
PSFE
PS
F E
PS
FE
FE
PS
PS
FE
PS
FE
PS
FE
FE
G
R
F
PS FE
PS F E
E F
B A
E E FG H K
L
LAB
C D
KEY PLAN
Newcomb&&&&Boyd
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800
Atlanta, GA 30326
ph 404.814.9090
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
17220004
FEB 21 2016
A100
LOCATION PLAN/SPECS
0000
ISSUE FORCONSTRUCTION
CARDIOLOGY EXPANSION
1/32" = 1'-0"1
LOCATION PLAN - SECOND FLOOR
MARK DATE DESCRIPTION1 4/28/16 Addendum 1
1
CARDIACREHABILITATION
2E037
CONFERENCEROOM
2E038
EKG EXAM 1
E288
EKG EXAM 2
E280
EKG EXAM 3
E287
EKG EXAM 4
E281
SUPPLY
E286-1
A101
1
1
2
4
HOLTEREQUIPMENT
PROCEDURE
E282
A1014
A2.1
ALIGN
A101
6
5
5
3 5
5
APPROX. LOCATION OF TEMP. WALL
APPROX. LOCATIONOF TEMP WALL
5
6
5' -
2"
10' - 7"
9' -
8"
6' - 0 1/2"
1
7
EQ EQ EQ
3' -
0"
1' -
8"
4' - 2 1/4"
1' - 9"
7
6
5
3
2' -
6"
11/4"
2
A101
TYP
11
7
7
3
A101
TYP
1
A000 2
3
4
XX
ARCHITECTURAL SYMBOLS LEGEND
NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OFDETAIL
DETAIL NUMBER
SHEET NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
PLAN NOTE DESIGNATION
EQUIPMENT DESIGNATION. REFERTO EQUIPMENT SCHEDULE.
CORNER GUARD (REFER TOFINISH PLANS)
ELEVATION TAG
FIRE EXTINGUISHER CABINETF.E.C.
CG
GENERAL ARCHITECTURAL NOTES
A101
1 SIM SIMILAR
1
A101
SIM
000
ROOM
000
1
A. PROVIDE 18" MINIMUM ADA REQUIRED CLEARANCE ADJACENTTO STRIKE OF DOOR.
B. WORK AT DOORWAYS MUST BE COORDINATED WITH THEOWNER. DOORS MUST BE IN PLACE DURING BUSINESS HOURS
C. CONTRACTOR WILL COORDINATE ACCESS TO WORK AREASWITH THE OWNER AND SHALL NOT LEAVE WORK AREAUNPROTECTED DURING BUSINESS HOURS.
D. CONTRACTOR SHALL CONFIRM FINAL LOCATIONS OFTEMPORARY WALLS WITH OWNER.
SOLID 2XWOOD BLOCKING
WALL BASE. REFER TO INTERIORFINISH NOTES
SOLID SURFACE (SS-1 U.N.O.) SCRIBEDTO WALL WITH EASED EDGE ON 3/4"PLYWOOD.1
1/2"
ADA ACCESSIBLE LAMINATE ENCLOSUREPANEL. PROVIDE REMOVABLE ACCESSPANEL AT SINK LOCATIONS FOR PLUMBING.USE CONCEALED FASTENERS WHEREPOSSIBLE.
2' -
10"
1"
UNDER MOUNTED SINK FIXTURE.REFER TO PLUMBING DRAWINGS
9"1'
- 6
"
5 1/
2"
HATCHED AREA INDICATES ADACLEARANCE.
ADA TOE CLEARANCE.
CABINET PULL
ADJUSTABLE SHELF WITHPLASTIC LAMINATE ON ALLSURFACES.
CABINET DOOR. LOCKABLE WHEREINDICATED ON INTERIOR ELEVATIONS.
SOLID 2X6WOOD BLOCKING
HARDWOOD MOUNTING STRIPS
6" 1/2"
1 1/
2"
TY
P.
4"
CABINET PULL
CABINET DOOR
DRAWER
SOLID 2XWOOD BLOCKING
HARDWOOD MOUNTING STRIPS
WALL BASE. REFER TO INTERIORFINISH DRAWINGS.
SOLID SURFACE (SS1) (U.N.O.) WITHDOUBLE EASED EDGE ON 3/4" PLYWOODWITH INTEGRAL BACKSPLASH AND SINKWHERE INDICATED. PROVIDE SIDESPLASHWHERE SURFACE ABUTS A WALL
3' -
0"
A.F
.F. (
TY
P.)
TO
P O
F C
AB
INE
T:
7' -
2"
A.F
.F. (
TY
P.)
2' - 1" OR 2' - 6"
GENERAL WALL TYPE NOTES
A. DIMENSIONS IN PLAN AND ELEVATION ARE TAKEN TO THE FACE OF FINISHDRYWALL, FACE OF EXPOSED MASONRY, CONCRETE, OR CENTER LINE OFCOLUMN, UNLESS NOTED OTHERWISE.
B. ALL INTERIOR WALLS SHALL BE TYPE 'B2.1' UNLESS NOTED OTHERWISE.
1. INDICATES ENTIRE WALL CONSTRUCTION TO STOP 6" ABOVE FINISHEDCEILING.
WALL TYPE SYMBOL
X1.1x
INDICATES CONSTRUCTION TYPE
NUMERICAL INDICATION OF STUD/MASONRY SIZE
SUFFIX INDICATES MODIFICATIONS TO WALLCONSTRUCTION HEIGHT
SUFFIX INDICATES HORIZONTALMODIFICATIONS
WALL TYPES SUFFIX
A2 WALL PARTITION1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
A2-2 1/2" METAL STUDS
BASE: REFER TO FINISHDRAWINGS
FLOOR: REFER TO FINISHDRAWINGS
1/2" SEALANT SPACE
STEEL STUD RUNNER TRACK.STUDS SCREWED AT BOTTOM
FLOOR SLAB
5/8" GYPSUM WALL BOARD
METAL STUDS (REFERTO CHART BELOW)
TRACK
FASTEN GYPSUM BOARDTO STUDS NOT TO THETOP TRACK
NON-RATED
SOUND ATTENUATIONBATTS
16 GAUGE HORIZONTALSTEEL STRAPS AT 32"O.C. VERTICALLY.ANCHOR TO EACH STUD.
5/8"
FINISH CEILING. REFERTO REFLECTED CEILINGPLAN.
6" M
IN
2 1/2"
ELEVATION SYMBOL LEGEND
GENERAL ELEVATION NOTES
A. ALL DIMENSIONS ARE TAKEN TO THE FACE OF FINISHED MATERIAL.B. INSTALL WOOD BLOCKING TO STUDS TO SUPPORT ALL WALL-MOUNTED
CABINETRY AND EQUIPMENT AS REQUIRED.C. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO
CONSTRUCTING CABINETRY.D. ALL BASE CABINETS SHALL BE 2'-0" DEEP UNLESS NOTED OTHERWISE.E. ALL CASEWORK SHALL BE FINISHED IN PLASTIC LAMINATE UNLESS
NOTED OTHERWISE.F. PROVIDE FILLER PANELS AT ALL LOCATIONS WHERE CABINETRY ABUTS
A WALL.G. PROVIDE A 4" HIGH INTEGRAL BACK SPLASH ON ALL COUNTERS WITH
RECESSED SINKS. INSTALL SIDE SPLASHES WHERE THESE COUNTERSABUT A WALL.
H. PROVIDE ADJUSTABLE SHELVING WITHIN ALL WALL AND BASECABINETRY AS SHOWN BY DASHED LINE.
I. PROVIDE 12" CLEAR INTERIOR DIMENSION ON ALL UPPER WALLCABINETS UNLESS NOTED OTHERWISE.
J. CONSTRUCT GYPSUM DRYWALL BULKHEADS ABOVE UPPER CABINETRYTO BE 1" DEEPER AND LONGER THAN CABINETRY BELOW UNLESSINDICATED OTHERWISE.
K. COORDINATE ALL WALL OUTLETS TO AVOID CONFLICT WITH CASEWORK.L. PAINTING CONTRACTOR IS TO STENCIL WALL RATING ON WALLS
INDICATED AS RATED ABOVE THE CEILING ON 20'-30' INTERVALS.
XX NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OFDETAIL
DETAIL NUMBER
SHEET NUMBER
ELEVATION NOTE DESIGNATION
A101
1 SIM SIMILAR
1
A101
SIM
1
1
A000 2
3
4 ELEVATION TAG
6"3"
8"3'
- 7
"2'
- 9
"9
10
6
1
3
7
12
12
VIF
2' - 5 3/4"
3
A101
TYP
Newcomb&&&&Boyd
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800
Atlanta, GA 30326
ph 404.814.9090
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
PLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
17220004
FEB 21 2016
A101
ARCH PLAN/ ELEVATIONS/DETAILS
0000
ISSUE FORCONSTRUCTION
CARDIOLOGY EXPANSION
NOTES- ARCHITECTURAL PLAN** NOT ALL NOTES APPEAR ON EACH SHEET
1 NEW WALL HUNG SINK. SEE PLUMBING DRAWINGS
2 LOCATION OF NEW CARD READER. SEE ELECTRICAL DRAWINGS
3 NEW CASEWORK AND SINK. SEE ELEVATION
4 NEW GLASS VISION SLIT IN EXISTING DOOR
5 REPAINT ALL DISTURBED WALL SURFACES TO MATCH EXISTING
6 REMOVE ONLY CABINETS NEEDED FOR ADA ACCESSIBLE BASE. NEW SINKWITH ADA ACCESSBILITY.
7 REMOVE EXISTING COUNTER TOP. REPLACE WITH NEW SOLID SURFACECOUNTERTOP
NOTES- INTERIOR ELEVATION** NOT ALL NOTES APPEAR ON EACH SHEET
1 4" RESILIENT BASE
2 25" DEEP (UNO) PLASTIC LAMINATE (PL1 UNO) COUNTERTOP WITH SIDEAND BACK SPLASHES, AS INDICATED.
3 25" DEEP (UNO) SOLID SURFACE (SS1 UNO) COUNTERTOP WITH SIDE ANDBACK SPLASHES, AS INDICATED.
4 24" DEEP (PL-1 UNO) BASE CABINET; CONFIGURE DOOR(S), DRAWER(S),AND SHELVE(S) AS INDICATED.
5 15" DEEP (PL-1 UNO) WALL CABINET; CONFIGURE DOOR(S), SHELVE(S)AND LIGHT SKIRT(S) AS INDICATED.
6 ACESSIBLE (BARRIER FREE) SINK SKIRT ASSEMBLY.
7 FINISHED END PANEL.
8 COUNTER SUPPORT BRACKET @ 48" O.C. MAXIMUM.
9 EXISTING DOOR
10 NEW 1/4" CLEAR TEMPERED GLASS
11 LAMINATE CASEWORK BULKHEAD. TO MATCH CABINETS
12 EXISTING CASEWORK TO REMAIN
1/8" = 1'-0"1
SECOND FLOOR ARCHITECTURAL PLAN(EKG)
1/4" = 1'-0"4
CASEWORK RM. E282
3/4" = 1'-0"3
ADA SINK DETAIL
3/4" = 1'-0"2
CABINET DETAIL
INTERIORS- FINISH SPECIFICATIONS
MARK:MANUFACTU
RER: STYLE: NUMBER: COLOR: SIZE: COMMENTS: CONTACT:
PL-1
SS-1
Wilsonart 7935-7 Shaker Cherry
Corian WhitecapN/A
1/4" = 1'-0"6
EXISTING DOORRB-1 Johnsonite Stone80 4"
N/A
N/AN/A
N/A
N/A
MARK DATE DESCRIPTION1 4/28/16 Addendum 1
1/4" = 1'-0"5
CASEWORK RM 2E307
1
1
ADDENDUM NO. 1
April 28, 2016
EKG EXPANSION
Notice to Contractors
This Addendum has become a part of the drawings and specifications for the above project dated
04/28/2016.
Failure for a bidder to acknowledge receipt of this Addendum on the Proposal may be sufficient
cause for rejection of the Bid.
Addendum 1 includes the following documents:
DRAWING CHANGES
1. Sheet E101 - ELECTRICAL POWER SECOND FLOOR PLAN, added power and data in
Cardiac Rehabilitation 2E037.
2. Sheet P101 - PLUMBING SECOND FLOOR PLAN, relocated sink in Cardiac
Rehabilitation 2E037.
END ADDENDUM NO.1
PLUMBING SPECIFICATIONSPLUMBING LEGEND
PLUMBING NOTES AND SPECIFICATIONS:
1. FURNISH ALL LABOR, MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH
ALL NATIONAL, STATE AND LOCAL CODES.
2. FURNISH AND INSTALL ALL SYSTEMS OF SOIL, WASTE, AND VENT PIPING, HOT & COLD WATER PIPING, AND DRAINAGE
PIPING INCLUDING ALL FITTINGS, VALVES, ETC. AS REQUIRED.
3. FURNISH AND INSTALL ALL PLUMBING FIXTURES AND EQUIPMENT AS SHOWN ON THE DRAWINGS.
4. ALL PLUMBING WORK SHALL BE DONE UNDER THE SUPERVISION OF AND BY LICENSED AND QUALIFIED PLUMBERS, PER
ALL LOCAL, STATE, AND NATIONAL CODES, AND TO THE COMPLETE SATISFACTION OF THE PLUMBING INSPECTOR.
5. SUBMISSION OF A BID OR PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED
HIMSELF WITH THE PLANS, SPECIFICATIONS, AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO BIDS FOR MATERIALS
AND/OR LABOR DUE TO DIFFICULTIES ENCOUNTERED, WILL NOT BE RECOGNIZED, UNLESS DIFFICULTIES COULD NOT HAVE
BEEN FORESEEN EVEN THOUGH PROPER EXAMINATION HAD BEEN MADE.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL UTILITY CONNECTIONS.
7. ALL MATERIALS SHALL BE NEW, CLEAN, AND WITHOUT DEFECTS. ANY DEFECTIVE MATERIALS SHALL BE REMOVED FROM
THE JOB SITE.
8. ALL PLUMBING PIPING SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE AND ABOVE DROP CEILINGS.
9. ALL HOT AND COLD WATER PIPING, 0.5" TO 2.5", WITH SUPPLY SERVICE TO FIXTURES, SHALL BE COPPER TUBING, TYPE L,
HARD DRAWN, ASTM B88-2009 WITH WROUGHT COPPER SWEAT TYPE FITTINGS, ASME B16.22-2013.
10. ALL HOT WATER PIPING SHALL BE INSULATED WITH 1" THICK PRE-FORMED FOAM PIPE INSULATION, IMCOLOCK OR EQUAL.
INSULATE FITTINGS WITH MITERED SECTIONS.
11. SANITARY, WASTE AND VENT PIPING AND FITTINGS ABOVE GRADE SHALL BE NO HUB CAST IRON, TAR COATED INSIDE AND
OUT, CISPI 301-2012. COUPLINGS SHALL BE HEAVY DUTY MECHANICAL COMPRESSION TYPE; ANACO HUSKY, CLAMP ALL,
OR MG COUPLING.
12. FIXTURE ARMS AND CONNECTIONS SHALL BE COPPER TUBING, TYPE DWV, HARD DRAWN, ASTM B88-2009.
13. CLEANOUT PLUGS SHALL BE INSTALLED IN ACCORDANCE WITH THE PLUMBING CODE REQUIREMENTS, AT EACH CHANGE
OF DIRECTION AND AT THE BASE OF EACH SANITARY STACK. CLEANOUTS SHALL BE PLACED IN READILY ACCESSIBLE
LOCATIONS.
14. INSULATE ALL EXPOSED PIPING UNDER HANDICAPPED LAVATORIES WITH TRU-BRO OR EQUAL.
15. FIRESTOPS SHALL BE PROSET "FIRESTOP PENETRATORS" OR APPROVED EQUAL.
16. PROVIDE WATTS MODEL 15 WATER HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED. INSTALL PER
MANUFACTURERS SPECIFICATIONS. MODEL 15 ARRESTORS MEET ASSE STANDARD 1010.
17. UPON COMPLETION OF THE WORK, TEST ALL PIPING SYSTEMS AS FOLLOWS:
A. DRAINAGE SYSTEMS INCLUDING SANITARY SEWERS AND SANITARY VENTS: PLUG LOW POINTS OF
SYSTEM AND FILL WITH WATER TO UPPERMOST OUTLET UP TO TWELVE (12) FEET HIGH, WHICHEVER IS
LOWER. LET SYSTEM STAND FULL OF WATER WITH NO INDICATIONS OF LEAKS FOR 12 HOURS.
B. DOMESTIC HOT AND COLD WATER: 150 PSIG HYDROSTATIC TEST. HOLD HYDROSTATIC TESTS FOR A
MINIMUM OF EIGHT (8) HOURS WITHOUT LOSS OF PRESSURE. HOLD AIR TESTS FOR A MINIMUM OF ONE
HOUR WITHOUT SIGNIFICANT LOSS OF PRESSURE.
18. RETESTING: RETEST PIPING FAILING INITIAL TESTS FOLLOWING CORRECTION OF DEFECTIVE WORK. REQUIREMENTS OF
INITIAL TESTS SHALL APPLY.
19. DISINFECT WATER SYSTEM AS OUTLINED BY SECTION 610 IN THE INTERNATIONAL PLUMBING CODE.
20. PROVIDE FULL-OPEN VALVES IN ACCORDANCE WITH SECTION 606.1 OF THE INTERNATIONAL PLUMBING CODE.
PLUMBING FIXTURES:
F2 LAVATORY (ADA) - VITREOUS CHINA LAVATORY, 20"x18", WITH 8" CENTERS AND FITTED WITH FAUCET,
SUPPLIES WITH STOP VALVES, GRID DRAIN, P-TRAP, WASTE TO WALL, ESCUTCHEONS, ADA INSULATION AND FLOOR
MOUNTED CARRIER WITH CONCEALED ARM SUPPORTS - AMERICAN STANDARD 0356-015 ; FAUCET SHALL BE DUAL
HANDLE TYPE, POLISHED CHROMIUM-PLATED BRASS BODY WITH GOOSENECK SPOUT, 4" BRASS BLADE HANDLES,
COLOR CODED INDEXES, QUARTER TURN CERAMIC CARTRIDGES, 0.5" RIGID BRASS INLET SHANKS ON 8" CENTERS,
AND 0.5 GPM VANDAL RESISTANT AERATOR FLOW CONTROL - MOEN 8248 ; FLOOR MOUNTED CARRIER SHALL BE
SMITH OR EQUAL BY JOSAM, WADE OR ZURN.
F6 SINK (ADA) - UNDERMOUNT 18 GAUGE TYPE 304 STAINLESS STEEL ONE BOWL SINK, 16"x20"x5.5", FAUCET, SUPPLIES
WITH STOP VALVES, REAR DRAIN, P-TRAP WITH OFFSET, WASTE TO WALL, ADA INSULATION AND ESCUTCHEONS -
ELKAY ELUHAD1418 OR EQUAL BY JUST; FAUCET SHALL BE DUAL HANDLE TYPE, POLISHED CHROMIUM-
PLATED BRASS BLADE HANDLES, COLOR CODED INDEXES, QUARTER TURN CERAMIC CARTRIDGES, O.5" RIGID BRASS
INLET SHANKS ON 8" CENTERS, AND 1.5 GPM VANDAL RESISTANT AERATOR FLOW CONTROL - MOEN 8248 .
ABBREVIATIONS
ABOVEABV
ABOVE CEILINGAC
ARCH ARCHITECT/ARCHITECTURAL
BEL BELOW
BF BELOW FLOOR
CLG CEILING
CONC CONCRETE
CONN CONNECT/CONNECTION
CONT CONTINUATION/CONTINUOUS
DOWNDN
DWG DRAWING
ELEC ELECTRICAL/ELECTRIC
EXP EXPOSED
FL FLOOR
GR GRADE
LV LAVATORY
MECH MECHANICAL
PDI PLUMBING AND DRAINAGE INSTITUTE
SPEC SPECIFICATION
SSTL STAINLESS STEEL
TEMP TEMPERATURE
TS TIGHT TO STRUCTURE
UC UNDERCOUNTER
VB VACUUM BREAKER
ABOVE FINISHED FLOOR/GRADEAFF/AFG
WC WATER CLOSET
R
A-ATMOSPHERIC TYPE; D-DOUBLE CHECK VALVE TYPE).BACKFLOW PREVENTER (R-REDUCED PRESSURE TYPE;
TYPE INDICATED ON SCHEDULE).
PRV-X PRESSURE REDUCING VALVE (X INDICATES THE PRV NUMBER;
A
AS INDICATED ON THE DRAWINGS).
WATER HAMMER ARRESTER (PDI SIZE A, B, C OR D
PRESSURE GAUGE.
THERMOMETER (SEE SPECIFICATIONS FOR TYPE).
TEMPERATURE AND PRESSURE RELIEF VALVE.
CHECK VALVE.
BALL VALVE.
REDUCER - CONCENTRIC.
STRAINER.
BASE CLEANOUT
D INDIRECT DRAIN.
HOT WATER (HW).
COLD WATER (CW).
VENT (V).
SOIL (S) OR WASTE (W) BELOW FLOOR OR GRADE.
SOIL (S) OR WASTE (W) ABOVE FLOOR OR GRADE.
GLOBE VALVE.
CONNECT TO EXISTING.
WM WATER MACHINE
6. INSTALL PIPE I.D. WITH FLOW ARROWS AND INSULATION ON ALL DOMESTICWATER PIPING SYSTEMS THROUGHOUT. LABEL ALL OTHER SYSTEMSCOMPLETE WITH PIPE I.D. AND FLOW ARROWS.
GENERAL NOTES:
THESE DRAWINGS DO NOT PURPORT TO SHOW ALL EXISTING UTILITIES.
ALL EXISTING PIPING THAT IS TO BE CONNECTED INTO OR MODIFIED SHALLBE FIELD CONFIRMED AND VERIFIED BEFORE COMMENCING WORK.
INSULATE ALL DOMESTIC WATER PIPING THROUGHOUT THIS RENOVATION.
MAKE ALL VALVES ACCESSIBLE THROUGHOUT THIS RENOVATION; INSTALLVALVE TAGS.
ANCHOR AND SECURE ALL PIPING IN CHASES AND WALLS THROUGHOUTSO THAT NO MOTION OCCURS AFTER FINISHED WALLS ARE INSTALLED.
5.
4.
3.
2.
1.
7. WHERE THE EXISTING STRUCTURE OR SURROUNDING INTERIOR IS DAMAGEDDURING THIS RENOVATION, THE CONTRACTOR IS RESPONSIBLE TO MAKE ALLNECESSARY REPAIRS TO MATCH THE EXISTING AND SURROUNDINGSURFACES.
8. CONTRACTOR SHALL VERIFY THAT EXISTING WASTE AND WATER PIPINGSHALL BE OF AMPLE SIZE AT NEW WASTE AND WATER CONNECTION POINTSTO EXISTING.
SYMBOLS
9. PROVIDE AND INSTALL ESCUTCHEONS ON ALL VISIBLE PIPE PENETRATIONS
THROUGHOUT THIS PROJECT.
10. PROVIDE AND INSTALL ISOLATION BETWEEN DISSIMILAR METALS, SUCH AS
COPPER TO CAST IRON PIPING.
PLUMBING FIXTURE SCHEDULENO.
F1
F6
FIXTURE TYPE
NOT USED
PIPING CONNECTION SIZE
HW-
CW S OR W
F2 LAVATORY, WALL TYPE, ADA
STAINLESS STEEL SINK, ONE BOWL, UNDERMOUNT, ADA 0.5" 0.5" 1.5"
0.5 1.250.5
0.5" 120°F HW SUPPLY
0.5" CW SUPPLY
3/8" FLEXIBLE RISER
MIXING VALVE, MV-1
0.5" 109°F HWTO LAVATORY
3/8" FLEXIBLE RISER
COUPLING
LAVATORY AND FAUCET (FAUCETDESIGN MAY VARY FROM SPEC)
NOTES:
1. MV-1 FOR SINGLE FIXTURE PER MANUFACTURER'S REQUIREMENTS.
MIXING VALVE SCHEDULE
NO.
MV-1
TYPE
(NOTE 1)SERVICE
DESIGN
GPM
MINIMUM CIRCULATING
FLOW RATE, GPM
PRESSURE DROP,
PSIG
TEMPERATURE
SETTING, °F
T,S FIXTURES 0.5 10 109° POWERS LF e480
NOTES
SINGLE VALVE
THERMOSTATICALLY CONTROLLED1. TYPE:
S
T
NOTES:
0.5
2. MANUFACTURER NOTED FOR BASIS OF DESIGN ONLY.
F3-F5 NOT USED
--
- --
11. CONTRACTOR SHALL PROVIDE ALL TEMPORARY OPENINGS, PENETRATIONS
AND REPAIRS REQUIRED TO COMPLETE THE SCOPE OF WORK, TO INCLUDE
BUT NOT LIMITED TO CEILING REMOVAL, PATCHING AND REPLACEMENT
AND INSTALLATION OF DAMAGED TILES.
1
P001 NO SCALE
PUBLIC LAVATORY/SINK MIXING VALVE
Newcomb&Boyd
9365 Counselors RowIndianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254
17220004
FEB 21 2016
P001
PLUMBINGSPECIFICATIONS ANDLEGEND
0000
ISSUE FORCONSTRUCTION
JAN 3, 201?JAN 4, 201?JAN 5, 201?JAN 6, 201?JAN 7, 201?
EKG EXPANSION
MARK DATE DESCRIPTION
CARDIAC
REHABILITATION
2E037
CONFERENCE
ROOM
2E038
Room
Room
Room
EKG EXAM 1
E288
EKG EXAM 2
E280
EKG EXAM 3
E287
EKG EXAM 4
E281
SUPPLY
E286-1
HOLTER
EQUIPMENT PROCEDURE
E282
5
F2
F2
F6
F6
5
7
7
4
4
66
0.5"
0.5" AC
0.5"
0.5"
AC
1
CARDIAC
REHABILITATION
2E037
CONFERENCE
ROOM
2E038
Room
Room
Room
EKG EXAM 1
E288
EKG EXAM 2
E280
EKG EXAM 3
E287
EKG EXAM 4
E281
SUPPLY
E286-1
HOLTER
EQUIPMENT PROCEDURE
E282
3
3
1
1
F2
F2
F6
F6
4"
3"
EX
W
EX
V
EX
W
2"3"
BF
2
W
BF
ACBF
4
4
2"
AC
3"
2"
1
Newcomb&Boyd
9365 Counselors RowIndianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254
17220004
FEB 21 2016
VZJ
VZJ P101
PLUMBING SECONDFLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EKG EXPANSION
1/8" = 1'-0"1
PLUMBING PRESSURE SECOND FLOOR PLAN 1/8" = 1'-0"
2PLUMBING WASTE SECOND FLOOR PLAN
1 2" WASTE AND VENT.
2 ROUTE 2" VENT PIPING AND CONNECT TO EXISTINGVENT PIPING IN TOILET ROOM CHASE.
3 ROUTE 1.25" WASTE ARM AT NEW LAVATORY ANDCONNECT TO EXISTING WASTE AND VENT PIPING INCHASE FROM EXISTING LAVATORY; ALLOW WASTEARMS IN CHASE TO OFFSET AND CONNECT ATSEPARATE HEIGHTS FOR EASE OF MAINTENANCE;MAINTAIN ADA CLEARANCE FOR WASTE PIPINGBELOW LAVATORY.
4 EXISTING LAVATORY.
REFERENCE NOTES:
5 0.5" HOT AND COLD WATER DROP TO FIXTURE ANDMIXING VALVE MV-1.
6 0.5" HOT AND COLD WATER PIPING SUPPLY TOFIXTURE AND MIXING VALVE MV-1; ROUTE ANDCONNECT TO EXISTING HOT AND COLD WATERSUPPLY PIPING IN CHASE.
7 ROUTE AND CONNECT TO MINIMUM EXISTING 0.75"HOT AND COLD WATER SUPPLY PIPING IN CEILINGSPACE.
MARK DATE DESCRIPTION1 4/28/2016 Addendum 1
2D
2D 2D
CARDIAC
REHABILITATION
2E037
CONFERENCE
ROOM
2E038
Room
Room
Room
EKG EXAM 1
E288
EKG EXAM 2
E280
EKG EXAM 3
E287
EKG EXAM 4
E281
SUPPLY
E286-1
HOLTER
EQUIPMENT PROCEDURE
E282
1
1
1
Newcomb&Boyd
9365 Counselors RowIndianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401Contact:Kidane AbebeN&B PROJECT:15N254
17220004
FEB 21 2016
MBE
ROW E101
ELECTRICAL POWERSECOND FLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EKG EXPANSION
1/8" = 1'-0"1
ELECTRICAL POWER SECOND FLOOR PLAN
1
KEYNOTE: (THIS DRAWING ONLY)
PROVIDE NEW CARD READER. MATCH EXISTING MANUFACTURER AND TYPE.COORDINATE WITH GRADY APPROVED SUB CONTRACTOR. PROVIDE ALLNECESSARY WORK NEEDED TO COORDINATE THE INSTALL OF WIRING, DOORCONTROLS, MAGNETIC LOCK, PROXIMITY SENSOR AND CONNECTION WITH SMOKEDETECTOR AND FIRE ALARM SYSTEMS. DOORS SHALL RELEASE UPON ACTIVATIONOF CARD READER, FIRE ALARM, SMOKE DETECTOR OR PROXIMITY SENSOR.
NEW SINK LOCATION. ALL EXISTING RECEPTACLE OUTLETS INSTALLED WITHIN 6FTOF THE OUTSIDE EDGE OF THE SINK LOCATION SHALL BE REPLACED WITHHOSPITAL GRADE GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLES.RECEPTACLES SHALL BE UL 943-2011 COMPLIANT, 20A, SELF-TESTING, TAMPERRESISTANT, FEED THROUGH TYPE, INDUSTRY MARKED AS "HOSPITAL GRADE".
MANUFACTURER: HUBBELL GF8300SG, LEVITON GFWT2-HG, OR P&S 2097HGTR.
PROVIDE NEW ABOVE THE COUNTER GFCI RECEPTACLE OUTLET. RECEPTACLEOUTLETS SHALL BE HOSPITAL GRADE GROUND FAULT CIRCUIT INTERRUPTER(GFCI) RECEPTACLES. RECEPTACLES SHALL BE UL 943-2011 COMPLIANT, 20A, SELF-TESTING, TAMPER RESISTANT, FEED THROUGH TYPE, INDUSTRY MARKED AS"HOSPITAL GRADE".
MANUFACTURER: HUBBELL GF8300SG, LEVITON GFWT2-HG, OR P&S 2097HGTR.
PROVIDE NEW WALL-MOUNTED HOSPITAL DUPLEX RECEPTACLE OUTLET.RECEPTACLE OUTLETS SHALL BE RATED 20A AND INDUSTRY MARKED AS"HOSPITAL GRADE". MOUNTING STRAP, GROUND CONTACTS, AND POWERCONTACTS SHALL BE NICKEL-PLATED.
MANUFACTURER: HUBBLE HBL8300, LEVITION 8300, OR P&S 8300.
2
1
2
2
2
2
ELECTRICAL LEGEND
CARD READER.
EXISTING RECEPTACLE, REPLACED WITH HOSPITAL GRADEGFCI DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED.
NEW GFCI DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED, ABOVE COUNTER.
HOSPITAL GRADE DUPLEX RECEPTACLE OUTLET, WALL-MOUNTED 18" ABOVEFINISHED FLOOR.
TELECOMMUNITION OUTLET - SINGLE GANG CUT IN RING MOUNTED 18" ABOVEFINISHED FLOOR. ROUTE (2) CATEGORY 6 CABLES TO COMM ROOM.PROVIDE 4 PORT FACEPLATE WITH LABELS.
CR
CR
2
3
3
3
GENERAL NOTES:(THIS DRAWING ONLY)
1. EXISTING WORK SHOWN WITH HALF-TONE LINE WEIGHT
2. NEW WORK SHOWN WITH HEAVIER LINE WEIGHT.
3. SERVE ALL NEW RECEPTACLES FROM EXISTING CIRCUITSERVING THE ROOM.
4. COORDINTATE INSTALLTION OF TELECOMMUNICATION OUTLETS WITHGRADY IT DEPARTMENT. ROUTE CABLES TO COMMUNICATIONSCLOSET DIRECTED BY GRADY IT. PROVIDE ALL EQUIPMENT ANDDEVICES NEEDED FOR A COMPLETE SYSTEM.
MARK DATE DESCRIPTION1 4/28/2016 Addendum 1