420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . www.mhtn.com2/18/20 12:50 PM . Page 1 of 4
document2
Addendum No. 01 Issued: 2/18/2020Project Name: Oquirrh Hills MS Remodel 2020
Project No.: 2019587
Addendum No. 01 to the Construction Contract for the above referenced project:
All Contractors submitting proposals on the above captioned project shall be governed by the following changes and explanations to the Bid Documents, dated [insert date of bid documents], and shall submit their bids in accordance therewith:
Changes to the Project Manual
1.1 Prior Approvals
PRIOR APPROVALS:The following manufacturers, trade names and products are allowed to bid on a name brand only basis with the provision that they completely satisfy all and every requirement of the drawings, specifications, and all addenda shall conform to the design, quality and standards specified, established and required for the complete and satisfactory installation and performance of the building and al its respective parts.
Product Manufacture
Resilient Athletic Flooring Durathon Elite Infield
VAV Re-Heat Boxes Tuttle & Bailey, KruegerPackaged Rooftop Units American Standard, LennoxPackaged AC Units LennoxMake-Air Units ModineExhaust Fans LorenRegisters, Grilles, Diffusers KruegerFire/Smoke Dampers United Enertech, RuskinFire Dampers United Enertech, RuskinManual Dampers United EnertechFlexible Duct JPL
Plumbing Fixtures SloanFaucets T&S Brass, American Standard, HydrotekFlush Valves American StandardDrinking Fountains OasisIce Maker Box LSPWasher Box LSPDrainage Products MifabFixture Carriers MifabTrap Guards MifabCleanouts MifabStops & Supplies LSP
![Page 2: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/2.jpg)
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . www.mhtn.com2/18/20 12:50 PM . Page 2 of 4
document2
Traps & Supplies McGuireToilets Seats American Standard
ELECTRIC ITEMSPRODUCT/TRADE MANUFACTURERCR1DL1FA1GA1GA2GA21GID1GID2HB1VF1X1
Approved Lighting Controls – Douglas Only – Match existing installed system.
Lithonia Williams Metalux Elite ILPLithonia Williams Halo Elite LitonLithonia Day-Brite Metalux Elite ColumbiaLithonia Day-Brite Metalux Elite ColumbiaLithonia Day-Brite Metalux Elite ColumbiaLithonia Day-Brite Metalux Elite ColumbiaLithonia Day-Brite Metalux Elite ColumbiaLithonia Day-Brite Metalux Elite ColumbiaLithonia GE Metalux Elite ILPLithonia Stonco Lumark Satco HubbleLithonia Williams Sure-Lites Elite Dual-Lite
Changes to the Drawings
A1.1 SHEET P101
a. At the contractor’s option, grease waste piping may be run south out of kitchen, then 4” grease waste main to run east out double doors of hall to avoid potential conflict with existing electrical conduits at east kitchen door.
b. Coordinate option with civil and location of grease interceptor and sampling manhole.
c. Contractor option shall be at no additional cost to owner or contract.
![Page 3: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/3.jpg)
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . www.mhtn.com2/18/20 12:50 PM . Page 3 of 4
document2
A1.2 SHEET M501 – Exhaust Fan Schedule
d. EF-2 – Reference with note (4)
e. EF-3 – Reference with note (2)
f. EF-4 – Reference with note (1)(2)(3)(5)
E1.1 Sheet ED102 – Electrical Demolition Plan1. Change keyed note #13 to read as follows: “EXISTING ELECTRICAL GEAR IS
LOCATED IN THE BOILER ROOM BELOW AND IS TO REMAIN IN PLACE. PROTECT FROM DAMAGE DURING CONSTRUCTION.”
2. Change keyed note #21 to read as follows: “THERE ARE MANY 480 VOLT AND 208 VOLT PANEL FEEDERS EXTENDING THROUGH THE EXISTING FLOOR SLAB FROM PANEL M AND MP. CONTRACTOR TO WORK WITH THE CONTRACTOR REMOVING THE SLAB TO PROTECT ALL FEEDERS FROM BEING CUT OR DAMAGED DURING THE SLAB REMOVAL. ANY DAMAGED FEEDERS SHALL BE REPAIRED AND REPLACED AT NO ADDITIONAL COST TO THE OWNER.”
E1.2 Sheet ED111 – Audio Visual Demolition Plan1. Modify demolition schedule. 2. Modify keyed notes.3. See sheet ED111.
E1.3 Sheet ED112 – Audio Visual Demolition Ceiling Plan1. Modify keyed notes. 2. See sheet ED112.
E1.4 Sheet EL101 – Lighting Plan1. Add exit signs in the Kitchen as show.2. Rotate exit sign at Corridor B115 as shown.3. See sheet EL101.
E1.5 Sheet EL601 – Lighting Controls1. Update sheet to Douglas Controls to match the existing installed system.2. See sheet EL601.
E1.6 Sheet EP101 – Power Plan1. Change the disconnects for the Kitchen Exhaust fans to non-fused. 2. Add receptacles to Gym.3. See sheet EP101.
E1.7 Sheet EP102 – Bid Alternates1. Update receptacle requirements for elevator equipment room as shown.2. See sheet EP102.
E1.8 Sheet EP401 – Enlarged Kitchen Power Plan1. Remove unused disconnects. 2. See sheet EP401.
![Page 4: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/4.jpg)
420 East South Temple, Suite 100 . Salt Lake City . Utah . 84111 . 801.595.6700 . www.mhtn.com2/18/20 12:50 PM . Page 4 of 4
document2
E1.9 Sheet EP701 – One-Line Diagram and Schedules1. Change the disconnects for the kitchen exhaust fans to non-fused.2. Update wiring for the Dishwasher. 3. See sheet EP701.
E1.10 Sheet ET102 – Audio Visual Ceiling Plan1. Modify intercom layout.2. See sheet ET102.
E1.11 Sheet ET401 – Audio Visual Section and Elevations1. Modify detail #1.2. See sheet ET401.
E1.12 Sheet ET702 – Audio Visual Riser and Equipment List1. Modify detail #2.2. Modify school intercom equipment list.3. See sheet ET702.
E1.13 Sheet ET703 – Audio Visual Riser and Equipment List1. Modify details #3 and #4.2. Modify school intercom equipment3. See sheet ET703.
Attachments
ED111, ED112, EL101, EL601, EP101, EP102, EP401, EP701, ET102, ET401, ET702, ET703
End of Addendum
![Page 5: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/5.jpg)
DEMOLITION SCHEDULE
WORK INVOLVED
ROOM SYMBOL SYMBOL NAME DISCONNECT REMOVE REMOVE REMOVE ASSOCIATED REMOVE RETURN REMAIN REMOVE SAVE TO BE OTHER REFER KEYED
NAME AND REMOVE MOUNT BACKBOXES CONDUIT/WIREMOLD WIRES TO OWNER FOR BY REINSTALLED TO NOTE #
DEVICE COMPLETELY REUSE OWNER
FACULTY CALL SWITCH X X X X X ED111
ROOM
INTERCOM WALL SPEAKER & CLOCK X X X X X ED111
KITCHEN INTERCOM WALL SPEAKER & CLOCK X X X X X ED111
GYM PENDANT SPEAKER X X X X X ED112
MIC & AUX INPUTS X X X ED111
MIC & AUX INPUTS X X X X X ED111
DINING AREA TV X X X X
ED111
CS
S
TV
SPK
MA
MA2
SPK
FC
FC
SPK
SP
K
CS
MA
MA
2
TV
65
B
D4
D4
D2
D1
D1
2
ET501
1
ET501
3
ET5014
ET501
FACULTY
KITCHEN
GYM
DINING AREA
AUDIO VISUAL DEMOLITION GENERAL NOTES:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, REMOVE ALL ELECTRICAL ITEMS SHOWN IN DARK & DASHED LINES. LIGHT & SOLID ITEMS ARE TO REMAIN. DEMOLITION ITEMS ARE SHOWN TO GIVE A BASIC DESCRIPTION OF THE EXTENT OF DEMOLITION WORK, BUT MAY NOT BE INCLUSIVE. PROVIDE DEMOLITION WORK IN ACCORDANCE WITH THE FOLLOWING REQUIREMENTS:
1.1. REMOVE AND DISPOSE OF ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE REUSED.
1.2. EXISTING RACEWAYS MAY BE REUSED, IF IN
PLACE, WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH THE UPGRADE AND OR PROVIDE NEW CONDUIT SUPPORTS WHERE NECESSARY FOR ALL RACEWAYS BEING REUSED. ENSURE INTEGRITY OF EXISTING RACEWAYS BEFORE REUSE.
1.3. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
1.4. COORDINATE WITH OWNER WHAT EQUIPMENT SHOULD BE DISPOSED OF AND WHAT EQUIPMENT IS TO BE RETURNED TO OWNER.
BID INSTRUCTIONS:
1. PROVIDE A BASE BID FOR THE WORK NOTED ON ED111, ED112, ET101, ET102, ET401, ET501, ET701, AND ET702.
2. INLIER OF BASE BID, PROVIDE AN ALTERNATE BID FOR THE WORK NOTED ON SHEET ED111, ED112, ET101, ET102, ET501, ET701, AND ET703.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:2
7 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALDEMOLITIONPLAN
ED111
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
4' - 0" 8' - 0" 16' - 0"
1/8" = 1'-0"
AUDIO VISUAL DEMOLITION PLANN
KEYED NOTES
D1 DISCONNECT, REMOVE, AND RETURN THE MICROPHONEINPUT AND AUDIO AUX INPUT TO THE OWNER. REMOVECABLING ASSOCIATED WITH THESE INPUTS ONLY BACK TOTHE EXISTING CABINET COMPLETELY. REMOVE THE EXISTINGWIREMOLD COMPLETELY AS WELL.
D2 DISCONNECT, REMOVE, AND RETURN THE INTERCOM CALLSWITCH TO THE OWNER. REMOVE CABLING ASSOCIATEDWITH IT ONLY BACK TO THE EXISTING CABINET COMPLETELY.
D4 DISCONNECT, REMOVE, AND RETURN THE INTERCOMSPEAKER AND CLOCK TO THE OWNER. REMOVE CABLINGASSOCIATED WITH THESE DEVICES ONLY BACK TO THEEXISTING CABINET COMPLETELY.
#
1 02/18/20 Addendum #1
1
1
![Page 6: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/6.jpg)
FC
FC
FC
FC
SSS
C.
D3 TYP. 5
ET501TYP.
65
B
D
4
B
D
4
AUDIO VISUAL DEMOLITION GENERAL NOTES:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, REMOVE ALL ELECTRICAL ITEMS SHOWN IN DARK & DASHED LINES. LIGHT & SOLID ITEMS ARE TO REMAIN. DEMOLITION ITEMS ARE SHOWN TO GIVE A BASIC DESCRIPTION OF THE EXTENT OF DEMOLITION WORK, BUT MAY NOT BE INCLUSIVE. PROVIDE DEMOLITION WORK IN ACCORDANCE WITH THE FOLLOWING REQUIREMENTS:
1.1. REMOVE AND DISPOSE OF ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE REUSED.
1.2. EXISTING RACEWAYS MAY BE REUSED, IF IN
PLACE, WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH THE UPGRADE AND OR PROVIDE NEW CONDUIT SUPPORTS WHERE NECESSARY FOR ALL RACEWAYS BEING REUSED. ENSURE INTEGRITY OF EXISTING RACEWAYS BEFORE REUSE.
1.3. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
1.4. COORDINATE WITH OWNER WHAT EQUIPMENT SHOULD BE DISPOSED OF AND WHAT EQUIPMENT IS TO BE RETURNED TO OWNER.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:2
9 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALDEMOLITIONCEILING PLAN
ED112
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
4' - 0" 8' - 0" 16' - 0"
1/8" = 1'-0"
AUDIO VISUAL DEMOLITION CEILING PLAN
N
KEYED NOTES
D3 DISCONNECT, REMOVE, AND RETURN THE PENDANTSPEAKERS TO THE OWNER. REMOVE CABLING ASSOCIATEDWITH THEM ONLY BACK TO THE EXISTING CABINETCOMPLETELY.
#
1 02/18/20 Addendum #1
1
![Page 7: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/7.jpg)
TYPICAL LIGHT FIXTURE CONVENTION
NOTE:
a
14L-4
14EL-3
LOWERCASE LETTER DESIGNATESSWITCHING OR CIRCUIT ASSIGNMENT.ASSIGNMENTS, SUCH AS a/b, INDICATEDUAL LEVEL SWITCHING.
CIRCUIT DESIGNATION
CIRCUIT DESIGNATION A2 LETTER DESIGNATESFIXTURE TYPE.
SHADING INDICATES EGRESS LIGHTFIXTURE. CONNECT TO UNSWITCHEDHOT EMERGENCY LIGHTING CIRCUIT.
EXIT SIGNS. CONNECTTO UNSWITCHED HOTEMERGENCY LIGHTINGCIRCUIT.
SCALE: NONE
1. SEE ELC SHEETS FOR LIGHTING
CONTROL REQUIREMENTS.
FC
FC
FC
FC
K
KK
KK
VS
LV2
LV2
LV2
LVVS
LV2
VS
LV2LV2
LV2
LV2
LV2
LV2
LV4D
LV2
LV2
LV2
LV2
KKKK
K K
KC.
1
2
3
BYY-8
1
2
6
6
2
21
21
3
ALTERNATE #2
4
ALTERNATE #2
4
7
7
HB1
HB1
HB1
HB1
HB1
HB1
HB1
HB1
HB1 HB1
HB1
HB1
HB1 HB1
GID1 GID1 GID1
GID1GID1
VF1 VF1
FA1FA1
FA1 FA1X1
X1
X1
DL1
DL1
DL1
DL1
DL1
DL1
GID1
GID1
GA21
GA21
GA21
GA21
GA21
GA21GA21
FA1
GID2
GA2GA2
GA2
GA2GA2
GA2
GA2 GA2 GA2
GA1
GA1
GA1
X1
5
5
5
X1X1
1
X1
1
X1
1
X1
1
1
KEYED NOTES:
1. RECONNECT TO EXISTING EMERGENCY LIGHTING CIRCUIT THAT WAS IN PLACE PRIOR TO THE DEMOLITION. CONTRACTOR TO VERIFY NEW LOAD ON EXISTING CIRCUIT AND MAKE SURE CIRCUIT IS NOT OVERLOADED.
2. RECONNECT TO EXISTING LIGHTING CIRCUIT THAT WAS IN PLACE PRIOR TO THE DEMOLITION. CONTRACTOR TO VERIFY NEW LOAD ON EXISTING CIRCUIT AND MAKE SURE CIRCUIT IS NOT OVERLOADED.
3. REINSTALL AND RECONNECT EXISTING KEYED SWITCHES THAT WERE REMOVED DURING THE DEMOLITION. KEYED SWITCHES TO FUNCTION THE SAME AS PRIOR TO THE DEMOLITION.
4. ALL WORK IN THIS AREA TO BE INCLUDED IN ALTERNATE #2.
5. IF EXISTING EMERGENCY CIRCUIT DOES NOT EXIST, CONNECT TO PANEL EM. PROVIDE NEW 20 AMP, 1-POLE CIRCUIT BREAKER FOR EACH CIRCUIT. NEW BREAKER TO BE OF THE SAME MANUFACTURE AND INTERRUPTING CURRENT AS THE EXISTING INSTALLED. CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS.
6. REINSTALL EXISTING LIGHT FIXTURE THAT WAS REMOVED DURING THE DEMOLITION.
7. PROVIDE ADDITIONAL POWER PACK FOR OCCUPANCY SENSOR AS REQUIRED TO SWITCH THE 120 VOLT EXHAUST FAN IN THIS ROOM. SEE EP101 FOR ADDITIONAL INFORMATION.
#
LIGHTING GENERAL NOTES:
1. REFER TO EL701 FOR TYPICAL CONTROL WIRING DIAGRAMS. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED CONDUIT, WIRING, SWITCHES, SENSORS, POWER PACK, ETC.
2. LOCATE POWER PACKS AND ROOM CONTROLLERS ABOVE ACCESSIBLE CEILING NEAR ROOM ENTRANCES.
3. CONFIRM ALL LOCATIONS OF LIGHT FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:3
2 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
LIGHITNG PLAN
EL101
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
4' - 0" 8' - 0" 16' - 0"
1/8" = 1'-0"
LIGHTING PLAN
N
1 02/18/20 Addendum #1
![Page 8: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/8.jpg)
SCALE:
SCALE:
LV
4D
LV
2
LV VS
VS
LOW VOLTAGE LIGHTING CONTROL WALL SWITCH DETAILS
LINE VOLTAGE LIGHTING CONTROL WALL SWITCH DETAILS
LIGHTING CONTROL SYSTEM REQUIREMENTS:
GENERAL NOTES:
TYPICAL SMALL OFFICE LIGHTING CONTROLS
CLASSROOM LIGHTING CONTROLS
TYPICAL KITCHEN LIGHTING CONTROLS
NONE
NONE
4
SYMBOL SYMBOL
5
SYMBOL
STANDALONE LOW VOLTAGE LIGHTING CONTROL SYSTEMS: PROVIDE DIGITAL STANDALONE LOW VOLTAGE LIGHTING CONTROL SYSTEMS IN THE
FOLLOWING ROOMS/AREAS:
LARGE BOYS AND GIRLS RESTROOMS
LARGE STORAGE ROOMS
TEACHERS LOUNGES
KITCHEN
THE SYSTEMS SHALL INCLUDE, BUT IS NOT LIMITED TO CEILING-MOUNTED OCCUPANCY SENSORS, LIGHT LEVELS SENSORS, LOW VOLTAGE CONTROL
WALL SWITCHES, POWER PACKS, LOW VOLTAGE CABLES, PROGRAMMING, ETC.
PROVIDE POWER PACKS IN TYPES AND RATINGS AS MAY BE REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM WHETHER SHOWN ON
THE DRAWINGS OR NOT. WHERE POWER PACKS ARE SERVING LOADS IN HIGH CEILING AREAS, LOCATE POWER PACKS IN THE ELECTRICAL ROOM
WHERE LINE VOLTAGE WIRING IS ORIGINATING FROM.
OCCUPANCY SENSORS SHALL BE SET FOR “MANUAL ON - AUTO OFF” WITH A 10 MINUTE DELAY IN THE FOLLOWING SPACES:
OFFICES
OCCUPANCY SENSORS SHALL BE SET FOR “AUTO ON - AUTO OFF” WITH A 10 MINUTE DELAY IN THE FOLLOWING SPACES:
LARGE BOYS AND GIRLS RESTROOMS
LARGE STORAGE ROOMS
TEACHERS LOUNGES
ALL CEILING-MOUNTED OCCUPANCY SENSORS SHALL BE PROVIDED WITH AN AUXILIARY CONTACT FOR HVAC CONTROL.
ALL LOW VOLTAGE LIGHTING CONTROL SWITCHES SHALL HAVE EACH SCENCE NAME SILKSCREENED ONTO THE FRONT OF THE SWITCH IN BLACK
LETTERS.
REFER TO LOW VOLTAGE LIGHTING CONTROL SCHEDULES FOR A COMPLETE DESCRIPTION ON PROGRAMMING SCENCES, TASK TUNING, ETC. EACH
STANDALONE SYSTEM SHALL BE PROGRAMMED TO REVERT BACK TO ITS NORMAL “ON” POSITION ONE HOUR AFTER SELECTING A SCENE OR
RAISING OR LOWERING A LIGHTING ZONE.
LINE-VOLTAGE LIGHTING CONTROL SYSTEM: PROVIDE LINE-VOLTAGE LIGHTING CONTROL SYSTEMS IN THE FOLLOWING ROOMS/AREAS:
WALL BOX OCCUPANCY SENSORS:
SMALL STORAGE ROOMS
SMALL TOILET ROOMS
LAUNDRY
SET OCCUPANCY SENSOR TO HAVE A 10 MINUTE DELAY
OCCUPANCY SENSORS: PLEASE NOTE THAT ELECTRICAL DRAWINGS INDICATE LOCATIONS OF OCCUPANCY SENSORS IN APPROXIMATE LOCATIONS
AND QUANTITIES. PROVIDE OCCUPANCY SENSORS IN LOCATIONS, QUANTITIES, AND TYPES AS RECOMMENDED BY THE MANUFACTURE. PROVIDE
COMPLETE PRODUCT DATA AND SHOP DRAWINGS INDICATING THE PROPOSED TYPES, COVERAGE PATTERNS, LOCATIONS, AND QUANTITIES.
COORDINATE THE LOCATION OF ALL DEVICES WITH CEILING GRIDS, LIGHT FIXTURES, CEILING DIFFUSERS, SPRINKLER HEADS, ETC.
LIGHT LEVEL SENSORS: PLEASE NOTE THAT THE ELECTRICAL DRAWINGS INDICATED LOCATIONS OF LIGHT LEVEL SENSOR IN APPROXIMATE
LOCATIONS ONLY. PROVIDE LIGHT LEVEL SENSORS IN LOCATIONS AND TYPES AND RECOMMENDED BY THE MANUFACTURER. PROVIDE COMPLETE
PRODUCT DATA AND SHOP DRAWINGS INDICATING THE PROPOSED TYPES AND LOCAITONS. COORDINATE THE LOCATION OF ALL DEVICES WITH
CEILING GRIDS, LIGHT FIXTURES, CEILING DIFFUSERS, SPRINKLER HEADS, ETC.
ZONING REQUIREMENTS: IT IS PERMISSIBLE FOR ZONES OF LIGHT FIXTURES TO BE CONTROLLED BY COMMON POWER PACKS IN LIEU OF INDIVIDUAL
POWER PACKS FOR EACH LIGHT FIXTURE EXCEPT AS FOLLOWS:
1. EGRESS LIGHT FIXTURES IN EACH ZONE SHALL BE PROVIDED WITH A POWER PACK UL LISTED FOR EMERGENCY OPERATIONS. SEE EMERGENCY
OPERATIONS BELOW.
2. EACH ROOM OR AREA SHALL BE CONSIDERED A SEPARATE ZONE, UNLESS NOTED OTHERWISE. PLEASE NOTE THE SOME ROOMS HAVE
MULTIPLE ZONES. REFER TO THE LIGHTING PLANS FOR DELINATED LIGHTING ZONES.
3. DIFFERENT LIGHT FIXTURE TYPES IN EACH ZONE SHALL HAVE SEPARATE POWER PACKS.
4. POWER PACKS SHALL BE RATED IN AMERPAGES AND VOLTAGES AS MAY BE REQUIRED TO SUIT APPLICATION.
5. PROVIDE A MINIMUM OF AT LEAST 10% EXTRA POWER PACKS OF EACH SIZE AND TYPE UTILZIED AND ZONE AS MAY BE DIRECTED BY THE
ELECTRICAL ENGINEER.
TASK TUNING:
SET THE DEFAULT (MAXIMUM) LIGHT LEVELS TO SUIT THE PARTICULAR TASK OR USE OF A WORKSPACE AS FOLLOWS:
FUNCTION / SPACE IILUMINANCE (AVG. FOOTCANDLES)
CLASSROOMS 50 FC
VESTIBULES 10 FC
OFFICES 50 FC
TEACHER'S LOUNGES 30 FC
LARGE STORAGE ROOMS 10 FC
CORRIDORS 10 FC
LARGE RESTROOMS: 10 FC
SMALL TOILET ROOMS: 10 FC
MULTIPURPOSE:
ASSEMBLY 50 FC
COMPETITIVE SPORTS 50 FC
GENERAL 50 FC
PHYSICAL EDUCATION 50 FC
KITCHEN 50 FC
VALUES INDICATED ABOVE ARE AVERAGE FOOTCANDLE LEVELS ON THE TASK SURFACE. TAKE METER READING AT THE COMPLETION OF THE
PROJECT AS MAY BE REQUIRED TO APPROPIRATELY TUNE EACH SPACE; METER TO BE FURNISHED BY LIGHTING CONTROL SUPPLIER.
EMERGENCY OPERATION: PROVIDE A UL 924 LISTED METHOD FOR OPERATING EGRESS LIGHT FIXTURES. FOR THE NLIGHT SYSTEM, THIS SHALL
INCLUDE “FOR USE WTH GENERATOR SUPPLY EM POWER” OPTION FOR EACH EGRESS LIGHT FIXTURE OR A UL 924 LISTED POWER PACKS FOR
GROUPS OF LIGHT FIXTURES. FOR OTHER LIGHTING CONTROL SYSTEMS THAT DO NOT HAVE A “FOR USE WITH GENERATOR SUPPLY EM POWER”
OPTION FOR DESIGNATED EGRESS LIGHT FIXTURES, PROVIDE A GENERATOR TRANSFER DEVICES EQUIVALENT TO BODINE GTD OR ITOA ETS FOR
EACH INDIVIDUAL OR GROUPS OF LIGHT FIXTURES DEPENDING UPON THE APPLICATION. REFER TO DRAWINGS AND LIGHT FIXTURES SCHEDULE. ALL
EGRESS LIGHT FIXTURES SHALL BE SWITCHED OFF WITH OTHER NORMAL-POWERED LIGHT FIXTURES DURING NORMAL OPERATION, BUT POWERED
“FULL ON” DURING AN EMERGENCY OPERATION.
ELECTRIC WATER COOLERS AND VENDING MACHINES: PROVIDE A POWER PACK FOR EACH WATER COOLER OR VENDING MACHINE BRANCH
CIRCUIT. PROGRAM POWER PACKS TO SWITCH OFF ELECTRIC WATER COOLERS AT 11:00 PM AND BE SWITCHED ON AT 6:00 AM, OR AS OTHERWISE
REQUESTED BY THE DISTRICT.
LOW VOLTAGE CABLES: PROVIDE CABLES IN TYPES AND SIZES IN ACCORDANCE WITH ALL MANUFACTURER'S WRITTEN INSTRUCTIONS AND
RECOMMENDATIONS. CABLES SHALL BE PLENUM RATED AND SUPPORTED BY J-HOOKS ATTACHED TO LIGHT FIXTURE DROP WIRES AT 12” ABOVE
RECESSED LAY-IN LIGHT FIXTURES. SECURE CABLES AT A SPACING OF NOT MORE THAN 60” ON CENTERS. PROVIDE J-HOOKS SUPPORTED FROM
ALL-THREAD AS MAY BE REQUIRED TO MEET SPACING CRITERIA. INSTALLATION SHALL MEET ALL APPLICABLE REQUIREMENTS OF THE NEC 300.11.
ALL CABLES SHALL BE ROUTED IN A NEAT WORKMANLIKE MANNER PARRALLEL AND/OR PERPENDICULAR TO CEILING GRIDS.
SHOP DRAWINGS AND PRODUCT DATA:
PRODUCT DATA: PROVIDE PRODUCT DATA FOR ALL SYSTEM COMPONENTS CLEARLY DELINEATING THE DEVICES WHICH ARE TO BE PROVIDED.
SHOP DRAWINGS: PROVIDE 1/8” SCALED 30” X 42” AUTOCAD DRAWINGS SHOWING THE LIGHTING CONTROL SYSTEM DEVICES PLACED ON THE
CEILING AND FLOOR PLANS. OBTAIN FLOOR AND CEILING PLANS FROM THE ARCHITECT. DRAWINGS SHALL INCLUDE COMPLETE LINE AND LOW
VOLTAGE INTERCONNECTION REQUIREMENTS. PROVIDE SEPARATE LINE AND LOW VOLTAGE DRAWINGS AS MAY BE REQUIRED FOR CLARITY. LOW
VOLTAGE DRAWING SHALL INCLUDE LENGTHS OF ALL CABLES. INCLUDE COMPLETE WIRING DIAGRAMS, ONE-LINE DIAGRAMS, DETAILS, ETC.
PROGRAMMING SCHEDULES: PROVIDE COMPLETE SEQUENCING AND PROGRAMMING SCHEDULES FOR ALL DEVICES, ZONES, AND SCENCES.
RECORD DRAWINGS: AT THE COMPLETION OF THE PROJECT, PROVIDE UPDATED SHOP DRAWINGS INCLUDING ALL CHANGES MADE DURING
CONSTRUCTION. INDICATE EXACT LOCATION BY DIMENSION OF ALL POWER PACKS AND OTHER DEVICES MOUNTED ABOVE ACCESSIBLE CEILINGS.
WARRANTY: WARRANTY ALL WORK INCLUDING PARTS AND LABOR FOR A PERIOD OF ONE YEAR.
PROGRAMMING: PROGRAMNG ALL SYSTEMS AS DIRECTED BY THE ELECTRICAL ENGINEER. MEET WITH THE ELECTRICAL ENGINEER AT THEIR OFFICE
PRIOR TO PREPARATION OF SHOP DRAWINGS TO DISCUSS SPECIFIC PROGRAMMING AND ZONING REQUIREMENTS. EACH NETWORKED OR
STANDALONE SYSTEM SHALL BE PROGRAMMED TO REVERT BACK TO ITS NORMAL “ON” POSITION ONE HOUR AFTER SELECTING A SCENE OR
RAISING OR LOWERING A LIGHTING ZONE.
COMMISSIONING: COMMISSION EACH PORTION OF THE LIGHTING CONTROL SYSTEMS AT THE COMPLETION OF THE PROJECT TO VERIFY THAT THE
SYSTEM PERFROMS AS INTENDED. COORDINATE COMMISSION SERVICES WITH COMMISSIONING AGENT. ASSIST THE CANYONS SCHOOL DISTRICT IN
PROGRAMMING AND MAPPING THE SYSTEM FOR INTEGRATION INTO THE BACNET BUILDING MANAGEMENT SYSTEM TO THEIR SATISFACTION.
RETRO-COMMISSIONING: DURING THE ONE YEAR WARRANTY PERIOD, PROVIDE RETRO-COMMISSIONING SERVICES AT THREE MONTH, SIX MONTH,
NINE MONTH, AND ONE YEAR MARKS. PROVIDE AT LEAST 8 HOURS OF COMMISSIONING SERVICE FOR EACH OF THE FOUR RETRO-COMMISSIONING
PERIODS. THIS WILL INCLUDE MEETING WITH THE CANYONS SCHOOL DISTRICT TO RECEVIE FEEDBACK ON THE SYSTEM AND MAKING CHANGES TO
THE SYSTEM INCLUDING PROGRAMMING, TASK TUNING, ETC.
TRAINING: PROVIDE EIGHT HOURS OF TRAINING FROM A FACTORY TRAINED AND CERTIFIED TECHNICIAN AT THE COMPLETION OF THE PROJECT.
SCHEDULE TRAIING WITH THE CANYONS SCHOOL DISTRICT.
BIDDING REQUIREMENTS: BIDDERS SHALL BREAK OUT THE LIGHT FIXTURE PACKAGE SEPARATE FROM THE LIGHTING CONTROL SYSTEM. ALL SPECIAL
FEATURES PERTAINING TO LIGHTING CONTROLS ASSOCIATED WITH THE LIGHT FIXTURES SHALL BE CONSIDERED LIGHTING CONTROLS. BIDDERS
WHO DO NOT CONFORM TO THIS REQUIREMENT MAY BE DISQUALIFIED.
1. THE LIGHTING CONTROLS AS SHOW ARE DOUGLAS LIGHTING CONTROLS.
NO OTHERS SYSTEMS WILL BE APPROVED.
2. COORDINATE ALL REQUIREMENTS, CONNECTIONS AND CABLE TYPE WITH
THE SUPPLIER PRIOR TO ANY INSTALLATION.
3. THE LIGHTING CONTROLS SYSTEM SUPPLIER SHALL PROVIDE COMPUTER
DRAFTED SHOP DRAWINGS OF THE ENTIRE LIGHTING CONTROL SYSTEM
USING FLOOR PLANS PROVIDED BY THE ENGINEER. SHOP DRAWINGS TO
INCLUDE PLANS, SECTIONS, ELEVATIONS, FINAL DEVICE LOCATIONS,
CONDUIT SIZE AND ROUTING AND ALL CONDUCTOR SIZES. TYPICAL
RISERS AND COPYING AND SUBMITTING THE CONTRACT DOCUMENTS
WILL NOT BE ACCEPTED.
4. PROVIDE CABLE SUPPORTS FROM DROP WIRE SUPPORTS (CADDY PCS2
OR APPROVED EQUIVALENT) AND SECURING CLIPS IN QUANTITIES AS MAY
BE REQUIRED FOR ROUTING OF LOW VOLTAGE LIGHTING CONTROL
CABLES. INSTALL SUPPORTS ABOVE LIGHT FIXTURES. SECURE CABLES AT
A SPACING OF NOT MORE THAN 60” ON CENTERS. SUPPLEMENT WITH
J-HOOKS SUSPENDED BY ALL-THREAD AS MAY BE REQUIRED TO MEET
SPACE CRITERIA. INSTALLATION SHALL MEET ALL APPLICABLE
REQUIREMENTS OF THE NEC 300.11. ALL CABLES SHALL BE ROUTED IN A
NEAT WORKMANLIKE MANNER PARALLEL AND PERPENDICULAR TO
STRUCTURE. SEE DETAIL 1/EL601.
5. THE RISER DIAGRAMS ON THIS SHEET REPRESENT THE MAJOR AREAS OF
THE BUILDING. THE LIGHTING CONTROL SUPPLIER SHALL PROVIDE ALL
LIGHTING CONTROLS FOR EACH SPACE AND ARE OF THE BUILDING AS CALLED
OUT IN THE LIGHTING CONTROL SYSTEM REQUIREMENTS ON SHEET EL602.
OFFICE
DIMMIMG LEADS:
PROVIDE DIMMING LEADS TO ALL FIXTURES THAT HAVE THE FOLLOWING :
1. NETWORK LOW-VOLTAGE LIGHTING CONTROL SYSTEMS.
2. STAND ALONE LOW-VOLTAGE LIGHTING CONTROL SYSTEMS.
3. ANYWHERE TASK TUNING IS REQUIRED.
4. EXTERIOR LIGHT FIXTURES AND POLE LIGHTS.
LIGHTING CONTROLS DIAGRAMS AS SHOWNARE FOR BASIC CONCEPT AND LAYOUT.LIGHTING CONTROLS SYSTEM SUPPLIER TOPROVIDE INSTALLATION DRAWINGS THATREFLECT THE ACTUAL INSTALLATIONREQUIREMENTS, WIRING AND ALL REQUIREDDEVICES. SEE ELC102 AND LIGHTING PLANSFOR ADDITIONAL INFORMATION ANDREQUIREMENTS.
OCCUPANCY SENSOR ON/OFF + RAISE LOWER
SYMBOL
ON/OFF
SCALE:2
NONE
WRC-3160
RoomController
LOAD 1
LOAD 2
LOAD 3
LOAD 4
To AdditionalDialog Devices
DIM 1
DIM 2
DIM 3
DIM 4
120-277V
Typical Dialog connectionfor room controllers
ab ab
From LCP orDRC-3160
SCALE:1
NONE
WRC-3160
Room
Controller
LOAD1 LOAD2 LOAD3 LOAD4
ToAdditionalDialogDevices
DIM1DIM
2DIM3DIM
4
120-277V
Typical Dialogconnectionfor roomcontrollers
ab ab abab
WORSDG1-P-NDataline VacancySensor
From LCPor
DRC-3160
WRC-3160
RoomController w/Emergency
Back Up
WUL-3924
LOAD 1
LOAD 2
LOAD 3
LOAD 4
LOAD 5
LOAD 6
DIM 1
DIM 2
DIM 3
DIM 4
120-277V
Typical Dialog connectionfor room controllers
ab
WSW-3528
4 SCENE CONTROL STATIONON/OFF + RAISE/LOWER
SCENE 1
SCENE 2
SCENE 3
SCENE 4
ON
OFF
WSW-3512
SINGLE CHANNEL ON/OFF
ONON
OFF
WSW-3528
4 SCENE CONTROL STATIONON/OFF + RAISE/LOWER
SCENE 1
SCENE 2
SCENE 3
SCENE 4
ON
OFF
WSW-3512
SINGLE CHANNEL ON/OFF
ONON
OFF
WOSSDU1-P-VW
OCCUPANCY SENSOR WALL SWITCH
BIDDERS SHALL BREAK OUT THE LIGHT
FIXTURE PACKAGE SEPARATE FROM THE
LIGHTING CONTROL SYSTEM. ALL
SPECIAL FEATURES PERTAINING TO
LIGHTING CONTROLS ASSOCIATED WITH
THE LIGHT FIXTURES SHALL BE
CONSIDERED LIGHTING CONTROLS.
BIDDERS WHO DO NOT CONFORM TO
THIS REQUIREMENT MAY BE
DISQUALIFIED.
SCALE:3
NONE
WRC-3160
RoomController
LOAD 1
LOAD 2
LOAD 3
LOAD 4
To AdditionalDialog Devices
DIM 1
DIM 2
DIM 3
DIM 4
120-277V
Typical Dialog connectionfor room controllers
ab
WSW-3512SINGLE CHANNEL
ON/OFF
ab
From LCP orDRC-3160
ONON
OFF
OCCUPANCY SENSORON/OFF + RAISE
LOWER
ON/OFF
WRC-3160
RoomController w/Emergency
Back Up
WUL-3924
LOAD 1
LOAD 2
LOAD 3
LOAD 4
LOAD 5
LOAD 6
DIM 1
DIM 2
DIM 3
DIM 4
120-277V
Typical Dialog connectionfor room controllers
ab
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:3
3 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
LIGHTINGCONTROLS
EL601
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
1 02/18/20 Addendum #1
1
![Page 9: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/9.jpg)
SCALE:
TYPICAL OUTLET CONVENTION
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
ISOLATED GROUND CIRCUIT.A1-40/IG
NONE
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
L6-30 PLUG TYPE. VERIFY EXACTPLUG TYPE WITH OWNER /EQUIPMENT SUPPLIER.
PROVIDE 4" SQUARE, 2-1/8" DEEPJUNCTION BOX WITH SINGLEGANG PLASTER RING ANDEXTEND 1" CONDUIT TO THEACCESSIBLE CEILING SPACETERMINATE CONDUIT IN CEILINGSPACE WITH A NYLON BUSHING.
DATA/COMMUNICATIONS SYMBOLS LEGEND:
WIFI ACCESS POINT LOCATION (YELLOW JACKET - DATA)
QTY. OF CAT. 6 CABLES.
DATA LOCATION (BLUE JACKET - DATA)
QTY. OF CAT. 6 CABLES.
1A
1
T
T
T
T
T
T
PP
PP
PP
PP PP
AT
S
K
F
K
K
TT
TT
K
T
POWER GENERAL NOTES:
1. ROUTE CONDUIT A MINIMUM OF 6" BELOW THE GRAVEL BASE.
2. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN POWER AND COMMUNICATIONS CONDUITS.
3. ALL CONDUITS THAT EXTEND THROUGH CONCRETE SHALL BE GALVANIZED RIGID CONDUIT AND SHALL BE WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.
4. ALL CONDUIT ELBOWS THAT ARE LOCATED BELOW THE FLOOR SLAB SHALL BE GALVANIZED RIGID CONDUIT AND SHALL BE WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.
KEYED NOTES:
1. POWER AND DATA FOR TV. SEE ET DRAWING FOR EXACT LOCATION.
2. POWER AND DATA FOR A/V RACK. SEE ET DRAWINGS FOR EXACT LOCATION. DO NOT SURFACE MOUNT CONDUIT ON FITNESS ROOM WALL. ROUTE CONDUIT IN STORAGE ROOM AND ON STORAGE ROOM WALL.
3. POWER FOR VENDING MACHINE. CONFIRM EXACT LOCATION WITH THE OWNER PRIOR TO ANY ROUGH-IN.
4. DO NOT SURFACE MOUNT CONDUIT ON CORRIDOR WALL. ROUTE CONDUIT IN STORAGE ROOM AND ON STORAGE ROOM WALL.
5. REINSTALL AND RECONNECT EXISTING WIFI DEVICE. DEVICE TO FUNCTION THE SAME AS PRIOR TO THE DEMOLITION.
6. DOOR CONTROLS FOR COILING DOORS ARE PROVIDED BY THE DOOR SUPPLIER AND INSTALLED AND WIRED COMPLETELY BY THE CONTRACTOR. CONFIRM EXACT LOCATION WITH THE OWNER PRIOR TO ROUGH-IN.
7. PROVIDE EDWARDS ELECTRIC CHIME # C212-W (OR APPROVED EQUIVALENT). PROVIDE NEMA 3R PUSH BUTTON AND TRANSFORMER AS NECESSARY FOR A COMPLETE INSTALLATION. PROVIDE ALL WIRING AS REQUIRED BY THE MANUFACTURER. VERIFY LOCATION OF CHIMES WITH THE OWNER. LOCATE PUSH BUTTON AT EXISTING BUTTON LOCATION.
8. REMOVE EXISTING SURFACE MOUNTED PANEL COVER AND PROVIDE NEW FLUSH MOUNT PANEL COVER. REINSTALL EXISTING PANEL TAG.
9. CONNECT TO EXISTING CIRCUIT THAT WAS IN PLACE PRIOR TO THE DEMOLITION.
10. PROVIDE NEW 20A, 1-POLE GFCI CIRCUIT BREAKER IN SPACE CALLED OUT. RETURN EXISTING BREAKER TO OWNER.
11. ALL NEW DATA CABLING TO BE EXTENDED TO DATA ROOM 139A, UNLESS OTHERWISE DIRECTED BY THE OWNER. DATA ROOM IS APPROXIMATELY 130' TO THE WEST OF TEACHER LOUNGE B17. PROVIDE NEW 48 PORT PATCH PANEL AND JACKS AS NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ONE PATCH CORD PER CABLE INSTALLING AT THE PATCH PANEL AND FIELD JACK. CONFIRM LENGTHS WITH OWNER.
12. WIRELESS ACCESS POINT AND MOUNTING HARDWARE ARE FURNISHED BY THE OWNER AND INSTALLED AND CONNECTED BY THE CONTRACTOR. CONFIRM EXACT LOCATION WITH THE OWNER.
13. DATA FOR WIRELESS ACCESS POINT. MOUNT ABOVE CEILING.
14. INTERLOCK WITH HOOD CONTROLS. COORDINATE WORK WITH HOOD INSTALLER.
15. PROVIDE NEW NEMA 0 STARTER BUCKET IN EXISTING MCC. NEW BUCKET TO BE THE SAME MANUFACTURER AND INTERRUPTING CURRENT AS THE EXISTING INSTALLED. CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS. PROVIDE ADDITIONAL CONTACTS FOR CONNECTIONS TO HOOD SYSTEM AND TO SHUNT-TRIP UNIT UPON FIRE ALARM OR HOOD SUPPRESSION SYSTEM ACTIVATION.
16. PROVIDE NEW NEMA 0 STARTER BUCKET IN EXISTING MCC. NEW BUCKET TO BE THE SAME MANUFACTURER AND INTERRUPTING CURRENT AS THE EXISTING INSTALLED. CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS. PROVIDE ADDITIONAL CONTACTS TO CONNECT TO HOOD SYSTEM.
17. SWITCH WITH LIGHTS. SEE LIGHTING PLAN.
18. PROVIDE NEW 30 AMP, 3-PHASE CIRCUIT BREAKER FOR AIR HANDLER. NEW CIRCUIT BREAKER TO BE OF THE SAME MANUFACTURER AND INTERRUPTING CURRENT AS THE EXISTING INSTALLED. CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS.
19. RECONNECT FIRE/SMOKE DAMPERS TO EXISTING BRANCH CIRCUIT THAT WAS IN PLACE PRIOR TO THE DEMOLITION.
#
65
B
EP101 1
1
EP401
65
B
2
'K3'
'K2'
'K1'
CORRIDOR
B15
FITNESS ROOM
B11
BOYS
B41
GIRLS
B40
TEACHER LOUNGE
B17SERVING
B18
KITCHEN
B39
FREEZER
B33
REFRIGERATOR
B32
OFFICE
B37
TOILET
B36
LOCKERS
B35
LAUNDRY
B34
RECEIVING
B29
DISH WASH
B31
'B1'
GYMNASIUM
A41
DRY FOOD STORAGE
B38
STORAGE
B13'B3'
'ACC'
'BY''BYY'
8
5
+60"
1
5
3 3
4 4
3
2
+60"
'B2'
'BX'
7
7
7
7
7
7
7
6
6
5
5
1+72"
+72"
+72"
+72"
+72" 1
1
1
1
11
1
1
1
1
1
1 1
1
1
1
B3-1 B3-1 B3-1
B3-2B3-2B3-8
B3-8
B3-7
B3-7
B3-7
B3-7
B1-5
10
B3-10
B3-10 B3-12 B3-12
B3-6
1A
13
12
K3-17
K3-19
K3-15
K3-19
K3-13
K3-11
K3-9
K3-7
K3-21
K3-21
K3-23
K3-23
B1-18
B1-18
B1-15
B1-15
B1-7 B1-7
B1-
9
7
B2-15
B2-17
10
10
B2-21B2-19
10 10
1A
13
12
1A
13121A
13
12
K3-25
M MP
11
11
11
11
11
'MCC'
'EM'
'EM2'
'EM3'
MAU2
MAU1
(ON ROOF)
(ON ROOF)
AC1
(ON ROOF)
AC1
K3-8
WP
WP
K3-31
1414
MCCMCC
1515
WPWP
K3-31K3-31
14
MCCMCC
14
1616 WPWP
EF4
EF3
(ON ROOF) (ON ROOF)
BYY-14
18
WP
K3-31
RT1
(ON ROOF)
14
K3-29
WPWP
K3-
31
EF5
(ON ROOF)
WP
WP
B3-3
B3-11
EF1
(ON ROOF)
19
WP
WP
B1-17
B1-23
EF6
(ON ROOF)
EF2
K3-27
17
1
B3-26 B3-26 B3-261
B1-22B1-20
B1-25B1-25
B2-14
B1-35
B1-33
B1-31
B1-24B1-24
B1-32
B2-11
PP PP
10
10
10 10
GFCIGFCI
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:3
5 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
POWER PLAN
EP101
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
4' - 0" 8' - 0" 16' - 0"
1/8" = 1'-0"
POWER PLAN
0
SCALE:
1' - 0" 2' - 0" 4' - 0"
1/2" = 1'-0"1
FACULTY 15 - SOUTH POWER ELEVATION
N
1 02/18/20 Addendum #1
![Page 10: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/10.jpg)
SCALE:
TYPICAL OUTLET CONVENTION
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
ISOLATED GROUND CIRCUIT.A1-40/IG
NONE
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
L6-30 PLUG TYPE. VERIFY EXACTPLUG TYPE WITH OWNER /EQUIPMENT SUPPLIER.
PROVIDE 4" SQUARE, 2-1/8" DEEPJUNCTION BOX WITH SINGLEGANG PLASTER RING ANDEXTEND 1" CONDUIT TO THEACCESSIBLE CEILING SPACETERMINATE CONDUIT IN CEILINGSPACE WITH A NYLON BUSHING.
DATA/COMMUNICATIONS SYMBOLS LEGEND:
WIFI ACCESS POINT LOCATION (YELLOW JACKET - DATA)
QTY. OF CAT. 6 CABLES.
DATA LOCATION (BLUE JACKET - DATA)
QTY. OF CAT. 6 CABLES.
1A
1
CO
LV2
LV2
LV4D
LV2
VS
Z Z II
K
FF
Z
K
CO
F
K
B3-2B3-2B3-8
B3-8
B3-10 B3-12 B3-12
B3-6
B3-7
B3-7
+60"
5
41
21
110cd 6 FITNESS ROOM
B11
STORAGE
B13 'B3'
'ACC'
'BY''BYY'
7 8
1A
18
6
CR1
CR1
CR1
FITNESS ROOM
B11
STORAGE
B13
BYY-8
1
2
GA1
KEYED NOTES:
1. UP TO LIGHT FIXTURES FOR STORAGE ABOVE.
2. SEE EL101 FOR CONTINUATION.
3. DOWN TO FITNESS ROOM FIXTURES.
4. POWER AND DATA FOR A/V RACK. SEE ET DRAWINGS FOR EXACT LOCATION. DO NOT SURFACE MOUNT CONDUIT ON FITNESS ROOM WALL. ROUTE CONDUIT IN STORAGE ROOM AND STORAGE ROOM WALL.
5. POWER FOR VENDING MACHINE. CONFIRM EXACT LOCATION WITH THE OWNER PRIOR TO ANY ROUGH-IN.
6. REINSTALL AND RECONNECT EXISTING WIFI DEVICE. DEVICE TO FUNCTION THE SAME AS PRIOR TO THE DEMOLITION.
7. WIRELESS ACCESS POINT AND MOUNTING HARDWARE ARE FURNISHED BY THE OWNER AND INSTALLED AND CONNECTED BY THE CONTRACTOR, CONFIRM EXACT LOCATION WITH THE OWNER.
8. DATA FOR WIRELESS ACCESS POINT. MOUNT ABOVE CEILING.
9. EXISTING FIRE ALARM DEVICE TO REMAIN IN PLACE. PROTECT FROM DAMAGE DURING CONSTRUCTION.
10. DISCONNECT POWER FROM EXISTING ELEVATOR CONTROLLER. REMOVE CONDUCTORS AND CONDUIT BACK TO DISCONNECT.
11. DISCONNECT POWER FROM EXISTING ELEVATOR CONTROLLER. EXISTING BRANCH CIRCUIT TO REMAIN IN PLACE FOR REUSE.
12. DISCONNECT PHONE LINE FROM EXISTING ELEVATOR CONTROLLER. EXISTING PHONE LINE TO REMAIN IN PLACE FOR REUSE.
13. EXISTING KEY SWITCH TO REMAIN IN PLACE. PROTECT FROM DAMAGE DURING CONSTRUCTION.
14. SEE ONE-LINE DIAGRAM AND EQUIPMENT SCHEDULE FOR FEEDER REQUIREMENTS.
15. PROVIDE NEW 60 AMP FUSES IN EXISTING DISCONNECT.
16. RECONNECT EXISTING PHONE LINE TO NEW ELEVATOR CONTROLLER. PHONE LINE TO FUNCTION THE SAME AS PRIOR TO THE DEMOLITION.
17. RECONNECT EXISTING KEYED SWITCH TO ELEVATOR CONTROLLER AS DIRECTED BY THE ELEVATOR INSTALLER. CONFIRM PRIOR TO ROUGH-IN.
18. PROVIDE NEW FIRE ALARM INITIATING DEVICE. NEW DEVICE TO BE THE SAME MANUFACTURE AS THE EXISTING INSTALLED. CONNECT TO ADDRESSABLE LOOP AS DIRECTED BY THE FIRE ALARM SUPPLIER. CONFIRM PRIOR TO THE ROUGH-IN.
19. HEAT DETECTOR TO HAVE A LOWER TEMPERATURE SETTING THAN THE SPRINKLER HEAD IN THE SPACE.
20. EXISTING LIGHTING AND POWER IN THIS SPACE TO REMAIN. PROTECT FROM DAMAGE DURING CONSTRUCTION.
21. DISCONNECT, REMOVE AND DISPOSE OF EXISTING RECEPTACLE. EXISTING BRANCH CIRCUIT TO REMAIN IN PLACE FOR REUSE.
22. PROVIDE NEW RECEPTACLE AS SHOWN. RECONNECT TO EXISTING BRANCH CIRCUIT THAT WAS IN PLACE PRIOR TO THE DEMOTION.
#
DD
19
18
18
17
1918
16
14 15
1
M
EM2-14ELEV1
221
D
18
17
STORAGE
B45
B3-7
6
18
6
STORAGE
B45
3
CR1
CR1
CR1
D
20
9
13
11
10
20
12
EM2-14
1
M
211
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:3
8 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
BIDALTERNATIVES
EP102
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
SCALE: 1/8" = 1'-0"1
FITNESS POWER AND SYSTEMS PLAN BID ALTERNATE #1
SCALE: 1/8" = 1'-0"2
FITNESS LIGHTING PLAN - BID ALTERNATE #1
SCALE: 1/8" = 1'-0"6
FIRST FLOOR ELEVATOR ELECTRICAL PLAN - BID ALTERNATE #3
SCALE: 1/8" = 1'-0"7
BASEMENT ELEVATOR ELECTRICAL PLAN - BID ALTERNATIVE #3
SCALE: 1/8" = 1'-0"3
STORAGE POWER AND SYSTEMS PLAN - BID ALTERNATE #1
SCALE: 1/8" = 1'-0"4
STORAGE LIGHTING PLAN - BID ALTERNATE #1
SCALE: 1/8" = 1'-0"5
FIRST FLOOR ELEVATOR ELECTRICAL DEMOLITION PLAN - BIDALTERNATE #3
1 02/18/20 Addendum #1
1
![Page 11: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/11.jpg)
KITCHEN GENERAL NOTES:
1. COORDINATE EXACT LOCATION, TERMINATIONS, AND
MOUNTING HEIGHTS WITH EQUIPMENT MANUFACTURER
DRAWINGS AND OWNER IN FIELD PRIOR TO ANY
INSTALLATION. REFER TO THE EQUIPMENT
INSTALLATION DRAWINGS FOR ADDITIONAL
INFORMATION.
2. VERIFY ALL MOUNTING HEIGHTS PRIOR TO INSTALLATION
WITH THE EQUIPMENT INSTALLER/SUPPLIER.
3. CONTRACTOR SHALL COORDINATE EXACT ELECTRICAL
REQUIREMENTS WITH EQUIPMENT MANUFACTURER FOR
EACH SPECIFIC MODEL AND PIECE OF EQUIPMENT.
PROVIDE ELECTRICAL SERVICE AS REQUIRED.
4. ALL COVER PLATES IN THE KITCHEN SHALL BE STAINLESS
STEEL.
5. THE CONTRACTOR SHALL PROVIDE ALL DISCONNECT
SWITCHES, STARTERS, ETC. AS REQUIRED BY NEC. VERIFY
ALL ELECTRICAL REQUIREMENTS WITH THE EQUIPMENT
INSTALLER/SUPPLIER PRIOR TO ROUGH-IN.
6. THE ELECTRICAL CONTRACTOR TO PROVIDE ALL
HARDWIRED CONNECTIONS TO EQUIPMENT.
7. PROVIDE WATERTIGHT FITTINGS, BOXES, COUPLINGS, ETC.
IN ALL PREP AREAS THAT ARE EXPOSED TO SPRAY DOWN.
8. ANY CONNECTION TO EQUIPMENT SHALL BE MADE USING
SEALTIGHT CONDUIT AND WATERTIGHT FITTINGS.
9. ALL DISCONNECT SWITCHES LOCATED IN THE KITCHEN
AREAS SHALL BE RATED FOR SPRAY DOWN, NEMA 4X
STAINLESS STEEL.
10. ALL EQUIPMENT ROUGH-IN REQUIREMENTS SHALL
COORDINATED WITH THE EQUIPMENT SUPPLIER PRIOR TO
ANY ROUGH-IN. CONTRACTOR TO OBTAIN CUT SHEETS FOR
EACH PIECE OF EQUIPMENT FROM THE EQUIPMENT
SUPPLIER AND VERIFY EXACT ROUGH-IN LOCATIONS. IF THE
CONTRACTOR FAILS TO COORDINATE THE LOCATIONS WITH
THE SUPPLIER, THE CONTRACTOR FIX THE ROUGH-IN AT NO
ADDITIONAL COST TO THE OWNER.
SCALE:
TYPICAL ELECTRICAL SHUT-TRIP DETAILNONE
C
PROVIDE MICRO SWITCH
PROTECTION CYLINDER
WITH NORMALLY OPEN
ELECTRICAL PANEL
CONTACT AT FIRE
120V GAS SOLENOID (CLOSE)
VERIFY EXACT LOCATION.
#12 CU. THRU-OUT
CIRCUIT TO NEAREST
AVAILABLE 120V POWER.
SHUNT TRIP COIL C
TYP.
TO EQUIPMENT BELOW HOOD.SEE PANEL SCHEDULES FOR EQUIPMENT.
SCALE:
TYPICAL OUTLET CONVENTION
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
ISOLATED GROUND CIRCUIT.A1-40/IG
NONE
A1-40 DESIGNATION OF CIRCUIT.WIRE COMPLETE.
L6-30 PLUG TYPE. VERIFY EXACTPLUG TYPE WITH OWNER /EQUIPMENT SUPPLIER.
PROVIDE 4" SQUARE, 2-1/8" DEEPJUNCTION BOX WITH SINGLEGANG PLASTER RING ANDEXTEND 1" CONDUIT TO THEACCESSIBLE CEILING SPACETERMINATE CONDUIT IN CEILINGSPACE WITH A NYLON BUSHING.
DATA/COMMUNICATIONS SYMBOLS LEGEND:
WIFI ACCESS POINT LOCATION (YELLOW JACKET - DATA)
QTY. OF CAT. 6 CABLES.
DATA LOCATION (BLUE JACKET - DATA)
QTY. OF CAT. 6 CABLES.
1A
1
CONNECTION REQUIREMENTSROUGH-IN REQUIREMENTS REMARKS
ELECTRICAL ROUGH-IN/FINAL CONNECTION SCHEDULE
ITEMS A THROUGH I. NOTE #4.
INTERCONNECT WITH SHUNT TRIPBREAKERS FOR HOOD EQUIPMENT.PROVIDED WITH FIVE CONTACTS.
PROVIDED WITH HOOD. NOTE #5.
AND TO HOOD LIGHTS
CONNECTION REQUIREMENTSROUGH-IN REQUIREMENTS REMARKS
ELECTRICAL ROUGH-IN/FINAL CONNECTION SCHEDULE
NOTE #1: VERIFY THE REQUIREMENTS OF THE POS SYSTEM WITH THE SUPPLIER INCLUDING ELECTRICAL REQUIREMENTS AND THE INTERCONNECTION REQUIREMENTS.
NOTE #2: PROVIDE DATA CONDUIT AS REQUIRED BY POS SUPPLIER. VERIFY INTERCONNECTION REQUIREMENTS BETWEEN COMPONENTS OF SYSTEM.
NOTE #5: ELECTRICIAN TO FIELD WIRE LOW VOLTAGE FROM EACH TEMPERATURE CONTROLLER TO HEAT SENSOR PROVIDED WITH HOOD AT EACH EXHAUST RISER.
ELECTRICIAN TO INTERLOCK CONTACTORS OR STARTERS SPECIFIED BY MECHANICAL SYSTEM TO THE CONTACTS AT THE TERMINAL BLOCK TO OPERATE FAN.
HP: HORSE POWER
AMP: AMPERESDFA: DROP FROM ABOVE
J-BOX: JUNCTION BOX CONNECTION
C&P: CORD AND PLUG CONNECTION
ARE FURNISHED AS PART OF THE SYSTEM BY THE KEC. THE ELECTRICAL CONTRACTOR IS TO INSTALL THESE CORDS AND CORD CAPS TO
NOTE #4: ROUGH-INS ARE FED FROM ITEM #K-39 ENERGY DISTRIBUTION SYSTEM. HEAVY DUTY CORDS WITH RESTRAINING DEVICES AND CORD CAPS
EACH ITEM AS REQUIRED. REMOVE ANY FACTORY CORDS, IF INSTALLED ON INDIVIDUAL ITEMS. ELECTRICAL CONTRACTOR SHALL FURNISH ALL
ADDITIONAL MATERIAL AS REQUIRED AND MAKE ALL INTERCONNECTIONS AS REQUIRED.
NOTE #3: RUN FROM ROUGH-IN TO CONNECTION AT UNDERSIDE OF SERVING SHELF/BREATH GUARD, IN SERVING SHELF/BREATH GUARD SUPPORT LEG.
ICE MAKER/DISPENSEROUTLETE-101 :#K83+18 115/60/1 -C&P11 AMP
POS COMPUTERDATA OUTLETE-100 :#E1+24" -GROMMET TO CONNECTION.NOTE #2. RUN CABLE THROUGH--
POS COMPUTEROUTLETE-99 :#E1+24" 120/60/1GROMMET TO OUTLETNOTE #1. RUN CORD THROUGHC&PVERIFY
COUNTER REFRIGERATOROUTLETE-98 :#K77+18" 115/60/1TO OUTLET IN COUNTER BASE.RUN CORD THROUGH GROMMETC&P2.7 AMP
HEAT LAMPJUNCTION BOXE-97 :#K74+18" 120/60/1CONTROLS AT APRON.NOTE #3. INTERCONNECTJ-BOX8.18 AMP
HOT FOOD WARMERJUNCTION BOXE-96 :#K73+18" 208/60/3 INTERCONNECT CONTROLS.J-BOX3720 WATT
WORK COUNTERCONVENIENCE OUTLETE-95 :#K66+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-94 :#K66+48" 120/60/1 -C&P10 AMP
HOT FOOD WARMING CABINETOUTLETE-93 :#K64+18" 115/208/60/1 -C&P7.8 AMP
REACH-IN REFRIGERATOROUTLETE-92 :#K65+90" 115/60/1 -C&P5.5 AMP
NOT USEDE-91
POS COMPUTERDATA OUTLETE-90 :#E1+24" -GROMMET TO CONNECTION.NOTE #2. RUN CABLE THROUGH--
POS COMPUTEROUTLETE-89 :#E1+24" 120/60/1GROMMET TO OUTLETNOTE #1. RUN CORD THROUGHC&PVERIFY
COUNTER REFRIGERATOROUTLETE-88 :#K77+18" 115/60/1TO OUTLET IN COUNTER BASE.RUN CORD THROUGH GROMMETC&P2.7 AMP
HEAT LAMPJUNCTION BOXE-87 :#K74+18" 120/60/1CONTROLS AT APRON.NOTE #3. INTERCONNECTJ-BOX8.18 AMP
HOT FOOD WARMERJUNCTION BOXE-86 :#K73+18" 208/60/3 INTERCONNECT CONTROLS.J-BOX3720 WATT
WORK COUNTERCONVENIENCE OUTLETE-85 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-84 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-83 :#K63+48" 120/60/1 -C&P10 AMP
HOT FOOD WARMING CABINETOUTLETE-82 :#K64+18" 115/208/60/1 -C&P7.8 AMP
REACH-IN REFRIGERATOROUTLETE-81 :#K65+90" 115/60/1 -C&P5.5 AMP
NOT USEDE-80
POS COMPUTERDATA OUTLETE-79 :#E1+24" -GROMMET TO CONNECTION.NOTE #2. RUN CABLE THROUGH--
POS COMPUTEROUTLETE-78 :#E1+24" 120/60/1GROMMET TO OUTLETNOTE #1. RUN CORD THROUGHC&PVERIFY
COUNTER REFRIGERATOROUTLETE-77 :#K77+18" 115/60/1TO OUTLET IN COUNTER BASE.RUN CORD THROUGH GROMMETC&P2.7 AMP
HEAT LAMPJUNCTION BOXE-76 :#K74+18" 120/60/1CONTROLS AT APRON.NOTE #3. INTERCONNECTJ-BOX8.18 AMP
HOT FOOD WARMERJUNCTION BOXE-75 :#K73+18" 208/60/3 INTERCONNECT CONTROLS.J-BOX3720 WATT
HOT FOOD WARMING CABINETOUTLETE-74 :#K64+18" 115/208/60/1 -C&P7.8 AMP
REACH-IN REFRIGERATOROUTLETE-73 :#K65+90" 115/60/1 -C&P5.5 AMP
WORK COUNTERCONVENIENCE OUTLETE-72 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-71 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-70 :#K63+48" 120/60/1 -C&P10 AMP
NOT USEDE-69
POS COMPUTERDATA OUTLETE-68 :#E1+24" -GROMMET TO CONNECTION.NOTE #2. RUN CABLE THROUGH--
POS COMPUTEROUTLETE-67 :#E1+24" 120/60/1GROMMET TO OUTLETNOTE #1. RUN CORD THROUGHC&PVERIFY
COUNTER REFRIGERATOROUTLETE-66 :#K77+18" 115/60/1TO OUTLET IN COUNTER BASE.RUN CORD THROUGH GROMMETC&P2.7 AMP
REFRIGERATED COLD PANOUTLETE-65 :#K72+18" 115/60/1TO OUTLET.INTERCONNECT SWITCH AT APRONJ-BOX7 AMP
HEAT LAMPJUNCTION BOXE-64 :#K74+18" 120/60/1CONTROLS AT APRON.NOTE #3. INTERCONNECTJ-BOX8.18 AMP
HOT FOOD WARMERJUNCTION BOXE-63 :#K73+18" 208/60/3 INTERCONNECT CONTROLS.J-BOX3720 WATT
HOT FOOD WARMING CABINETOUTLETE-62 :#K64+18" 115/208/60/1 -C&P7.8 AMP
REACH-IN REFRIGERATOROUTLETE-61 :#K65+90" 115/60/1 -C&P5.5 AMP
NOT USEDE-60
POS COMPUTERDATA OUTLETE-59 :#E1+24" -GROMMET TO CONNECTION.NOTE #2. RUN CABLE THROUGH--
POS COMPUTEROUTLETE-58 :#E1+24" 120/60/1GROMMET TO OUTLETNOTE #1. RUN CORD THROUGHC&PVERIFY
COUNTER REFRIGERATOROUTLETE-57 :#K77+18" 115/60/1TO OUTLET IN COUNTER BASE.RUN CORD THROUGH GROMMETC&P2.7 AMP
REFRIGERATED COLD PANOUTLETE-56 :#K72+18" 115/60/1TO OUTLET.INTERCONNECT SWITCH AT APRONJ-BOX7 AMP
HEAT LAMPJUNCTION BOXE-55 :#K74+18" 120/60/1CONTROLS AT APRON.NOTE #3. INTERCONNECTJ-BOX8.18 AMP
HOT FOOD WARMERJUNCTION BOXE-54 :#K73+18" 208/60/3 INTERCONNECT CONTROLS.J-BOX3720 WATT
WORK COUNTERCONVENIENCE OUTLETE-53 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-52 :#K63+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-51 :#K63+48" 120/60/1 -C&P10 AMP
EQUIPMENT DESCRIPTIONROUGH-IN TYPERI# :ITEM #HGT. VLY/CYC/PH REMARKCONNLOAD
HOT FOOD WARMING CABINETOUTLETE-50 :#K64+18" 115/208/60/1 -C&P7.8 AMP
REACH-IN REFRIGERATOROUTLETE-49 :#K65+90" 115/60/1 -C&P5.5 AMP
WORK COUNTERCONVENIENCE OUTLETE-48 :#K66+48" 120/60/1 -C&P10 AMP
WORK COUNTERCONVENIENCE OUTLETE-47 :#K66+48" 120/60/1 -C&P10 AMP
NOT USEDE-46
30 GALLON TILT SKILLET:#K43I 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P1.8 AMP
40 GALLON TILT KETTLE: CONTROLS:#K44H 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P10 AMP
CONVECTION OVEN:#K45G 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P8 AMP
CONVECTION OVEN:#K45F 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P8 AMP
MINI ROTATING RACK CONVECTION OVEN:#K42E 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P6.6 AMP
COMBI-OVEN:#K40D 208/60/1NOTE #4.CONNECT TO UDS SYSTEM.J-BOX3.85 AMP
STEAMER:#K37C 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P300 WATT
CONVECTION OVEN:#K36B 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P8 AMP
CONVECTION OVEN:#K36A 120/60/1NOTE #4.CONNECT TO UDS SYSTEM.C&P8 AMP
EXHAUST HOOD: HEAT SENSOR SYSTEMTEMPERATURE SENSORE-44 :#K34+48" CONTROL WIREBOX PROVIDED WITH HOOD.INTERCONNECT FROM CONTROL--
EXHAUST HOOD: HEAT SENSORJUNCTION BOXE-43 :#K34+30" 120/60/1SENSOR AND CONTROL BOXINTERCONNECT TO DUCT HEATJ-BOX15 AMP
GAS SHUT OFF VALVEJUNCTION BOXE-42 :#K35DFA 120/60/1AND HOOD CONTROLS AS REQ'D.CONNECT TO GAS SHUT OFFJ-BOX1 AMP
UTILITY DISTRIBUTION SYSTEMJUNCTION BOXE-45 :#K39DFA 120-208/60/3SYSTEM TO POWER FOLLOWINGCONNECT MAIN POWER TO UDSJ-BOX50 AMP
EXHAUST HOODJUNCTION BOXE-41 :#K34+30" 120/60/1PANEL TO MECHANICAL SYSTEMINTERCONNECT FROM CONTROLJ-BOX1200 WATT
NOT USEDE-40
WORK TABLECONVENIENCE OUTLETE-39 :#K20+48" 120/60/1 -C&P10 AMP
FOOD PROCESSOROUTLETE-38 :#K22+48" 120/60/1 -C&P3.5 AMP
WORK TABLECONVENIENCE OUTLETE-37 :#K20+48" 120/60/1 -C&P10 AMP
HOT FOOD WARMING/PROOFING CABINETOUTLETE-36 :#K16+18" 120/60/1 -C&P16.7 AMP
SHEETEROUTLETE-35 :#K18+18" 120/60/1 -C&P3/4 HP
BAKERY WORK TABLECONVENIENCE OUTLETE-34 :#K13+48" 120/60/1 -C&P10 AMP
BAKERY WORK TABLECONVENIENCE OUTLETE-33 :#K13+48" 120/60/1 -C&P10 AMP
BAKERY WORK TABLECONVENIENCE OUTLETE-32 :#K13+48" 120/60/1 -C&P10 AMP
60 QUART MIXERJUNCTION BOXE-31 :#K12+18" 200-240/60/3 -J-BOX10 AMP
MICROWAVE OVENOUTLETE-30 :#K25+48" 120/60/1 -C&P16.8 AMP
WORK TABLECONVENIENCE OUTLETE-29 :#K20+48" 120/60/1 -C&P10 AMP
WORK TABLECONVENIENCE OUTLETE-28 :#K20+48" 120/60/1 -C&P10 AMP
30 QUART MIXEROUTLETE-27 :#K26+18" 120/60/1 -C&P9.5 AMP
WORK TABLECONVENIENCE OUTLETE-26 :#K27+48" 120/60/1 -C&P10 AMP
WORK TABLECONVENIENCE OUTLETE-25 :#K27+48" 120/60/1 -C&P10 AMP
WORK TABLECONVENIENCE OUTLETE-24 :#K27+48" 120/60/1 -C&P10 AMP
SLICEROUTLETE-23 :#K29+48" 120/60/1 -C&P5.6 AMP
WORK TABLECONVENIENCE OUTLETE-22 :#K23+48" 120/60/1 -C&P10 AMP
ICE MAKERJUNCTION BOXE-21 :#K30+84" 208/60/1 -J-BOX13.1 AMP
NOT USEDE-20
DISHWASHER: BOOSTER HEATERJUNCTION BOXE-19 :#K57+18" 480/60/3 -J-BOX40.1 AMP
DISHWASHER: MOTOR/CONTROLS/TANKJUNCTION BOXE-18 :#K57+18" 480/60/3 -J-BOX27.9 AMP
VENT HOOD: SWITCHSWITCH/CONTROLSE-17 :#K58+48" 120/60/1EXHAUST SYSTEM.INTERCONNECT WITH VENT HOOD--
POS COMPUTEROUTLETE-15 :#E2+18" 120/60/1 NOTE #1.C&PVERIFY
POS COMPUTERDATA OUTLETE-16 :#E2+18" - NOTE #2.--
POS COMPUTEROUTLETE-13 :#E2+18" 120/60/1 NOTE #1.C&PVERIFY
POS COMPUTERDATA OUTLETE-14 :#E2+18" - NOTE #2.--
TEMPERATURE MONITORJUNCTION BOXE-10 :#K4BDFA 120/60/1 -J-BOX2 AMP
COOLER REFRIGERATION SYSTEMDATA OUTLETE-11 :#K4BDFA -CABLE TO I.T.RUN CONDUIT FOR DATA--
WALK-IN COOLER: LIGHTS AND HEATERJUNCTION BOXE-12 :#K3DFA 115/60/1 INTERCONNECT (4) LIGHTS.J-BOX1.76 AMP
WALK-IN COOLER REF: BLOWER COILSJUNCTION BOXE-09 :#K4BDFA 115/60/1REMOTE CONDENSER.INTERCONNECT CONTROLS WITHJ-BOX1.6 AMP
WALK-IN COOLER REF: CONDENSERJUNCTION BOXE-08 :#K4ASTUB 208/60/1ON ROOF.VERIFY LOCATION OF REMOTEJ-BOX11.4 AMP
WALK-IN FREEZER: LIGHTS AND HEATERJUNCTION BOXE-07 :#K3DFA 115/60/1 INTERCONNECT (4) LIGHTS.J-BOX2.29 AMP
TEMPERATURE MONITORJUNCTION BOXE-05 :#K5BDFA 120/60/1 -J-BOX2 AMP
WALK-IN FREEZER REF: HEAT TRACEJUNCTION BOXE-04 :#K5BDFA 120/60/1 CONNECT TO DRAIN HEAT CABLE.J-BOX3 AMP
FREEZER REFRIGERATION SYSTEMDATA OUTLETE-06 :#K5BDFA -CABLE TO OFFICERUN CONDUIT FOR DATA--
WALK-IN FREEZER REF: DEFROSTJUNCTION BOXE-03 :#K5BDFA 208/60/1REMOTE CONDENSER.INTERCONNECT DEFROST WITHJ-BOX9.8 AMP
WALK-IN FREEZER REF: BLOWER COILSJUNCTION BOXE-02 :#K5BDFA 208/60/1REMOTE CONDENSER.INTERCONNECT CONTROLS WITHJ-BOX1 AMP
EQUIPMENT DESCRIPTIONROUGH-IN TYPERI# :ITEM #HGT. VLY/CYC/PH REMARKCONNLOAD
WALK-IN FREEZER REF: CONDENSERJUNCTION BOXE-01 :#K5AVER. 208/60/1UNIT IN MECHANICAL ROOM.VERIFY LOCATION OF REMOTEJ-BOX17 AMP
LL
PENETRATION TO SPLICE BOX
WITH FREEZER DEFROST.
TYPICAL COLD STORAGE ROOMS ELEC. DIAGRAM
HEATED VACUUM VENT
CEILING BY ELEC.DIVISION (TYP)
RUN ABOVE C.S.R.
C.S.R. - COLD STORAGE ROOM
EMT RIGID CONDUIT
CONDUIT & WIRING.
COLD STORAGE ROOMS. ELECTRICAL
BUILDING SERVICE TO COMPONENTS.
COMPONENTS.
ELECTRICAL DIVISION TO PROVIDE ALLBUILDING SERVICES INCLUDING J-BOXES,INTERCONNECTING CONDUIT & WIRING FROM
EYS FITTING FURNISHED WITH COLD STORAGE
& SPLICE BOXES ARE FURNISHED LOOSE WITH
DIVISION TO INSTALL ALL ITEMS FURNISHEDLOOSE INCLUDING ALL INTERCONNECTING
EVAPORATORS FOR COLD STORAGE ROOMARE FURNISHED & INSTALLED COMPLETE WITHROOM THERMOSTAT, LIQUID LINE SOLENOID &DISCONNECT SWITCH. ELECTRICAL DIVISIONTO PROVIDE INTERCONNECTING CONDUIT &WIRING FORM BUILDING SERVICE TO ALL
LIGHT FIXTURES, SWITCH BOXES, SWITCHES,
WIRE & SEAL BY ACCEPTED INDUSTRY
& EXTERIOR ESCUTCHEON PLATES.
HOLES THROUGH INSULATED PANELS ARE
EVAPORATOR FAN MOTORS FOR REFRIGER-ATORS RUN CONTINUOUSLY. DO NOT WIREINTERNALLY WITH THERMOSTAT. EVAPOR-ATOR FAN MOTORS FOR FREEZERS CYCLE
FURNISHED WITH COLD STORAGE ROOM.ELECTRICAL DIVISION TO SEAL ALL PENE-TRATIONS WITH CAULKING ON THE C.S.R.INTERIOR & EXTERIOR AND INSTALL INTERIOR
STAINLESS STEEL ESCUTCHEON PLATES &
ROOMS. ELECTRICAL DIVISION TO INSTALL,
.2
5.
J
FREEZER
S
J
J
6.S 3P4P S
A
HEATER CABLE
KW HIGH TEMP. ALARM (WHEN SPECIFIED)
S
T *****L
DRAIN LINE CABLE
L
4.
PRACTICE.
VIEWPORT &DOOR HEATER
3.
HIGH TEMP. ALARM
EVAPORATOR, TERMINAL BLOCK, ROOM THERMOSTAT, LIQUID LINESOLENOID & ELECTRIC PANEL AT COMPRESSOR RACK SUPPLIED ASPART OF THE REFRIGERATION SYSTEM. ELECTRICAL DIVISION TOFURNISH & INSTALL CONDUIT, J-BOXES AND WIRING BETWEEN COLDSTORAGE ROOM AND COMPRESSOR RACK. SEE PLAN FOR LOCATION.
110 V. ABOVE COLD STORAGE ROOM CEILINGKW LIGHTS (EACH)KW VIEWPORT & DOOR HEATER (FREEZER)
.2
.4
REFRIGERATOR
2.
(WHEN SPECIFIED)
1.
TO LIGHTS AS REQUIRED.SEE PLAN FOR QUANTITY
VERIFY KW EVAPORATOR MOTORS
110 V. ABOVE C.S.R. CEILING
J
T
J
S
*****EXTEND CONDUIT
A SWITCH
NOTES:
EXTERIORINTERIOR/
LIGHT
SS
J
*****
THERMOSTAT
JUNCTION BOX
EYS & NIPPLE FOR CEILING
LIQUID LINE SOLENOID
S
LIGHT FIXTUREVAPOR PROOF
EVAPORATOR
J
T
S
HIGH TEMP. ALARM(WHEN SPECIFIED)
REQUIRMENTS WITH POS SYSTEM SUPPLIER.)
120V, 1 PHASE, SERVICE, 10.0 AMPS, STUB AS NOTED,
FOR POS/PRE-CHECK SYSTEM STATIONS. (DEDICATED
CIRCUIT, ISOLATED GROUND, PROVIDE (ADD PHONE LINE)
EMPTY J-BOX WITH CONDUIT FOR INTERCONNECTING POS
SYSTEM, PRE-CHECK AND PRINTERS) (VERIFY ALL
POINT OF CONNECTION. UNDER NO CIRCUMSTANCES, WILL
ALL CONDUIT SHALL BE RUN ON THE EXTERIOR CEILING OF ALL
COLD STORAGE ROOMS AND SHALL PENETRATE THE CEILINGAT A POINT WHERE THE CONDUIT CAN DROP DIRECTLY TO THE
ELECTRICAL CONDUIT BE PERMITTED ON THE INTERIOR.
NOTE: WALK-IN ELECTRICAL
TO PROVIDE MINIMUM WALL FURRING IF REQUIRED.
ALL WALL MOUNT ELECTRICAL RECEPTACLE AND J-BOXES
CONDUIT SHOWING ON SURFACE OF WALLS. ARCHITECT
ARE TO BE FLUSH MOUNTED IN WALLS WITH NO EXPOSED
BRUSHED STAINLESS STEEL FURNISHED BY ELECTRICAL DIVISION.
DIVISION. CONDUIT SHALL HAVE 24" (600MM) MINIMUM RADIUS BENDS.
SYSTEM LINES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL
ALL CONDUIT RUNS INDICATED FOR REFRIGERATION, DRINK AND LIQUOR
PRE-FABRICATED COLD STORAGE ROOMS ARE FURNISHED BY THE KITCHEN
CONDUIT AND WIRE BETWEEN SWITCH, DISPOSER AND COMPONENTS.
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL INTER-CONNECTING
JUNCTION BOXES FOR INSTALLATION OF OWNER SUPPLIED I.T. EQUIPMENT
INCLUDING POS/ ELECTRONIC CASH CONTROL SYSTEM. ELECTRICAL
CONDUIT AND WIRING BETWEEN MICRO-SWITCH AND SOLENOID FUEL SHUT
REQUIREMENTS AND MANUFACTURER'S INSTRUCTIONS.
BLOCK, SWITCH, FAN DOOR SWITCH AND COMPRESSOR CONTROL PANEL.
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL ALL INTERCONNECTING
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL EMPTY CONDUIT WITH
CONDUIT AND WIRING BETWEEN KITCHEN EQUIPMENT CONTRACTOR
FURNISHED LOW TEMP COLD STORAGE ROOM EVAPORATOR TERMINAL
EQUIPMENT CONTRACTOR COMPLETE WITH SPLICE BOXES, LIGHT FIXTURES,
TO INSTALL SAME AND SHALL FURNISH AND INSTALL INTERCONNECTING
CONDUIT, WIRING SEALOFFS, SEALANT AND MAKE FINAL CONNECTIONS.
LAMPS, LIGHT SWITCHES AND DOOR HEATERS. ELECTRICAL DIVISION
ALL ELECTRICAL EQUIPMENT UNDER HOOD ACTIVATED BY FIRE
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL DISCONNECTS FOR
DIVISION TO VERIFY INSTALLATION IN ACCORDANCE WITH OWNER'S
BY THE ELECTRICAL ENGINEER/ ARCHITECT AND AS REQUIRED BY CODE.
OFF VALVE FURNISHED WITH FIRE SUPPRESSION SYSTEM SUPPLIED BY
THE KITCHEN EQUIPMENT CONTRACTOR.
PROOF VENTILATOR LIGHTS COMPLETE WITH LAMPS. INTERCONNECTING
CONDUIT, WIRING WITH WALL SWITCH FURNISHED AND INSTALLED BY THE
ADDITIONAL CONVENIENCE RECEPTACLES, TELEPHONE AND INTERCOM
KITCHEN EQUIPMENT CONTRACTOR SHALL FURNISH AND INSTALL VAPOR
KITCHEN EQUIPMENT CONTRACTOR SHALL FURNISH DISPOSER CONTROLS.
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL ALL INTERCONNECTING
JACKS AND TEMPERATURE MONITORING SYSTEM ETC.. SHALL BE LOCATED
SUPPRESSION SYSTEM.
ELECTRICAL DIVISION.
EXCEPT WHERE NOTED. RECEPTACLES AND COVER PLATES SHALL BE
DRAWINGS FOR CONSTRUCTION.
60 HERTZ, 4 WIRE SYSTEM.
ELECTRICAL PLAN SHOWS ROUGH-IN POINTS AND SCHEDULED CONNECTIONS.
KITCHEN EQUIPMENT CONTRACTOR WILL PROVIDE DIMENSIONED ROUGH-IN
ELECTRICAL SYSTEM IS DESIGNED FOR 120/208 VOLTS, 1&3 PHASE,
ELECTRICAL DIVISION SHALL FURNISH AND INSTALL ALL JUNCTION BOXES,
RECEPTACLES, COVER PLATES, PULL BOXES, CONDUIT AND WIRING
ELECTRICAL NOTES
NOTE: POS ELECTRICAL
NOTE: ELECTRICAL MOUNTING
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
JJ
JJ
JJ
JJ
JJ
J
J
J
J
J
J
J
J
J
J
J
J
J J
JJ
JJ
FF
FF
5
B
A
A
A
A
A
AAA
A
A
AA
A
A
A
A
A
A
A
A
A A
A
A
A
A
A
+90"
E- 95
E- 94
E- 93
E- 92
E- 85
E- 84
E- 83
E- 98
E- 82
E- 81
E- 88
E- 77
E- 74
E- 73
E- 72
E- 71
E- 70
E- 62
E- 61
E- 30
E- 29
E- 28
E- 26
E- 25
E- 24
E- 32E- 33E- 34E- 35E- 36
E- 37
E- 38
E- 39
E- 22 E- 23
E- 53
E- 52
E- 51
E- 48
E- 47
E- 57
E- 66
E- 65
E- 56
E- 50
E- 49+90"
+90"
+90"
+90"
E- 27
E- 54
E- 55
E- 63
E- 64
E- 75
E- 76
E- 86
E- 87
E- 96
E- 97
E- 99
E- 100
E- 90
E- 89
E- 78
E- 79
E- 68
E- 67
E- 58
E- 59
+24"
+24"
+24"
+24"
+24"
+24"
+24"
+24"
+24"
+24"
E- 31
E- 45
E- 42
+84"
E- 12
E- 9
E- 10
E- 4
E- 3
E- 2
E- 7
E- 5
E- 11
E- 6 1
1
E- 21
E- 18E- 19
E- 17
E- 43
+30"
E- 41
E- 44+30"
+48"
E- 15
E- 13
E- 16
E- 14
E- 1
E- 8
1
1
1
1
1
2
2
1
+48"
K1-32
K2-7
K1-26
K2-5
K2-3
K1-48
K1-46
K1-44
K1-42
K1-40
K1-38
K1-36
K2-7K2-4
K2-14K2-20K2-22K2-24K2-26K2-28
K1-32
K1-45
K1-20
K1-45
K1-34
K1-47
K1-41
K1-14
K1-41
K1-43
K1-21
K1-8
K1-23
K1-23
K1-25
K1-15
K1-12
K1-17
K1-17
K1-19
K2-7
K2-37
K2-35
K2-33
K2-31
K2-29
K2-27
K2-25 K1-27
K1-29
K1-31
K1-33
K1-35
K1-37
K1-39
K2-11
K2-7
K2-11K2-11
K2-30
K2-32
K2-34
K2-41
K2-39
K2-13
K2-13
K2-13
K2-9
K2-9
K2-1
K2-2K2-9
K2-9
K2-9
K2-11
+48"
K2-6
K2-36
K2-21 K2-23
K1-13
K1-11
K1-9
K1-7
K1-5
K1-3
K1-1
K2-7
K2-15
1
4
5
1
2
3
1
9
9
9
9
9
9
9
'K1'
'K2'
'K3'
8
8
M
M
7
6
EM3-1
EM3-2
EM3-5
EM3-5
EM3-5
EM3-15
EM3-15
EM3-6
EM3-6
EM3-61
1
1
KEYED NOTES:
1. INTERCONNECT TO VENT HOOD EXHAUST SYSTEM. COORDINATE ALL WORK WITH THE HOOD INSTALLER.
2. INTERCONNECT TO VENT HOOD LIGHTS. COORDINATE ALL WORK WITH THE HOOD INSTALLER.
3. INTERCONNECT WITH DUCT HEATER AND CONTROL PANEL. COORDINATE ALL WORK WITH THE KITCHEN EQUIPMENT INSTALLER.
4. PROVIDE 4" SQUARE JUNCTION BOX FOR HOOD SUPPRESSION PULL STATION. EXTEND A 3/4" CONDUIT TO THE CEILING SPACE.
5. KITCHEN TELEPHONE. CONFIRM EXACT LOCATION WITH THE OWNER PRIOR TO ANY ROUGH-IN.
6. TO DISHWASHER E-18.
7. TO BOOSTER HEATER E-19.
8. TO DISCONNECT.
9. ALL NEW DATA CABLING TO BE EXTENDED TO DATA ROOM 139A, UNLESS OTHERWISE DIRECTED BY THE OWNER. DATA ROOM IS APPROXIMATELY 130' TO THE WEST OF TEACHER LOUNGE B17. PROVIDE NEW 48 PORT PATCH PANEL AND JACKS AS NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ONE PATCH CORD PER CABLE INSTALLING AT THE PATCH PANEL AND FIELD JACK. CONFIRM LENGTHS WITH OWNER.
#
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
0 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
ENLARGEDKITCHEN POWERPLAN
EP401
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
SCALE: 1/4" = 1'-0"1
KITCHEN POWER PLAN
1 02/18/20 Addendum #1
![Page 12: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/12.jpg)
PANELBOARD SCHEDULEPANEL NAME: K1 (EXISTING) VOLTAGE: MAINS TYPE: SPD:
MOUNTING: PHASE: BUS MATERIAL: NEUTRAL:ENCLOSURE: WIRE: BUS RATING: BRANCH OCP TYPE:
DOOR STYLE: MIN. A.I.C. RATING: MCB RATING: ISOLATED GROUND:
KEYEDCIRCUIT DESCRIPTION
BREAKER LOAD CKT. CONNECTED LOAD/PHASE (VA) CKT. LOAD BREAKERCIRCUIT DESCRIPTION
KEYEDNOTE AMPS POLE TYPE # A B C # TYPE AMPS POLE NOTE
TOTAL CONNECTED LOAD PER PHASE (VA):TOTAL ESTIMATED DEMAND LOAD PER PHASE (VA):
TOTAL ESTIMATED DEMAND LOAD PER PHASE (AMPS):
TYPE LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
208Y/120 MLO NONE
SURFACE 3 ALUMINUM 100% RATEDNEMA 1 4 225 AMPS BOLT-ON CBs
STANDARD CONTRACTOR TO VERIFY NONE NO
6,8 WORK COUNTER C.O. E-47 20 1 K 1 1,200 1,240 2 K 20 3 HOT FOODK WARMER K-54 6,106,8 WORK COUNTER C.O. E-48 20 1 K 3 1,200 1,240 4 K - - - -
1,6,8 REACH-IN REFRIGERATOR E-49 20 1 K 5 660 1,240 6 K - - - -1,6,8 WARMING CABINET E-50 20 1 K 7 936 1,240 8 K 20 3 HOT FOODK WARMER K-63 6,10
WORK COUNTER C.O. E-51 20 1 K 9 1,200 1,240 10 K - - - -WORK COUNTER C.O. E-52 20 1 K 11 1,200 1,240 12 K - - - -WORK COUNTER C.O. E-53 20 1 K 13 1,200 1,240 14 K 20 3 HOT FOODK WARMER K-75 6,8
1,6,8 HEAT LAMP E-55 20 1 K 15 982 1,240 16 K - - - -1,6,8 COLD PAN E-56 / REFRIG E-57 20 1 K 17 1,200 1,240 18 K - - - -
POS E-58 20 1 K 19 1,200 1,240 20 K 20 3 HOT FOODK WARMER K-86 6,81,6,8 HEAT LAMP E-64 20 1 K 21 982 1,240 22 K - - - -1,6,8 COLD PAN E-65 / REFRIG E-66 20 1 K 23 1,200 1,240 24 K - - - -
POS E-67 20 1 K 25 1,200 1,240 26 K 20 3 HOT FOODK WARMER K-96 6,81,6,8 REACH-IN REFRIGERATOR E-61 20 1 K 27 660 1,240 28 K - - - -1,6,8 WARMING CABINET E-62 20 1 K 29 936 1,240 30 K - - - -
WORK COUNTER C.O. E-70 20 1 K 31 1,200 1,200 32 K 20 1 COLD PAN E-97 / REFRIG E-98 1,6,8WORK COUNTER C.O. E-71 20 1 K 33 1,200 1,200 34 K 20 1 POS E-99 6,8WORK COUNTER C.O. E-72 20 1 K 35 1,200 660 36 K 20 1 REACH-IN REFRIGERATOR E-81 1,6,8
1,6,8 REACH-IN REFRIGERATOR E-73 20 1 K 37 660 936 38 K 20 1 WARMING CABINET E-82 1,6,81,6,8 WARMING CABINET E-74 20 1 K 39 936 1,200 40 K 20 1 WORK COUNTER C.O. E-83 6,81,6,8 COLD PAN E-76 / REFRIG E-77 20 1 K 41 1,200 1,200 42 K 20 1 WORK COUNTER C.O. E-84 6,86,8 POS E-78 20 1 K 43 1,200 1,200 44 K 20 1 WORK COUNTER C.O. E-85 6,8
1,6,8 COLD PAN E-87 / REFRIG E-88 20 1 K 45 1,200 660 46 K 20 1 REACH-IN REFRIGERATOR E-92 1,6,86,8 POS E-89 20 1 K 47 1,200 936 48 K 20 1 WARMING CABINET E-93 1,6,8
18,332 17,620 17,79211,916 11,453 11,565
99 95 96
P SUB-PANEL SUB-PANEL LOADS BROKEN OUT BY LOAD CLASIFICATION BELOWR RECEPTACLES - - - TOTAL CONNECTED LOAD: 53,744 VAL LIGHTING - - - 25% OF LARGEST MOTOR: -C CONTINUOUS - - - TOTAL ESTIMATED DEMAND LOAD: 34,934 VAE EQUIPMENT - - - TOTAL ESTIMATED DEMAND BALANCED CURRENT: 97 AMPSM MOTOR - - - MAXIMUM ESTIMATED DEMAND PHASE CURRENT: 99 AMPSK KITCHEN 53,744 VA 65% 34,934 VA
OTHER - - -
PANELBOARD SCHEDULEPANEL NAME: K2 (EXISTING) VOLTAGE: MAINS TYPE: SPD:
MOUNTING: PHASE: BUS MATERIAL: NEUTRAL:ENCLOSURE: WIRE: BUS RATING: BRANCH OCP TYPE:
DOOR STYLE: MIN. A.I.C. RATING: MCB RATING: ISOLATED GROUND:
KEYEDCIRCUIT DESCRIPTION
BREAKER LOAD CKT. CONNECTED LOAD/PHASE (VA) CKT. LOAD BREAKERCIRCUIT DESCRIPTION
KEYEDNOTE AMPS POLE TYPE # A B C # TYPE AMPS POLE NOTE
TOTAL CONNECTED LOAD PER PHASE (VA):TOTAL ESTIMATED DEMAND LOAD PER PHASE (VA):
TOTAL ESTIMATED DEMAND LOAD PER PHASE (AMPS):
TYPE LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
208Y/120 MLO NONE
SURFACE 3 ALUMINUM 100% RATEDNEMA 1 4 225 AMPS BOLT-ON CBs
STANDARD CONTRACTOR TO VERIFY NONE NO
9 WASHER 20 1 M 1 1,200 2,496 2 M 30 2 DRYER 9WORK TABLE C.O. E-94 20 1 K 3 1,200 2,496 4 M - - - -WORK TABLE C.O. E-95 20 1 K 5 1,200 6,000 6 K 70 3 UTILITY DISTRIBUTION SYSTEM E-45 6,8
KITCHEN C.O. 20 1 R 7 600 6,000 8 K - - -KITCHEN C.O. 20 1 R 9 600 6,000 10 K - - -KITCHEN C.O. 20 1 R 11 600 12 K - - SHUNT-TRIPOFFICE C.O. 20 1 K 13 600 1,200 14 K 20 3 MIXER E-31 6,10
VENT HOOD SWITCH E-17 20 1 K 15 600 1,200 16 K - - - -9 FIRE RISER BELL 20 1 E 17 1,200 1,200 18 K - - - -
1,6,8 ICE MAKER E-21 20 1 K 19 1,572 1,200 20 K 20 1 WORK TABLE C.O. E-32 8WORK TABLE C.O. E-22 20 1 K 21 1,200 1,200 22 K 20 1 WORK TABLE C.O. E-33 8
8 SLICER E-23 20 1 K 23 720 1,200 24 K 20 1 WORK TABLE C.O. E-34 88 WORK TABLE C.O. E-24 20 1 K 25 1,200 1,680 26 K 25 1 SHEETER E-35 1,6,88 WORK TABLE C.O. E-25 20 1 K 27 1,200 2,040 28 K 25 1 HOT FOOD CABINET E-36 1,6,8
WORK TABLE C.O. E-26 20 1 K 29 1,200 1,200 30 K 20 1 WORK TABLE C.O. E-37 81,6,8 MIXER E-27 20 1 K 31 1,200 480 32 K 20 1 FOOD PROCESSOR E-38 8
8 WORK TABLE C.O. E-28 20 1 K 33 1,200 1,200 34 K 20 1 WORK TABLE C.O. E-39 88 WORK TABLE C.O. E-29 20 1 K 35 1,200 120 36 K 20 1 GAS VALVE E-42 88 MICROWAVE. E-30 25 1 K 37 2,040 38 40 3 SPARE
1,6,8 EXHAUST HOOD E-41 20 1 K 39 1,200 40 - - -1,6,8 HEAT SENSOR E-43 20 1 K 41 1,800 42 - - -
21,468 21,336 17,64016,082 15,576 12,096
134 130 101
P SUB-PANEL SUB-PANEL LOADS BROKEN OUT BY LOAD CLASIFICATION BELOWR RECEPTACLES 1,800 VA 100% 1,800 VA TOTAL CONNECTED LOAD: 60,444 VAL LIGHTING - - - 25% OF LARGEST MOTOR: 1,248 VAC CONTINUOUS - - - TOTAL ESTIMATED DEMAND LOAD: 43,754 VAE EQUIPMENT 1,200 VA 100% 1,200 VA TOTAL ESTIMATED DEMAND BALANCED CURRENT: 121 AMPSM MOTOR 6,192 VA 100% 6,192 VA MAXIMUM ESTIMATED DEMAND PHASE CURRENT: 134 AMPSK KITCHEN 51,252 VA 65% 33,314 VA
OTHER - - -
PANELBOARD SCHEDULEPANEL NAME: K3 (EXISTING) VOLTAGE: MAINS TYPE: SPD:
MOUNTING: PHASE: BUS MATERIAL: NEUTRAL:ENCLOSURE: WIRE: BUS RATING: BRANCH OCP TYPE:
DOOR STYLE: MIN. A.I.C. RATING: MCB RATING: ISOLATED GROUND:
KEYEDCIRCUIT DESCRIPTION
BREAKER LOAD CKT. CONNECTED LOAD/PHASE (VA) CKT. LOAD BREAKERCIRCUIT DESCRIPTION
KEYEDNOTE AMPS POLE TYPE # A B C # TYPE AMPS POLE NOTE
TOTAL CONNECTED LOAD PER PHASE (VA):TOTAL ESTIMATED DEMAND LOAD PER PHASE (VA):
TOTAL ESTIMATED DEMAND LOAD PER PHASE (AMPS):
TYPE LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
208Y/120 MLO NONE
SURFACE 3 ALUMINUM 100% RATEDNEMA 1 4 225 AMPS BOLT-ON CBs
STANDARD CONTRACTOR TO VERIFY NONE NO
SPACE 1 2 SPACESPACE 3 4 SPACESPACE 5 6 SPACE
8 SERVING OHD 30 1 M 7 1,920 1,352 8 M 25 2 SPLIT SYSTEM AC-1 88 SERVING OHD 30 1 M 9 1,920 1,352 10 M - - -8 SERVING OHD 30 1 M 11 1,920 12 40 2 SPARE8 SERVING OHD 30 1 M 13 1,920 14 - - -8 SERVING OHD 30 1 M 15 1,920 16 40 2 SPARE
DISHWASH AREA OHD 20 1 M 17 1,200 18 - - -DISPLAYS 20 1 E 19 1,200 20 30 2 SPAREDISPLAYS 20 1 E 21 1,200 22 - - -DISPLAYS 20 1 E 23 1,200 24 30 2 SPARE
KITCHEN DOOR BELL 20 1 E 25 1,200 26 - - -EXHAUST FAN EF-2 20 1 M 27 87 28 30 2 SPAREEXHAUST FAN EF-5 20 1 M 29 720 30 - - -
8 ROOF C.O. 20 1 R 31 720 32 SPACESPACE 33 34 SPACESPACE 35 36 SPACESPACE 37 38 SPACESPACE 39 40 SPACESPACE 41 42 SPACESPACE 43 44 SPACESPACE 45 46 SPACESPACE 47 48 SPACE
8,312 6,479 5,0408,650 6,817 5,040
72 57 42
P SUB-PANEL SUB-PANEL LOADS BROKEN OUT BY LOAD CLASIFICATION BELOWR RECEPTACLES 720 VA 100% 720 VA TOTAL CONNECTED LOAD: 19,831 VAL LIGHTING - - - 25% OF LARGEST MOTOR: 676 VAC CONTINUOUS - - - TOTAL ESTIMATED DEMAND LOAD: 20,507 VAE EQUIPMENT 4,800 VA 100% 4,800 VA TOTAL ESTIMATED DEMAND BALANCED CURRENT: 57 AMPSM MOTOR 14,311 VA 100% 14,311 VA MAXIMUM ESTIMATED DEMAND PHASE CURRENT: 72 AMPSK KITCHEN - - -
OTHER - - -
EQUIPMENT SCHEDULEUNIT CONDUIT WIRES STARTER / DISCONNECT/ CONNECTION AT UNIT
NAME DESCRIPTION LOAD TYPE VOLTAGE PHASE AMPERAGE SIZE OCP DISCONNECT REMARKS
NO. SIZE NOTE STARTER SIZE SIZE POLES SIZE POLES
AC-1 SPLIT SYSTEM - INDOOR UNIT 1 MCA 208 1 1 3/4" 2 12 1A - - - 1 HP 2 POWERED FROM OUTDOOR UNITSPLIT SYSTEM - OUTDOOR UNIT 13 MCA 208 1 13 3/4" 2 12 10A - 25 2 30 2 NEMA 3R DISCONNECT
EF-1 EXHAUST FAN 1/4 HP 120 1 5.8 3/4" 2 12 1A - - - 1 HP 1 NEMA 3R DISCONNECTEF-2 EXHAUST FAN 87 WATTS 120 1 0.73 3/4" 2 12 1A - - - 1 HP 1EF-3 EXHAUST FAN 1-1/2 HP 480 3 3 3/4" 3 12 9A - - - 30 3 NEMA 3R DISCONNECTEF-4 EXHAUST FAN 1-1/2 HP 480 3 3 3/4" 3 12 9A - - - 30 3 NEMA 3R DISCONNECTEF-5 EXHAUST FAN 1/4 HP 120 1 5.8 3/4" 2 12 1A - - - 1 HP 1 NEMA 3R DISCONNECTEF-6 EXHAUST FAN 1/4 HP 120 1 5.8 3/4" 2 12 1A - - - 1 HP 1 NEMA 3R DISCONNECT
ELEV-1 ELEVATOR 25 HP 480 3 50 1-1/2" 3 4 10A - 60 3 60 3GROUND TO BE THE SAME SIZE AS THEPHASE CONDUCTORS. REUSE EXISTING
FEDER CONDUIT AND DISCONNECTELEVATOR CAB LIGHTS AND CONTROLS 10 AMPS 120 1 10 3/4" 2 12 10A - 20 1 30 1
MAU-1 MAKE-UP AIR UNIT 10 MCA 480 3 10 3/4" 3 12 12A - - - - - DISCONNECT BY MECHANICALMAU-2 MAKE-UP AIR UNIT 10 MCA 480 3 10 3/4" 3 12 12A - - - - - DISCONNECT BY MECHANICAL
RT-1 ROOF TOP UNIT 22 MCA 480 3 22 3/4" 3 10 12A - - - - - DISCONNECT BY MECHANICAL
SIZE ALL FUSES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
STARTER / DISCONNECT NOTES: INSTALLATION NOTES:
1. MANUAL STARTER WITH THERMAL OVERLOAD 9. NON-FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED, & CONNECTED UNDER DIVISION 26.2. MANUAL STARTER WITH THERMAL OVERLOAD PROTECTION & 10. FUSED DISCONNECT SWITCH B. FURNISHED & INSTALLED UNDER ANOTHER DIVISION
LOW VOLTAGE RELAY / CONTACTOR FOR ATC CONTROL 11. BREAKER AND ENCLOSURE REQUIRING CONNECTIONS UNDER DIVISION 26.3. COMBINATION MAGNETIC STARTER / FUSED DISCONNECT 12. DIRECT CONNECTION C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED4. COMBINATION MAGNETIC STARTER / MOTOR CIRCUIT PROTECTOR (MCP) 13. DUPLEX RECEPTACLE OUTLET AND CONNECTED UNDER DIVISION 26.5. COMBINATION VARIABLE FREQUENCY DRIVE / MOTOR CIRCUIT PROTECTOR (MCP) 14. SPECIAL PURPOSE OUTLET D. FURNISHED, INSTALLED, & CONNECTED UNDER ANOTHER DIVISION6. REDUCED VOLTAGE STARTER 15. SHUNT-TRIP BREAKER AND ENCLOSURE E. FURNISHED BY OWNER, INSTALLED & CONNECTED BY DIVISION 267. COMBINATION TWO-SPEED STARTER / FUSED DISCONNECT 16. TOGGLE SWITCH8. COMBINATION TWO-SPEED STARTER / MOTOR CIRCUIT PROTECTOR (MCP) 17. MAGNETIC STARTER
PANELBOARD SCHEDULEPANEL NAME: EM3 (EXISTING) VOLTAGE: MAINS TYPE: SPD:
MOUNTING: PHASE: BUS MATERIAL: NEUTRAL:ENCLOSURE: WIRE: BUS RATING: BRANCH OCP TYPE:
DOOR STYLE: MIN. A.I.C. RATING: MCB RATING: ISOLATED GROUND:
KEYEDCIRCUIT DESCRIPTION
BREAKER LOAD CKT. CONNECTED LOAD/PHASE (VA) CKT. LOAD BREAKERCIRCUIT DESCRIPTION
KEYEDNOTE AMPS POLE TYPE # A B C # TYPE AMPS POLE NOTE
TOTAL CONNECTED LOAD PER PHASE (VA):TOTAL ESTIMATED DEMAND LOAD PER PHASE (VA):
TOTAL ESTIMATED DEMAND LOAD PER PHASE (AMPS):
TYPE LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
208Y/120 MCB NONE
SURFACE 3 ALUMINUM 100% RATEDNEMA 1 4 100 AMPS BOLT-ON CBs
STANDARD CONTRACTOR TO VERIFY 50 AMPS NO
6,8 WALK-IN CONDENSER E-1 25 2 M 1 1,768 1,186 2 M 20 2 WALK-IN CONDENSER E-8 6,8- - - - M 3 1,768 1,186 4 M - - - -8 WALK-IN HEAT / MONITOR E-4,5,7 20 1 E 5 960 720 6 E 20 1 WALK-IN LTS / HEAT / COIL E-9,10,12 89 OUTLET AT PHONE PANEL 20 1 E 7 960 8 20 2 SPARE9 FIRE PANEL 20 1 E 9 960 10 - - -9 FRONT DOOR 20 1 E 11 1,200 960 12 E 20 1 DATA RACK 9
SPARE 20 1 13 1,200 14 E 20 1 ELEVATOR 96,8 WALK-IN COIL / DEFROST E-2, E-3 20 2 E 15 1,144 16 SPACE- - - - E 17 1,144 18 SPACE
SPACE 19 20 SPACESPACE 21 22 SPACESPACE 23 24 SPACESPACE 25 26 SPACESPACE 27 28 SPACESPACE 29 30 SPACESPACE 31 32 SPACESPACE 33 34 SPACESPACE 35 36 SPACESPACE 37 38 SPACESPACE 39 40 SPACESPACE 41 42 SPACE
5,114 5,058 4,9845,556 5,500 4,984
46 46 42
P SUB-PANEL SUB-PANEL LOADS BROKEN OUT BY LOAD CLASIFICATION BELOWR RECEPTACLES - - - TOTAL CONNECTED LOAD: 15,156 VAL LIGHTING - - - 25% OF LARGEST MOTOR: 884 VAC CONTINUOUS - - - TOTAL ESTIMATED DEMAND LOAD: 16,040 VAE EQUIPMENT 9,248 VA 100% 9,248 VA TOTAL ESTIMATED DEMAND BALANCED CURRENT: 45 AMPSM MOTOR 5,908 VA 100% 5,908 VA MAXIMUM ESTIMATED DEMAND PHASE CURRENT: 46 AMPSK KITCHEN - - -
OTHER - - - BRANCH CIRCUIT GENERAL NOTES: PANELBOARD SCHEDULE NOTES:
ONE-LINE DIAGRAM
3P150A
3P150A
3P150A
3P100A
3P100A
3P150A
3P100A
3P50A
G
3P800A
EXISTING DISTRIBUTION PANEL 'MP'(120/208V, 3 PHASE, 4W, 800A)
PANEL'K1'
EXISTPANEL
'K2'
EXISTPANEL
'K3'
EXIST
EXISTING DISTRIBUTION PANEL 'M'(277/480V, 3 PHASE, 4W, 1600A)
PANEL'BYY'
EXISTPANEL
'BY'
EXISTPANEL
'BX'
EXISTPANEL
'B1'
EXIST
TRANSFORMEREXISTING
PANEL'B2'
EXIST
TRANSFORMEREXISTING
PANEL'B3'
EXIST
3P70A
BOOSTERTO
HEATER E-19DISHWASHER
TO
E-18
3P40A
50A40A
PANEL'EM'
EXIST
ATSEXISTING
GENERATOREXISTING 60KW
TRANSFORMEREXISTING
PANEL'EM2'
EXIST
TRANSFORMEREXISTING
PANEL'EM3'
EXIST
3P50A
MCCTO
SCALE:1
NONE
3. PROVIDE 30 MILLIAMPERE EQUIPMENT GROUND FAULT PROTECTOR TYPE CIRCUIT BREAKER.
6. PROVIDE HANDLE CLAMP FOR HOLDING CIRCUIT BREAKER IN THE "ON" OR "OFF" POSITION.
8. PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANELBOARD (WHERE PANEL IS INDICATED AS EXISTING) OF SAME MANUFACTURER AND A.I.C. RATING AS EXISTING.
1. PROVIDE CLASS A GROUND FAULT INTERRUPTER TYPE CIRCUIT BREAKER.
2. PROVIDE ARC FAULT CIRCUIT INTERRUPTER TYPE CIRCUIT BREAKER.
4. PROVIDE SHUNT-TRIP TYPE CIRCUIT BREAKER WITH 120V COIL.
9. EXISTING LOAD.
5. PROVIDE HACR RATED CIRCUIT BREAKER.
7. PROVIDE SWITCHING RATED CIRCUIT BREAKER.
PANELBOARD SCHEDULE KEYED NOTES:
1. PROVIDE DEDICATED NEUTRAL FOR ALL BRANCH CIRCUITS.
2. CONTRACTOR SHALL UPSIZE ALL BRANCH CIRCUITS AS NECESSARY FOR VOLTAGE DROP
WHETHER SHOWN OR NOT.
1. CONTRACTOR SHALL USE THE ROOM NAMES LISTED ON
THE ARCHITECTURAL SIGNAGE PLAN FOR ALL ROOM
NAMES ON THE FINAL PANEL SCHEDULE CIRCUIT
DESCRIPTIONS. IF IT IS FOUND THAT THE ARCHITECTURAL
FLOOR PLAN ROOM NAMES HAVE BEEN USED THE
SCHEDULES WILL BE UPDATED TO FOR THE CORRECT
ROOM NAMES AT NO ADDITIONAL COST TO THE OWNER.
10. REUSE EXISTING BREAKER.
KEYED NOTES:
1. CONTRACTOR TO PROVIDE ALTERNATE PRICE TO REPLACE
PANELBOAD COMPLETELY.
2. REMOVE EXISTING BREAKER THAT WAS FEEDING EXISTING
ELEVATOR AND RETURN TO OWNER. PROVIDE NEW BREAKER AS
CALLED OUT. NEW BREAKER TO BE OF THE SAME MANUFACTURE
AND INTERRUPTING CURRENT AS THE EXISTING INSTALLED.
CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS.
3. REMOVE EXISTING BREAKER THAT WAS FEEDING EXISTING
BOOSTER HEATER AND RETURN TO OWNER. PROVIDE NEW
BREAKER AS CALLED OUT. NEW BREAKER TO BE OF THE SAME
MANUFACTURE AND INTERRUPTING CURRENT AS THE EXISTING
INSTALLED. CONTRACTOR TO FIELD VERIFY ALL REQUIREMENTS.
4. PROVIDE NEW 600 VOLT, 60 AMP, 3 PHASE STAINLESS STEEL
FUSED DISCONNECT WITH FUSES INDICATED. CONFIRM ALL
POWER REQUIREMENTS WITH THE KITCHEN EQUIPMENT
INSTALLER.
5. PROVIDE NEW BREAKER AS CALLED OUT. NEW BREAKER TO BE OF
THE SAME MANUFACTURE AND INTERRUPTING CURRENT AS THE
EXISTING INSTALLED. CONTRACTOR TO FIELD VERIFY ALL
REQUIREMENTS.
6. CONTRACTOR TO VERIFY LOADING ON EXISTING PANEL PRIOR TO
THE DEMOLITION AND AFTER THE NEW CONSTRUCTION TO
ENSURE PANEL IS NOT OVERLOADED. IF THE PANEL IS
OVERLOADED ONCE THE NEW LOADS ARE ADDED CONTACT THE
ENGINEER FOR OTHER OPTIONS.
#
111
ELEV
1
23
EXISTING CONDUITWITH NEW4 #41 #8 GND.THWN, CU.
1-1/4" C4 #61 #10 GND.THWN, CU.
1-1/4" C4 #61 #10 GND.THWN, CU.
1" C4 #81 #10 GND.THWN, CU.
44
3
666
6 6
6666
6 6
6
6
1" C4 #81 #10 GND.THWN, CU.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
1 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
ONE-LINEDIAGRAM ANDSCHEDULES
EP701
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
1 02/18/20 Addendum #1
1
1
![Page 13: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/13.jpg)
FC
FC
C
C
C
C
V
V FITNESS ROOM
B11
GIRLS
B40
BOYS
B41
CORRIDOR
B15
TEACHER LOUNGE
B17
SERVING
B18
KITCHEN
B39
DISH WASH
B31
RECEIVING
B29
REFRIGERATOR
B32
FREEZER
B33
OFFICE
B37
TOILET
B36
LOCKERS
B35
LAUNDRY
B34
A21
AUDIO VISUAL GENERAL NOTES:
1. NO CHANGES SHALL BE MADE WITHOUT THE AV CONSULTANT'S WRITTEN CONSENT.
2. PROVIDE #6 AWG THHN WIRE WITH GREEN INSULATION FROM EACH AV EQUIPMENT CABINET TO THE MAIN BUILDING ELECTRICAL PANEL.
3. COLORS OF ALL SOUND DEVICES THAT ARE EXPOSED, INCLUDING INPUT AND OUTPUT PLATES, VOLUME CONTROLS, SWITCHES, SPEAKERS, SPEAKER ENCLOSURES, SPEAKER MOUNTING HARDWARE, ETC. SHALL BE REVIEWED AND APPROVED BY OWNER PRIOR TO ORDERING.
4. CABLE ROUTES SHOWN ON DRAWINGS DO NOT ACTUALLY REFLECT THE RACEWAYS. THE RACEWAYS SHALL BE DETERMINED IN THE FIELD.
5. REFER TO RISER DIAGRAMS AND EQUIPMENT LISTS FOR THE TYPES AND NUMBERS OF WIRES REQUIRED FOR EACH AV DEVICE.
6. SETUP COMPRESSORS AND LIMITTERS IN ALL OF THE DSPS TO PROTECT THE AMPLIFIERS AND SPEAKERS. ALSO SETUP A PASSWORD ON THE DSP, TO CONTROL THE ACCESS TO THEM.
7. CONTRACTORS ARE REQUIRED TO VISIT THE JOBSITE, DOCUMENT EXISTING CONDITIONS THAT WILL AFFECT FINAL CONSTRUCTION COSTS PRIOR TO FINAL BID.
8. PROVIDE AND INSTALL ALL NECESARY INTERCOM HARDWIRES TO COMPLETE THE INSTALLATION.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
2 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALCEILING PLAN
ET102
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
4' - 0" 8' - 0" 16' - 0"
1/8" = 1'-0"
AUDIO VISUAL CEILING PLANN
KEYED NOTES
A2 RUN A SPEAKER CABLE TO THE EXISTING INTERCOM RACK WHICH ISAPPROXIMATELY 200' AWAY. THE CABLE MUST BE CONCEALED.
#
1 02/18/20 Addendum #1
![Page 14: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/14.jpg)
HO
HH
MLC CS
12
' -
0"
2
ET401
________
FITNESS ROOM
B11
3
ET401
________
(2)
(2)
ET401
5
A3
1
ET501
2
ET501
1
1
12
' -
0 1
/8"
50.0
0°
6' -
0"
3/4" C. 3/4" C.
1-GANG BOXSPEAKER
1-GANG BOXSPEAKER
3/4" C.
3/4" C.
3/4" C.
1-GANG BOXINTERCOM CALL SWITCH
AV CONTROLLER2-GANG BOX
HUBBELL HBL OR EQUIVALENTWITH HDMI INPUT
PROJECTOR MOUNTHUBBELL LARGE CAPACITY OUTLET BOX HBL 260 OR EQUIVALENT WITH
2-GANG MUD RING
3/4" C.
3' -
6"
58" X 104"
REFER TO PROJECTORMANUAL FOR ROUGH-IN REQUIREMENTS
3' -
10
"
SIGNAGE DISPLAY 65" TYP.
FLOOR
3' -
6"
DISPLAY
HDMI OUTPUT2-GANG BOX
HDMI INPUT2-GANG BOX
1-1/4" C.
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
3 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALSECTION ANDELEVATIONS
ET401
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
SCALE: 1/4" = 1'-0"2
ENLARGED FITNESS ROOM B11 SECTION
SCALE: 1/4" = 1'-0"1
ENLARGED FITNESS ROOM B11 PLAN
SCALE: 1/4" = 1'-0"3
ENLARGED FITNESS ROOM B11 SECTION 2
SCALE: 1/4" = 1'-0"5
ENLARGED FITNESS ROOM B11 ELEVATION
SCALE: 1/4" = 1'-0"4
ENLARGED CORRIDOR B15 ELEVATION
SCALE: 1/4" = 1'-0"6
ENLARGED TEACHER LOUNGE B17 ELEVATION
KEYED NOTES
A3 RUN A INTERCOM CABLE TO THE EXISTING INTERCOM RACK, WHICH ISAPPROXIMATELY 200' AWAY. THE CABLE NEEDS TO BE CONCEALED.
#
1 02/18/20 Addendum #1
![Page 15: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/15.jpg)
SCHOOL INTERCOM EQUIPMENT LIST
SYMBOL DESCRIPTION QTY SUPPLIER MODEL ROUGH-IN CABLE
CALL SWITCH A/R QUAM CIB3 1 GANG, 3" DEEP
3/4" C. TO ACCESSIBLE CEILING WEST PENN 25355B
RECESSED INTERIOR CEILING SPEAKER:
ROUND BACK BOX A/R QUAM ERD8U 3/4" C. TO ACCESSIBLE CEILING
SPEAKER/GRILLE ASSEMBLY A/R ATLAS SOUND SD72W PAINT GRILL IN COLOR AS SELECTED BY WEST PENN 25225B
TILE SUPPORT A/R QUAM SSB-2 ARCHITECT
RECESSED INTERIOR WALL SPEAKER:
SQUARE BACK BOX A/R LOWELL P875X-4 3/4" C. TO ACCESSIBLE CEILING
SPEAKER A/R ATLAS SOUND SD72W PAINT GRILL IN COLOR AS SELECTED BY WEST PENN 25225B
GRILL, WHITE A/R LOWELL JG8X ARCHITECT
VOLUME CONTROL SWITCH A/R QUAM QC10 1-GANG 3" DEEP 22/4 SOLID BC, SHIELDED
SWITCH HEIGHT 3/4" C. TO ACCESSIBLE CEILING WEST PENN 25225B
RECESSED ENCLOSURE A/R ATLAS CS-195B WEST PENN 25225B
SPEAKER A/R SD-72W
A/R = AS REQUIRED
SCALE:
Flexmike.
lightspeed
AMPLYFIED AUDIO OUT AUDIO OUT PAGINGSENSOR
LANINPUTS OUTPUT
VO
ICELIF
T REMOTE OVER PVT INPUT 7 AUX
PVT IN PVT IN HDMI HDMI
PVS 407D
SCREEN
AUDIO/VIDEO EQUIPMENT LIST (FITNESS B11)
SYMBOL DESCRIPTION QTY/RM SUPPLIER MODEL ROUGH-IN CABLE
EQUIPMENT CABINET, WALL MOUNT, 18RU 1 MIDDLE ATLANTIC DWR-18-26 12"X12"X4" OR SIZE TO FIT, 45" AFF
DOOR 1 MIDDLE ATLANTIC LVFD-18 (2) 3/4" CONDUITS TO
SURGE SUPPRESSOR 1 SURGE X SX-1115 ACCESSIBLE CEILING SPACE
BLANK PANEL A/R MIDDLE ATLANTIC
WALL MOUNT SPEAKER MOUNTING KIT 2 JBL 5215/95 3" DEEP, 1-GANG BOX WEST PENN 25227B
ROTATE HORN BY 90 DEGREE 2 MTUI 3/4" CONDUIT THROUGHOUT
AMPLIFIER, 1250X2 1 CROWN DCI 2/1250
SWITCHER / POWER AMPLIFIER 1 EXTRON PVS 407D EXTRON HDMI CABLE
MEDIA LINK CONTROLLER WITH ETHERNET CONTROL 1 EXTRON MLC 104 IP PLUS 2 GANG 2-1/2" DEEP WESTPENN 254246, TO DATA RACK
48" AFF 3/4" C. TO CEILING ENCLOSURE EXTRON MLC IR/RS-232-50, TO PROJECTOR
EXTRON MLC PW/RS-232/VC-50, TO SWITCHER
HDMI AND STEREO AUDIO INPUTS 1 EXTRON PVT HDMI 2 GANG 2-1/2" DEEP EXTRON VGA WITH AUDIO CABLE, COMPUTER TO WALL, 2 REQUIRED
18" AFF 3/4" C. TO CEILING ENCLOSURE EXTRON HDMI CABLE, COMPUTER TO WALL
EXTRON XTP DTP 24P
RF WIRELESS RECEIVING SYSTEM 1 LIGHT SPEED AR-FS
INCLUDES:
ACCESS LINK BASIC STATION WITH POWE SUPPLY
TEACHER'S MICROPHONE FLEXMIKE
RECHARGEABLE BATTERY
LANYARD, AND CABLE
STUDENT MICROPHONE SHARE MIKE
WALL MOUNTED ULTRA SHORT-THROW PROJECTOR 1 EPSON POWERLITE 700U 2-GANG BOX
ULTRA SHORT-THROW PROJECTOR MOUNT 1 EPSON ELPMB53
SCREEN, MANUAL, 58"X104" 1 DA-LITE MODEL C WITH CSR 79884
HDMI TX 1 CRESTRON HD-TX-101-C-E WEST PENN 254246
CRESTRON HDMI CABLE
HDMI RX 1 CRESTRON HD-RX-101-C-1G-E-B-T 2-GANG BOX WEST PENN 254246
3/4" C. ACCESSIBLE CEILING SPACE
DIGITAL SIGNAL PROCESSOR 1 SYNTRIX SOLUS NX4X4 WEST PENN 25291B
A/R = AS REQUIRED
1
INTERCOM SYSTEM RISER
AV SYSTEM - FITNESS B11
SCALE:2
NONE
2W
RESTROOMS
2W
CALLSWITCH
FITNESS ROOM
EXISTING INTERCOM RACK (BOGEN)
NONE1
PVT HDMI
Cat 6 A
RS232
25291BL
SPEAKER
HDMI
MLC 104 IP PLUSA
B
C
D
E
B
C
F
F XTP DTP 24P
E
G MLC IR/RS232
G
AMP
C
CABINET #1
* INSTALL THE ACCESS LINK OUTSIDE THE CABINET
*
TEACHER'S MICROPHONE
STUDENT'S MICROPHONE
NOTE:1. PROGRAM WALL CONTROLLER TO CONTROL MASTER AUDIO
VOLUME, PROJECTOR AUDIO INPUT VOLUME, PROJECTORPOWER ON/OFF AND INPUT SELECTIONS.
CACCESS LINK
TO NEARESTDATA RACK
A
A
PVS 407D
PROJECTOR
SCREEN
DSP
HDMI
TX
HDMI
RX
2W 2W
2W
KITCHEN, ETC.
CS
MLC
HH
HI
HO
C
V
C
V
VOLUME
DISPLAY
MLC 104 IP PLUS
ON OFF VCR
DVD
PC
HDMI IN
IR OUT
S
G
AUDIO IN
HDMI IN
IR OUT
S
G
AUDIO IN
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
3 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALRISER ANDEQUIPMENT LIST
ET702
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
1 02/18/20 Addendum #1
1 1
![Page 16: Addendum No. 01Issued: 2/18/2020 - Arnell-West · Addendum No. 01 to the Construction Contract for the above referenced project: ... SPK FC FC SPK SPK CS MA MA 2 TV 5 6 B D4 D4 D2](https://reader033.vdocuments.site/reader033/viewer/2022060802/608673951b98571d5e70284e/html5/thumbnails/16.jpg)
SCHOOL INTERCOM EQUIPMENT LIST (ALTERNATE #1)
SYMBOL DESCRIPTION QTY SUPPLIER MODEL ROUGH-IN CABLE
CALL SWITCH A/R QUAM CIB3 1 GANG, 3" DEEP
3/4" C. TO ACCESSIBLE CEILING WEST PENN 25355B
RECESSED INTERIOR CEILING SPEAKER:
ROUND BACK BOX A/R QUAM ERD8U 3/4" C. TO ACCESSIBLE CEILING
SPEAKER/GRILLE ASSEMBLY A/R ATLAS SOUND SD72W PAINT GRILL IN COLOR AS SELECTED BY WEST PENN 25225B
TILE SUPPORT A/R QUAM SSB-2 ARCHITECT
RECESSED INTERIOR WALL SPEAKER:
SQUARE BACK BOX A/R LOWELL P875X-4 3/4" C. TO ACCESSIBLE CEILING
SPEAKER A/R ATLAS SOUND SD72W PAINT GRILL IN COLOR AS SELECTED BY WEST PENN 25225B
GRILL, WHITE A/R LOWELL JG8X ARCHITECT
VOLUME CONTROL SWITCH A/R QUAM QC10 1-GANG 3" DEEP 22/4 SOLID BC, SHIELDED
SWITCH HEIGHT 3/4" C. TO ACCESSIBLE CEILING WEST PENN 25225B
RECESSED ENCLOSURE A/R ATLAS CS-195B WEST PENN 25225B
SPEAKER A/R SD-72W
A/R = AS REQUIRED
SCALE:
Flexmike.
lightspeed
AMPLYFIED AUDIO OUT AUDIO OUT PAGINGSENSOR
LANINPUTS OUTPUT
VO
ICELIF
T REMOTE OVER PVT INPUT 7 AUX
PVT IN PVT IN HDMI HDMI
PVS 407D
SCREEN
AUDIO/VIDEO EQUIPMENT LIST (FITNESS B11 ALTERNATE #1)
SYMBOL DESCRIPTION QTY/RM SUPPLIER MODEL ROUGH-IN CABLE
EQUIPMENT CABINET, WALL MOUNT, 18RU 1 MIDDLE ATLANTIC DWR-18-26 12"X12"X4" OR SIZE TO FIT, 45" AFF
DOOR 1 MIDDLE ATLANTIC LVFD-18 (2) 3/4" CONDUITS TO
SURGE SUPPRESSOR 1 SURGE X SX-1115 EACH CEILING ENCLOSURE
BLANK PANEL A/R MIDDLE ATLANTIC
WALL MOUNT SPEAKER MOUNTING KIT 2 JBL 5215/95 3" DEEP, 1-GANG BOX WEST PENN 25227B
ROTATE HORN BY 90 DEGREE 2 MTUI 3/4" CONDUIT THROUGHOUT
AMPLIFIER, 1250X2 1 CROWN DCI 2/1250
SWITCHER / POWER AMPLIFIER 1 EXTRON PVS 407D EXTRON HDMI CABLE
MEDIA LINK CONTROLLER WITH ETHERNET CONTROL 1 EXTRON MLC 104 IP PLUS 2 GANG 2-1/2" DEEP WESTPENN 254246, TO DATA RACK
48" AFF 3/4" C. THROUGHOUT EXTRON MLC IR/RS-232-50, TO PROJECTOR
EXTRON MLC PW/RS-232/VC-50, TO SWITCHER
HDMI AND STEREO AUDIO INPUTS 1 EXTRON PVT HDMI 2 GANG 2-1/2" DEEP EXTRON VGA WITH AUDIO CABLE, COMPUTER TO WALL, 2 REQUIRED
18" AFF 3/4" C. THROUGHOUT EXTRON HDMI CABLE, COMPUTER TO WALL
EXTRON XTP DTP 24P
RF WIRELESS RECEIVING SYSTEM 1 LIGHT SPEED AR-FS
INCLUDES:
ACCESS LINK BASIC STATION WITH POWE SUPPLY
TEACHER'S MICROPHONE FLEXMIKE
RECHARGEABLE BATTERY
LANYARD, AND CABLE
STUDENT MICROPHONE SHARE MIKE
WALL MOUNTED ULTRA SHORT-THROW PROJECTOR 1 EPSON POWERLITE 700U 2-GANG BOX
ULTRA SHORT-THROW PROJECTOR MOUNT 1 EPSON ELPMB53 3/4" C. THROUGHOUT
SCREEN, MANUAL, 58"X104" 1 DA-LITE MODEL C WITH CSR 79884
HDMI TX 1 CRESTRON HD-TX-101-C-E WEST PENN 254246
CRESTRON HDMI CABLE
HDMI RX 1 CRESTRON HD-RX-101-C-1G-E-B-T 2-GANG BOX
DIGITAL SIGNAL PROCESSOR 1 SYNTRIX SOLUS NX4X4 WEST PENN 25291B
A/R = AS REQUIRED
1
AV SYSTEM - FITNESS B11 ALTERNATE
ALTERNATE #1
INTERCOM SYSTEM RISER (ALTERNATE)
NONE1
PVT HDMI
Cat 6 A
RS232
25291BL
SPEAKER
HDMI
MLC 104 IP PLUS A
B
C
D
E
B
C
F
F XTP DTP 24P
E
G MLC IR/RS232
G
AMP
C
CABINET #1
* INSTALL THE ACCESS LINK OUTSIDE THE CABINET
*
TEACHER'S MICROPHONE
STUDENT'S MICROPHONE
NOTE:1. PROGRAM WALL CONTROLLER TO CONTROL MASTER AUDIO
VOLUME, PROJECTOR AUDIO INPUT VOLUME, PROJECTORPOWER ON/OFF AND INPUT SELECTIONS.
CACCESS LINK
TO NEARESTDATA RACK
A
A
PVS 407D
PROJECTOR
SCREEN
DSP
HDMI
TX
HDMI
RX
SCALE:3
NONE
2W
RESTROOMS
2W
CALLSWITCH
FITNESS ROOM
EXISTING INTERCOM RACK (BOGEN)
2W 2W
2W
KITCHEN, ETC.
MLC
HH
HI
HO
C
V
CS
C
V
VOLUME
DISPLAY
MLC 104 IP PLUS
ON OFF VCR
DVD
PC
HDMI IN
IR OUT
S
G
AUDIO IN
HDMI IN
IR OUT
S
G
AUDIO IN
HH
MLC CS
HO
FITNESS ROOM
B11
ET703
2
1
(2)
(2)
1
ET501
2
ET501
A3
3/4" C. TO ACCESSIBLE
CEILING SPACE
1
3/4" C.
1-GANG BOXSPEAKER
1-GANG BOXSPEAKER
3/4" C.
3/4" C.
3/4" C.
1-GANG BOXINTERCOMCALL SWITCH
AV CONTROLLER2-GANG BOX
HUBBELL HBL OR EQUIVALENTWITH HDMI INPUT
PROJECTOR MOUNT
HUBBELL LARGE CAPACITY OUTLET BOX HBL 260 OR EQUIVALENT WITH
2-GANG MUD RING
3/4" C. TO EQUIPMENT CABINET
3' -
6"
INTERCOM SPEAKER
58" X 104"
REFER TO PROJECTORMANUAL FOR ROUGH-IN REQUIREMENTS
1TO
3/4" C.
TO ACCESSIBLECEILING SPACE
240 E. MORRIS AVE. SUITE 200SALT LAKE CITY, UT 84115
P (801) 534-1130F (801) 534-1080
www.envisioneng.com
SHEET NUMBER
1
E
D D
C
B
A
E
C
B
A
2 3 4 5
1 2 3 4 5
MHTN PROJECT NO.
SEAL
SHEET NAME
REVISIONSCONTRACTOR TO VERIFY DRAWINGS IN FIELD USE REFLECT LAST REVISION DATE.
DESCRIPTIONDATE
MHTN Architects, Inc.420 East South Temple Suite 100 Salt Lake City, Utah 84111Telephone (801) 595-6700Telefax (801) 595-6717www.mhtn.com
NO.
ISSUE
Confidentiality Notice: This document is intended for use on the Project identified herein by individuals and companies involved in the design, permitting, bidding and construction of the Project. MHTN Architects, Inc. grants limited rights to distribute and reproduce this document for this express purpose only. Distribution, printing or copying this document for purposes other than those indicated is strictly prohibited. If a digital copy of this document is received in error, please delete it.
Original drawing is 30 x 42. Do not scale contents of this drawing.
2/1
8/2
020
11:5
2:4
4 A
M
C:\R
evit 2
020
Lo
ca
l F
iles\2
01
9-1
82
_E
LE
C-C
EN
TR
AL
_V
20_
SK
ing
ery
.rvt
AUDIO VISUALRISER ANDEQUIPMENT LIST
ET703
FEBRUARY 6, 2020
CONSTRUCTION DOCUMENTS
2019587
OQ
UIR
RH
HIL
LS
M.S
. R
EM
OD
EL
129
49 S
OU
TH
27
00
WE
ST
RIV
ER
TO
N, U
TA
H 8
40
65
JO
RD
AN
SC
HO
OL D
IST
RIC
T
©2020 MHTN ARCHITECTS, INC.
0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1'-0"4
AUDIO VISUAL - FITNESS BID ALTERNATE #1
0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1'-0"2
ENLARGED FITNESS ROOM B11 ELEVATION ALTERNATE #1
KEYED NOTES
A3 RUN A INTERCOM CABLE TO THE EXISTING INTERCOM RACK, WHICH ISAPPROXIMATELY 200' AWAY. THE CABLE NEEDS TO BE CONCEALED.
#
1 02/18/20 Addendum #1
1
1