addendum #2 demolition of existing tlc building … 2 project 19-004 w demo specs.pdfexisting...

4
Page 1 of 1 Addendum #2 DEMOLITION OF EXISTING TLC BUILDING REQUEST FOR BIDS #19-004 Owner: EL SEGUNDO UNIFIED SCHOOL DISTRICT (“DISTRICT”) Project Title: DEMOLITION OF EXISTING TLC BUILDING Bid No.: 19-004 Date: June 27, 2018 NOTICE TO BIDDERS: The following changes, additions and clarifications have been made to the original Bid Documents for the above referenced project (“Project”) and shall be incorporated into the Bidder’s response. The Bidders shall incorporate all information set forth herein to the Bid Documents, as necessary. All other aspects of the work and services required by the Bid Documents shall remain unchanged. In case of conflict between the Bid Documents and this Addendum, this Addendum shall govern. Demolition Plans / Specifications The demolition plans were erroneously omitted from the bid documents. The plans are now posted on the website and attached to this addendum.

Upload: others

Post on 12-Nov-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Addendum #2 DEMOLITION OF EXISTING TLC BUILDING … 2 Project 19-004 w Demo Specs.pdfexisting partition new partition n - 58' 2" e - 150' 11" 1 a-100 section callout symbol a sheet

Page 1 of 1

Addendum #2

DEMOLITION OF EXISTING TLC BUILDING

REQUEST FOR BIDS #19-004

Owner: EL SEGUNDO UNIFIED SCHOOL DISTRICT (“DISTRICT”)

Project Title: DEMOLITION OF EXISTING TLC BUILDING

Bid No.: 19-004

Date: June 27, 2018

NOTICE TO BIDDERS: The following changes, additions and clarifications have been made

to the original Bid Documents for the above referenced project (“Project”) and shall be

incorporated into the Bidder’s response. The Bidders shall incorporate all information set forth

herein to the Bid Documents, as necessary. All other aspects of the work and services required

by the Bid Documents shall remain unchanged. In case of conflict between the Bid Documents

and this Addendum, this Addendum shall govern.

Demolition Plans / Specifications

The demolition plans were erroneously omitted from the bid documents. The plans are now

posted on the website and attached to this addendum.

Page 2: Addendum #2 DEMOLITION OF EXISTING TLC BUILDING … 2 Project 19-004 w Demo Specs.pdfexisting partition new partition n - 58' 2" e - 150' 11" 1 a-100 section callout symbol a sheet

A-1

D125

DIMENSIONS

NOTE: all dimensions to face of wall unlessotherwise noted

COLUMN LINE

FLOOR LINE

MATCH LINE

NORTH SYMBOL

INTERIOR ELEVATION SYMBOL

DOOR DESIGNATION

EXTERIOR ELEVATION SYMBOL

PLAN OR DETAIL ENLARGED

DETAIL AND VERTICAL SECTIONS

PARTITION TYPE

REVISION NUMBER

DETAIL ENLARGED

WINDOW DESIGNATION

EXISTING ELEVATION

FINISH GRADE ELEVATION

AREA DRAIN

PROPERTY LINE

NO.

NO.

5

A1.01 1

2

3

4

1/A1.01 12

A6.01

1

LEVEL

+100'-0" ELEVATION

10'-0".

6'-0". 4'-0".

1

18'-6"

SPOT COORDINATE

KEY NOTE

BREAK LINE

MATCH LINE

SEE XX/X-XXX

EQUIPMENT DESIGNATION

TOILET ACCESSORY SYMBOL

GRAPHIC SCALE

ROOM NAME AND NUMBER

SPOT ELEVATION

WHICH CONTINUATIONSHEET NUMBER ON

IS FOUND

PROPERTY LINE

FHCFHC

FIRE HOSE CABINET

FECFEC

FIRE EXTINGUISHER CABINET(RECESSED AND SURFACE MOUNTED)

(RECESSED AND SURFACE MOUNTED)

SHOWER HEAD

RTUREFER TO MECHANICAL FOR TYPE

ROOF TOP UNIT

F.D.

FLOOR SINK

FLOOR DRAIN

OVERFLOW DRAIN AND ROOF DRAIN

F.S.

FENCING (WITH POSTS)

NORTH

TRUE NORTH

ROOM

1

100SF

123

OVERFLOW DRAIN

ROOF DRAIN

25C

TA1

1

A-100

SCALE: 1" = 4'-0"

0 2' 4' 8'

1

A-100

EXISTING PARTITION

NEW PARTITION

N - 58' 2"E - 150' 11"

1

A-100

SECTION CALLOUT SYMBOL

A

SHEET NUMBER

SHEET DISCIPLINE TYPE

DISCIPLINE

A2.01

0 - SITE PLANS & DETAILS1 - COMPOSITE FLOOR PLANS2 - FLOOR PLANS 3 - ROOF4 - ADA & ENLARGED PLANS5 - PLAN DETAILS6 - BUILDING SECTIONS, EXTERIOR/INTERIOR ELEVATIONS7 - PARTITION TYPES & WALL SECTIONS8 - CASEWORK ELEVATIONS AND DETAILS9 - WINDOWS, DOORS, FRAME ELEVATIONS & DETAILS10 - REFLECTED CEILING PLANS & DETAILS11 - EQUIPMENT AND FURNITURE PLANS

SEQUENCE (.01 - .99......etc.)

G - GENERAL (Cover, A0 Sheets)C - CIVILL - LANDSCAPED - DEMOA - ARCHITECTURALS - STRUCTURALI - INTERIORSM - MECHANICALE - ELECTRICALP - PLUMBINGT - TECHNOLOGY

TRUE NORTH

105 FWY / IMPERIAL HWY

THE LEARNING CONNECTIONM

AIN

ST

.

IMPERIAL AVE.

MAPLE AVE.

PALM AVE.

MARIPOSA AVE.

VIR

GIN

IA S

T.

RIC

HM

ON

D S

T.

PARTIAL LIST OF APPLICABLE CODES

2016 California Administrative Code (CAC) ......................................................................... (Part 1, Title 24, CCR)

2016 California Building Code (CBC) ................................................................................... (Part 2, Title 24, CCR) (2015 International Building Code Volumes 1-2 and 2016 California Amendments)

2016 California Electrical Code (CEC) ................................................................................... (Part 3, Title 24, CCR) (2014 National Electrical Code and 2016 California Amendments)

2016 California Mechanical Code (CMC) .............................................................................. (Part 4, Title 24, CCR) (2015 Uniform Mechanical Code and 2016 California Amendments)

2016 California Plumbing Code (CPC) ................................................................................... (Part 5, Title 24, CCR) (2015 Uniform Plumbing Code and 2016 California Amendments)

2016 California Energy Code (CEC) ....................................................................................... (Part 6, Title 24, CCR)

2016 California Fire Code (CFC) ............................................................................................. (Part 9, Title 24, CCR) (2015 International Fire Code and 2016 California Amendments)

2016 California Green Building Standards Code ................................................................ (Part 11, Title 24, CCR)

2016 California Referenced Standards Code ...................................................................... (Part 12, Title 24, CCR)

Title 19 CCR, Public Safety, State Fire Marshall Regulations

2013 ASME A17.1 Safety Code For Elevators and Escalators

PARTIAL LIST OF APPLICABLE STANDARDS

NFPA 13 Automatic Fire Sprinkler Systems ........................................................................................(2016 Edition)

NFPA 72 National Fire Alarm & Signaling Code .................................................................................(2016 Edition)

NFPA 80 Fire Doors and Other Opening Protectives .........................................................................(2016 Edition)

-Reference Code Section for NFPA Standards - 2016 CBC (SFM) Chapter 35. See Chapter 35 for State of California Admendments to NFPA Standards.

FOR ARCHITECTS/ENGINEERS WHO UTILIZE PLANS, INCLUDING BUT NOT LIMITED TO SHOP DRAWINGS, PREPARED BY OTHER LICENSED DESIGN PROFESSIONALS AND/OR CONSULTANTS

(Application No. ______________________ File No. ______________)

The drawings or sheets listed on the cover or index sheet (see asterisk *)This drawing, page of specifications/calculations

have been prepared by other design professionals or consultants who are licensed and/or authorized to prepare such drawings in this state. It has been examined by me for:

1) design intent and appears to meet the appropriate requirements of Title 24, California Code of Regulations and the project specifications prepared by me, and

The Statement of General Conformance “shall not be construed as relieving me of my rights, duties, and responsibilities under Sections 17302 and 81138 of the Education Code and Sections 4-336, 4-341 and 4-344” of Title 24, Part 1. (Title 24, Part 1, Section 4-317 (b))

I certify that: The drawings or sheets listed on the cover or index sheet

is/are in general conformance and

Signature Date

Architect or Engineer designated to be in general responsible charge

Print Name

License Number Expiration Date

Signature Date

Architect or Engineer deligated responsibility for this portion of the work

Print Name

License Number Expiration Date

2) coordination with my plans and specifications and is acceptable for incorporation into the construction of this project.

This drawing or page

have been coordinated

is/are in general conformance and

have been coordinated

X

X

X

X

MARK EACRETT

C-28195 5-31-19

19-34

1. ALL WORK SHALL CONFORM TO 2016 EDITION TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)

2. CHANGES TO THE APPROVED DRAWINGS AND SPECIFICATIONS SHALL BE MADE BY A CONSTRUCTION CHANGE DOCUMENT (CCD) APPROVED BY THE DIVISION OF THE STATE ARCHITECT, AS REQUIRED BY SECTION 4-338, PART I, TITLE 24, CCR

3. A PROJECT INSPECTOR EMPLOYED BY THE DISTRICT (OWNER) AND APPROVED BY THE DIVISION OF THE STATE ARCHITECT SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4-32, PART 1, TITLE 24, CCR; CLASS __3__

BUILDING

GROUP

OCCUPANCY

CLASS

NO. OF

STORIES

TYPE OF

CONSTRUCTION

ALLOWANCE

SQ. FOOTAGE

ACTUAL SQ.

FOOTAGE

BLDG 'B' E 1 VB 9,500 ??

BLDG '?' E 1 VB 9,500 ??

BLDG 'C'(TOILET)

E 1 VB 9,500 ??

1. CONSTRUCTION DOCUMENTS DESCRIBE THE PRODUCTS, SYSTEMS, QUANTITIES, CONFIGURATION AND PERFORMANCE SPECIFICATIONS THAT DELIVER THE OVERALL DESIGN INTENT OF THE PROJECT.

2. THE CONSTRUCTION DOCUMENT DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY BOTH.

3. PERFORMANCE BY THE CONSTRUCTION TEAM SHALL BE CONSISTENT WITH THE CONSTRUCTION DRAWINGS AND SPECIFICATIONS AS NECESSARY TO DELIVER THE INDICATED RESULTS OF THE DESIGN INTENT.

4. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL GOVERNING CODES, ORDINANCES, REGULATIONS AND LAWS.

5. THE DESIGN ADEQUACY AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS AND SCAFFOLDING IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

6. WHERE ANY CONFLICT OCCURS BETWEEN THE REQUIREMENTS OF LAWS, CODES, ORDINANCES, RULES AND REGULATIONS, THE MOST STRINGENT SHALL GOVERN.

7. ENACT ALL MEASURES TO PROTECT AND SAFEGUARD ALL EXISTING ELEMENTS TO REMAIN FROM BEING DAMAGED. REPLACE OR REPAIR EXISTING ELEMENTS DAMAGED BY THE EXECUTION OF THIS CONTRACT TO EQUAL OR BETTER CONDITION.

8. CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE EXISTING OR NEW STRUCTURAL ELEMENTS SHALL NOT BE STARTED UNTIL THE DETAILS HAVE BEEN REVIEWED AND APPROVED BY THE ARCHITECT, AND STRUCTURAL ENGINEER OF RECORD.

9. VERIFY DIMENSIONS AND EXISTING CONDITIONS BEFORE COMMENCING WORK. REPORT DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING WITH AFFECTED WORK.

10. DIMENSIONS NOTED AS "FIELD VERIFY" SHALL BE CHECKED AT THE SITE BY THE CONTRACTOR AND REVIEWED WITH THE ARCHITECT BEFORE INCORPORATING INTO THE WORK.

11. DO NOT SCALE DRAWING. WRITTEN DIMENSIONS TAKE PRECEDENCE. IF CLARIFICATION IS REQUIRED IN ORDER TO DETERMINE THE INTENT OF THE CONTRACT DOCUMENTS, CONTACT THE ARCHITECT.

12. NOTES OR DIMENSIONS LABELED "TYPICAL" SHALL APPLY TO SITUATIONS THAT ARE THE SAME OR SIMILAR.

13. ALL DIMENSIONS ARE TO FACE OF STUD, UNLESS NOTED OTHERWISE.14. ALL SPACES WITH FLOOR DRAINS TO HAVE FINISHED FLOORS SLOPED TO DRAIN NOT TO

EXCEED ONE IN FIFTY.15. COORDINATE HOUSEKEEPING PAD DIMENSIONS AND LOCATIONS WITH EQUIPMENT TO BE

INSTALLED.16. ALL DOORS IN INTERIOR GYP. BD STUD WALLS SHALL BE SET 4" OFF THE PERP. ADJ. WALL

ON THE HINGE SIDE OF THE DOOR UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL CONTACT THE ARCHITECT IF ANY CONFLICTS OCCUR.

17. ALUM. THRESHOLDS TO BE SET IN FULL BED OF SEALANT AT ALL EXT. DOORS.18. COORDINATE ROOF DRAIN LEADER LOCATIONS WITH FLOOR PLAN PRIOR TO SLAB

CONSTRUCTION.19. PROVIDE VINYL REDUCER AT ALL DISSIMILAR FLOOR MATERIALS UNLESS OTHERWISE

NOTED.20. UNLESS OTHERWISE NOTED, ALL ELECTRICAL AND MECHANICAL OPERABLE DEVICES

SHALL BE MOUNTED WITH THE HIGHEST OPERABLE CONTROL AT MAX. OF 42" AFF.21. SHOULD ANY EXISTING CONDITIONS SUCH AS DETERIORATION OR NON-COMPLYING

CONSTRUCTION BE DISCOVERED WHICH IS NOT COVERED BY THE DSA APPROVED DOCUMENTS WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH TITLE 24, CALIFORNIA CODE OF REGULATIONS, A CONSTRUCTION CHANGE DOCUMENT, OR A SEPARATE SET OF PLANS AND SPECIFICATIONS, DETAILING AND SPECIFYING THE REQUIRED REPAIR WORK SHALL BE SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE REPAIR WORK, PER CAC, 2016, 4-317(c)

.

te

cEkra

M

A a r

t

3 -1 20 1 9

5.NER

-

A

CT

ET

HCREDSNE

CIL

I

C L F

IN

RFO

E

AT

S

T

A

A

OI

No. C-28195

NORTHKEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

ONTARIO2855 E. Guasti Road, Suite 402

Ontario, CA 91761909-937-9200 P909-937-6161 F

PBK.com

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

FILE NO.

ACS ______ FLS ______ SS ______

DATE ________________________

APPL.

ENGINEER

ARCHITECT

19-34

00-0000

PARKINGLOT

A

BC

6/1

2/2

01

8 2

:44:4

3 P

M

C:\U

sers

\aro

drig

uez\D

ocum

ent s

\17

163_

Ric

hm

ond E

S D

aycare

_aro

drigu

ez.r

vt

TH

E L

EA

RN

ING

CO

NN

EC

TIO

N

G0.01

SHEET INDEX,DRAWING

CONVENTIONS, ANDVICINITY MAP

Checker

Author

Issue Date

17163

CLIENT NAME

640

Virg

inia

St.

El S

egun

do, C

A 9

0 245

DRAWING CONVENTIONS

SVDF SHEET VINYL DANCE FLOORING

SVF SHEET VINYL FLOORING

T.A.S. TEXAS ACCESSIBLITY STANDARDS(2012)

T.B. TACK BOARD

T.D.R. TOWEL DISPENSER AND RECEPTACL

T.O. TOP OF

T.O.B. TOP OF (WOOD) BLOCKING

T.O.M. TOP OF MASONRY

T.O.P. TOP OF PARAPET

T.O.S. TOP OF STEEL

T.T.D. TOILET TISSUE DISPENSER

TEL TELEPHONE

TERR TERRAZZO

THK THICK (NESS)

TYP TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

UR. URINAL

V VENT

V.C.T. VINYL COMPOSITION TILE

V.I.F. VERIFY IN FIELD

VENT. VENTILATING, VENTILATED

VER. VERIFY

VERT. VERTICAL

VGB (PREFINISHED) VINYL CLAD GYPSUMBOARD

VWC VINYL WALL COVERING

W WASHING MACHINE

W.P. WATER PROOFING

W.S. WEATHERSTRIP

W.W. WATER WELL

W.W.F. WELDED WIRE FABRIC

W.W.M. WOVEN WIRE MESH

W/ WITH

WC WATER CLOSET

WD WOOD

WDW WINDOW

WT WEIGHT

N.D. NAPKIN DISPOSAL

N.I.C. NOT IN CONTRACT

N.T.S. NOT TO SCALE

N.V. NAPKIN VENDOR

NO. NUMBER

NOM. NOMINAL

O.C. ON CENTER (S)

O.C.E.W. ON CENTER EACH WAY

O.D. OUTSIDE DIAMETER

O.F.C.I. OWNER FURNISHED, CONTRACTORINSTALLED

O.H. OPPOSITE HAND

OPNG. OPENING

OPP. OPPOSITE

P. LAM. / PLAM PLASTIC LAMINATE

P.C. PRECAST

P.H. PAPER HOLDER

P.L. PROPERTY LINE

P.P. POWER POLE

P.W.B. PREFINISHED WALL BOARD

PL. PLATE

PLUMB. PLUMBING

PLYWD. PLYWOOD

POL. POLISHED

PR. PAIR

PREFIN. PRE-FINISHED

PT PRESSURE-TREATED

PT. POINT

PTD. PAINTED

Q.T. QUARRY TILE

R / RAD RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE. , REF. REFER TO / REFERENCE / SEE

RECP. RECEPTACLE

REINF. REINFORCE (D), (ING)

REQ'D. REQUIRED

RES. RESILIENT

REV. REVISION (S), REVISED

RF RECREATIONAL RESILIENT FLOORING

RPG. RELOCATABLE PAINTED GYPSUMBOARD

RSS. ROD STOCK AND SEALANT

S.C. SEALED CONCRETE

S.D. SOAP DISPENSER

S.N.D. SANITARY NAPKIN DISPOSAL

SCHED SCHEDULE

SCPL SOLID CORE PLASTIC LAMINATE

SECT SECTION

SHT SHEET

SIM SIMILAR

SPC SPECIAL COATING SYSTEM

SPEC SPECIFICATION (S)

SQ. SQUARE

SS / SS. STL. STAINLESS STEEL

STL STEEL

STRUC / STRUCT STRUCTURAL

SUSP SUSPENDED

EXT EXTERIOR

F.E. FIRE EXTINGUISHER

F.E.C. FIRE EXTINGUISHER CABINET

F.H.C. FIRE HOSE CABINET

FB. FACE BRICK

FD. FLOOR DRAIN

FIN. FINISH (ED)

FIXT. FIXTURE

FLR. FLOOR (ING)

FLSHG. FLASHING

FLUOR FLUORESCENT

FRP FIBER REINFORCED PLASTIC

G.B. GRAB BAR

G.I. GALVANIZED IRON

GA. GAUGE

GALV. GALVANIZED

GCMU GLAZED CONCRETE MASONRY UNIT

GEN. GENERAL

GEN. GENERAL

GL. GLASS / GLAZING

GL. GLASS

GR. GRADE

GTP. GLAZED TILE PAVER

GYP. GYPSUM DRYWALL

H.W. HOT WATER

HM HOLLOW METAL FRAME

HORIZ. HORIZONTAL

HT. HEIGHT

I.D. INSIDE DIAMETER

I.P.S. IRON PIPE SIZE

INSUL INSULATE (ED), (ION)

INT. INTERIOR

JT. JOINT

L.P. LIGHT POLE

LAM. LAMINATE (D)

LAV. LAVATORY

LT. LIGHT

LT. WT. LIGHTWEIGHT

M.O. MASONRY OPENING

MAS. MASONRY

MATL. MATERIAL (S)

MAX. MAXIMUM

MB. MARKER BOARD

MECH. MECHANICAL

MEM MEMBRANE

MEM. WP. MEMBRANE WATERPROOFING

MEP MECHANICAL, ELECTRICAL, PLUMBING

MEPT MECHANICAL, ELECTRICAL, PLUMBING,TECHNOLOGY

MEZZ. MEZZANINE

MFR. / MANUF. MANUFACTURE (R)

MH. MANHOLE

MIN. MINIMUM

MISC. MISCELLANEOUS

MOD MODULAR

MTL METAL

MTP. METAL TOILET PARTITION

A.D. AREA DRAIN

A.D.A. AMERICANS WITH DISABILITIES ACT

A.D.A. 2010 ADA STANDARDS FORACCESSIBLE DESIGN

A.D.A.A.G. AMERICANS WITH DISABILITIES ACTACCESSIBILITY GUIDELINES

A.F.F. ABOVE FINISH FLOOR

A.F.G. ABOVE FINISH GRADE

A.H.J. ATHORITY HAVING JURISDICTION

A/C AIR CONDITIONING

ACP. ACOUSTICAL PANEL

ACT. ACOUSTICAL TILE

ADJ. ABADJUSTABLE

ALT. ALTERNATE

ALUM. ALUMINUM

ASPH. ASPHALT

ے ANGLE

B.O.D. BOTTOM OF DECK

B.U.R. BUILT-UP ROOF

BD. BOARD

BLDG. BUILDING

BLK. BLOCK

BM. BEAM

C CHANNEL

C.J. CONTROL JOINT

C.M.U. CONCRETE MASONRY UNIT

C.W. COLD WATER

CAB, CABT CABINET

CFMF COLD-FORMED METAL FRAMING

CFSF COLD-FORMED STEEL FRAMING

CL CENTERLINE

CLG. CEILING

COL. COLUMN

COMP. COMPRESSIBLE

CONC. CONCRETE

COND. CONDITION

CONT. CONTINUOUS

CORR. CORRIDOR

CPT. CARPET (ED)

CT. CERAMIC TILE

CTSK. COUNTER SINK

D DRYER

D.F. DRINKING FOUNTAIN

D.P. DAMPPROOFING

D.S. DOWN SPOUT

DIA. DIAMETER

DIM. DIMENSION

DTL. DETAIL

DWG. DRAWING

E.J. EXPANSION JOINT

E.Q. EQUAL

EA. EACH

EDF ELECTRIC DRINKING FOUNTAIN

EL. ELEVATION (HEIGHT)

ELEC. ELECTRICAL

ELECT. ELECTRICAL

ELEV ELEVATION (DRAWING)

EQUIP EQUIPMENT

EXIST EXISTING

EXP EXPANSION

ABBREVIATIONS

SHEET NUMBERINGVICINITY MAP

OWNER

EL SEGUNDO UNIFIED

SCHOOL DISTRICT

641 SHELDON STREET,EL SEGUNDO, CA 90245T: 310.615.2650 X.1510F: -CONTACT: DYLAN FARRIS

ARCHITECTURAL

PBK ARCHITECTS, INC.

2855 E. GUASTI RD., SUITE 402ONTARIO, CA 91761T: 909-937-9200F: 909-937-6161CONTACT: MARCO EACRETT

ELECTRICAL

TK1SC

15231 LAGUNA CANYON RD., #100IRVINE, CA 92618T: 951.299.4160F: -CONTACT: BILL VOLLER

PROJECT TEAM

CODE & STANDARDS

ALL CONTRUCTION AND SERVICES REQUIRED TO PROVIDE THE INSTALLATION OF ONE (1) NEW 40'x72' MODULAR CLASSROOM, ONE (1) NEW 40'x12' MODULAR TOILET BUILDING, PARKING LOT, AND SITE WORK.

NOTE:FIRE SAFETY DURING DEMOLITION AND/OR CONSTRUCTION SHALL COMPLY WITH 2016 CFC CHAPTER 33

SCOPE OF WORK

STATEMENT OF GENERAL CONFORMANCE

DSA NOTES

GENERAL NOTES DEFERRED APPROVAL ITEMS

CODE ANALYSIS

NONE

DRAWING INDEX

CIVIL

FPL & ASSOCIATES, INC.

30 CORPORATE PARK, #401IRVINE, CA 92606T: 949.252.1688 X. 203F: 949.252.0088CONTACT: RON CANEDY

ARCHITECTURALA0.02 ENLARGED SITE PLANS & DETAILS

A0.03 SITE DETAILS

A2.02 FIRST FLOOR PLAN BLDG 'A'

A4.01 ENLARGED PLANS

A4.06 ENLARGED STAIR PLANS, SECTIONS AND DETAILS

A5.01 PLAN DETAILS

A6.01 EXTERIOR ELEVATIONS

AV0.00 ACOUSTICAL AV SHEET

AV1.01 ACOUSTICAL AV SHEET

AV1.02 ACOUSTICAL AV SHEET

AV1.03 ACOUSTICAL AV SHEET

CIVILC.000 CIVIL SHEET

C.101 CIVIL SHEET

C.102 CIVIL SHEET

C.103 CIVIL SHEET

ELECTRICALE0.00 ELECTRICAL SHEET

E1.01 ELECTRICAL SHEET

E1.02 ELECTRICAL SHEET

E1.03 ELECTRICAL SHEET

*MODULAR BUILDINGSTH0.00 THEATRICAL SHEET

TH1.01 THEATRICAL SHEET

TH1.02 THEATRICAL SHEET

TH1.03 THEATRICAL SHEET

No. Description Date

TOTAL SHEETS:

GENERALG0.01 SHEET INDEX, DRAWING CONVENTIONS, AND

VICINITY MAP

G0.02 ACCESSIBILITY SITE PLAN

G0.03 FIRE ACCESS SITE PLAN

G0.04 ARCHITECTURAL SPECIFICATIONS

STRUCTURALS.000 STRUCTURAL SHEET

S.001 STRUCTURAL SHEET

S.100 STRUCTURAL SHEET

S.101 STRUCTURAL SHEET

SD-1.00 OPTION 2

SD-1.01 OPTION 3

SD-1.02 OPTION 4B

SD-1.03 OPTION 4-A

SD-1.04 OPTION 5

SD-1.05 Unnamed

DEMOLITIOND0.01 SITE DEMOLITION PLAN

D0.02 TOPO& UTILITY SURVEY - FOR REFERENCE ONLY

DD.01 SITE PLAN

DD.02 PROPOSED FLOOR PLAN

DD.03 PROGRESS-SITE PLAN

TH

E L

EA

RN

ING

CO

NN

EC

TIO

ND

EM

OL

ITO

N O

F E

XIS

TIN

G B

LD

G.

TLC

DEMOLITIOND0.01 SITE DEMOLITION PLAN

D0.02 TOPO& UTILITY SURVEY - FOR REFERENCE ONLY

DEMOLITION OF BUILDING 'TLC' AND INSTALLATION OF ONE (1) TEMPORARY POLE.

EL SEGUNDO USD

Page 3: Addendum #2 DEMOLITION OF EXISTING TLC BUILDING … 2 Project 19-004 w Demo Specs.pdfexisting partition new partition n - 58' 2" e - 150' 11" 1 a-100 section callout symbol a sheet

GENERAL DEMOLITION NOTES

1. DEMOLITION PLANS INDICATE SOME OF THE SCOPE-OF-WORK INVOLVED FOR THE DEMOLITION PHASE OF THIS PROJECT. CONTRACTOR SHALL REVIEW ALL SHEETS FOR ADDITIONAL DEMOLITION SCOPE.

2. CONTRACTOR SHALL VERIFY EXISTING SITE AND BUILDING CONDITIONS AND DIMENSIONS IN THE FIELD PRIOR TO DEMOLITION ACTIVITIES AND WORK.

3. CONTRACTOR SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES IN WRITING.4. CONTRACTOR SHALL NOTIFY ARCHITECT AND OWNER OF ANY POSSIBLE ASBESTOS

CONTAINING MATERIALS DISCOVERED BEFORE PROCEEDING WITH WORK, PROTECT INTERIOR CONSTRUCTION TO REMAIN DURING DEMOLITION AND CONSTRUCTION.

5. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS BEFORE COMMENCING WORK.6. AFTER AWARD OF THE CONTRACT, CHANGE ORDER REQUESTS FOR ADDITIONAL

MONEY WILL NOT BE APPROVED IF THE WORK COULD HAVE BEEN ANTICIPATED DURING A SITE VISIT BY THE CONTRACTOR.

7. CONTRACTOR SHALL NOT SCALE DRAWINGS.8. CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY SHORING, TEMPORARY

BRACING, AND OR TEMPORARY SUPPORTS AS REQUIRED TO MAINTAIN STRUCTURAL INTEGRITY OF EXISTING STRUCTURE TO REMAIN AND OR EXISTING BUILDING ELEMENTS TO REMAIN.

9. CONTRACTOR IS TO VERIFY THE EXACT LOCATION OF ALL EXISTING UTILITIES PRIOR TO DEMOLITION ACTIVITIES AND WORK.

10. CONTRACTOR SHALL REMOVE TRASH AND DEBRIS REGULARLY AS NECESSARY TO ELIMINATED INTERFERENCE WITH ROADS, STREET, WALKS, AND ALL OTHER ADJACENT FACILITIES.

11. CONTRACTOR SHALL REMOVE TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.12. CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION OF TEMPORARY DUST AND OR

SOUND PARTITION BETWEEN CONSTRUCTION AREA AND AREAS NOT IN SCOPE AS NECESSARY. DEMOLITION ACTIVITIES SHALL BE PERFORMED SO AS TO PRODUCE MINIMAL DISTURBANCE TO EXISTING FACILITY AND OCCUPANTS (I.E. MINIMIZE EXCESSIVE AND PROLONGED NOISE LEVELS AND DUST).

13. CONTRACTOR SHALL REPAIR, REPLACE, OR PATCH EXISTING BUILDINGS, DRIVEWAYS, SIDEWALKS, CANOPIES, AND OR PARKING AREAS DAMAGED, MODIFIED, AND OR DISTURBED BY DEMOLITION WORK AT NO COST TO THE OWNER.

14. ALL EXISTING EQUIPMENT THAT REMAINS SHALL BE PROTECTED DURING DEMOLITION AND OR CONSTRUCITON TO PREVENT DAMAGE. ANY DAMAGE TO REMAINING EXISTING EQUIPMENT SUSTAINED DURING DEMOLITION AND OR CONSTRUCITON SHALL BE EQUIVALENTLY REPLACED OR EQUIVALENTLY REPAIRED AT NO COST TO THE OWNER.

15. CONTRACTOR SHALL PROVIDE TRAFFIC HANDLING MEASURES TO PROTECT THE GENERAL PUBLIC AT ALL TIMES, AS NECESSARY AND AS REQURED BY AUTHORITIES HAVING JURISDICTION.

16. DO NOT INTERRUPT EXISTING UTILITIES, EXCEPT WHEN AUTHORIZED IN WRITING BY AUTHORITIES HAVING JURISDICTION. PROVIDE TEMPORARY SERVICES DURING INTERRUPTIONS TO EXISTING UTILITIES, AS ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.

17. WHEN UTILITY SERVICES ARE REQUIRED TO BE REMOVED, RELOCATED, OR ABANDONED, PROVIDE BYPASS CONNECTIONS TO MAINTAIN CONTINUITY OF SERVICE BEFORE PROCEEDING WITH DEMOLITION.

18. CONTRACTOR SHALL CONTACT ALL UTILITY COMPANIES INCLUDING BUT NOT LIMITED TO THE FOLLOWING: ELECTRIC, GAS, WATER, TELEPHONE, STORM SEWER, AND SANITARY SEWER FOR FIELD LOCATION OF ALL UNDERGROUND AND OVERHEAD UTILITY LINES. PRIOR TO COMMENCEMENT OF ANY DEMOLITION WORK, CONTRACTOR SHALL IDENTIFY ALL ELECTRICAL CIRCUITS SERVICING THE AREA INVOLVED WITH THIS DEMOLITION. THOSE CIRCUITS SHALL THEN BE LOCKED OUT AND TAGGED OUT IF THEY DO NOT SERVICE ANY OF THE REMAINING BUILDING. THOSE CIRCUITS WHICH ARE IDENTIFIED TO SERVICE BOTH THE AREA TO BE DEMOLISHED AND THE REMAINING BUILDING SHALL BE SPLIT SO AS TO KILL ALL ELECTRICAL POWER TO THE AREA TO BE DEMOLISHED WHILE MAINTAINING POWER TO THE REMAINDER OF THE BUILDING.

19. PROTECT EXISTING SITE ELEMENTS AND EXISTING LANDSCAPING TO REMAIN. PROTECTION SHALL INCLUDE BUT NOT BE LIMITED TO EXISTING TREES AND OTHER EXISTING VEGETATION INDICATED TO REMAIN IN PLACE AGAINST UNNECESSARY CUTTING, BREAKING, OR SKINNING OF ROOTS, SKINNING OR BRUISING OF BARK, SMOTHERING OF TREES BY STOCKPILING CONSTRUCTION MATERIAL OR EXCAVATED MATERIAL WITHIN DRIP LINES.

20. CONTRACTOR SHALL REGRADE AND HYDROMULCH AREAS AFFECTED BY DEMOLITION.21. OWNER HAS RIGHT OF FIRST REFUSAL OF ALL ITEMS REMOVED AS PART OF THE

SCOPE OF WORK, WHETHER IDENTIFIED AS SALVAGE OR NOT.22. NOTIFY THE BUILDING OWNER OF ANY MATERIALS, FIXTURES, ETC. TO BE REMOVED

THAT ARE DEEMED SALVAGEABLE. TURN OVER ANY REQUESTED ITEMS TO THE BUILDING OWNER IN GOOD CONDITION.

23. ALL FURNITURE WILL BE REMOVED OR RELOCATED BY THE OWNER AS NECESSARY PRIOR TO THE DEMOLITION WORK OF THIS PROJECT. CONTRACTOR SHALL COORDINATE WITH OWNER AS REQUIRED.

24. REMOVE EXISTING CONSTRUCTION TO THE EXTENT INDICATED ON THE DRAWINGS. SHOULD ANY DAMAGE OCCUR TO ANY EXISTING CONSTRUCTION TO REMAIN, THE CONTRACTOR SHALL REPAIR THE DAMAGE TO MATCH EXISTING AND OR ADJACENT CONSTRUCTION AT NO COST TO THE OWNER.

25. WHEN UNANTICIPATED MECHANICAL, ELECTRICAL, OR STRUCTURAL ELEMENTS THAT CONFLICT WITH THE INTENDED FUNCTION OR DESIGN ARE ENCOUNTERED, DETERMINE THE NATURE AND EXTENT OF THE CONFLICT AND NOTIFY THE ARCHITECT IMMEDIATELY FOR RESOLUTION.

26. EXISTING WALLS (OR PORTIONS OF WALLS) TO BE REMOVED SHALL BE CUT FLUSH WHERE INTERSECTING WITH WALLS TO REMAIN.

27. COORDINATE WITH RELATED SUB CONTRACTORS THE EXTENT OF ALL DEMOLITION WORK.

28. THE CONTRACTOR SHALL NOT ABANDON IN PLACE ANY EXISTING UNDERGROUND STRUCTURE, UTILITY, OR IMPROVEMENT SO DESIGNATED FOR REMOVAL ON THE PROJECT PLANS UNLESS DIRECTED BY THE OWNER.

29. CONTRACTOR SHALL INSTALL A MINIMUM OF 8 FOOT HIGH CONSTRUCTION FENCE AROUND PERIMETER OF DEMOLITION AREA WITH GREEN OR BLUE SCREEN.

30. ALL DASHED LINES ARE DEMOLITION LINES UNLESS NOTED OTHERWISE.

PALM AVE.

VIR

GIN

IA S

T.

BLDG. 'A'A# 03-104326

(EXISTING BLDG TO REMAIN)

DOWN

DF

DF

C

C

BLDG. 'TLC'(EXISTING BLDG., ROOF CANOPIES,

EXPOSED COLUMNS, AND FOOTINGS TO BE

DEMOLISHED)

S

01.16

02.12

01.02

01.05

01.05

01.09

01.05

01.04

01.11

02.12

02.03 TYP.02.25

02.0602.06

02.0402.04

02.0502.05

02.09

02.0502.05

02.0702.07

02.10

EM

02.11

TYP.

02.1302.13

02.1202.12

02.14TYP.

02.15

02.16

02.14

02.06

02.06

6' - 0"

D0.01

1

02.17

EE

E

EE

02.19

02.03

02.03

01.15

02.20

01.14

02.0502.05

02.14

02.24

02.14

02.16

02.21

02.1402.14

02.2302.23

02.22

02.24

32.0132.01

32.01

32.01

02.14

02.08

EM

02.11

02.16

02.18

E

.

te

cEkra

M

A a r

t

3 -1 20 1 9

5.NER

-

A

CT

ET

HCREDSNE

CIL

I

C L F

IN

RFO

E

AT

S

T

A

A

OI

No. C-28195

NORTHKEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

ONTARIO2855 E. Guasti Road, Suite 402

Ontario, CA 91761909-937-9200 P909-937-6161 F

PBK.com

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

FILE NO.

ACS ______ FLS ______ SS ______

DATE ________________________

APPL.

ENGINEER

ARCHITECT

19-34

00-0000

PARKINGLOT

A

BC

6/1

2/2

01

8 2

:21:3

7 P

M

C:\U

sers

\aro

drig

uez\D

ocum

ent s

\17

163_

Ric

hm

ond E

S D

aycare

_aro

drigu

ez.r

vt

TH

E L

EA

RN

ING

CO

NN

EC

TIO

N

D0.01

SITE DEMOLITIONPLAN

Checker

Author

Issue Date

17163

CLIENT NAME

640

Virg

inia

St.

El S

egun

do, C

A 9

0 245

3/32" = 1'-0"6 DEMOLITION SITE PLAN

DEMOLITION KEY NOTES` Description

01.02 DEMO (E) AC PAVING AND BASE MATERIAL

01.04 DEMO (E) CONC. WALKWAY

01.05 DEMO (E) CONC. STEPS

01.09 DEMO (E) DRINKING FOUNTAIN

01.11 DEMO (E) CONC. CURB

01.14 DEMO (E) WATER RISER, CAP FOR FUTURE USE

01.15 DEMO (E) BLDG. GAS LINE BELOW GRADE TO (E) GAS METER. CAP AT MAIN

01.16 DEMO (E) RAISED CONC. PLATFORM AND FOOTINGS

NORTH

NOTE:

- MAINTAIN ELECTRICAL CONTINUITY PER 1/D0.01

- CONTRACTOR TO VERIFY LOCATION OF ALL EXISTING UTILITIES PRIOR TO DEMOLITION.

- FOR REFERENCE ONLY SEE SHEET D0.02 FOR EXISTING SITE UTILITIES AND TOPO SURVEY.

- DISCONNECT WATER, SEWER, AND GAS AND CAP BELOW GRADE AS REQUIRED.

- PROTECT PUBLIC SIDEWALK

- PICNIC TABLES TO BE REMOVED BY THE OWNER BEFORE DEMOLITION

CONSTRUCTION KEY NOTES` Description

02.03 (E) TREES TO REMAIN

02.04 (E) RUBBERIZED PLAY AREA TO REMAIN

02.05 (E) CONC. PAVEMENT TO REMAIN, PROTECT IN PLACE

02.06 (E) GRASS AREA TO REMAIN

02.07 (E) PLAY FIELD TO REMAIN

02.08 (E) UTILITY/POWER POLE TO REMAIN

02.09 (E) TETHER-BALL COURT TO REMAIN

02.10 (E) CONC. WALL TO REMAIN, PROTECT IN PLACE

02.11 (E) ELECTRICAL PANEL & METER TO BE REMOVED

02.12 (E) AC PAVING TO REMAIN

02.13 (E) CONC. RAMP AND HANDRAILS TO REMAIN, PROTECT IN PLACE

02.14 (E) C.L. FENCE TO REMAIN

02.15 (E) MARQUEE TO REMAIN

02.16 (E) CONC. CURB/LOW WALL TO REMAIN

02.17 (E) OVERHEAD SCE COMPANY ELECTRICAL SURVICE TO BE RELOCATED

02.18 TEMP. POWER POLE TO BE PROVIDED, INTERCEPT (E) POWER CONDUCTORS SERVINGBLDG. 'A' AND CONNECT TO TEMP. POWER

02.19 (E) UNDERGROUND ELECTRICAL CONDUIT AND WIRING TO REMAIN

02.20 (E) IRRIGATION BACKFLOW PREVENTER TO REMAIN, PROTECT IN PLACE

02.21 (E) C.L. GATE TO REMAIN

02.22 PROVIDE ACCESS DURING DEMOLITION

02.23 EXTENT OF DEMOLITION

02.24 (E) ACCESSIBLE GATE WITH PANIC HARDWARE AND KEYPAD, TO REMAIN AND PROTECTIN PLACE

02.25 (E) UTILITY/POWER POLE TO REMAIN, PROVIDES OVERHEAD LINE TO (E) ELECTRICALPANEL

32.01 REGRADE TO MATCH ADJACENT (E) FINISH GRADE, BACKFILL AREA AS REQUIRED ANDINSTALL (N) SOD, CONTRACTOR TO PROVIDE IRRIGATION SHOP DWGS FOR REVIEW ANDAPPROVAL

1/2" = 1'-0"1 EXTENT OF WALL DEMO - ELECT. METER

No. Description Date

DE

MO

LIT

ON

OF

EX

IST

ING

BL

DG

.

TLC

EL SEGUNDO USD

Page 4: Addendum #2 DEMOLITION OF EXISTING TLC BUILDING … 2 Project 19-004 w Demo Specs.pdfexisting partition new partition n - 58' 2" e - 150' 11" 1 a-100 section callout symbol a sheet

BLDG 'TLC'(TO BE DEMOLISHED)

BLDG. 'A'A# 03-104326(TO REMAIN)

SEWER

GAS

STORM DRAIN

DOMESTIC WATER

SANITARY SEWER

GAS

ELECTRICAL/POWER

COMMUNICATIONS

STREET LIGHT

UNKNOWN UTILITY

DEPTHS SHOWN ARE APPROXIMATE. ESTIMATED DEPTHS ARE FROM THE GROUND SURFACE TO THE CENTER OF THE FACILITY, INVERT OF WASTE LINES, OR TO THE FACILITY TRACER WIRE. DEPTH ESTIMATES SHOULD BE USED WITH CAUTION AND MAY VARY ALONG THE LENGTH OF THE FACILITY.

DEPTH FROM SURFACE 1'-6"

SD SD

W W

S S

G G

E E

C C

SL SL

U U U

CIVIL LEGEND

.

te

cEkra

M

A a r

t

3 -1 20 1 9

5.NER

-

A

CT

ET

HCREDSNE

CIL

I

C L F

IN

RFO

E

AT

S

T

A

A

OI

No. C-28195

NORTHKEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

ONTARIO2855 E. Guasti Road, Suite 402

Ontario, CA 91761909-937-9200 P909-937-6161 F

PBK.com

IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT

FILE NO.

ACS ______ FLS ______ SS ______

DATE ________________________

APPL.

ENGINEER

ARCHITECT

19-34

00-0000

PARKINGLOT

A

BC

6/1

2/2

01

8 2

:21:4

1 P

M

C:\U

sers

\aro

drig

uez\D

ocum

ent s

\17

163_

Ric

hm

ond E

S D

aycare

_aro

drigu

ez.r

vt

TH

E L

EA

RN

ING

CO

NN

EC

TIO

N

D0.02

TOPO& UTILITYSURVEY - FOR

REFERENCE ONLY

Checker

Author

Issue Date

17163

CLIENT NAME

640

Virg

inia

St.

El S

egun

do, C

A 9

0 245

1/16" = 1'-0"6 TOPO & UTILITY SURVEY - FOR REFERENCE ONLY

NORTH

No. Description Date

DE

MO

LIT

ON

OF

EX

IST

ING

BL

DG

.

TLC

EL SEGUNDO USD