addendum #1 - iowa

8
IMCC Boiler #1 Replacement Coralville, Iowa 52241 DAS#9054.01 RFB905401-01 Page 1 of 2 Addendum #1 ADDENDUM #1 Project Name: IMCC Boiler #1 Replacement DAS#9054.01 RFB 905401-01 Addendum #1 Dated: March 29, 2021 This Addendum forms a part of the bidding and contract documents. This Addendum supersedes and supplements all portions of the original bidding and contract documents dated March 17, 2021 with which it conflicts. ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE SPACE PROVIDED ON THE BID FORM. FAILURE TO DO SO MAY SUBJECT THE BIDDER TO DISQUALIFICATION. 1. BID CLARIFICATIONS A. CHANGES TO BID SUBMITTAL AND OPENING Due to the circumstances surrounding COVID-19, the State is amending the bid submittal and public opening procedures of the above RFB. BID SUBMITTAL The Bid shall be submitted to the Issuing Officer through the Iowa VSS electronic bidding system. The link to VSS is: https://vss.iowa.gov/webapp/VSS_ON/AltSelfService. VSS should be accessed via Internet Explorer. Bidder will need to register regardless of whether it has already done business with the State of Iowa. Click the Register button on the left side of the VSS screen to start the registration process. If you have any issues with registration, please call the helpdesk at 515-281-6614. Bidders should complete the registration process and ensure the ability to log in as soon as possible to ensure Bids can be submitted on the due date as the helpdesk is not available 24/7. Bids should be split into several files if the bid exceeds the 10MB threshold. There is no limit on the number of files which can be uploaded. Please make sure the electronic documents submitted contain all of the required signatures. Digital signatures will be accepted. Bidders without access to electronic means should contact the issuing officer at 515-322-2893. PUBLIC OPENING The public opening will be held via conference call only. The call details are below. Call time: 3:00pm on (April 14, 2021) Call number: 617-675-4444 Pin: 279 966 995 3317#

Upload: others

Post on 01-Jan-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM #1 - Iowa

IMCC Boiler #1 Replacement Coralville, Iowa 52241

DAS#9054.01 RFB905401-01

Page 1 of 2 Addendum #1

ADDENDUM #1

Project Name: IMCC Boiler #1 Replacement DAS#9054.01 RFB 905401-01 Addendum #1 Dated: March 29, 2021

This Addendum forms a part of the bidding and contract documents. This Addendum supersedes

and supplements all portions of the original bidding and contract documents dated March 17,

2021 with which it conflicts.

ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE SPACE PROVIDED ON THE

BID FORM. FAILURE TO DO SO MAY SUBJECT THE BIDDER TO

DISQUALIFICATION.

1. BID CLARIFICATIONS

A. CHANGES TO BID SUBMITTAL AND OPENING

Due to the circumstances surrounding COVID-19, the State is amending the bid submittal and public opening procedures of the above RFB. BID SUBMITTAL The Bid shall be submitted to the Issuing Officer through the Iowa VSS electronic bidding system. The link to VSS is: https://vss.iowa.gov/webapp/VSS_ON/AltSelfService. VSS should be accessed via Internet Explorer. Bidder will need to register regardless of whether it has already done business with the State of Iowa. Click the Register button on the left side of the VSS screen to start the registration process. If you have any issues with registration, please call the helpdesk at 515-281-6614. Bidders should complete the registration process and ensure the ability to log in as soon as possible to ensure Bids can be submitted on the due date as the helpdesk is not available 24/7. Bids should be split into several files if the bid exceeds the 10MB threshold. There is no limit on the number of files which can be uploaded. Please make sure the electronic documents submitted contain all of the required signatures. Digital signatures will be accepted. Bidders without access to electronic means should contact the issuing officer at 515-322-2893. PUBLIC OPENING The public opening will be held via conference call only. The call details are below. Call time: 3:00pm on (April 14, 2021) Call number: 617-675-4444 Pin: 279 966 995 3317#

Page 2: ADDENDUM #1 - Iowa

IMCC Boiler #1 Replacement Coralville, Iowa 52241

DAS#9054.01 RFB905401-01

Page 2 of 2 Addendum #1

2. SPECIFICATIONS

A. Section 00 0107 – Seals Page:

1. Change footer from 00 0105 to 00 0107.

B. Section 00 0110 – Table Of Contents:

1. Change 23 4313 Fans to 23 3413.

C. Section 22 1116 – Domestic Water Piping:

1. Change footer from 00 0110 to 22 1116.

D. Section 23 1123 – Facility Natural-Gas Piping:

1. Change footer from 00 0110 to 23 1123.

E. Section 26 0533.16 – Boxes For Electrical Systems:

1. Change footer from 26 0533 to 26 0533.16

3. DRAWINGS

A. Replace the following drawing sheets: A10, MD01, M11, M51, E00 & E11.

4. QUESTIONS AND CLARIFICATIONS

A. Estimated cost of the project? A> The estimated cost of the project is $520,000.00.

B. Who has roof warranties? A> No known warranties.

C. Do contractors supply boiler? A> Yes.

D. What weld inspection, xray, qualifications will be needed per B31.1. A> Welders to be

qualified per the ASME Boiler & Pressure Vessel Code, Section IX. Provide Weld procedure

specifications for each welder on the project. Non-destructive testing per ASME B&PV Code,

Section V. See Specifications (230500, 232213, 235239) for information.

5. ATTACHMENTS

A. Drawing sheets: A10, MD01, M11, M51, E00 & E11.

END OF ADDENDUM

Page 3: ADDENDUM #1 - Iowa

4 5 6 7 8

A

B

C

A.9

3.5

2

A20

2

A20

21'-2" 10'-0" 10" 20'-10" 3'-4" 7'-10"

NEW OVERHEAD SECTIONAL DOOR AND OVERHEAD TRACKS. FINISH OPENING EDGES PER MANUFACTURER'S WRITTEN RECOMMENDATION FOR METAL CAP AT PERIMETER. PREFINISHED METAL - MATCH EXISTING OVER HEAD DOOR. SEE

OFFICE

BOILER ROOM

32'-0" 32'-0"

NEW LOUVER OVER DOOR. SEE SHEET A20.

PRIME AND PAINT ALL NEW STEEL TO MATCH EXISTING - PRO-CRYL UNIVERSAL PRIMER WITH TWO COATS SHERWIN WILLIAMS SHER-CRYL HPA OR APPROVED EQUIVALENT -TYPICAL

5/A50

1. ALL DIMENSION SHALL BE FIELD VERIFIED PRIOR TO DEMOLITION AND RECONSTRUCTION. COORDINATE LOCATION OF PROPOSED COLUMNS, HEADERS, AND GIRTS WITH DOOR AND LOUVER MANUFACTURER INFORMATION FOR CLEAR OPENING DIMENSIONS.

2. ALL PROPOSED STRUCTURAL STEEL CHANNELS, PLATES, AND ANGLES SHALL BE MINIMUM ASTM A36 STEEL.

3. CONCRETE SCREWS SHALL BE GALVANIZED OR STAINLESS STEEL.

4. CONCRETE SCREWS SHALL BE ANCHORED INTO SOUND CONCRETE. CONTACT ENGINEER IF SCREW, WHERE INDICATED TO BE INSTALLED PER DETAILS, IS LOCATED IN CRACKED OR DELAMINATED CONCRETE PRIOR TO ANY STEEL FABRICATION.

5. REFER TO DRAWINGS OF ALL TRADES FOR ADDITIONAL INFORMATION REGARDING ITEMS PENETRATING FLOORS, WALLS, AND CEILINGS.

6. ALL NEW PARTITIONS ARE DIMENSIONED TO FACE OF STUD, MASONRY, OR CONCRETE COMPONENT UNLESS NOTED OTHERWISE. DIMENSIONS TO EXISTING ELEMENTS ARE TO EXPOSED FACE.

7. CONTRACTOR TO TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO OWNER'S OCCUPIED AREAS ADJACENT TO NEW CONSTRUCTION. CONTRACTOR TO PROVIDE ALL LABOR AND MATERIALS TO REPAIR ALL DISTURBED ELEMENTS AT CONSTRUCTION ACCESS AND ACCESS ROUTES. ALL REPAIRS SHALL MATCH EXISTING CONSTRUCTION AND FINISHES.

8. COORDINATE LOCATION OF CEILING MOUNTED OVERHEAD DOOR ITEMS WITH EXISTING CONDITIONS.

9. CONTRACTOR SHALL COVER ANY OPENINGS WITH TEMPORARY CLOSURES WHEN NOT WORKING ON SITE TO PREVENT WEATHER, INSECTS, RODENTS AND INTRUDERS FROM ENTERING FACILITY.

FLOOR PLAN NOTES

4 5 6 7 8

A

B

C

A.9

3.5

32'-0" 32'-0"

21'-2" 10'-0" 10" 20'-10" 3'-4" 7'-10"

1

A20

1

A20

CUT EXTERIOR WALL ABOVE EXISTING DOOR FOR NEW LOUVER - 3'-6" x 2'-6"

OFFICE

BOILER ROOM

CUT EXTERIOR WALL TO DIMENSION INDICATED. PREPARE EDGES TO RECEIVE NEW DOOR AND BENT METAL ENCLOSURE OR DOOR MANUFACTURER'S RECOMMENDED WALL CAPS TO MATCH EXISTING OVERHEAD DOOR

COORDINATE OPENING LOCATION TO ALLOW BOILER TUBES TO BE PULLED FOR CLEANING

1ADD 1

SECTION 08 3613 - SECTIONAL DOORS

PART 1 GENERAL1.1 SECTION INCLUDES

A. OVERHEAD SECTIONAL DOORS, MANUALLY OPERATED.1.2 SUBMITTALS

A. SHOP DRAWINGS: INDICATE OPENING DIMENSIONS AND REQUIRED TOLERANCES, CONNECTION DETAILS, ANCHORAGE SPACING, HARDWARE LOCATIONS, AND INSTALLATION DETAILS.B. MANUFACTURER'S CERTIFICATE: CERTIFY PRODUCT MEETS OR EXCEEDS SPECIFIED REQUIREMENTS. C. MANUFACTURER'S INSTALLATION INSTRUCTIONS: INCLUDE ANY SPECIAL PROCEDURES REQUIRED BY PROJECT CONDITIONS.D. WARRANTY: SUBMIT MANUFACTURER WARRANTY AND ENSURE FORMS HAVE BEEN COMPLETED IN OWNER'S NAME AND REGISTERED WITH MANUFACTURER.

PART 2 PRODUCTS2.1 MANUFACTURERS

A. OVERHEAD DOOR CORPORATIONB. CLOPAY DOOR CORPORATIONC. C.H.I. OVERHEAD DOORSD. OR ARCHITECT APPROVED EQUIVALENT

2.2 STEEL DOOR COMPONENTSA. BASIS OF DESIGN: INSULATED STEEL SECTIONAL OVERHEAD DOORS: 591 SERIES THERMACORE INSULATED STEEL DOORS BY OVERHEAD DOOR CORPORATION. UNITS SHALL HAVE THE FOLLOWING CHARACTERISTICS:

1. DOOR ASSEMBLY: METAL/FOAM/METAL SANDWICH PANEL CONSTRUCTION, WITH PVC THERMAL BREAK AND FLUSH DESIGN.A. PANEL THICKNESS: 1-5/8 INCHES (41 MM).B. EXTERIOR SURFACE: RIBBED, TEXTURED.C. EXTERIOR STEEL: .015 INCH (.38 MM), HOT-DIPPED GALVANIZED.D. END STILES: 16 GAUGE.E. SPRINGS:

1) 25,000 CYCLES.2) SHAFT TYPE: SOLID

F. INSULATION: CFC-FREE AND HCFC-FREE POLYURETHANE, FULLY ENCAPSULATED.G. THERMAL VALUES: R-VALUE OF 14.86; U-VALUE OF 0.067.H. AIR INFILTRATION: 0.08 CFM AT 15 MPH; 0.08 CFM AT 25 MPH.

1) PANEL THICKNESS: 1-3/4 INCHES (44 MM).2) EXTERIOR SURFACE: FLUSH, TEXTURED.3) THERMAL VALUES: R-VALUE OF 14.8;

2. FINISH AND COLOR: TWO COAT BAKED-ON POLYESTER:A. INTERIOR COLOR, WHITE. B. EXTERIOR COLOR, TO BE DETERMINED BY ARCHITECT FROM MANUFACTURER’S FULL RANGE OF STANDARD COLORS.

3. HARDWARE: GALVANIZED STEEL HINGES AND FIXTURES. BALL BEARING ROLLERS WITH HARDENED STEEL RACES.4. WEATHERSTRIPPING:

A. EPDM BULB-TYPE STRIP AT BOTTOM SECTION.B. FLEXIBLE JAMB SEALS.C. FLEXIBLE HEADER SEAL.

5. TRACK: PROVIDE HIGH HEADROOM TRACK AS RECOMMENDED BY MANUFACTURER TO SUIT LOADING REQUIRED AND CLEARANCES AVAILABLE. VERIFY MECHANICAL SYSTEM LOCATIONS WHEN RECOMMENDING.

2.3 MATERIALSA. SHEET STEEL: HOT-DIPPED GALVANIZED STEEL SHEET, ASTM A 653/A 653M, WITH G60/Z180 COATING, PLAIN SURFACE.B. INSULATION: FIBROUS GLASS BATT, UNFACED, BONDED TO FACING.

PART 3 EXECUTION3.1 EXAMINATION

A. VERIFY THAT WALL OPENINGS ARE READY TO RECEIVE WORK AND OPENING DIMENSIONS AND TOLERANCES ARE WITHIN SPECIFIED LIMITS.3.2 PREPARATION

A. PREPARE OPENING TO PERMIT CORRECT INSTALLATION OF DOOR UNIT TO PERIMETER AIR AND VAPOR BARRIER SEAL.3.3 INSTALLATION

A. INSTALL DOOR UNIT ASSEMBLY IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.B. ANCHOR ASSEMBLY TO WALL CONSTRUCTION AND BUILDING FRAMING WITHOUT DISTORTION OR STRESS.C. SECURELY BRACE DOOR TRACKS SUSPENDED FROM STRUCTURE. SECURE TRACKS TO STRUCTURAL MEMBERS ONLY.D. FIT AND ALIGN DOOR ASSEMBLY INCLUDING HARDWARE.E. COORDINATE INSTALLATION OF SEALANTS AND BACKING MATERIALS AT FRAME PERIMETER AS SPECIFIED IN SECTION 07 9005.F. INSTALL PERIMETER TRIM.

3.4 TOLERANCESA. MAXIMUM VARIATION FROM PLUMB: 1/16 INCH.B. MAXIMUM VARIATION FROM LEVEL: 1/16 INCH.C. LONGITUDINAL OR DIAGONAL WARP: PLUS OR MINUS 1/8 INCH FROM 10 FT STRAIGHT EDGE.D. MAINTAIN DIMENSIONAL TOLERANCES AND ALIGNMENT WITH ADJACENT WORK.

3.5 ADJUSTINGA. ADJUST DOOR ASSEMBLY FOR SMOOTH OPERATION AND FULL CONTACT WITH WEATHERSTRIPPING.B. HAVE MANUFACTURER'S FIELD REPRESENTATIVE PRESENT TO CONFIRM PROPER OPERATION AND IDENTIFY ADJUSTMENTS TO DOOR ASSEMBLY FOR SPECIFIED OPERATION.

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 1

0:4

5:0

7 A

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-A

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

A10

FLO

OR

PL

AN

BID

1208200

MS

R/A

MC

MS

R

03/1

7/2

021

0

NORTH

1/8" = 1'-0"2FIRST FLOOR PLAN

12'

0

NORTH

1/8" = 1'-0"1FIRST FLOOR DEMOLITION PLAN

12'

AD

D 1

10

3/2

9/2

1A

DD

EN

DU

M #

1

Page 4: ADDENDUM #1 - Iowa

H

T

EJB

F

T

AVA

BS

DA

FM

P

F

P

*HB

WH

FD

FS

RD

OR

CO

CO

TAD

AP

*

NEW OPENING

CAP EXISTING

NEW CONNECTION

THERMOSTAT

HUMIDISTAT

SENSOR

FLEXIBLE DUCT

DOOR UNDERCUT

DOOR GRILLE

LINEAR DIFFUSER

ACCESS PANEL

ACCESS DOOR

FLOOR GRILLE

SAFETY RELIEF VALVE

QUICK OPENING VALVE

PRESSURE REG. VALVE

POST INDICATOR VALVE

PLUG VALVE

NEEDLE VALVE

OS&Y VALVE

GLOBE VALVE

GENERIC VALVE

GATE VALVE

CHECK VALVE

BUTTERFLY FLY VALVE

BALL VALVE

ANGLE GLOBE VALVE

ANGLE GATE VALVE

3-WAY CONTROL VALVE

BALANCING VALVE

WALL HYDRANT

HOSE BIBB

WALL OUTLET

OPEN RECEIVER

ROOF DRAIN

FLOOR SINK

FLOOR DRAIN

END RUN CLEANOUT

FLOOR CLEANOUT

PIPE CAP

TEE TURNED UP

TEE TURNED DOWN

ELBOW UP

ELBOW DOWN

PIPE TRAP

UNION

STRAINER W/ DRAIN

STRAINER

FLEXIBLE CONNECTION

EXPANSION JOINT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

AIR VENT

ALIGNMENT GUIDES

DIRECTION OF PITCH

DIRECTION OF FLOW

PIPE ANCHOR BLIND FLANGE

WATER HAMMER

VENTURI FLOW METER

FLOW METER

DRIP ASSEMBLY

BALANCE STATION

AUTO VALVE ASSEMBLY

GENERIC STEAM TRAP

THERMOSTATIC TRAP

FLOAT TRAP

BUCKET TRAP

PRESSURE SWITCH

FIRE ALARM SWITHCH

FLOW SWITCH

PRESSURE SENSOR

THERMOMETER

PRESSURE GUAGE

PLAN MARK DESCRIPTION

LEGEND

TEMPERATURE SENSOR

LEGEND

DESCRIPTIONPLAN MARK DESCRIPTION

LEGEND

PLAN MARK PLAN MARK

LEGEND

DESCRIPTIONDESCRIPTIONPLAN MARKDESCRIPTIONPLAN MARKPLAN MARK DESCRIPTION

DEMOLITION SCHEMATIC STEAM SYSTEMNO SCALE1

DEVICES FITTINGS VALVES HVAC

CWBOILER #1250 HP

ASMEBOILERVALVE

DRIPPANELBOW

BOILERTESTVALVE

BLOW DOWNSEPARATOR(TYP. OF 3)

2-1/2" VENT

VENT

4"

FMTG

DEMO COOLINGWATER AS REQUIREDFOR BOILERINSTALLATION

DEMOLISH BOILER 1VENTS THRU ROOF INTHEIR ENTIRETY

REMOVE VALVE AND HPSPIPING FOR INSTALLATIONOF NEW FLOW METER

CWBOILER #2150 HP

ASMEBOILERVALVE

CWBOILER #3150 HP

ASMEBOILERVALVE

DEAERATOR/FEED WATER

PRV

DUPLEX CONDENSATEPUMP IN TUNNEL

WAREHOUSE/BOILERBUILDINGHEATINGSYSTEM

6" 5 PSI CONDENSATE IN TUNNEL

8" 100 PSI STEAM INTUNNEL

100 PSITO 15 PSI

PRV STATION

SAFETY RELIEFUP THRU ROOF

2-1/2" VENT

VENT

2-1/2" VENT

VENT

15 PSI LPS

3"

4" 4"

TO BOILER

TO BOILER

PG

PG

FM FMTG TG

8" TEMP. BOILER CONNECTION

HPSFM

FM

TOTEMPBOILERSVTR

SOFTWATERINLET

OVERFLOWTANK

OVERFLOW

NOTES:

1. DEMOLISH PIPING AS REQUIRED FOR INSTALLATION OF NEW BOILER. PIPING

SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO, STEAM, FEEDWATER, NATURAL GAS, AND

FUEL OIL.

2. DEMOLISH ALL BLOWDOWN PIPING AND ACCESSORIES IN THEIR ENTIRETY.

3. ANY SYSTEM OUTAGE MUST BE COORDINATED WITH OWNER. MINIMUM 10 DAYS

NOTICE OF ALL PROPOSED SYSTEM OUTAGES

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 9

:19:1

6 A

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-M

EP

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

MD01

DE

MO

LIT

ION

SC

HE

MA

TIC

-S

TE

AM

SY

ST

EM

BID

1208200

JJS

TA

B

03/1

7/2

021

AD

D1

10

3/2

9/2

1A

DD

EN

DU

M #

1

1ADD1

Page 5: ADDENDUM #1 - Iowa

61-130

BOILERROOM

61-128

BOILEROFFICE

61-133

LOW VOLTAGESWITCHGEAR

61-128A

BOILERTOILET RM

6 7 8

61-127

PUMP ROOM

6 7 8

A

B

A.9

2

M11

3"

NG

EXISTING FUELOIL DAY TANK

EXISTING BOILER #2 EXISTING BOILER #3

3" NG 3" NG

8" HPS

3/4" FOR

1" FOS3/4" FOR

1" FOS3/4" FOR

1" FOS

NEW OVERHEAD DOORREQUIRED FOR INSTALLATIONAND MAINTENANCE

TU

BE

PU

LL

COLUMN

1-1/4" & 3/4" GAS VENTSUP THRU ROOF

20ø

3

M11

EXISTING COMBUSTION AIR DUCTWORK FOR BOILERS #2 AND #3

COMBUSTION AIR DUCTWORK FOR BOILER #1. INSTALL LOUVER LD-01 AT WALL

2 1/2" BFW

PRV STATION

◄2 1/2" HPS

EXISTING DEAERATOR

3" NG

20ø EA UP

BLR

-1

1" FOS3/4" FOR

42x30

1 1/2" FOS

1 1/2" FOR

PIPING CL @11'-8"

HANG FAN FROM EXST ROOF PURLINS (MINIMUM 2 PURLINS). PROVIDE WEB STIFFENER IN PURLINS AT HANGER LOCATIONS

4" FPW 1 1/2" CW

1 1/2" SCW

1" CA

PIPE SAFETY VALVE THRU ROOF

BURNER

FM-01

SF-01

ABOVE

1" CA

1" CA

2 1/2" HPS

RELOCATE CONDUIT

INSTALL LADDER FOR ACCESS TO BOILER PLATFORM. PLATFORM TO BE PROVIDED BY BOILER MANUFACTURER

2M21

3M21

NEW BOILER EQUIPMENT PAD. HEIGHT TO MATCH EXISTING PADSEE 8/M51

BOILER EQUIPMENT PAD TO REMAIN

4" LPS

6" HPS

MOTORIZED DAMPER MD-01 AND FAN SF-01 MOTOR STARTER INTERLOCKED TO BOILER #1. EXTEND 24V CIRCUIT TO MD-01

AIRFLOW

ADJUSTABLE LOUVERED SUPPLY GRILLE SG-01

SYSTEM OUTAGES TO BE COORDINATED WITH OWNER. FACILITY REQUIRES OUTAGES TO OCCUR BETWEEN THE HOURS OF 8 PM AND 4 AM TO AVOID DISRUPTION OF NORMAL OPERATIONS.

1ADD1

5'-0

"

8'-10"

1ADD1

AB A.9

100' - 0"Level 1

112' - 6"B.O. SOFFIT

3

M11

OVERHEAD DOOR

FUEL PIPING

ECONOMIZER(DEDUCT ALT 1

RELOCATE FOR INSTALLATION OF BOILER:(1) CONDUIT(1) COMPRESSED AIR(1) SOFT WATER

1 1/2" SCW

1 1/2" CW

4" FPW

2 1/2" BFW

6" HPS

3" NG

EXST COLUMN

20" EXHAUST

STEAM SAFETY RELIEF DISCHARGE

NATURAL GAS VENTS

BLR-1

FLASHING ON NEW PIPE PENETRATIONS THRU ROOF TO BE INSTALLED SIMILAR TO DETAIL 6/M51

6

100' - 0"Level 1

112' - 6"B.O. SOFFIT

2

M11

8" HPS

3'-8"

6" HPS

1 1/4" NG3/4" NG

2 1/2" BFW

20ø

BLR-1

3/4" FOR

1" FOS

FUEL OIL PIPING

EXST COLUMN

STEAM RELIEF VALVE DISCHARGE

20" BOILER EXHAUST

4" FPW

BLR-2

BLR-2 BLOWDOWNSEPARATOR VENT

GAS VENTS

BLR-3

2" NG

3/4" NG

1 1/4" NG

2" NG

3/4" NG

1 1/4" NG

4" HPS

12ø

3/4" NG

1 1/4" NG2 1/2" HPS3/4" NG

1 1/4" NG

4" HPS

FM-01

8" HPS

8" HPS

4" LPS

3" NG

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 9

:19:1

5 A

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-M

EP

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

M11

ME

CH

AN

ICA

LP

LA

N -

BO

ILE

RR

OO

MB

ID

1208200

JJS

BA

L

03/1

7/2

021

0

NORTH

1/4" = 1'-0"1MECHANICAL PLAN - BOILER ROOM

6'

01/4" = 1'-0"2MECHANICAL SECTION - LOOKING EAST

6' 01/4" = 1'-0"3MECHANICAL SECTION - LOOKING NORTH

6'

AD

D1

10

3/2

9/2

1A

DD

EN

DU

M #

1

Page 6: ADDENDUM #1 - Iowa

TO COND RECEIVER

STEAM TRAP

GATE VALVE

UNION

H/LPS

END OF MAIN, RISE ON MAIN OR EQUIP.

CONNECTION

SAME AS LINE SIZE

TRAP TEE

DIRT LEG

STRAINER W/BLOW DOWN VALVE

CHECK VALVE

STEEL PIPE

18 GA SHEET METAL COUNTERFLASHINGCLAM WATERTIGHT AROUND PIPE WITHDRAWBAND AND CAULKING

PACK WITH HIGH TEMP CAULKING COMPOUND

SLEEVE 2" DIA LARGER THANVENT PIPE EXTENDING 8" ABOVEROOF LINE

PROVIDE FLASHING ANDMOP INTO ROOF

BUILT UP ROOFING

WELD 12 GE FLASHING COLLARTO PIPE SLEEVE AND ANCHORTO EXST ROOF OPENING STEEL

EXISTING METAL ROOF DECK

DISCHARGE THROUGH ROOF

DISCHARGE HEADER

SUPPORT VENT RISERFREE AND INDEPENDENTOF DRIP PAN

SEE "DRIP PAN ELBOWFOR STEAM VENTS" DETAILTHIS SHEET

3/4" IPS TOFLOOR DRAINNIPPLE SHORT

AS POSSIBLE

SAFETYVALVE

8"

5'-0"

6" MIN

ROD

INSULATED PIPE

PROTECTION SADDLE (SIZE AS REQUIRED BY INSULATION)

ADJUSTABLE STEEL YOKE ROLLER TYPE PIPE HANGER

ROD

HANGER

INSULATION

SHEET METAL SHIELD

6" LONG COMPOSITE BLOCKS SHAPED TO FIT PIPE AND HANGER OR STEEL PIPE SADDLE

6" LONG HARDWOODBLOCKS SHAPED TOFIT PIPE AND HANGER

PIPE

PIPE PIPE

ROD

HANGER

TYPE-B6" OR SMALLER

TYPE-A8" OR LARGER

SHIELD SCHEDULE

TYPICAL ELEVATION

2" AND SMALLER: 16 GAGE

2 1/2" TO 6": 14 GAGE

8" AND LARGER: 12 GAGE

LENGTH OF SHIELD TO BE AT LEAST 6" LONGER THAN THE OUTSIDE DIAMETER OF THE INSULATION

1. SIZE STRUT AND CLAMP TO ADEQUATELY SUPPORT LOAD

2. STRUT SHALL BE EPOXY PAINTED

SHIELD SCHEDULE

2" AND SMALLER: 16 GAGE

2 1/2" TO 6": 14 GAGE

8" AND LARGER: 12 GAGE

LENGTH OF SHIELD TO BE AT LEAST 6" LONGER THAN THE OUTSIDE DIAMETER OF THE INSULATION

NOTES:

ADJUSTABLE HANGER ROD

STRUT MOUNTED PIPE GUIDE

INSULATION

PIPE

SHEET METAL SHIELD

6" LONG HARDWOOD BLOCKS SHAPED TO FIT PIPE & SHIELD OR STEEL PIPE SADDLE

NUT & FLAT WASHER (TYP)

STRUT

STAINLESS STEEL RAIN CAPENGINEER PRE-APPROVED EQUAL TO METALBESTOS "P-SK"

20" BOILER STACKUL ENGINEER PRE-APPROVED EQUALTO METALBESTOS "PS"

STORM COLLAR

FLASHING

ROOF OPENING, STRUCTURAL FRAMING,FLASHING, ETC. COORDINATE LOCATION AND SIZE OF ROOF OPENING TO ASSURE PROPER ROOF OPENING IS PROVIDED.

ROOF BASE SUPPORTTEE THIMBLE

7'-0"

MIN

IMU

M

~L

VENT TO ATMOSPHERE

BLOWDOWNSEPARATOR

METAL STAND

FLANGED CONNECTION

THERMOMETER

TEMPERATUREREGULATORVALVE BULB

COLD WATER MAKE-UP

BYPASS

LOW PRESSURECONDENSATE INLET

STRAINER WITHVALVE AND CAP

GATE VALVE(TYPICAL)

SOLENOID VALVE

NOTE:SEE PLANS FOR SIZE ANDCONTINUATION OF PIPING

FINISHED FLOOR

AFTERCOOLERASSEMBLY

TO DRAIN

BOILER SCHEDULE

BLOWER MOTOR AIR COMPRESSOR OIL PUMP TURNDOWN BASIS OF DESIGN

MANUFACTURER MODELOILGASFLA AMPSPHASEVOLTSHPFLA AMPSPHASEVOLTSRPMHPFLA AMPSPHASEVOLTSHPOPERATING

STEAM PRESSURE

FUEL OIL PRESSURE

GROSS OUTPUT MBTU/HR

INPUT MBTU/HR

(NG)

NATURAL GAS

PRESSURE

FUELNOMINAL BHP

TAG NO.

BLR-1 300 NATURAL GAS AND FUEL OIL NO. 2 5 PSIG 12,553 10,167 2 PSIG 100 PSIG 5 460 3 7.2 3 1750 460 3 5.5 1/2 460 460 460 10:1 8:1 BURNHAM 3P-300

NOTES: 1. BOILER SHALL BE CAPABLE OF BURNING DUAL FUEL. PRIMARY FUEL IS NATURAL GAS.2. BOILER SHALL BE PROVIDED WITH A UL/FM APPROVED GAS TRAIN.3. NATURAL GAS PRESSURE SCHEDULED IS THE PRESSURE UPSTREAM OF THE PRESSURE REGULATOR4. BOILER SHALL BE PROVIDED WITH A CONTROL VOLTAGE TRANSFORMER FOR ANY ASSOCIATED BOILER EQUIPMENT OR

ACCESSORIES REQUIRING LOWER VOLTAGE5. FUEL OIL PRESSURE SCHEDULED IS THE PRESSURE SUPPLIED TO THE SUCTION SIDE OF THE PUMP PROVIDED BY THE BOILER

MANUFACTURER.

6. BOILER SHALL BE PROVIDED WITH ACCESS PLATFORM AND LADDER, PROVIDED BY BOILER MANUFACTURER.7. MAXIMUM BOILER DIMENSIONS AS FOLLOWS: LENGTH = 20'-0" WIDTH = 8'-0" HEIGHT = 8'-6"8. SERVICE CLEARANCES REQUIRED: 18" ON EACH SIDE. 48" BEHIND. FRONT CLEARANCES SHOULD ACCOUNT FOR TUBE PULLS. ASSUME

OVERHEAD DOOR WILL OPEN FOR TUBE PULLS.9. PROVIDE ECONOMIZER TO OPTIMIZE EFFICIENCY OF THE OVERALL SYSTEM. MINIMUM HEAT RECOVERY = 330,000 BTUH. (DEDUCT ALTERNATE #1)10. MANUFACTURER: BURNHAM, HURST, SUPERIOR, JOHNSTON, CLEAVER-BROOKS, OR ENGINEER PRE-APPROVED EQUIVALENT.

FAN SCHEDULE

BASIS OF DESIGN

MANUFACTURER MODELDRIVE TYPE

MOTORDATA

STATIC PRESSUREAIR FLOW

TEMPERATURE RATING

MEDIATAG NO.

SF-01 COMBUSTION AIR -20 TO 120 F 3,925 CFM 1.25 IN WC 2 HP / 480 V / 3 PH DIRECT LOREN COOK 165SQ17D

NOTES: 1. FAN TO SUPPLIED WITH MOTOR STARTER. FAN STATUS MUST BE INTERLOCKED TO BOILER 1 RUN STATUS. BOILER 1 WILL NOT BE ALLOWED TO OPERATE UNLESS STATUS OF THE FAN CAN BE PROVEN AS 'ON' AND POSITION OF LD-01 DAMPER IS 'OPEN'.

2. INSTALL FAN PER MANUFACTURER'S RECOMMENDATIONS.3. PROVIDE REDUCERS, FLANGES, AND FITTINGS AS REQUIRED TO MAKE FAN CONNECTIONS TO INLET AND OUTLET DUCTWORK.

STEAM FLOW METER SCHEDULE

BASIS OF DESIGN

MANUFACTURER MODELUPSTREAM

PIPE DIAMETERS

PIPING CONNECTIONS

MINIMUM FLOW

MAXIMUM FLOW

TEMPERATURE RATING

MEDIATAG NO.

FM-01100 PSIG

SATURATED STEAM450 F 24,000 LB/HR 2,400 LB/HR

CLASS 150 FLANGE

1 McCROMETER V-CONE

NOTES: 1. SEND DIGITAL SIGNAL BACK TO EXISTING BAS FOR STEAM FLOW. 2. INSTALL FLOW METER PER MANUFACTURER'S RECOMMENDATIONS.3. PROVIDE REDUCERS, FLANGES, AND FITTINGS AS REQUIRED TO MAKE FLOW METER CONNECTION TO PIPING SYSTEM.

DOWNSTREAM PIPE

DIAMETERS

2

MOTORIZED DAMPER SCHEDULE

BASIS OF DESIGN

MANUFACTURER MODELDEPTH

WIDTHHEIGHTPRESSURE DROP

CFMEQUIPMENT SERVED

TAG NO.

MD-01 BOILER 1 3,925 0.20 IN WG 30" 42" 5" GREENHECK VCD-23

NOTES: 1. DAMPER POSITION MUST BE INTERLOCKED TO BOILER 1 RUN STATUS. BOILER 1 WILL NOT BE ALLOWED TO OPERATE UNLESS STATUS OF THE FAN CAN BE PROVEN AS 'ON' AND POSITION OF MD-01 DAMPER IS 'OPEN'.

2. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.3. GREENHECK OR ENGINEER PRE-APPROVED EQUIVALENT. 4. EXTEND 24 V CIRCUIT FROM THE EXISTING MOTORIZED DAMPER SHOWN ON MD11. 5. RE-ESTABLISH CONTROL POINT FROM NEW DAMPER TO BOILER CONTROL SYSTEM VIA MODBUS.

POWER FAILURE POSITION

LAST

VOLTAGE

24 V

ADJUSTABLE LOUVERED SUPPLY GRILLE SCHEDULE

BASIS OF DESIGN

MANUFACTURER MODELDELFECTION DIRECTION

FREE AREA REQUIRED

PRESSURE DROP @ 0o BLADE ANGLE

CFMEQUIPMENT SERVED

TAG NO.

SG-01 BOILER 1 3,925 0.1 IN WG 6.25 FT2 VERTICAL PRICE INDUSTRIES 150

NOTES: 1. LOUVERS MUST BE ADJUSTABLE FOR USE BY IMCC STAFF. INSTALL AT 0o BLADE ANGLE UNLESS DIRECTED OTHERWISE BY IMCC STAFF.2. BLADES MUST LOCK IN TO PLACE TO AVOID UNWANTED CHANGES IN BLADE DIRECTION. 3. MANUFACTURERS: PRICE INDUSTRIES OR ENGINEER PRE-APPROVED EQUIVALENT.

4"

± F

V

+6" EACH SIDE UNO

PAD SIZE TO BE EQUIPMENT SIZE

REINFORCE WITH #4 @ 12" OC EACH WAY

3/4" CHAMFER ALL EXPOSED TOP EDGES

EX. CONCRETE FLOOR

ROUGHEN EXISTING CONCRETE TO 1/4" AMPLITUDE AND APPLY CONCRETE BONDING AGENT BEFORE POURING NEW EQUIPMENT PAD

SEE 1/M11 FOR LOCATION.

NOTES:1. CONCRETE COMPRESSIVE STRENGTH (28 DAY)(f'c): 4000 PSI (W/C = .45). 2. REINFORCEMENT PROTECTION: 1 1/2" UNLESS NOTED OTHERWISE. 3. REINFORCING STEEL SHALL BE SECURELY FASTENED IN FORMS PRIOR TO POURING CONCRETE. WET

SETTING OF REINFORCING STEEL WILL NOT BE ACCEPTED PER ACI. 4. WHERE NEW CONCRETE IS TO BE CAST AGAINST EXISTING CONCRETE, PREPARE SURFACE OF EXISTING BY

REMOVING ALL SPALLS, CORROSION AND LOOSE CONCRETE.

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 9

:19:1

5 A

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-M

EP

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

M51

ME

CH

AN

ICA

LD

ET

AIL

SB

ID

1208200

JJS

TA

B

03/1

7/2

021

NOT TO SCALE1STEAM DRIP LEG AND STEAM TRAP DETAIL

NOT TO SCALE6SAFETY VALVE DISCHARGE PIPING DETAIL

NOT TO SCALE2ROLLER HANGER DETAIL

NOT TO SCALE5INSULATED PIPE HANGER DETAIL

NOT TO SCALE3TRAPEZE TYPE HANGER DETAIL

NOT TO SCALE4BOILER STACK ROOF PENETRATION DETAIL

NOT TO SCALE7BLOWDOWN SEPARATOR DETAIL

AD

D1

10

3/2

9/2

1A

DD

EN

DU

M #

1

4. WATER PENETRATION NO GREATER THAN 0.012 OZ/SQ FT AT 1000 FPM FACE VELOCITY.

3. BAKED ENAMEL FINISH. COLOR APPROVED BY OWNER PRIOR TO PLACING ORDER.

2. 4" FRAME DEPTH. EXTRUDED 6063 ALUMINUM FRAME AND BLADES. WELDED CONSTRUCTION.

1. RUSKIN, GREENHECK, OR ENGINEER PRE-APPROVED EQUIVALENT

REMARKS:

LOUVER SCHEDULE

MARK AREA SERVEDAIR FLOW

(CFM)

DIMENSIONSMAX FREEAREA (%)

FREE AREAVELOCITY

(FPM)PRESSUREDROP (WG) DESIGN BASIS REMARKSH W D

LD-01 SF-01 3925 30 42 0' - 4" 46 980 0.30 GREENHECKEDD-401

1, 2, 3,4

NOT TO SCALE8EQUIPMENT PAD DETAIL

1ADD1

Page 7: ADDENDUM #1 - Iowa

HT AFF SYMBOL DESCRIPTION

SURFACE LIGHT (TYPE DENOTED)X

X RECESSED LIGHT (TYPE DENOTED)

X

X

X

EM

E E

3

4

K

D

OS

MC

T

SP

M

UC

CLG

A

A

P

E

J J

T

25 KVA

1 SF-1

M

R

OS IR

LS A

PC

1

W

X

TV

SS

S S

S

V

IC

FS

TS

F

F 110cd

F

F 110cd

F

F 110cd

F

F S 110cd

FA ANNUN

FACP

FARP

P P

R/F135 R/F135

P

FP

DH

CH

FR

FB 1

ASD

DR

TV

WALL MOUNTED LIGHT (TYPE DENOTED)PER SCHED

WALL MOUNTED FLOOD LIGHT (TYPE DENOTED)PER SCHED

POLE MOUNTED LIGHT (TYPE DENOTED)PER SCHED

SURFACE LIGHT (TYPE DENOTED)

SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

FLUORESCENT STRIP LIGHT (TYPE DENOTED)

TRACK AND TRACK LIGHT (TYPE DENOTED)AS NOTED

EMERGENCY BATTER LIGHT (TYPE DENOTED)96"

EXIT SIGN (TYPE DENOTED)

LIGHT FIXTURE ON EMERGENCY CIRCUITAS NOTED

SINGLE POLE SWITCH

3-WAY SWITCH

48"

48"

4-WAY SWITCH48"

KEYED SWITCH48"

DIMMER SWITCH48"

OCCUPANCY SENSOR SWITCH48"

MOMENTARY CONTACT SWITCH48"

TIMER SWITCH48"

FAN SPEED CONTROL48"

MOTOR HORSEPOWER RATED SWITCH48"

PUSH BUTTON48"

DURESS PUSH BUTTON, UNDER COUNTER48"

DUPLEX RECEPTACLE18" UNO

FOURPLEX RECEPTACLE18" UNO

FLOOR BOX (TYPE DENOTED)

CEILING MOUNTED DUPLEX RECEPTACLE

HT AFF SYMBOL DESCRIPTION

SURFACE RACEWAY (TYPE DENOTED)18"

CLOCK (TYPE DENOTED)

POWER POLE (OPEN OFFICE STYLE)

ELECTRICAL CONNECTION (SEE SCHEDULE)

JUNCTION BOXAS NOTED

CIRCUIT BREAKER PANEL72"**

POWER OR DISTRIBUTION PANEL72"**

SPECIAL CABINET (TYPE DENOTED)72"**

TRANSFORMER (TYPE DENOTED)

GENERATOR (KVA DENOTED)

MOTOR (SEE SCHEDULE)

MOTORIZED DAMPER

SAFETY DISCONNECTION SWITCH72"**

ADJUSTABLE SPEED DRIVE

RELAY72"**

OCCUPANCY SENSOR (TYPE DENOTED)

LIGHT LEVEL SENSOR (TYPE DENOTED)

SM

PHOTOCELLAS NOTED

CCTV CAMERA (TYPE DENOTED)AS NOTED

SURVEILLANCE MONITOR

HT AFF SYMBOL DESCRIPTION HT AFF SYMBOL DESCRIPTION

CONDUIT CONCEALED IN WALL OR OVERHEAD

CONDUIT CONCEALED BELOW FLOOR

CONDUIT TRANSITION UP

CONDUIT TRANSITION DOWN

CONDUIT STUBBED OUT

BRANCH CIRCUIT HOME RUN

CABLE TRAY (TYPE DENOTED)

CONDUIT SLEEVE (SIZE DENOTED)

WALL TELEPHONE OUTLET (TYPE DENOTED)48"***

TELEPHONE OUTLET (TYPE DENOTED)18" UNO

DATA OUTLET (INDICATED QTY CABLES)18" UNO

VOICE/DATA OUTLET (TYPE DENOTED)18" UNO

WIRELESS ACCESS POINT

TELEVISION OUTLET18" UNO

CEILING MOUNTED TELEVISION OUTLET

SPEAKER (WALL OR CEILING MOUNT)84"

HORN TYPE SPEAKER84"

SURFACE MOUNT SPEAKER SUSPENDED FROM CEILING

VOLUME CONTROL48"

INTERCOM STATION48"

ICM INTERCOM MASTER

KEYED NOTE (SEE SCHEDULE)E#

SPRINKLER FLOW SWITCH

SPRINKLER VALVE TAMPER SWITCH

FIRE ALARM HORN80"***

FIRE ALARM HORN WITH STROBE (CANDELAS)80"***

FIRE ALARM BELL80"***

FIRE ALARM BELL WITH STROBE (CANDELAS)80"***

FIRE ALARM CHIME80"***

FIRE ALARM CHIME WITH STROBE (CANDELAS)80"***

FIRE ALARM STROBE CANDELAS80"***

FIRE ALARM SPEAKER WITH STROBE (CANDELAS)80"***

FIRE ALARM REMOTE ANNUNCIATOR 72"**

FIRE ALARM CONTROL PANEL72"**

FIRE ALARM RELAY PANEL72"**

SMOKE DETECTOR (TYPE DENOTED)8"****

HEAT DETECTOR (TYPE AND TEMP DENOTED)

DUCT SMOKE DETECTOR (TYPE DENOTED)

LINEAR HEAT DETECTOR

REMOTE TEST/STATUS STATION48"

PULLSTATION48"***

DOOR HOLDER

DOOR HOLDER/HOLD OPEN

SMOKE DAMPER RELEASE

FIRE ALARM SHUT DOWN RELAY

ELECTRICAL SYMBOL LEGEND

ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48".

* DISTANCE ABOVE DOOR FRAME ** DISTANCE TO TOP OF EQUIPMENT OR DEVICE *** DISTANCE TO HIGHEST OPERABLE POINT OF EQUIPMENT **** DISTANCE BELOW CEILING ***** DISTANCE TO BOTTOM OF DEVICE

GENERAL ELECTRICAL NOTES:

1. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE - LATEST EDITION ADOPTED BY THE STATE, ALONG WITH THE STATE AMENDMENTS.

2. IT IS THE INTENT OF THESE DOCUMENTS TO COMPLY WITH THE APPLICABLE CODES. WHERE DISCREPANCIES OCCUR, NOTIFY THE ENGINEER IN WRITING FOR INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS TO COMPLY WITH THE CODES AND STANDARDS AT NO ADDITIONAL COST TO THE OWNER.

3. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY INCLUDING ALL LABOR, MATERIALS, PERMITS, TAXES, FEES, INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR A COMPLETE AND OPERATIONAL SYSTEM.

4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW, COMPLETE WITH MANUFACTURER’S GUARANTEE OR WARRANTY AND SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).

5. COORDINATE ELECTRICAL INSTALLATION WITH ALL TRADES PRIOR TO INSTALLATION. IF ELECTRICAL WORK INSTALLED INTERFERES WITH OTHER TRADES AFTER INSTALLATION, THE CONTRACTOR SHALL MAKE ALL NECESSARY CHANGES TO CORRECT THE CONDITION AT NO ADDITIONAL COST TO THE OWNER.

6. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS WITH OTHER TRADES, ELEVATIONS AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL ADJUST CONNECTION LOCATIONS AS REQUIRED TO ACCOMMODATE CONFLICTS.

7. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED WITH TYPED, CLEAR DESIGNATION OF LOADS BEING FED. THE CONTRACTOR SHALL VERIFY THAT ALL UNUSED EQUIPMENT BAYS ARE TURNED ‘OFF’ AND PROPERLY INDICATED AS ‘SPARE’ON THE EQUIPMENT.

8. NO ENERGIZED CONDUCTORS SHALL BE EXPOSED AT ANYTIME EXCEPT WHEN THE IMMEDIATE AREA IS UNDER THE SUPERVISION OF A QUALIFIED ELECTRICIAN.

9. PENETRATIONS THROUGH FIRE RATED WALLS, BY DIVISION 26, CONTRACTOR SHALL BE SEALED WITH APPROPRIATE FIRE PROOFING MATERIAL TO RESTORE FIRE RATING.

10. THE CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF ALL DEBRIS ON A DAILY BASIS. ALL NEW MATERIALS AWAITING INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE OWNER.

11. THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. REFER TO DIMENSIONED VIEWS, ETC. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ADDITIONAL INFORMATION.

12. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST DEFECTS OR DEFICIENCIES IN THE WORK OF THE CONTRACTOR.

13. THE INFORMATION CONTAINED ON THE ELECTRICAL DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC., AND SHALL BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH ALL THEREIN BY REFERENCE, WHICH THE CONTRACTOR CERTIFIES KNOWLEDGE OF BY SIGNING THE CONTRACT.

14. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AND CORRELATED ON THE JOB SITE AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION, SHORING, SCAFFOLDING, BRACING, ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER IS OBTAINED.

PHDP-4

CTP-1

CTP-2

CWP-1

CWP-2

CWP-3

DX-1

DA-1

CP-1

CP-2

CT

-2A

CT

-2A

B-1

B-2

SPARE(B-3)

AC-1

AC-2

B-3E01

CDP-1

CT-1A

CT-1B

CT-2B

CT-3A

CT-3B

CT-4A

CT-4B

SF-3

COMP-1

SPARE

SPARE

DX-2

FA SPRCOMP

SPARE

SF-1 (AHU-1)

SF-4 (DH-1)

SPACE

E02

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 1

:32:5

6 P

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-M

EP

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

E00

ELE

CT

RIC

AL

GE

NE

RA

LIN

FO

RM

AT

ION

BID

1208200

MK

G

JC

H

03/1

7/2

021

Notes:

TOTAL EST. DEMAND... 0.0 A

TOTAL CONN. CURRENT: 0.0 A

TOTAL EST. DEMAND: 0.0 VA

SPEC 0 0.00% 0 TOTAL CONN. LOAD: 0.0 VA

Load ClassificationConnected Load

(VA)Demand Factor

EstimatedDemand (VA)

PANEL TOTALS

TOTAL AMPS: 0.0 A 0.0 A 0.0 A

TOTAL LOAD: 0.0 VA 0.0 VA 0.0 VA

SPARE -- 1 20 41 0.0 / 0.0 42 20 1 -- SPARE

SPARE -- 1 20 39 0.0 / 0.0 40 20 1 -- SPARE

SPARE -- 1 20 37 0.0 / 0.0 38 20 1 -- SPARE

SPARE -- 1 20 35 0.0 / 0.0 36 20 1 -- SPARE ROOF DAMPER

SPARE -- 1 20 33 0.0 / 0.0 34 20 1 -- SPARE ROOF DAMPER

EQUIP SF-2B (FAN) -- 1 15 31 0.0 / 0.0 32 20 1 -- EQUIP ELEV. SMOKE DAMPER

EQUIP SF-2A (FAN) -- 1 15 29 0.0 / 0.0 30 20 1 EQUIP DAY TANK

EQUIP HWCP-1 (PUMP) -- 1 15 27 0.0 / 0.0 28 20 1 EQUIP DAY TANK

EQUIP DH-2 (SF-5) -- 1 25 25 0.0 / 0.0 26 20 1 EQUIP DAY TANK

EQUIP FCU-1, 2, 3, 4, 5, 6 -- 1 20 23 0.0 / 0.0 24 20 1 -- EQUIP FCU-7, 8, 9, 10, 11, 12

SPARE -- 1 20 21 0.0 / 0.0 22 20 1 -- EQUIP HEAT TRACE

EQUIP EF-2 -- 1 50 19 0.0 / 0.0 20 20 1 -- SPARE

EQUIP EF-8, 9, 10 -- 1 20 17 0.0 / 0.0 18 40 1 -- EQUIP EF-12

EQUIP EF-1, 11, 13 -- 1 20 15 0.0 / 0.0 16 20 1 -- EQUIP EF-3, 4, 5, 6, 7

SPARE -- 1 20 13 0.0 / 0.0 14 20 1 -- SPARE

EQUIP UH-12 -- 1 15 11 0.0 / 0.0 12 15 1 -- EQUIP UH-17

EQUIP UH-13 -- 1 15 9 0.0 / 0.0 10 15 1 -- EQUIP UH-11

EQUIP UH-18 -- 1 15 7 0.0 / 0.0 8 15 1 -- EQUIP UH-14, 15, 16

EQUIP UH-8 -- 1 15 5 0.0 / 0.0 6 15 1 -- EQUIP UH-9, 10

EQUIP UH-3 -- 1 15 3 0.0 / 0.0 4 15 1 -- EQUIP UH-4, 5, 6, 7

EQUIP UH-1 -- 1 15 1 0.0 / 0.0 2 15 1 -- EQUIP UH-2

LO

AD

CO

DE

PO

LE

BK

R

CK

T # A

KVAB

KVAC

KVA

CK

T #

BK

R

PO

LE

CO

DE

LO

AD

FED... FEED:

ROOM: ENCLOSURE: NEMA 1

CODE: L=LIGHTING, R=RECEPTACLES, M=MOTORS, K=KITCHEN MOUNTING: SURFACE

PHM120/208 Wye 3 4 225 AMPS 225

10,000 AMPSSYMMETRICAL

BRANCH PANEL NAME VOLTAGE PHASE WIRE BUS SIZE MAIN OCP AIC RATING

NOTES:

EST. DEMAND... 0

CONN. CURRENT: 0

EST. DEMAND LOAD: 0

CONN. LOAD: 0

LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

30 100 3 100 0.0 kVA SPACE

29 100 1 15 0.0 kVA DEHUMIDIFIER DH-1 (SF-4)

28 100 1 15 0.0 kVA SF-1 (AHU-1)

27 100 3 100 0.0 kVA OIL PUMPSET (1HP)

26 100 3 100 0.0 kVA FA SPR COMP

25 100 1 15 0.0 kVA CONDENSER FAN, DX-2

24 400 3 20 0.0 kVA SPEC

23 400 3 20 0.0 kVA BOILER MAU, SF-01

22 100 1 25 0.0 kVA AIR COMPRESSOR PUMP, COMP-1

21 100 1 20 0.0 kVA SF-3 (MUAU-1)

20 100 3 20 0.0 kVA COOLING TOWER, CT-1B (SUMP HEATER)

19 100 3 20 0.0 kVA COOLING TOWER, CT-1A (FAN)

18 100 1 25 0.0 kVA CONDENSATE RET. PUMP, CDP-1

17 100 3 25 0.0 kVA BOILER, B-3 (10HP)

16 100 1 25 0.0 kVA AIR CURTAIN, AC-2

15 100 1 25 0.0 kVA AIR CURTAIN, AC-1

14 100 3 100 0.0 kVA SPARE

13 100 3 25 0.0 kVA BOILER, B-2

12 100 3 25 0.0 kVA BOILER, B-1

11 100 3 20 0.0 kVA COOLING TOWER, CT-2A (FAN)

10 100 3 20 0.0 kVA COOLING TOWER, CT-2A (FAN)

9 100 3 70 0.0 kVA CHILLER PUMP, CP-2

8 100 3 70 0.0 kVA CHILLER PUMP, CP-1

7 100 3 60 0.0 kVA BOILER FEEDWATER PUMP, DA-1

6 100 1 15 0.0 kVA CONDENSER FAN, DX-1

5 100 3 100 0.0 kVA CHILLED WATER PUMP, CWP-3

4 100 3 100 0.0 kVA CHILLED WATER PUMP, CWP-2

3 100 3 100 0.0 kVA CHILLED WATER PUMP, CWP-1

2 100 3 80 0.0 kVA COOLING TOWER PUMP, CTP-2

1 100 3 80 0.0 kVA COOLING TOWER PUMP, CTP-1

BUCKET FRAME POLES RATING LOAD DESCRIPTION/NAMEPLATE NOTES

SECTION No. 1

BUS AMPS: SPECIAL:

MAIN DEVICE: A.I.C....

LOCATION: VOLTAGE: 480/277 Wye V. 3 ø 4 W.

MCC: PHDP-4

NOT TO SCALE1MCC ELEVATION VIEW

KEYNOTES

KEY NOTE

E01 LABEL EXISTING MOTOR STARTER BUCKET AS 'SF-01'AND CIRCUIT MOTOR STARTER CONTACT TO B-1CONTROLS THROUGH A DEDICATED 3/4"C. WHEN INAUTO, FAN SHALL OPERATE UPON BOILER STARTSIGNAL. WHEN MANUAL, FAN SHALL OPERATE AT FULLSPEED.

E02 LABEL EXISTING SPARE BUCKET AS 'B-1 OIL PUMPSET'

AD

D1

10

3/2

9/2

1A

DD

EN

DU

M #

1

1ADD1

1ADD1

1ADD1

1ADD1

Page 8: ADDENDUM #1 - Iowa

fec

61-132

HIGH VOLTAGESWITCHGEAR

61-130

BOILERROOM

61-128

BOILEROFFICE

61-133

LOW VOLTAGESWITCHGEAR

61-128A

BOILERTOILET RM

61-127

PUMP ROOM

61-127-C

61-1

27-D

61-128-A 61-128-B

61-1

30-A

61-130-B

61-130-C

C61

-132

-A

61-1

32-B

61-1

33

61-1

43 61W-128

61-128A

feE

E

E

E

E

J

E

E EE

E

E

fec

61-132

HIGH VOLTAGESWITCHGEAR

61-130

BOILERROOM

61-128

BOILEROFFICE

61-133

LOW VOLTAGESWITCHGEAR

61-128A

BOILERTOILET RM

61-127

PUMP ROOM

61-127-C

61-1

27-D

61-128-A 61-128-B

61-1

30-A

61-130-B

61-130-C

C61

-132

-A

61-1

32-B

61-1

33

61-1

43 61W-128

61-128A

feE

E

E

E

E

E

J

EE

5 6 7 8

A

B

A.9

OVERHEAD DOOR

PANEL PHM

PANEL PHL

PANEL PHLSECTION 1

PANEL PHLSECTION 2

SWITCHBOARD

EXISTING BOILER #2 EXISTING BOILER #3

EXISTING TO REMAIN

EXISTING TO REMAIN

EXISTING TO REMAIN

PHM - 26

PHM - 28

PHM - 30

FOP-2

FOP-1

EXISTING TO REMAIN

DPS

DOOR CONTACT, SECURITY SENSOR FOR NEW OVERHEAD DOOR

COMBUSTION AIR DUCTWORK FOR BOILER #1

NEW BOILER, B-1

CONNECT NEW BOILER #1 TO EXISTING EPO SWITCH WIRING

MCC PHDP-4 BUCKET #12

EXTEND ACTIVATION CIRCUIT FOR DOOR MONITORING SENSOR FROM EXISTING OVERHEAD DOOR

DPS

(3) #10 WITH #10GND IN 3/4"C

OIL PUMPSET

MCC PHDP-4 BUCKET #27

(3) #12 WITH #12 GND IN 3/4"C

MOTOR CONTROL CENTER "MCC" PHDP-4

MCC PHDP-4 BUCKET #23

(3) #10 WITH #10 GND IN 3/4"C

PHL - 32

PHL - 34

RECONNECT RELOCATED LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT, REATTACH RIGID SUSPENSION TO PREVENT LIGHT FROM SWAYING. SUSPEND LIGHT INBETWEEN TRACK OF OVERHEAD DOOR AND INLET FAN.

RECONNECT RELOCATED EXTERIOR LIGHT FIXTURE TO EXISTING LIGHTING

RECONNECT RELOCATED EXIT SIGN TO EXISTING LIGHTING CIRCUIT

RECONNECT RELOCATED LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT, REATTACH RIGID SUSPENSION TO PREVENT LIGHT FROM SWAYING. SUSPEND LIGHT INBETWEEN OVERHEAD COLD WATER PIPING ALONG NORTH WALL

SF-01

1ADD1

5 6 7 8

A

B

A.9

EXISTING BOILER #1 EXISTING BOILER #2 EXISTING BOILER #3

BOILER EMERGENCY 'OFF' SWITCH

BOILER EMERGENCY 'OFF' SWITCH

BOILER EMERGENCY 'OFF' SWITCH

PANEL PHM

T45

150ADISCONNECT

MOTOR CONTROL CENTER "MCC" PHDP-4

PHDP-4 #12

DISCONNECT AND REMOVE BOILER #1, ASSOCIATED CIRCUIT, PHDP-4 MCC BUCKET #12, AND CONDUIT BACK TO THE NEAREST ACCESSIBLE LOCATION

EXISTING TO REMAIN

EXISTING TO REMAIN

EXISTING TO REMAIN

PANEL PHM

PANEL PHL

PANEL PHLSECTION 1

PANEL PHLSECTION 2

SWITCHBOARD

DISCONNECT BOILER #1 FROM EMERGENCY OFF SWITCH AT EPO SPLICE POINT

FOP-2

FOP-1

PHM - 30

PHM - 28

PHM - 26

EXISTING TO REMAIN

DPS

RELOCATE EXIT SIGN AND ASSOCIATED CONDUIT/CONDUCTORS FOR NEW MECHANICAL OPENING

PHL - 32

PHL - 34

DISCONNECT LIGHT FIXTURE IN TANDEM ROW OF LIGHTS TO ALLOW FOR INSTALLATION OF NEW FAN, SEE NEW WORK PLAN FOR RELOCATION

RELOCATE EXISTING LIGHT AND ASSOCIATED CONDUIT/CONDUCTORS. REFER TO NEW WORK PLAN FOR RELOCATION.

DISCONNECT LIGHT FIXTURE IN TANDEM ROW OF LIGHTS TO ALLOW FOR INSTALLTION OF BOILER, SEE NEW WORK PLAN FOR RELOCATION

DISCONNECT EXISTING CONDUIT AND 120V 20A CIRCUIT ON EXISTING PIRLINS BACK TO LAST ACTIVE JUNCTION BOX FOR INSTALLATION OF NEW DOOR.

1ADD1

6

5

4

3

BA D E

1

FC G

2

DR

AW

N:

AP

PR

OV

ED

:

ISS

UE

D F

OR

:

DA

TE

:

FIE

LD

BO

OK

:

PR

OJE

CT

#:

H

6

5

4

3

1

2

BA D E FC G H

Autodesk Revit 2021

2839 N

ort

hgate

Drive | Iow

a C

ity, IA

52245

319.3

54.3

040 | w

ww

.shiv

e-h

attery

.com

Iow

a | Illi

nois

| India

na | N

ebra

ska | W

isconsin

3/2

9/2

021 1

:33:2

6 P

M

BIM

360:/

/1208200 ID

AS

Boile

r #1

Repla

cem

ent/

1208200-M

EP

-Cent.rv

t

905

4.0

1 I

MC

C B

OIL

ER

#1

RE

PLA

CE

ME

NT

IOW

A M

ED

ICA

L C

LA

SS

IFIC

AT

ION

CE

NT

ER

2700 C

OR

AL R

IDG

E A

VE

, C

OR

ALV

ILLE

, IA

52241

E11

ELE

CT

RIC

AL

DE

MO

AN

D N

EW

WO

RK

PL

AN

SB

ID

1208200

MK

G

JC

H

03/1

7/2

021

0

NORTH

1/4" = 1'-0"2ELECTRICAL LIGHTING, POWER, AND SYSTEMS PLANS - NEW WORK

6'

0

NORTH

1/4" = 1'-0"1ELECTRICAL LIGHTING, POWER, AND SYSTEMS PLANS - DEMO

6'

AD

D1

10

3/2

9/2

1A

DD

EN

DU

M #

1