F6447.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E90
Rendered to:
MODERNUS
SERIES/MODEL: Lama Dual Glazed
TYPE: Double Glazed Wall System
Summary of Test Results
Data File No. Glazing (Nominal Dimensions) STC OITC RW
F6447.01C Wall System: 1/2" tempered exterior, 2" glass-to-glass air space, 3/8" tempered interior
43 34 43
Reference should be made to Intertek-ATI Report No. F6447.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Acoustical Performance Test Report
MODERNUS 234 5th Avenue, Suite #315 New York, New York 10001
Report No F6447.01-113-11 Test Date 06/17/16 Report Date 07/13/16 Project Scope Architectural Testing, Inc., a subsidiary of Intertek ("Intertek-ATI"), was contracted to conduct a sound transmission loss test. The complete test data is included as Appendix B of this report. The client provided the test specimen. Test Methods Testing for this project was conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements ASTM E413-10, Classification for Rating Sound Insulation ASTM E1332-10a, Standard Classification for Rating Outdoor-Indoor Sound Attenuation ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods
Test Procedure All measurements were conducted in the HT test chambers at Intertek-ATI located in York, Pennsylvania. The sensitivity of the microphones was checked before measurements were conducted. The transmission loss values were obtained for a single direction of measurement. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Two sound pressure levels were made simultaneously in the receive and source rooms at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all measurements.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
F6447.01-113-11-R0 Page 2 of 5
Specimen Installation A sound transmission loss test was initially performed on a filler wall. The specimen plug was removed from the filler wall assembly. The specimen was placed on an isolation pad in the test opening. Duct seal was used to seal the perimeter of the specimen to the test opening on both sides. The interior side of the specimen, when installed, was approximately 1/4" from being flush with the receive room side of the filler wall. A stethoscope was used to check for any abnormal air leaks around the test specimen prior to testing. Test Calculations Transmission loss (TL) at each 1/3 octave frequency is the average source room sound pressure level minus the average receive room sound pressure level, plus, 10 times the log of the specimen area divided by the sound absorption of the receive room with the sample in place. STC Rating To obtain the Sound Transmission Class (STC), read the TL of the contour curve at 500 Hz. The sum of the deficiencies below the contour curve must not exceed 32. The maximum deficiency at any one frequency must not exceed 8. OITC Rating The Outdoor-Indoor Transmission Class (OITC) is calculated by subtracting the logarithmic summation of the TL values from the logarithmic summation of the A-weighted transportation noise spectrum stated in ASTM E1332. Specimen Descriptions
Frame
Size 96" by 96"
Thickness 3-1/4"
Corners Butted
Fasteners Screws
Seal Method Sealant/Foam pads
Material Aluminum
Reinforcement N/A
Thermal Break Material N/A
N/A-Not Applicable
F6447.01-113-11-R0 Page 3 of 5
Specimen Descriptions (Continued)
Glazing
Exterior Sheet
Measured Thickness 0.491"
Muntin Pattern N/A
Material Tempered
Laminate Material N/A
Glazing Method Channel
Glazing Material Foam tape
Comments The glass-to-glass air space was 2".
Interior Sheet
Measured Thickness 0.368"
Muntin Pattern N/A
Material Tempered
Laminate Material N/A
Glazing Method Channel
Glazing Material Foam tape
Components
Type Quantity Location
Weatherstrip
7/16" Double-sided adhesive vinyl center gasket 1 Row Glass vertical center joint
Hardware
No hardware
Drainage
No drainage
* - Stated per Client/Manufacturer, N/A-Not Applicable
F6447.01-113-11-R0 Page 4 of 5
Specimen Descriptions (Continued)
Total Weight (lbs) Average Weight (lbs/ft2)
667 10.42
Comments The client did not supply a report drawing of the test specimen. The specimen was held for further testing per the client's request. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Amanda N. Smith Kurt A. Golden Technician - Acoustical Testing Project Lead – Acoustical Testing ANS:jmcs
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix A: Equipment description (1) Appendix B: Complete test results (2) Appendix C: Photographs (1)
F6447.01-113-11-R0 Page 5 of 5
Revision Log
Rev. # Date Page(s) Revision(s)
R0 07/13/16 N/A Original Report Issue
This report produced from controlled document template ATI 00272, revised 08/31/15.
Source Room 206.6 m3 (7296.3 ft3)Stationary diffusers only
Temperature and humidity controlled
Maximum Size Description
1251 Pistonphone Calibrator 65105 05/16
N/A-Not Applicable
TL Test Opening4.27 m (14 ft) wide by
Vibration break between source and receive rooms3.05 m (10 ft) high
Receive Room 234 m3 (8291.3 ft3)
Rotating vane and stationary diffusers Temperature and humidity controlledIsolation pads under the floor
Microphone and Preamplifier
*- Note: The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Test Chamber:
Volume Description
Microphone Calibrator Norsonic
Receive Room
Environmental Indicator64915 03/16
Source Room
Environmental IndicatorComet T7510 Source Room 64914 03/16
Comet T7510
Receive Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64910 12/15
Receive Room
378B20 Microphone and Preamplifier 64908 12/15
Receive Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64911 12/15
Microphone and Preamplifier 12/15
Receive Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64909 12/15
Receive Room
MicrophonePCB Piezotronics
12/15
Receive Room
MicrophonePBC Piezotronics 378B20 Microphone and Preamplifier 64907 12/15
Microphone and Preamplifier 65103
Source Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64906
64905Source Room
MicrophonePCB Piezotronics
Source Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64340 07/15
64903 12/15
378B20
12/15
Source Room
MicrophonePCB Piezotronics 378B20
Source Room
MicrophonePCB Electronics 378B20
Data Acquisition Unit National Instruments PXI-1033
Description ATI NumberDate of
Calibration
Data Acquisition card 65126 05/16 *
F6447.01 -113-11
Appendix A
Instrumentation:
Instrument Manufacturer Model
F6447.01-113-11-R0
Appendix B
Complete Test Results
STC Rating (Sound Transmission Class)
Deficiencies (Sum of Deficiencies)
OITC Rating (Outdoor-Indoor Transmission Class)
Rw Rating (Sound Reduction Index)
Technician
FreqBackground
AbsorptionSpecimen
TL
95%
Amanda N. Smith
SPL
Specimen Area 5.95 m² Receive Temp. 22.2 °C Source Temp.
Source Receive
Receive Humidity 52% Source Humidity
Number
(dB)
Series/Model: Lama Dual Glazed, double glazed wall system with 1/2" tempered exterior, 2"
glass to glass air space, 3/8" tempered interior
21.6 °C
Confidence of
52%
1.70 -
160 42.2
Limit Deficiencies
125 39.4 5.1 103
Data File No. F6447.01C
Client Modernus
Description
(Hz) (dB) (m²) (dB) (dB)
2.02 -
SPL SPL
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
Test Date 06/17/16
78 24.9
100 37.6 5.1 104 80 23.9
80 39.8 4.7 103 82 22.2
0.99 0
4.6 104 76 29.3
200 40.3 4.5 106 72 34.6
1.97 2
250 35.6 5.1 105 73 32.4
0.85 1
0.84 4
315 29.6 5.4 98 62 36.5 0.52 2
0.39 0
400 25.2 5.7 95 57 38.5 0.40 3
44.1
41.3
00.17
500 21.8 5.8 95 53 42.6
54 44.8 0.37
0.22 5
630 19.6 5.5 100 56
1000 13.3 6.1 95 54
0800 17.2 5.9 99
0.27 797 56
0.17 0
102 54 46.8 0.14 0
0.21 0
1600 8.9 7.0
63.6
92
1250 10.9 6.6 40.3
7.42000 7.4
93
283150 6.3 9.8
8.1
36
94
2500
53.6
43
7.9 15.5
94 38 55.0
31 59.8
23 0.17 -
43
24
34
91
Notes:
Page 1 of 2
1) Receive Room levels less than 5 dB above the Background levels are red.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
0.13
0.26 0
ATI 00760 Revised 05/23/16
5000
6.9 12.1
63.8
6.3
4000
0
Page 2 of 2
22.2 °C Source Temp.
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
06/17/16Test Date
ATI 00760 Revised 05/23/16
Description Series/Model: Lama Dual Glazed, double glazed wall system with 1/2" tempered exterior, 2"
glass to glass air space, 3/8" tempered interior
Specimen Area
Client Modernus
52%Technician Amanda N. Smith
Data File No.
Receive Humidity 52%
F6447.01C
Source Humidity
5.95 m² Receive Temp. 21.6 °C
0
10
20
30
40
50
60
70
80
90
100
31.5 63 125 250 500 1000 2000 4000 8000
Sou
nd
Tra
nsm
issi
on
Lo
ss (
dB
)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL Contour Curve
F6447.01-113-11-R0
Appendix C
Photographs
Receive Room View of Installed Specimen
Source Room View of Installed Specimen