F6447.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: MODERNUS SERIES/MODEL: Lama Dual Glazed TYPE: Double Glazed Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC RW F6447.01C Wall System: 1/2" tempered exterior, 2" glass-to-glass air space, 3/8" tempered interior 43 34 43 Reference should be made to Intertek-ATI Report No. F6447.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request. 130 Derry Court York, PA 17406 p. 717.764.7700 f. 717.764.4129 www.archtest.com www.intertek.com/building

Upload: ngokien

Post on 30-Aug-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E90

Rendered to:

MODERNUS

SERIES/MODEL: Lama Dual Glazed

TYPE: Double Glazed Wall System

Summary of Test Results

Data File No. Glazing (Nominal Dimensions) STC OITC RW

F6447.01C Wall System: 1/2" tempered exterior, 2" glass-to-glass air space, 3/8" tempered interior

43 34 43

Reference should be made to Intertek-ATI Report No. F6447.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 2: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

Acoustical Performance Test Report

MODERNUS 234 5th Avenue, Suite #315 New York, New York 10001

Report No F6447.01-113-11 Test Date 06/17/16 Report Date 07/13/16 Project Scope Architectural Testing, Inc., a subsidiary of Intertek ("Intertek-ATI"), was contracted to conduct a sound transmission loss test. The complete test data is included as Appendix B of this report. The client provided the test specimen. Test Methods Testing for this project was conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements ASTM E413-10, Classification for Rating Sound Insulation ASTM E1332-10a, Standard Classification for Rating Outdoor-Indoor Sound Attenuation ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods

Test Procedure All measurements were conducted in the HT test chambers at Intertek-ATI located in York, Pennsylvania. The sensitivity of the microphones was checked before measurements were conducted. The transmission loss values were obtained for a single direction of measurement. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Two sound pressure levels were made simultaneously in the receive and source rooms at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all measurements.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 3: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0 Page 2 of 5

Specimen Installation A sound transmission loss test was initially performed on a filler wall. The specimen plug was removed from the filler wall assembly. The specimen was placed on an isolation pad in the test opening. Duct seal was used to seal the perimeter of the specimen to the test opening on both sides. The interior side of the specimen, when installed, was approximately 1/4" from being flush with the receive room side of the filler wall. A stethoscope was used to check for any abnormal air leaks around the test specimen prior to testing. Test Calculations Transmission loss (TL) at each 1/3 octave frequency is the average source room sound pressure level minus the average receive room sound pressure level, plus, 10 times the log of the specimen area divided by the sound absorption of the receive room with the sample in place. STC Rating To obtain the Sound Transmission Class (STC), read the TL of the contour curve at 500 Hz. The sum of the deficiencies below the contour curve must not exceed 32. The maximum deficiency at any one frequency must not exceed 8. OITC Rating The Outdoor-Indoor Transmission Class (OITC) is calculated by subtracting the logarithmic summation of the TL values from the logarithmic summation of the A-weighted transportation noise spectrum stated in ASTM E1332. Specimen Descriptions

Frame

Size 96" by 96"

Thickness 3-1/4"

Corners Butted

Fasteners Screws

Seal Method Sealant/Foam pads

Material Aluminum

Reinforcement N/A

Thermal Break Material N/A

N/A-Not Applicable

Page 4: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0 Page 3 of 5

Specimen Descriptions (Continued)

Glazing

Exterior Sheet

Measured Thickness 0.491"

Muntin Pattern N/A

Material Tempered

Laminate Material N/A

Glazing Method Channel

Glazing Material Foam tape

Comments The glass-to-glass air space was 2".

Interior Sheet

Measured Thickness 0.368"

Muntin Pattern N/A

Material Tempered

Laminate Material N/A

Glazing Method Channel

Glazing Material Foam tape

Components

Type Quantity Location

Weatherstrip

7/16" Double-sided adhesive vinyl center gasket 1 Row Glass vertical center joint

Hardware

No hardware

Drainage

No drainage

* - Stated per Client/Manufacturer, N/A-Not Applicable

Page 5: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0 Page 4 of 5

Specimen Descriptions (Continued)

Total Weight (lbs) Average Weight (lbs/ft2)

667 10.42

Comments The client did not supply a report drawing of the test specimen. The specimen was held for further testing per the client's request. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Amanda N. Smith Kurt A. Golden Technician - Acoustical Testing Project Lead – Acoustical Testing ANS:jmcs

Attachments (pages): This report is complete only when all attachments listed are included.

Appendix A: Equipment description (1) Appendix B: Complete test results (2) Appendix C: Photographs (1)

Page 6: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0 Page 5 of 5

Revision Log

Rev. # Date Page(s) Revision(s)

R0 07/13/16 N/A Original Report Issue

This report produced from controlled document template ATI 00272, revised 08/31/15.

Page 7: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

Source Room 206.6 m3 (7296.3 ft3)Stationary diffusers only

Temperature and humidity controlled

Maximum Size Description

1251 Pistonphone Calibrator 65105 05/16

N/A-Not Applicable

TL Test Opening4.27 m (14 ft) wide by

Vibration break between source and receive rooms3.05 m (10 ft) high

Receive Room 234 m3 (8291.3 ft3)

Rotating vane and stationary diffusers Temperature and humidity controlledIsolation pads under the floor

Microphone and Preamplifier

*- Note: The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Test Chamber:

Volume Description

Microphone Calibrator Norsonic

Receive Room

Environmental Indicator64915 03/16

Source Room

Environmental IndicatorComet T7510 Source Room 64914 03/16

Comet T7510

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64910 12/15

Receive Room

378B20 Microphone and Preamplifier 64908 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64911 12/15

Microphone and Preamplifier 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64909 12/15

Receive Room

MicrophonePCB Piezotronics

12/15

Receive Room

MicrophonePBC Piezotronics 378B20 Microphone and Preamplifier 64907 12/15

Microphone and Preamplifier 65103

Source Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64906

64905Source Room

MicrophonePCB Piezotronics

Source Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64340 07/15

64903 12/15

378B20

12/15

Source Room

MicrophonePCB Piezotronics 378B20

Source Room

MicrophonePCB Electronics 378B20

Data Acquisition Unit National Instruments PXI-1033

Description ATI NumberDate of

Calibration

Data Acquisition card 65126 05/16 *

F6447.01 -113-11

Appendix A

Instrumentation:

Instrument Manufacturer Model

Page 8: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0

Appendix B

Complete Test Results

Page 9: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

OITC Rating (Outdoor-Indoor Transmission Class)

Rw Rating (Sound Reduction Index)

Technician

FreqBackground

AbsorptionSpecimen

TL

95%

Amanda N. Smith

SPL

Specimen Area 5.95 m² Receive Temp. 22.2 °C Source Temp.

Source Receive

Receive Humidity 52% Source Humidity

Number

(dB)

Series/Model: Lama Dual Glazed, double glazed wall system with 1/2" tempered exterior, 2"

glass to glass air space, 3/8" tempered interior

21.6 °C

Confidence of

52%

1.70 -

160 42.2

Limit Deficiencies

125 39.4 5.1 103

Data File No. F6447.01C

Client Modernus

Description

(Hz) (dB) (m²) (dB) (dB)

2.02 -

SPL SPL

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Test Date 06/17/16

78 24.9

100 37.6 5.1 104 80 23.9

80 39.8 4.7 103 82 22.2

0.99 0

4.6 104 76 29.3

200 40.3 4.5 106 72 34.6

1.97 2

250 35.6 5.1 105 73 32.4

0.85 1

0.84 4

315 29.6 5.4 98 62 36.5 0.52 2

0.39 0

400 25.2 5.7 95 57 38.5 0.40 3

44.1

41.3

00.17

500 21.8 5.8 95 53 42.6

54 44.8 0.37

0.22 5

630 19.6 5.5 100 56

1000 13.3 6.1 95 54

0800 17.2 5.9 99

0.27 797 56

0.17 0

102 54 46.8 0.14 0

0.21 0

1600 8.9 7.0

63.6

92

1250 10.9 6.6 40.3

7.42000 7.4

93

283150 6.3 9.8

8.1

36

94

2500

53.6

43

7.9 15.5

94 38 55.0

31 59.8

23 0.17 -

43

24

34

91

Notes:

Page 1 of 2

1) Receive Room levels less than 5 dB above the Background levels are red.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

0.13

0.26 0

ATI 00760 Revised 05/23/16

5000

6.9 12.1

63.8

6.3

4000

0

Page 10: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

Page 2 of 2

22.2 °C Source Temp.

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

06/17/16Test Date

ATI 00760 Revised 05/23/16

Description Series/Model: Lama Dual Glazed, double glazed wall system with 1/2" tempered exterior, 2"

glass to glass air space, 3/8" tempered interior

Specimen Area

Client Modernus

52%Technician Amanda N. Smith

Data File No.

Receive Humidity 52%

F6447.01C

Source Humidity

5.95 m² Receive Temp. 21.6 °C

0

10

20

30

40

50

60

70

80

90

100

31.5 63 125 250 500 1000 2000 4000 8000

Sou

nd

Tra

nsm

issi

on

Lo

ss (

dB

)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL Contour Curve

Page 11: Acoustical Field Test Report - modernus.commodernus.com/downloads/f6447.01-113-11-r0_Dual Glazed Fixed.pdf · Acoustical Performance Test Report . MODERNUS . 234 5th Avenue, Suite

F6447.01-113-11-R0

Appendix C

Photographs

Receive Room View of Installed Specimen

Source Room View of Installed Specimen