achieving & sustaining high performance building operations december 2007 bank of america tower,...
TRANSCRIPT
Achieving & SustainingHigh Performance Building Operations
December 2007
Bank of America Tower, NYC
Today’s AgendaToday’s Agenda
Challenges with keeping buildingsoperating at peak performance
An alternative approach
Applications Re-circulated air systems 100% OA systems
Benefits summary
The Rise of High Performance BuildingsThe Rise of High Performance Buildings
3 trends are driving High Performance Buildings
1. Soaring energy costs
2. Rise of LEED & green buildings construction
3. Increased focus on indoor environmental quality (IEQ)
Tension between Ventilation & EnergyTension between Ventilation & Energy
Ventilationwants moreoutside air
Energy Savingswants morereturn air
Trends Are Driving Increased SensingTrends Are Driving Increased Sensing
Increased need for controls & sensors Min. outside air, DCV, economizers,
pressurization, humidity control, etc.
Controls require many sensors
– CO2, CO, T, RH, static pressure
IEQ monitoring
– Particles, TVOCs, formaldehyde, etc.
Tighter sensor accuracies and proper application are major issues Inaccurate or mis-applied sensors can
actually increase energy costs
– Ex. - normal CO2 errors waste energy
Unfulfilled Promise of Hi-Perf & LEED BldgsUnfulfilled Promise of Hi-Perf & LEED Bldgs
High Performance Buildings idea is NOT new Demand Controlled Ventilation (DCV) Economizers Annual commissioning
Failure has been in implementation (not design) “50% of all buildings are over ventilated” – ASHRAE
“70% of economizers don’t work” – New Buildings Institute
“Less than 5% of buildings are commissioned” –ASHRAE
Conventional approaches are not up to the task!
Conventional ApproachConventional Approach
T TTT
VAV VAV VAV VAV
Room 101 Room 102 Room 103 Room 104
CF
M
BldgCtrlr
Simple
Reliable
Cost Effective
Conventional Sensing Approach (Yikes!)Conventional Sensing Approach (Yikes!)
Extra hard-wired points
Sensor quality (accuracy)
Sensor quantity (cost)
Sensor maintenance & calibration
BAS: knowledge vs. data
VAV VAV VAV VAV
Room 101 Room 102 Room 103 Room 104
RH
CO
CO2 P
V
T RH
CO
CO2 P
V
RH
CO
CO2 P
V
T T RH
CO
CO2 P
V
T
Ctrlr CtrlrCtrlr Ctrlr
CF
M
Bldg Ctrlr
ASHRAE: Ventilation needs differential CO2 measurement
Conventional COConventional CO22 Sensing Sensing
OA CO2
300
400
500
600
12:00 AM 6:00 AM 12:00 PM 6:00 PM 12:00 AM
PP
M
±75 PPM Error
+ ±75 PPM Error
= ±150 PPM Error
CO2 set point must account for total error-If 500 PPM (20 CFM OA/person) is target: set point 350 PPM
Due to sensor error, actual level can vary from 200–500 PPM
Potential over-ventilation is huge! Up to 150%
Even w/calibrated sensors, avg. OA can be 43% high!Potential energy penalty: ~$0.10–$0.20/ft2/year
Return Air Sensor
Outside Air Sensor
Differential Measurement
At the 2007 ASHRAE IAQ Conference…
Accuracy of CO2 Sensorsin Commercial Buildings: A Pilot Study
Lawrence Berkeley National Laboratories
10% were dead: no output at all!
Of the “working” sensors: 10% had negative errors (half off by more than 50%!) 90% had positive error (average positive error: +39%!)
If DCV control was used: 10% would have the OA dampers fully closed The average OA airflow would be 260% too high! 20% would have the OA dampers at 100% OA!
LBNL CO2 Field Sensor Study Results10% Dead
81% Read High(avg. 39%!)
9% Low(½ by 50%)
LBNL: A Review of DCV; LBNL-60170
Michael G. Apte, Environmental Energy Technologies Division, Indoor Environment Department
“…data from the Iowa Energy Center showed long-term output from three “self calibrating” NDIR CO2 sensors operated side by side. Although these new sensors are guaranteed to hold calibration for five years, one unit was observed to have a positive baseline offset of 105 ppm compared to the other two that registered with 25 ppm at about 400 ppm. Nine months later, the baseline of the same unit had diverged by 265 ppm.”
EconomizersEconomizers
Control Method Dry Bulb Temperature
– Outside air sensor versus fixed setpoint in design• ASHRAE Std 90-2004 has max values from 65-75
Differential Enthalpy Control– Same outside air and return air sensor for °F
– Relative Humidity sensor for outside and return air• Need High Quality or Expect Failure
Dry Bulb Economizer
55º F 75º F
OA is at Min
OA is at Max
OA/RA Mix
Differential Enthalpy Economizer
55º F
OA is at Min
OA/RA Mix h = 26.1 Btu/lbm
75º F/40% RH
OA is at Max
Dry Bulb vs. Diff. Enthalpy Economizer
55º F
OA/RA Mix
75º F/40% RH
OA is at Min
OA is at Max
DB: OA is at MaxDE: OA is at Min
DB: OA is at MinDE: OA is at Max
h = 26.1 Btu/lbm
Dry Bulb vs. Diff. Enthalpy Economizer
55º F
OA/RA Mix
65º F
OA is at Min
OA at Max
DB: OA is at MaxDE: OA is at Min
DB: OA is at MinDE: OA is at Max
h = 26.1 Btu/lbm
Differential Enthalpy Economizer SavingsDifferential Enthalpy Economizer Savings
CityNo
Economizer70º
Dry-bulbDifferential Enthalpy
Madison, WI 0% 11% 27%
Lake Charles, LA 0% 3% 9%
New York, NY 0% 12% 33%
Los Angeles, CA 0% 51% 76%
Seattle, WA 0% 25% 51%
Albuquerque, NM 0% 3% 22%
Economizer Savings Study, ASHRAE No. 3200, 1989, P.C. Wacker, P.E.
Example 2: Differential Enthalpy SensingExample 2: Differential Enthalpy Sensing
Best economizer is differential enthalpy Savings increased by 15–100% over dry bulb type Comfort and IEQ increased as well
Yet, dry bulb economizers dominate usage
WHY?
Enthalpy/humidity sensors are problematic High drift from outside air, low temp, particles, etc.
– Sensors often hard to access & calibrate
Differential measurement is prone to error– If sensor error is ±5%, total error of two sensors is ±10%
– For a 10% RH difference, measurement error is ±100%
Poorly working economizers waste $0.10–$0.50/ft2/yr
A New Approach: Multiplexed Air PacketsA New Approach: Multiplexed Air Packets
BACnetto BAS
Air DataRouters
SensorSuite
Transformer
VacuumPump
BrowserInterface
WebAccessibleReports
Knowledge
Center
StructuredCable
I/OI/O I/O I/O
Particles
TVOCs
Dewpt
CO2
COInternet
InformationManagementServer
A New Approach: Multiplexed Air PacketsA New Approach: Multiplexed Air Packets
BACnetto BAS
Air DataRouters
SensorSuite
Xfrmr
VacuumPump
BrowserInterface
WebAccessibleReports
Knowledge
Center
I/O I/O
Internet
IMS
OA
RASA
Conf.
Lobby
Office
Office
CO
CO2
Dew pt.
TVOCs
Particles
Optimizing VentilationOptimizing Ventilation
Zone Control AHU Control
Any building that has Economizer Dampers
Any space that hasVAV or 2-pos. Control
SchoolsOffices
HospitalsLabs & Vivariums
SchoolsOffices
Hospitals
Outside Air ApplicationsOutside Air Applications
Demand Control Ventilation DCV saves energy by
decreasing OA “Non-human pollutants” override
– If indoor air is “dirty”, OA increased
Differential Enthalpy Economizer Control Saves energy by
increasing OA Contaminated OA override
– If outside air is “dirty”, OA reduced
Particulate Control
VAV ORs
Data Centers Econ.
Filter Validation
OA Measurement
1 Sensor
VAV for Operating RoomsVAV for Operating Rooms
OR-1
EF
C
C
PH
C
SF
OR-2 OR-3
HumidityParticlesTVOCs
CO2
CO
Ensuring Filter PerformanceEnsuring Filter Performance
1 Check and change filters often (open loop)
2 Check & Change filters; measure ΔP (open loop)
3 Change filters when needed; measure ΔP; monitor particulates (closed loop)
??
Data Center EconomizersData Center Economizers
Most Data Centers use little (if any) OA
RH and Particle concerns have been drivers
OA can be used safely to achieve huge energy savings
7,000 ft2 data center could save up to 230MWh/year!
OA Measurement using COOA Measurement using CO22
Use Mass Balance
Supply Air CO2 equals the sum of the concentration of CO2 in the OA and RA weighted by the percentage of those components of the supply air. Or…
)(
)(
22
22
OACORACO
SACORACOSAcfmOAcfm
RA
OA SA
Multi-parameter Demand Control Multi-parameter Demand Control VentilationVentilationDemand Control Ventilation DCV saves energy by
decreasing OA “Non-human pollutants” override
– If indoor air is “dirty”, OA increased
Traditional DCV/CO2: waste energy or under-ventilate
Single CO2 set point: not the answer
ASHRAE says more than CO2 is needed
Multi-parameter DCV provides
Better ventilation
More energy savings
OA Need Based on Design Occupancy
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
600 people @ 20 CFM/person = 12,000 CFM
Single Set point Wastes Energy
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
Typical Fixed Setpoint Occupancy Based OA
Excess OA = Wasted EnergyShoulder periods
OA Need Based on TVOC Events
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
TVOC Based OA
• Not periodically predictable• Need more OA than required
by occupancy
OA Requirements for ASHRAE DCV
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
TVOC Based OAOccupancy Based OA
What happens ifonly CO2 is used?
Max Vent Usually Becomes OA Set Point
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
Max Vent OSA Typical Fixed Setpoint
TVOC OA Occupancy Based OA
Potentially Huge Energy Savings
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
18,000
1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P 1 A 9 A 5 P
OA
CF
M
Max Vent OA Traditional System Error
TVOC OA Design Occupancy Based OA
Actual Occupancy Based OA
Excess OA = Wasted Energy =Savings Potential
Over-Ventilation: A Real ExampleOver-Ventilation: A Real Example
0
20
40
60
80
100
120
140
160
180
200
6/18/0611:19 PM
6/19/065:17 AM
6/19/0611:15 AM
6/19/065:12 PM
6/19/0611:10 PM
6/20/065:08 AM
6/20/0611:06 AM
6/20/065:04 PM
6/20/0611:02 PM
6/21/065:00 AM
6/21/0610:58 AM
CFM
of O
A/P
erso
n
AHU 3 AHU 4 AHU 2
Room Level Airflow Control ApplicationsRoom Level Airflow Control Applications
Simple dynamic override cuts across all markets Reduce room airflow min when CO2 and contaminants are low
Increase airflow when CO2 or contaminants are high
Reduces both fan power & htg/clg costs from OA
Particularly appropriate for multi-zone air handlers
Sample applications Use for DCV control of “critical” zones in offices, schools, etc.
– Critical zones are rooms w/lower supply air & higher occupancy
– Reduces AHU’s outside air volume beyond AHU only control
Reduces outside air dramatically in labs and vivariums Vary airflow use in hospital OR’s when unused
Dynamic Control of Min Ventilation & Fresh AirDynamic Control of Min Ventilation & Fresh Air
VAV vs. OAVAV vs. OAF
low
Time
OA
VAV
CO2
100% Open
Stage 1: Increase VAV Flow Stage 2: Add More OA
CO
2 in
PP
M
Another Application: Humidity ControlAnother Application: Humidity Control
Replace local RH sensor w/multiplexed dewpoint sensor Applications at the air handling unit
– Humidity control of outside & mixed return air
Applications at the room/zone level– Supplemental humidity control in OR’s, animal rooms, offices, etc.
Multiplexed dewpoint sensing has many benefits More accurate – Uses high quality sensor More reliable – Calibration is cost effective & regular More cost effective – One vs. many sensors
Current Drivers of Lab AirflowCurrent Drivers of Lab Airflow
Hood & thermal airflows are reduced; vary for peaks
Higher “dilution” requirement is typically the driver
Ven
tila
tio
n R
ate
(CF
M)
VAVVAV
FumeHoods
ThermalLoad
6-12 ACH
2- 4 ACH
ACH/Dilution
Constant
Trends in LaboratoriesTrends in Laboratories
VAV Fume Hood Control has gained wide acceptance
Fume hood densities are much lower More computation & lower chemical quantities Increased number of life sciences labs
Thermal loads have peaked & are dropping Plug loads down from energy efficient equipment Higher efficiency lighting & more day lighting
Energy costs are soaring LEED labs
Typical Life Sciences LabTypical Life Sciences Lab
Typical Life Sciences LabTypical Life Sciences Lab
Low Load (blue)
Medium Load (yellow)
High Load (red)
AZ Lab Trend FindingsAZ Lab Trend Findings
Lab Min Vent CFM range:9–16 ACH (Avg ~14)
Max Cooling CFM::10–21 Watts/ft2 (Avg ~14)
Many Min Vent CFM ≈ Max Cooling CFM
– Almost no VAV activity
71% always at min vent
Mixed fume hood sash positions
Always in Reheat (Low Load)
Always Full Cooling(High Load)
Mixed Clg/Reheat(Medium Load)
81%
14%5%
Yet Requirements Stay The SameYet Requirements Stay The Same
Minimum air changes still fixed at 6 to 12 ACH
Need still exists for dilution ventilation in labs Dilute vapors from a spill when lab is unoccupied Dilute vapors & gases caused by poor lab practices
– Working outside the hood
– Improper storage of chemicals
– No localized exhaust for instruments
– “Overworking” & overcrowding of hoods
Dilution: a backup to containment
Fortunately, for most labs, room air is often “clean”
Actual Lab IEQ Case StudyActual Lab IEQ Case Study
Major University laboratory facility 15 labs monitored continuously for 10 months Ventilation rate at 12 ACH per university IH group
Result Two recorded “incidents” of elevated TVOC levels in several
laboratories totaling 4-5 hours (0.07% of total hours) 99.93% of the time, these labs could have been operated at
lower airflow rates
Cause Workers using fume hoods during scheduled hood
maintenance periods
Solution Better internal communication between maintenance and
occupants – No further incidents
Actual Data: 35 Days at 2 FacilitiesActual Data: 35 Days at 2 Facilities
0.00%
0.20%
0.40%
0.60%
0.80%
1.00%
1.20%
1.40%
0.10 0.25 0.50 1.00 1.50 2.00 4.00 8.00
Threshold TVOC Values in PPM at 4 ACH
% o
f T
ime
Ove
r T
hre
sho
ld
Bio-B Pilot @ 4 ACH Harvard FXB @ 4 ACH
Lab Demand Controlled Ventilation (DCV)Lab Demand Controlled Ventilation (DCV)
Varies dilution/min ACHs by sensing lab IEQ If lab air is clean, dilution airflow can be reduced Plus, greater lab dilution is provided when
needed by sensing or manual override
Most lab controls can vary min ACH levels
Critical piece: Sensing of IEQ parameters Lab TVOCs, Particles, RH, CO, & CO2
Barriers to date: Cost & practicality Sensor cost Long term reliability Calibration of Distributed Sensors
Solution: Vary Dilution to Save EnergySolution: Vary Dilution to Save Energy
Lab DCV: Next generation lab airflow control Apply VAV control, to all lab air requirements Significantly reduce energy, find a way to increase safety
Ven
tila
tio
n R
ate
(CF
M)
VAVVAV
FumeHoods
ThermalLoad
6-12 ACH
2- 4 ACH
Energy &First Cost
Savings
ACH/Dilution
VAV
Dynamic Control of Dilution RatesDynamic Control of Dilution RatesSpill Dilution Concentration vs. Time
0
500
1,000
1,500
2,000
2,500
0 5 10 15 20 25 30 35 40 45 50 55 60Time in Minutes
PP
M C
on
ce
ntr
ati
on
10 ACH Baseline 250PPM Threshold Level Dynamic 4-16 ACH
1.5 L spill of acetone in 200ft2 lab
Total PPM is lower with dynamic ventilation
After vaporized, dynamic system hits TLV faster
After 1 hour Dynamic control has dropped level to .53 PPM
Dynamic Dilution Ventilation ControlDynamic Dilution Ventilation Control
There is no need to dilute clean air w/ clean air TVOC, particle counter, etc. sense air
– Hundreds of compounds are detected below TLV threshold
– Small number of compounds not detected are fairly dangerous• Should not be used in a fume hood
Set min dilution levels per OSHA or as desired For high concern: 4 ACH occupied; 2 ACH unoccupied
– OSHA guidelines have a minimum at 4 ACH (range of 4–12)
For less severe applications, use 2 ACH as minimum– ASHRAE fresh air min for science lab is 0.18 CFM/ft2 or 1.2 ACH
– Appropriate for life sciences & less critical lab and support areas
Set max dilution level at 12–16 ACH for safest purge Or as high as the supply/exhaust valves can go
0 CFM
2,000 CFM
4,000 CFM
6,000 CFM
8,000 CFM
10,000 CFM
12,000 CFM
14,000 CFM
16,000 CFM
18,000 CFM
May-17 May-31 Jun-15 Jun-29 Jul-16 Jul-30 Aug-13 Aug-27 Sep-11 Sep-25 Oct-10
Exhaust CFM Supply CFM
ASU Biodesign B – Aircuity ResultsASU Biodesign B – Aircuity Results
Average Savings: 10,636 CFMAt $6.00/CFM annually = $63,816 per year = $7.98/ft2 per year = 9 month payback!
New Average Supply: 5,229 CFM
Old Average Supply: 15,978 CFM
10,6
36 C
FM
Sav
ing
sJune 4, 2007Aircuity Activation
Chilled Beams in Labs
Multiplexed dewpoint sensing benefits: More reliable
– Calibration is cost effective
– Calibration regularly done
More accurate – Uses high quality sensor– (NDIR hygrometer)
More cost effective– 1 vs. many sensors
Reduced Costs– Smaller ∆T
DCV Case Study: GreenLab, SeattleDCV Case Study: GreenLab, Seattle
Project Facts Project team:
– Owner – Vulcan (Paul Allen)
– Architect – Perkins & Will
– Mechanical Eng. – Stantec (Keen Eng.)
– Contractor – Sellen
– Estimator – Davis Langdon
215,000 ft2 mixed use building– 75,000 ft2 lab area
– 75,000 ft2 office
– 25,000 ft2 optional vivarium
Design based on Aircuity Lab DCV
DCV Case Study: GreenLab, SeattleDCV Case Study: GreenLab, Seattle
Lab DCV analysis assumptions: Lab area: 4–16 ACH vs. a fixed 9 ACH
Vivarium: 8–16 ACH vs. a fixed 15 ACH
Gross first cost savings: $1,025,000 $13.68/ft2 gross or $8.68/ft2 net for lab
Total bldg energy cut by $250,000/yr. Reduced total bldg’s utility bill by 20%
ROI: 1.5 yr energy payback
“Single greatest energy savings measure of the project”
Harvard Allston Lab ProjectHarvard Allston Lab Project
Annual Energy Savings Energy Savings for 350K ft2 Lab $528,360 Energy Savings for 50K ft2 Vivarium $275,200 Total Annual Savings $803,560
Total Installed Optinet System Cost Research Lab OptiNet system cost $750,000 Vivarium OptiNet system cost $185,000 Public Area OptiNet system cost $75,000 Labor assumed at 35% of materials $355,000 Total Installed OptiNet cost $1,365,000
Simple Payback
payback year7.1savings 560,803$
cost 000,365,1$
Brigham & Women’s Hospital ExampleBrigham & Women’s Hospital Example
Annual Energy Savings: Floors 1 – 3 Fan power savings $40,414 Floors 1 – 3 Outside Air savings $41,344 Diff enthalpy vs. dry bulb economizers $58,788 Total Energy Savings $140,546
Total Installed System Cost Material & Startup costs $96,000 Deduct for 15 CO2 sensors - $18,000 Deduct for 10 RH sensors - $10,000 Installation cost $38,000 Total adjusted installed cost $106,000
Simple payback on above scope 0.76 years
5 Year lifecycle analysis results +$504,235 Assumes annual services of $18,500/yr
Aircuity at UC San Diego, Center Hall
University Classroom Bldg.
2,100 Student Facility
Applied MpDCV
Net 1st Cost: $29K
Saves over $38,000/year in energy 45% of annual HVAC energy!
Saves 310,000 Kwh & 1,100 MBTU
9-Month Payback
5-Year savings nearly $200K
Aircuity at Bank of America Tower, NYC
1st LEED Platinum Skyscraper
JB&B, NYC Specified Aircuity
$1.0B budget, 2.1M ft2 building
40 Suites vs. 700+ CO2 sensors
Saves $160K/year in maintenance
Saves $400K in replacement costs Every 2-5 years!
One Bryant Park
Aircuity at UBS in Stamford, CT
World’s largest open securities trading floor
Aircuity Energy Retrofit
Van Zelm Engineers, CT
1.7 year energy payback
Aircuity at the Newark Arena (NJ Devils)
100,000 ft2 sports arena; $310M budget
Vanderweil Associates; Flat specified Aircuity
Demanding Dew Point & DCV control Multiple IEQ Parameters
Project 1st Cost reduced by over $100K ($1/ft2)
Saves $40,000/year in maintenance
Saves $90K in sensor replacement costs Every 2-5 years
Some Laboratory/Vivarium Customers
Harvard School of Public Health
Merck Research Labs
Grand Valley State Univ
Acadia Univ
Univ of Cincinnati
Arizona State Univ
Rice Univ
Texas Children’s Hospital
Children’s Hospital of Philadelphia
Case Western Reserve Univ
Regina Provincial Labs
Some Commercial Applications Customers
Yale Univ
NYU Medical Center
Boston Univ
Univ of Nevada – Las Vegas
Carnegie Mellon Univ
Boeing
UBS Financial
St. Francis Hospital
Bristol Myers Squibb
Brigham & Women’s Hospital
Packard Humanities Inst. Film Vault
New Jersey Devils Arena
Bank of America
Cost Effective LEED NC PointsCost Effective LEED NC Points
Primary impact on up to 4 points:
IEQ potential: 3 pts. EQ - 1 : Permanent CO2/OA Monitoring
EQ - 3.2: Construction IAQ Mgmt Plan EQ - 7.2: Permanent Comfort Monitoring
Innovation in Design potential: 1 pt. Comprehensive IEQ Mgmt System
– Multi-parameter DCV
Cost Effective LEED NC PointsCost Effective LEED NC Points
System can assist/lower cost on up to 13 pts:
Energy & Atmosphere potential: 12 pts.
EA - 1: Optimize Energy: up to 10 pts.
EA - 3 Enhanced Commissioning: 1 pt.
EA - 5 Measurement & Verification: 1 pt.
IEQ potential: 1 point
EQ - 3.1: Construction IAQ Mgmt Plan: 1 pt.
Facility monitoring can impact up to 15% of LEED points
ReviewReview
Traditional technology has many shortfalls in the quest for long-term high performance building operation
Now a solution exists to ensure that buildings satisfy both owners and occupants
OA management and associated sensors are key factors
The benefits are measurable and can be substantial
Aircuity Summary Aircuity Summary
An alternative approach for sustainable control
Cost effectively improves OA efficiency
Key Benefits Energy savings
– 5-50% annually
Reduced labor & operating costs– 20-40% annually
Improved IEQ– Increased productivity, peace of mind
LEED Points “Actionable” information
– Gives you the power to keep your facilities operating at a high performance level today AND tomorrow.
Aircuity Summary Aircuity Summary
An alternative approach for sustainable control
Cost effectively improves OA efficiency
Key Benefits Energy savings
– 5-50% annually
Reduced labor & operating costs– 20-40% annually
Improved IEQ– Increased productivity, peace of mind
LEED Points “Actionable” information
– Gives you the power to keep your facilities operating at a high performance level today AND tomorrow.
A New Approach: Multiplexed Air PacketsA New Approach: Multiplexed Air Packets
BACnetto BAS
Air DataRouters
SensorSuite
Xfrmr
VacuumPump
BrowserInterface
WebAccessibleReports
Knowledge
Center
I/O I/O
Internet
IMS
OA
RASA
Conf.
Lobby
Office
Office
CO
CO2
Dew pt.
TVOCs
Particles