724 ACCUMULATORS AC&R VERTICAL SUCTION ACCUMULATORS Optional: 1-in. FPT con- nection is available on S-7700 series for in of an S-9400-1 type Liquid Level Switch. Selection of a suction line accumulator should be made on the basis of the following three capabilities. The accumulator should have an adequate liquid holding capacity, which can vary with the system. Normally this should not be less than 50% of the system charge. If possible this value should be checked based on actual tests. A second consideration should be the ability of the accumulator to perform without adding excessive pres- sure drop to the system. The recommended maximum tonnages shown in the following tables are based on a pressure drop equivalent to 1/2° F. These ratings are those of the accumulator, based on oil return through the accumulator, and will be modified by the length of the suction line and compressor displacement. Finally an accumulator should have the capability of returning liquid at the proper rate and under a range of load conditions. Accumulators should have a Heat Element added on low temperature applications (0° F and below) such as the S-9111 or S-9112 to help boil off liquid refrigerant and raise the oil temperature to help facilitate oil flow. S-7700 Series HE: Heat Exchanger models available by ordering with an HE suffix (i.e. S-7065HE). Heat Exchanger models feature a boil out coil to boil off liquid refrigerant in the bottom of the accumulator. The ODS connection size of the boil out coil is shown in Column E. SPECIFICATIONS PART NUMBER ODS CONN. DIA. A B C D ODS E S-7043 5/8 4 6.38 1.88 N/A N/A S-7044 1/2 10.38 S-7045 S-7045HE 5/8 2.50 2.50 3/8 S-7046 S-7046HE 3/4 S-7057 S-7057HE 7/8 5 13 2.25 2.75 1/2 S-7061 S-7061HE 1-1/8 6 15 3 2.88 5/8 S-7063S 1-3/8 20.25 N/A N/A S-7063 S-7063HE 24.75 2.88 5/8 S-7065 S-7065HE 1-5/8 3/4 S-7721 S-7721HE 2-1/8 8-5/8 23.13 3.50 5.50 7/8 S-7725 S-7725HE 2-5/8 10-3/4 22.75 4.63 1-3/8 S-7731 S-7731HE 3-1/8 12-3/4 25 5.50 5.88 1-3/8 S-7741 S-7741HE 4-1/8 16 35.50 CONTACT FACTORY 2-5/8 S-7742 4-1/8 20 44.50 CONTACT FACTORY N/A PART NO. REFRIGERANT HOLDING CAP. (lbs 0°F sat) RECOMMENDED TONS REFRIGERATION AT SUCTION EVAPORATING TEMPERATURE (°F) R-134a R-22 R-404A/R-507 R-134a R-22 R-404a/R-507 +40°F +20°F +0°F -20°F -40°F +40°F +20°F +0°F -20°F -40°F +40°F +20°F +0°F -20°F -40°F S-7043 MAX MIN 2.3 2.1 1.9 0.92 0.19 0.64 0.16 0.44 0.13 0.29 0.11 0.18 0.08 1.81 0.26 1.27 0.22 0.87 0.19 0.59 0.16 0.38 0.12 1.78 0.26 1.21 0.21 0.80 0.17 0.52 0.14 0.32 0.10 S-7044 MAX MIN 4.4 4.1 3.7 0.46 0.09 0.33 0.07 0.23 0.06 0.14 0.05 0.18 0.04 0.91 0.13 0.65 0.10 0.46 0.09 0.28 0.07 0.20 0.06 0.89 0.13 0.62 0.09 0.42 0.08 0.25 0.06 0.17 0.05 S-7045 MAX MIN 0.92 0.19 0.64 0.16 0.44 0.13 0.29 0.11 0.18 0.08 1.81 0.26 1.27 0.22 0.87 0.19 0.59 0.16 0.38 0.12 1.78 0.26 1.21 0.21 0.80 0.17 0.52 0.14 0.32 0.10 S-7046 MAX MIN 1.28 0.25 0.88 0.21 0.60 0.17 0.39 0.14 0.24 0.11 2.51 0.35 1.76 0.29 1.19 0.24 0.79 0.20 0.52 0.16 2.46 0.36 1.67 0.28 1.09 0.22 0.70 0.18 0.44 0.14 S-7057 MAX MIN 9.2 8.5 7.7 2.19 0.37 1.53 0.32 1.02 0.26 0.66 0.21 0.40 0.17 4.32 0.51 3.05 0.45 2.02 0.37 1.34 0.30 0.86 0.25 4.24 0.50 2.90 0.43 1.85 0.34 1.19 0.27 0.73 0.21 S-7061 MAX MIN 12.7 11.8 10.7 4.62 0.61 3.25 0.52 2.08 0.43 1.35 0.35 0.82 0.28 9.09 0.85 6.49 0.72 4.10 0.62 2.75 0.51 1.74 0.41 8.92 0.83 6.16 0.68 3.76 0.57 2.44 0.45 1.48 0.35 S-7063S MAX MIN 17.1 15.4 14.0 7.91 1.25 5.33 1.05 3.42 0.87 2.17 0.71 1.34 0.57 15.6 1.73 10.7 1.46 6.75 1.25 4.42 1.03 2.85 0.83 15.3 1.70 10.2 1.39 6.18 1.15 3.92 0.91 2.43 0.71 S-7063 MAX MIN 21.8 20.1 18.2 7.91 1.25 5.33 1.05 3.42 0.87 2.17 0.71 1.34 0.57 15.6 1.73 10.7 1.46 6.75 1.25 4.42 1.03 2.85 0.83 15.3 1.70 10.2 1.39 6.18 1.15 3.92 0.91 2.43 0.71 S-7065 MAX MIN 14.0 2.15 9.61 1.80 5.99 1.50 3.82 1.25 2.34 1.00 27.5 2.98 19.2 2.51 11.8 2.16 7.79 1.81 4.98 1.46 27.0 2.92 18.2 2.38 10.8 1.98 6.91 1.61 4.25 1.25 S-7721 MAX MIN 32.5 30 27 31.0 4.0 20.0 3.5 14.0 3.0 7.5 2.5 5.00 2.00 58.0 6.0 40.0 5.5 26.0 4.5 18.0 4.0 12.0 3.0 57.0 6.0 38.0 5.0 24.0 4.0 16.0 3.5 10.0 2.5 S-7725 MAX MIN 48.5 44 40 49.0 6.0 32.0 5.5 21.5 4.5 12.0 3.5 6.5 1.0 89.0 9.0 61.0 8.5 41.0 7.0 28.0 6.5 15.5 1.5 87.5 9.0 58.0 8.0 37.5 6.5 25.0 6.0 13.5 1.5 S-7731 MAX MIN 80 73 66 72.0 10.0 55.0 9.0 37.0 7.0 24.0 6.5 9.5 1.5 132.0 15.5 92.0 13.0 61.0 11.5 40.0 9.5 23.5 2.5 129.5 15.0 87.5 12.5 56.0 10.5 35.5 8.5 20.0 2.5 S-7741 MAX MIN 136 135 122 114.0 31.0 73.7 25.4 44.2 21.5 30.5 17.0 19.8 13.4 225.0 43.0 145.0 35.4 87.0 30.9 60.0 24.6 39.0 9.0 215.0 49.5 143.0 32.0 91.0 21.0 57.0 13.0 33.0 7.0 S-7742 MAX MIN 279 277 251 114.0 31.0 73.7 25.4 44.2 21.5 30.5 17.0 19.8 13.4 225.0 43.0 145.0 35.4 87.0 30.9 60.0 24.6 39.0 9.0 215.0 49.5 143.0 32.0 91.0 21.0 57.0 13.0 33.0 7.0 P1145 P1146 S-7000 Series P1144 Maximum WP 400 PSI

Upload: phamhanh

Post on 30-Jan-2018

240 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

724

ACCUMULATORS

AC&R VERTICAL SUCTION ACCUMULATORS

Optional: 1-in. FPT con-nection is available on S-7700 series for in of an S-9400-1 type Liquid Level Switch.

Selection of a suction line accumulator should be made on the basis of the following three capabilities. The accumulator should have an adequate liquid holding capacity, which can vary with the system. Normally this should not be less than 50% of the system charge. If possible this value should be checked based on actual tests.

A second consideration should be the ability of the accumulator to perform without adding excessive pres-sure drop to the system. The recommended maximum tonnages shown in the following tables are based on a pressure drop equivalent to 1/2° F. These ratings are those of the accumulator, based on oil return through the accumulator, and will be modified by the length of the suction line and compressor displacement.

Finally an accumulator should have the capability of returning liquid at the proper rate and under a range of load conditions.

Accumulators should have a Heat Element added on low temperature applications (0° F and below) such as the S-9111 or S-9112 to help boil off liquid refrigerant and raise the oil temperature to help facilitate oil flow.

S-7700 Series

HE: Heat Exchanger models available by ordering with an HE suffix (i.e. S-7065HE). Heat Exchanger models feature a boil out coil to boil off liquid refrigerant in the bottom of the accumulator. The ODS connection size of the boil out coil is shown inColumn E.

SPECIFICATIONS

PART NUMBER ODS CONN.

DIA. A B C D ODS

E

S-7043 5/8

4

6.381.88 N/A N/A

S-7044 1/2

10.38S-7045 S-7045HE 5/82.50 2.50 3/8

S-7046 S-7046HE 3/4S-7057 S-7057HE 7/8 5 13 2.25 2.75 1/2S-7061 S-7061HE 1-1/8

6

15

3

2.88 5/8

S-7063S1-3/8

20.25 N/A N/A

S-7063 S-7063HE24.75 2.88

5/8S-7065 S-7065HE 1-5/8 3/4

S-7721 S-7721HE 2-1/8 8-5/8 23.13 3.505.50

7/8S-7725 S-7725HE 2-5/8 10-3/4 22.75 4.63 1-3/8S-7731 S-7731HE 3-1/8 12-3/4 25 5.50 5.88 1-3/8

S-7741 S-7741HE 4-1/8 16 35.50CONTACT FACTORY 2-5/8

S-7742 4-1/8 20 44.50 CONTACT FACTORY

N/A

PARTNO.

REFRIGERANT HOLDING CAP.

(lbs 0°F sat)

RECOMMENDED TONS REFRIGERATION AT SUCTION EVAPORATING TEMPERATURE (°F)

R-134a R-22 R-404A/R-507

R-134a R-22 R-404a/R-507 +40°F +20°F +0°F -20°F -40°F +40°F +20°F +0°F -20°F -40°F +40°F +20°F +0°F -20°F -40°F

S-7043 MAXMIN 2.3 2.1 1.9

0.920.19

0.640.16

0.440.13

0.290.11

0.180.08

1.810.26

1.270.22

0.870.19

0.590.16

0.380.12

1.780.26

1.210.21

0.800.17

0.520.14

0.320.10

S-7044 MAXMIN

4.4 4.1 3.7

0.460.09

0.330.07

0.230.06

0.140.05

0.180.04

0.910.13

0.650.10

0.460.09

0.280.07

0.200.06

0.890.13

0.620.09

0.420.08

0.250.06

0.170.05

S-7045 MAXMIN

0.920.19

0.640.16

0.440.13

0.290.11

0.180.08

1.810.26

1.270.22

0.870.19

0.590.16

0.380.12

1.780.26

1.210.21

0.800.17

0.520.14

0.320.10

S-7046 MAXMIN

1.280.25

0.880.21

0.600.17

0.390.14

0.240.11

2.510.35

1.760.29

1.190.24

0.790.20

0.520.16

2.460.36

1.670.28

1.090.22

0.700.18

0.440.14

S-7057 MAXMIN

9.2 8.5 7.72.190.37

1.530.32

1.020.26

0.660.21

0.400.17

4.320.51

3.050.45

2.020.37

1.340.30

0.860.25

4.240.50

2.900.43

1.850.34

1.190.27

0.730.21

S-7061 MAXMIN 12.7 11.8 10.7

4.620.61

3.250.52

2.080.43

1.350.35

0.820.28

9.090.85

6.490.72

4.100.62

2.750.51

1.740.41

8.920.83

6.160.68

3.760.57

2.440.45

1.480.35

S-7063S MAXMIN

17.1 15.4 14.07.911.25

5.331.05

3.420.87

2.170.71

1.340.57

15.61.73

10.71.46

6.751.25

4.421.03

2.850.83

15.31.70

10.21.39

6.181.15

3.920.91

2.430.71

S-7063 MAXMIN

21.8 20.1 18.2

7.911.25

5.331.05

3.420.87

2.170.71

1.340.57

15.61.73

10.71.46

6.751.25

4.421.03

2.850.83

15.31.70

10.21.39

6.181.15

3.920.91

2.430.71

S-7065 MAXMIN

14.02.15

9.611.80

5.991.50

3.821.25

2.341.00

27.52.98

19.22.51

11.82.16

7.791.81

4.981.46

27.02.92

18.22.38

10.81.98

6.911.61

4.251.25

S-7721 MAXMIN 32.5 30 27

31.04.0

20.03.5

14.03.0

7.52.5

5.002.00

58.06.0

40.05.5

26.04.5

18.04.0

12.03.0

57.06.0

38.05.0

24.04.0

16.03.5

10.02.5

S-7725 MAXMIN

48.5 44 40 49.06.0

32.05.5

21.54.5

12.03.5

6.51.0

89.09.0

61.08.5

41.07.0

28.06.5

15.51.5

87.59.0

58.08.0

37.56.5

25.06.0

13.51.5

S-7731 MAXMIN 80 73 66

72.010.0

55.09.0

37.07.0

24.06.5

9.51.5

132.015.5

92.013.0

61.011.5

40.09.5

23.52.5

129.515.0

87.512.5

56.010.5

35.58.5

20.02.5

S-7741 MAXMIN

136 135 122 114.031.0

73.725.4

44.221.5

30.517.0

19.813.4

225.043.0

145.035.4

87.030.9

60.024.6

39.09.0

215.049.5

143.032.0

91.021.0

57.013.0

33.07.0

S-7742 MAXMIN

279 277 251114.0

31.073.725.4

44.221.5

30.517.0

19.813.4

225.043.0

145.035.4

87.030.9

60.024.6

39.09.0

215.049.5

143.032.0

91.021.0

57.013.0

33.07.0

P1145P1146

S-7000 Series

P1144

Maximum WP 400 PSI

Page 2: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

725

ACCUMULATORS

AC&R HORIZONTAL ACCUMULATORSLiquid accumulators of this design should not be used when the temperature of the liquid refrigerant is less than +15° F in the accumulator. These accumulators have a 1/2-in. FPT connection for liquid injection and a 3/4-in. FPT connection for hot gas bypass. These connections can also be used for a relief device as required byUL 207.

S-7600 SERIES

P1147

DISCHARGE LINE MUFFLERS

PART NUMBER

SIZE CONN.

DIMENSIONS (in.)REFRIGERANT HOLDING CAP.

(lbs 0° F SAT.)

RECOMMENDED TONS OF REFRIGERANT AT SUCTION EVAPORATING TEMPERATURE (°F)

R-134a R-22 R-404A/R-507DiaA

B C R-134a R-22 R0404A/R-507 +40°F +20°F +0°F +40°F +20°F +0°F +40°F +20°F +0°F

S-7615 1-5/8 ODS6

28 21.50 23.3 21.3 19.3 15 10 6.25 29 20 12.5 28.5 19 11.5S-7621 2-1/8 ODS 36.75 30.25 31.6 29 26.2 28.6 19.5 12.5 50 30 25 49.1 33.2 22.9S-7625 2-5/8 ODS 50 43.50 46.7 42.6 38.6 50 35 23 95 65 45 93.2 61.7 41.2

PART NUMBER

SIZE CONN. Dia. A B

S-6304 1/2 ODS

3

7.75S-6305 5/8 ODS 7.75S-6307 7/8 ODS 9.69S-6311 1-1/8 ODS 9.69S-6405 5/8 ODS

4

6.75S-6407 7/8 ODS 7S-6411 1-1/8 ODS 13.25S-6413 1-3/8 ODS 13.75S-6415 1-5/8 ODS 18.25S-6621 2-1/8 ODS

621

S-6625 2-5/8 ODS 21S-6631 3-1/8 ODS 22.38

Mufflers have internal baffles designed for minimum pressure drop. These baffles change the velocity of the discharge gasses passing through the muffler. This results in a dampening effect on high frequency sound waves on high speed compressors. Pulsating waves are also muffled in both low speed and high speed compressors.

Mufflers are sized to the discharge line of the compressor.

COMPRESSOR COMMERCIAL MUFFLERS 5-150 TONS

*Inlet and outlet dimensions are specified as I.D. unless otherwise indicated.**Steel tube on inlet end.†Internal oil pick-up tube on outlet end.

NOM.TONCAP

O.D.(in.)

LENGTH(in.)

INLET*DIM.(in.)

OUTLET*DIM.(in.)

P/N

5 2 7-7/16 5/8 5/8 LM10KH00510 3 11-1/4 7/8 7/8 06DA60560410 3-1/8 10 7/8 OD** 7/8 50K8-391310 3 11-11/16 7/8 7/8 OD 38BA40060310 3 12-1/4 7/8 OD** 7/8 50K8-450315 3 11-1/4 1-1/8 1-1/8 06DA60561425 4 13-3/4 1-3/8 OD 1-3/8 OD 05HY50085325 4 13-7/8 1-1/2 OD 1-1/2 OD† LM10HH10030 4 15-5/8 1-3/8 1-3/8† 06EA50030240 4 13-7/8 1-5/8 1-5/8† 06EA50071240 4 15-5/8 1-5/8 1-5/8† 06EA50042250 4 14-3/8 1-1/8 1-1/8† 48DD51104275 6 22-5/8 2-5/8 OD 2-5/8 OD 05HG680007

100 6 22-5/8 3-1/8 OD 3-1/8 OD 05HG680005150 8 22-5/8 3-1/8 3-1/8 05HY501013

P75

P1148

MAXIMUM WP 302 PSI

Page 3: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

726

ACCUMULATORS

PARKER STEEL SUCTION LINE ACCUMULATORS"U" Tube Style Accumulators

The Parker “U” tube accumulator design is a result of extensive laboratory testing plus detailed investigation of the various accumulators currentlyavailable. It takes into account all of the requirements essential for heat pump applications, including safe holding volume (relative to the system’s total charge), protected flow control for positive refrigerant and oil return, and minimum pressure drop across the accumulator.

Parker offers standard accumulator models designed for application on heat pump and refrigeration systems from 1/4 through 12 tons. Liquid refrigerant holding requirements of suction accumulator may vary by application. Because of the diversity in heat pump systems, accumulator capacityselection should be determined by actual testing. Consult Parker forassistance if required.

Key Features & Benefits

• Solid copper connections.

• “U” tube design for maximum flow of refrigerant and minimum oilentrapment.

• Inlet flow deflector guides refrigerant toward wall for smooth tangential flow and gradual expansion.

• “U” tube entrance is positioned behind the inlet flow deflector to prevent unwanted liquid refrigerant from entering and damaging compressor.

• Metering orifice matched to system capacity assures optimum liquid refrigerant and oil flow back to compressor.

• Protective screen and orifice assembly on “U” tube protects againstforeign particles and contaminants affecting metering function.

• Fittings and “U” tube are matched to accumulator holding capacity and total system charge for minimum pressure drop and maximum refrigerant flow.

• U.L. listed for 355 psig design pressure. File No. SA5172.

• Powder paint exterior coating surpasses 500 hour ASTM salt spray tests.

• Integral 430° F Fuse Plugs (U.L. File No. SA5441).

also available:

Heat Exchanger Accumulator

• Can be made in all models of Parker's standard accumulators.

• Copper heat exchange coil for superior heat exchange.

• Liquid line connections available in 3/8″ I.D..

P4042

P4043

Page 4: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

727

ACCUMULATORS

PARKER STEEL SUCTION LINE ACCUMULATOR DIMENSIONS AND FLOW DATA

*Holding capacity of R-22 at 40° F. Divide by .7 to obtain recommended maximum system charge on fixed orifice systems. Consult Parker for availability.

PARTNUMBER

SOLDERFITTING

SIZE(in.)

DIMENSIONS(in.)

CAPACITY1

(oz)

EVAPTEMP(°F)

RECOMMENDED CAPACITY IN TONS OF REFRIGERATION

Length O.D.22 & 404A 134a 401A 402A 407C 410A 502 & 507A

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

Tons @1 psi

Min.Tons

PA3060-10-4 1/2 10.35 3 35 40 2.00 0.35 1.67 0.30 1.42 0.25 1.97 1.01 1.97 0.46 1.93 1.44 1.48 0.27PA3060-10-5 5/8 10.35 3 35 0 1.54 0.25 0.98 0.16 1.06 0.18 1.53 0.41 1.53 0.18 1.50 0.65 1.10 0.2

-20 1.33 0.21 0.69 0.11 0.90 0.15 1.32 0.25 1.32 0.11 1.30 0.42 0.93 0.16

PA3060-15-5 5/8 15.05 3 5540 2.10 0.35 1.75 0.30 1.49 0.25 2.07 1.01 2.07 0.46 2.02 1.44 1.55 0.27

0 1.62 0.25 1.03 0.16 1.11 0.18 1.61 0.41 1.60 0.18 1.57 0.65 1.16 0.2-20 1.40 0.21 0.73 0.11 0.95 0.15 1.39 0.25 1.39 0.11 1.36 0.42 0.98 0.16

PA3060-15-6 3/4 15.05 3 5440 2.30 0.35 1.92 0.30 1.63 0.25 2.27 1.01 2.27 0.46 2.22 1.44 1.70 0.27

0 1.77 0.25 1.12 0.16 1.22 0.18 1.76 0.41 1.75 0.18 1.72 0.65 1.27 0.2-20 1.53 0.21 0.80 0.11 1.04 0.15 1.52 0.25 1.52 0.11 1.49 0.42 1.07 0.16

PA4065-9-5C 5/8 9.62 4 6040 2.96 0.35 2.47 0.30 2.10 0.25 2.92 1.01 2.92 0.46 2.85 1.44 2.19 0.27

0 2.28 0.25 1.44 0.16 1.57 0.18 2.27 0.41 2.26 0.18 2.21 0.65 1.63 0.2-20 1.98 0.21 1.03 0.11 1.34 0.15 1.97 0.25 1.96 0.11 1.93 0.42 1.39 0.16

PA4065-9-6C 3/4 9-5/8 4 5840 3.00 0.35 2.53 0.30 2.10 0.25 2.96 1.01 2.96 0.46 2.89 1.44 2.20 0.28

0 2.30 0.25 1.48 0.16 1.60 0.18 2.29 0.41 2.28 0.18 2.23 0.65 1.70 0.2-20 2.00 0.21 1.05 0.11 1.40 0.15 1.99 0.25 1.98 0.11 1.95 0.42 1.40 0.16

PA5083-9-6C 3/4 9.62 5 8940 3.82 0.57 3.19 0.49 2.71 0.41 3.76 1.51 3.77 0.69 3.68 2.16 2.82 0.46

0 2.95 0.41 1.86 0.27 2.03 0.30 2.94 0.61 2.92 0.27 2.86 0.98 2.10 0.33-20 2.55 0.35 1.32 0.18 1.73 0.24 2.53 0.37 2.53 0.16 2.48 0.63 1.79 0.27

PA5083-9-7C 7/8 9.63 5 8640 3.90 0.57 3.21 0.49 2.70 0.41 3.84 1.51 3.85 0.69 3.76 2.16 2.80 0.46

0 3.00 0.41 1.88 0.27 2.00 0.30 2.98 0.61 2.97 0.27 2.91 0.98 2.10 0.33-20 2.60 0.35 1.33 0.18 1.70 0.24 2.58 0.37 2.58 0.16 2.53 0.63 1.80 0.27

PA5083-12-7C 7/8 12.88 5 12540 5.41 0.88 4.51 0.75 3.83 0.64 5.33 2.12 5.34 0.96 5.21 3.03 4.00 0.7

0 4.17 0.64 2.64 0.42 2.87 0.45 4.15 0.86 4.13 0.38 4.05 1.37 2.98 0.51-20 3.61 0.54 1.87 0.28 2.45 0.37 3.59 0.52 3.58 0.22 3.52 0.88 2.53 0.41

PA5083-11-7C 7/8 11.33 5 10840 4.38 0.57 3.21 0.43 3.10 0.41 4.32 1.51 4.32 0.69 4.22 2.16 3.23 0.46

0 3.37 0.41 1.88 0.24 2.32 0.30 3.35 0.61 3.34 0.27 3.27 0.98 2.41 0.33-20 2.92 0.35 1.33 0.16 1.98 0.24 2.90 0.57 2.89 0.16 2.84 0.63 2.04 0.27

PA5083-11-6C 3/4 11.33 5 11140 3.85 0.57 3.21 0.49 2.72 0.41 3.79 1.51 3.80 0.69 3.71 2.16 2.84 0.46

0 2.97 0.41 1.88 0.27 2.04 0.30 2.96 0.61 2.94 0.27 2.88 0.98 2.12 0.33-20 2.56 0.35 1.33 0.18 1.74 0.24 2.54 0.57 2.54 0.16 2.49 0.63 1.80 0.27

PA5083-15-7C 7/8 15.34 5 15640 6.20 0.88 5.17 0.75 4.39 0.64 6.11 2.12 6.12 0.96 5.97 3.03 4.58 0.7

0 4.78 0.64 3.03 0.42 3.29 0.45 4.76 0.86 4.73 0.38 4.64 1.37 3.41 0.51-20 4.13 0.54 2.15 0.28 2.80 0.37 4.10 0.52 4.09 0.22 4.02 0.88 2.90 0.41

PA5083-17-7C 7/8 17.25 5 17940 6.20 0.88 5.17 0.75 4.39 0.64 6.11 2.12 6.12 0.96 5.97 3.03 4.58 0.7

0 4.78 0.64 3.03 0.42 3.27 0.45 4.76 0.86 4.73 0.38 4.64 1.37 3.41 0.51-20 4.13 0.54 2.15 0.28 2.80 0.37 4.10 0.52 4.09 0.22 4.02 0.88 2.90 0.41

PA6125-15-9C 1-1/8 15.00 6 21140 9.00 3.00 8.83 1.97 6.10 1.90 8.87 3.45 8.88 1.57 8.67 4.93 7.30 3

0 5.60 2.00 5.62 0.82 3.70 1.20 5.57 1.40 5.55 0.62 5.44 2.23 4.50 2-20 4.30 0.80 4.31 0.50 2.80 0.05 4.27 0.85 4.26 0.36 4.19 1.43 3.40 0.8

PA6125-15-11C 1-3/8 15.25 6 21440 12.00 3.00 12.05 1.97 6.20 1.90 11.82 3.45 11.85 1.57 11.56 4.93 9.80 3

0 7.50 2.00 7.52 0.82 5.00 1.20 7.46 1.40 7.43 0.62 7.28 2.23 6.00 2-20 5.80 0.80 5.82 0.50 3.60 0.05 5.76 0.85 5.75 0.36 5.65 1.43 4.60 0.8

PA6125-18-9C 1-1/8 18.00 6 26440 8.80 3.00 8.84 1.97 6.00 1.90 8.67 3.45 8.69 1.57 8.48 4.93 7.20 3

0 5.50 2.00 5.52 0.82 3.70 1.20 5.47 1.4 5.45 0.62 5.34 2.23 4.40 2-20 4.30 0.80 4.31 0.50 2.80 0.05 4.27 0.85 4.26 0.36 4.19 1.43 3.40 0.8

PA6125-18-11C 1-3/8 18.00 6 26740 11.00 3.00 11.05 1.97 7.50 1.90 10.84 3.45 10.86 1.57 10.59 4.93 9.10 3

0 7.00 2.00 7.02 0.82 4.60 1.20 6.96 1.4 6.93 0.62 6.80 2.23 5.50 2-20 5.40 0.80 5.42 0.50 3.50 0.05 5.37 0.85 5.35 0.36 5.26 1.43 4.20 0.8

PA6125-20-11C 1-3/8 20.25 6 30240 11.00 3.00 11.05 1.97 7.50 1.90 10.84 3.45 10.86 1.57 10.59 4.93 9.10 3

0 7.00 2.00 7.02 0.82 4.60 1.20 6.96 1.4 6.93 0.62 6.80 2.23 5.50 2-20 5.40 0.80 5.42 0.50 3.50 0.05 5.37 0.85 5.35 0.36 5.26 1.43 4.20 0.8

P/N STEEL SUCTION LINE ACCUMULATORS089036-01 PA3060-10-4 Suction Line Accumulator089115-01 PA3060-10-5 Suction Line Accumulator089116-01 PA3060-15-5 Suctioin Line Accumulator089117-01 PA3060-15-6 Suction Line Accumulator089122-01 PA4065-9-5C Suction Line Accumulator089123-01 PA4065-9-6C Suction Line Accumulator089119-01 PA5083-12-7C Suction Line Accumulator089118-01 PA5083-9-6C Suction Line Accumulator089103-01 PA5083-11-7C Suction Line Accumulator089104-01 PA5083-11-6C Suction Line Accumulator089102-01 PA5083-9-7C Suction Line Accumulator089120-01 PA5083-15-7C Suction LIne Accumulator089121-01 PA5083-17-7C Suction Line Accumulator089283-00 PA6125-15-9C Suction Line Accumulator089285-00 PA6125-15-11C Suction Line Accumulator089284-00 PA6125-18-9C Suction Line Accumulator089286-00 PA6125-20-11C Suction Line Accumulator089287-00 PA6125-22-11C Suction Line Accumulator

Page 5: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

728

LIQUID REFRIGERANT RECEIVERS

AC&R LIQUID REFRIGERANT RECEIVERSReceivers should be selected based on the operating charge for all system com-ponents, including the liquid lines. It is usual to add a small percentage to cover the refrigerant in long runs of suction and discharge lines, etc. It is essential that the maximum operating charge be determined, e.g., winter charge in air cooled condenser having flooded head pressure control, this being much greater than the normal summer charge.

S-8060 SERIES VERTICAL RECEIVERS

Maximum WP 450 PS *All Pump Down Capacities are calculated @ 90% of receiver volume @ 90° F.

PARTNUMBER

*PUMP DOWNCAPACITY (lbs)

DIMENSIONS (in.) CONNECTIONSWT.

R-34a R-22R404A/R-507

Dia.A

B C D INLET OUTLET

S-8060 þþ2.4 þþ2.4 þþ2.0 3.00 10 7 7

1/4 FLARE 1/4 FLARE

2S-8061 þþ2.4 þþ2.4 þþ2.1 3.50 7.5 5 5 2S-8062 þþ3.3 þþ3.3 þþ2.8 3.50

107.63 7.63 3

S-8063 þþ4.3 þþ4.2 þþ3.7 4.00 7.25 7.25 4S-8064 þþ6.7 þþ6.6 þþ5.7 5.00 6.75 6.75 6S-8065 11.6 11.5 10.0

6.00

12 8 8 3/8 FLARE 3/8 FLARE 10S-8066 17.6 17.3 15.0 18 15 15 3/8 FLARE 1/2 FLARE 16S-8067 23.5 23.2 20.1 24 21.25 14.88 1/2 FLARE 1/2 FLARE 21S-8068 29.4 29.1 25.2 30 27.25 14.88 5/8 FLARE 5/8 FLARE 26

S-8600 SERIES HORIZONTAL RECEIVERS S-8600V SERIES HORIZONTAL RECEIVERS w/BRACKETS & VALVES

S-8600 SERIES HORIZONTAL RECEIVERS

S-8600V SERIES HORIZONTAL RECEIVERS WITH BRACKETS & VALVES

PARTNUMBER

*PUMP DOWN CAPACITY (lbs) DIMENSIONS (in.) INLET SHIP WEIGHT

(lbs)R-134a R-22R-404A/R-507

DIA.A

B C INLET OUTLET FPT

S-8600 18.8 18.6 16.25.00

283.00 5/8 ODS 5/8 ODS 3/8

19S-8610 24.3 24.0 20.9 36 25S-8620 29.2 28.8 25.0

6.0030

3.63 5/8 ODS 5/8 ODS 3/824

S-8630 35.0 34.6 30.1 36 28

PARTNUMBER

*PUMP DOWN CAPACITY (lbs) DIMENSIONS (in.) CONNECTIONS SHIP WEIGHT

(lbs)R-134a R-22R-404A/R-507

DIA.A

B C D E F G INLET OUTLET FPT

S-8600V 18.8 18.6 16.2 5.00 28 3.00 14 5.50 .44 7.00 1/2 ODS 1/2 ODS 3/8 19S-8630V 35.0 34.6 30.1 6.00 36 3.63 18 5.50 .44 7.00 1/2 ODS 1/2 ODS 3/8 28

*Pump Down Capacities are calculated @ 90% of receiver volume @ 90° F.

P1149

MAXIMUM WP 450 PSI

P1150

Page 6: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

729

LIQUID REFRIGERANT RECEIVER ACCESSORIES

AC&R RECEIVER ACCESSORIES

ROTO-LOC/ODS ADAPTERS

PARTNUMBER

THREAD ODS

2-009-037 1″ - 14 5/83-009-308 1-1/4″ - 12 7/82-009-046 1-3/4″ - 12 1-3/8

ROTO-LOC VALVES

PARTNUMBER

THREAD ODS

3-030-140 1″ - 14 1/23-030-141 1-1/4″ - 12 7/83-030-142 1-1/4″ - 12 1-1/83-030-143 1-3/4″ - 12 1-3/83-030-150 1″ - 14 5/8

BRACKET KITS

PARTNUMBER

RECEIVER DIA.

3-019-908 8-5/83-019-910 10-3/43-019-912 12-3/4

LIQUID LEVEL GAUGES

PARTNUMBER

RECEIVER DIA.

S-9450 8-5/8S-9451 10-3/4S-9452 12-3/4S-9453 14S-9454 16S-9455 18S-9456 20

NOTE: Designed for horizontal mounting use only.

P1165

P1168

P1167

P1166

Page 7: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

730

OIL SEPARATORS

AC&R HELICAL OIL SEPARATORSHelical Oil Separators: A new twist from AC&R Components Inc., the leader in Oil Control Systems, puts oil separator efficiency at a new high. The helical oil separator features a centrifugal flow path achieving approximately 99% efficiency of oil separation with low pressure drop. Testing by an independent laboratory found that only .006% oil by volume was being discharged into the system after leaving a helical oil separator.

How the Helical Oil Separator functions: Upon separator entry, refrigerant gas containing oil in aerosol form, encounters the lead-ing edge of the helical flighting. The gas/oil mixture is centrifugally forced along the spiral path of the helix, causing heavier oil parti-cles to spin to the perimeter, where impingement with a screen layer occurs. The screen layer serves dual functions as an oil stripping and draining medium. Separated oil flows downward along the boundary of the shell through a baffle and into the oil collection area at the bottom of the separator. The specially engineered baffle isolates the oil collection area and eliminates oil

reentrainment by preventing turbulence. Virtually oil-free refriger-ant gas exits through a fitting just below the lower edge of the heli-cal flighting. A float activated oil return valve allows the captured oil to return to the crankcase or oil reservoir, thereby completing the oil circuit. Our Patented Mechanical Design offers high oil sep-aration efficiency, plus the following advantages not found in a Coalescing Oil Separator:

• Low pressure drop throughout the entire range of velocities found in a refrigeration system.

• No clogging elements because of too much oil in the system.

• No oil blow-out at start-up from oil left in a coalescing element.

Oil can be drained from the separator when necessary through a 1/8-in. NPT fitting at the bottom of the separator.

S-5108/S-5181 S-5202/S-5203/S-5204S-5290/S-5292S-5190/S-5192S-5182 THRU S-5188

P1151

S-5100’s - Connections are nickel plated steel.S-5200’s - Connections are copper plated steel.All the capacities shown are based on 100° F condensing. Minimum tonnage is 50% of rated capacity, oversizing is not acceptable.

PARTNUMBER

SIZECONN.

DIMENSIONS (in.)MAX. CAPACITY IN TONS OF REFRIGERATION AT

EVAPORATOR TEMPERATURE (nominal) MAXIMUMDISCHARGE

CFM

PRE-CHARGEDAMOUNT

(oz)R-134a R-22 R-404A/R-507

Dia A

B C D +40°F +20°F +40°F +20°F +40°F +20°F

S-5180 1/4 ODS 2.50 6.38 1.75 .44 2.12 .50 .75 .75 1.00 .75 1.00 .75 4S-5181 3/8 ODS 2.50 7.50 1.75 .50 3.25 .75 1.00 1.00 1.50 1.00 1.50 1.00 4S-5182 1/2 ODS 4 13 2.75 2.44 1.00 1.50 1.50 2.00 1.50 2.00 1.50 25S-5185 5/8 ODS 4 15 2.75 2.50 3.00 4.00 4.50 5.50 4.00 5.50 4.00 25S-5187 7/8 ODS 4 17 3 2.94 4.50 5.50 7.00 8.00 6.50 8.50 6.00 25S-5188 1-1/8 ODS 4 19 3 3.06 6.00 7.50 9.00 10.50 8.50 11.00 8.00 25S-5190 1-3/8 ODS 6 15 4.25 3.69 8.00 10.00 13.00 14.00 12.00 15.00 11.00 40S-5192 1-5/8 ODS 6 17 4.25 3.95 11.00 13.00 16.00 18.00 15.00 19.00 14.00 40S-5194 2-1/8 ODS 6 17 4.38 4.19 18.00 21.00 25.00 30.00 24.00 31.00 22.00 40S-5290 1-3/8 ODS 6 15 4.25 3.69 8.00 10.00 13.00 14.00 12.00 15.00 11.00 25S-5292 1-5/8 ODS 6 17 4.25 3.95 11.00 13.00 16.00 18.00 15.00 19.00 14.00 25S-5294 2-1/8 ODS 6 17 4.38 4.19 18.00 21.00 25.00 30.00 24.00 31.00 22.00 25S-5202 2-1/8 ODS 8 24 5.38 5.06 22.00 27.00 35.00 39.00 31.00 41.00 29.00 25S-5203 2-5/8 ODS 10 27 6.50 5.63 46.00 56.00 71.00 80.00 64.00 83.00 60.00 25S-5204 3-1/8 ODS 12 30 7.75 6.45 72.00 88.00 112.00 127.00 100.00 131.00 94.00 25

Page 8: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

731

OIL SEPARATORS

AC&R CONVENTIONAL OIL SEPARATORS

DISCHARGE CFM CHARTS

DCFM CHART - R-22

Connections are nickel plated steel. Oil flow rate @ 175 PSI differential .80 gal/min. 3/8″ flare oil return connection

All other capacities shown are based on 100° F condensing. Minimum tonnage is 50% of rated capacity, oversizing is not acceptable.

PARTNUMBER

SIZECONN.

DIMENSIONS(in.)

CAPACITY IN TONS OF REFRIGERATION AT EVAPORATOR TEMPERATURE (nominal) MAXIMUM

DISCHARGE CFM

PRE-CHARGEDAMOUNT

(oz)

R-134a R-22 R-404A/R-507

Dia A B –40°F +40°F –40°F +40°F –40°F +40°F

S-5582 1/2 ODS

4

10.25 1.00 1.50 1.50 2.00 1.50 2.00 1.50

12S-5585 5/8 ODS 14.25 3.00 4.00 4.50 5.50 4.00 5.50 4.00S-5587 7/8 ODS 17.75 4.50 5.50 7.00 8.00 6.50 8.50 6.50S-5588 1-1/8 ODS 21.00 6.00 7.50 9.00 10.50 8.50 11.00 8.00S-5590 1-3/8 ODS 21.25 8.00 9.50 11.50 13.50 10.50 14.00 10.00

S-5500’s

P1152

DCFM CHART - R-404a/R/507

HOW TO CALCULATE DISCHARGE CFM (DCFM)

Example: 50 ton R-22 system

-25° F Evaporator Temp.

115° F Condensing Temp.

From the R-22 DCFM Chart, follow the -25° F evaporator tempera-ture line to the intersection of the 115° F condensing temperature line. Extend a line horizontally from this point to the DCFM/tonfactor. Multiply the DCFM/ton factor by the total tonnage to calcu-late the total DCFM.

DCFM CHART - R-134a

Example:

.72 DCFM x 50 ton = 36.0 DCFM

Oil Separator Selected: S-5203ton

P1153 P1155

P1154

How the Conventional Oil Separator functions: Refrigerant gas from the compressor containing oil in aerosol form enters the sep-arator and passes through the inlet baffling. As it passes through the inlet screen, the fine particles collide with one another and form heavier particles that impinge on the surface of the shell wall. The gas then passes through the outlet screen where there is a

final separation. The oil free gas escapes through the outlet fitting and goes to the condenser. The separated oil drips to the bottom of the separator where a float operated needle valve returns the oil to the crankcase or oil reservoir in the same way as the Helical Oil Separator.

Page 9: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

732

OIL SEPARATORS

PARKER POS-321 OIL SEPARATORThe Parker oil separator removes oil from system refrigerant by means of a highly efficient coalescing filter. The filter is 98.5% efficient, filtering oil and particles down to 1/10 of a micron while leaving a trace amount of oil necessary for adequate system lubrication. The separator is ideal for recovery and reclaim operations.

Key Features and Benefits

• 3.6 ounces/108 ml capacity

• standard 1/8″ npt connection size.

• 1/4″ or 3/8″ flare or sweat connections optional

• for use with all CFC, HCFC and HFC refrigerants

• design pressure of 500 psig/3550 kPa/35.5 bar.

• U.L. listed SA5915.

Oil ReservoirsParker oil reservoirs are holding vessels for stand-by oil necessary for the operation of a system.

Key Features and Benefits

• Two or three sight glass ports for oil level monitoring.

• 3/8″ flare valve on the top and bottom shipped separately to be adjusted per customer requirements. Allows isolation of the reservoir for addition or removal of oil from the tank.

• Vent port for connection to the suction line to prevent pressure build up in the reservoir.

• Available with mounting studs and brackets.

• Other sizes available: 1/4 and 1/2 tons.

A capacity is the capacity to the first sight glass.B capacity is the capacity between the glasses.

PS-033 Oil StrainerParker oil strainers removes contaminant from the oil line by means of a 200 mesh filter screen.

Key Features and Benefits

• Filtration area = 7.0 square inches.

• 3/8″ SAE steel male flare connections.

• U.L. listed.

• Design pressure of 500 psig (3550 kPa).

PARTNO.

PARKERPART NO.

TOTAL CAPACITY

IN GALLONS

A CAPACITY

(gal.)

B CAPACITY

(gal.)

LENGTH(in.)

POR-2 089351-00 2 3/4 3/4 18POR-3 089379-00 3 3/4 3/4 23POR-4 089350-00 3 3/4 1-1/2 36

P4098

P4099

P4100

Page 10: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

733

OIL SEPARATORS ACCESSORIES

AC&R HEAT ELEMENTS

Heat elements add heat to oil separators located in low ambient temperatures or in low temperature applications, to prevent con-densation of refrigerant vapor in the vessel.

Heat elements add heat to oil separators to prevent migration of refrigerant to the vessel during both the running and the off cycles of the compressor. 4-in. diameter heat band can also be installed on oil sump of S-1900 Series oil separators.

Heat elements add heat to suction line accumulators to keep the oil warm permitting oil return to the compressor on low tempera-ture application.

DIAMETER (in.)

WATTAGE VOLTS P/N

4 25W 110V S-91014 25W 220V S-91116 50W 220V S-9112

P380

Page 11: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

734

OIL LEVEL REGULATORS

AC&R OIL LEVEL REGULATORSThe oil level regulator controls the oil level in the compressor crankcase with a float operated valve.

Oil level regulators are designed to attach directly to the sight glass housing on compressor crankcases. Adapter kits are avail-able for compressors that have a different sight glass configura-tion. The sight glass from the compressor or supplied with an adapter kit, bolts to the second regulator flange for visual obser-vation of the oil level.

The oil supply line from the reservoir is connected to the 3/8-in. flare fitting on top of the regulator.

These regulators feature a 3/8-in. flare equalization connection on the side of the regulator that allows the crankcases to be

interconnected. This maintains the same pressure in all of the crankcases including any compressor that is running. This pre-vents running compressor(s) from siphoning the oil out of the idle compressor(s).

The 3/8-in. flare equalization connection is at the half sight glass level. It helps prevent over filling of the regulators caused by oil returning down the suction line to an idle compressor. If a regula-tor fills up to a half sight glass, the oil will be picked up by the equalization connection and sent to the running compressor crankcase.

S-9010 FIXED LEVEL REGULATORThe S-9010 regulator maintains the oil level in the compressor crankcase at 3/8-in. sight glass. The S-9010 maintains the level at any pressure differential between 5 and 30 psi.The S-9010 oil level regulator is designed to bolt directly to the 3 bolt sight glass hous-ing found on many compressor crankcases.Do not use on Satellite Compressor.

P/N: S-9010

S-9090 ADJUSTABLE REGULATOROne oil level regulator for all applicationsThe S-9090 regulator allows the oil level in the compressor crankcase to be maintained at any level between 1/4 and 1/2 sight glass.The S-9090 maintains the level at any pressure differential between 5 and 90 psi. If the oil level in the crankcase is too high or too low, the level can be adjusted by turning the adjustment screw on top of the regulator. This can be done while the system is in operation. Our exclusive design eliminates the need of shutting down the system and disconnecting the oil feed lines in order to adjust the regulator.

P/N: S-9090

S-9130 ADJUSTABLE REGULATOR

The S-9130 regulator allows the oil level in the compressor crankcase to be main-tained at any level between 1/4 and 1/2 sight glass.

The S-9130 maintains the level at any pressure differential between 5 and 90 psi. If the oil level in the crankcase is too high or too low, the level can be adjusted by turning the adjustment screw on top of the regulator. This can be done while the system is in operation. Our exclusive design eliminates the need of shutting down the system and disconnecting the oil feed lines in order to adjust the regulator.

P/N: S-9130

P1156

P1157

P1158

P4405

SIGHT GLASS INSTALLATION TOOLUsed on all 06D, 06CC, and 06E models.

P/N: T133300B-1

06D BARREL NUT SOCKETSpecial socket to remove and torque 06D terminal nuts. Used on all 06D models.

P/N: P920-0009

Page 12: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

735

OIL CONTROL SYSTEMS

AC & R OIL RESERVOIRHOW IT WORKS

A reserve of oil is necessary for the operation of the system. The oil reservoir is the holding vessel for this stand-by oil. It has two sight glass ports on the shell to observe the oil level inside the vessel. Oil is fed into the oil reservoir by the oil separator.

The valve on the top of the oil reservoir automatically receives oil from the oil separator (open position). To add oil to the oil reservoir manually, close the valve and fill the oil reservoir through the 1/4-in. flare connection on the side of the valve. Open valve after filling.

The valve on the bottom of the oil reservoir is the distribution valve to the oil level regulators (open position). To remove oil from the oil reservoir, close the valve and use the 1/4-in. flare connection on the side of the valve to drain the oil out. Open valve after draining.

HOW TO INSTALL

Whenever possible, the oil reservoir should be mounted above the oil level regulators for gravity feed of oil. It can be realized that high pressure from the high side returns with the oil from the oil separator to the reservoir. In a period of time, enough pressure could build up to adversely affect the float and needle assembly in the oil level regulator. For protection, a vent line is installed from the top of the oil reservoir (a fitting is provided) back to the low pressure suction line. This line permits the pressure in the oil res-ervoir to be approximately the same as the pressure in the suction line and the crankcases of the compressors. Oil in the oil reservoir feeds down through the 3/8-in. and 1/4-in. OD tubing and keeps the oil level regulators supplied with oil.

NEW SYSTEM STARTUP

On system startup of a new parallel system, oil should be added to the oil reservoir to the upper sight glass port, NOT ABOVE IT It is commonly accepted that in a new refrigeration system, some oil will be absorbed by the refrigerant as the system becomes bal-anced out. After two hours of operation, the oil reservoir, if neces-sary should again be filled to the upper sight glass and also after two days, by which time the entire refrigeration system should be balanced out. Then the oil reservoir must be observed on each service call. No oil should be added again until the oil level falls below the lower sight glass port.

EXISTING SYSTEM STARTUP

When installing this oil control system, on a parallel system that has been in operation for some time, the amount of oil should be added cautiously. With the efficiency of the new oil separator, the oil return could likely be sufficient to fill the oil reservoir. So fill the oil reservoir to the lower sight glass port only. Observe for one day. After the second day, if the oil level has not risen to the upper sight glass, add oil. If the oil level has risen above the upper sight glass port, remove the excess oil from the oil reservoir.

CAPACITY (IN GALLONS)DIMENSIONS

(in.)P/N

A B C D4 3 3/4 37.94 S-91082 3/4 3/4 19.94 S-9109

P378

Page 13: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

736

OIL CONTROL SYSTEMS

OMA TRAXOIL

DIMENSIONAL DATA

DiaData

TraxOil unit must be mounted horizontally for correct operation.

APPLICATION

• Compressor crankcase oil level protective control.• Warranty requirement for Copeland ZF, ZB and ZS

refrigeration scroll compressors.• Recommended for Copeland, Carlyle, Bitzer and

other semi-hermetic compressors.

FEATURES

• Self contained unit with oil level sensor and integral solenoid to manage oil level supply.

• Hall-effect sensor for precise measurement of oil level.

• Alarm and status indication by LEDs.• SPDT output contact for compressor shutdown or

alarming.• Easy installation by sightglass replacement.• Adapters suitable for various types of compressors

including conventional and scroll compressors.• Signal generated by gravity based float - not prone

to errors from foaming like optical sensors.• Debris retention magnet for reliable operation.• UL recognized.

SPECIFICATIONS

Maximum Working Pressure: 500 psigSolenoid MOPD: 300 psiSupply Voltage 24 VAC, 50/60 HzSolenoid Coil: Alco AMF or ASC2

24 VAC, 50/60 HzCurrent Consumption: 0.6ATime Delay for Low Level Signalling: 10 secondsTime Delay After Setpoint Recovery 10 secondsAlarm Delay Time

(including alarm contact): 120 secondsAlarm Switch: SPDTAlarm Contact Rating: 1.2A@ 125 VAC 50/60

0.6A@ 250 VAC 50/60Refrigerant Compatibility: HFC, HCFC, CFC(not for use with flammablerefrigerants or ammonia)Refrigerant Temp.: 180° F MaximumStorage and Transport Temp.: 120° F MaximumAmbient Temp. (Housing): 120° F MaximumOil Supply Fitting: 1/4″ Male SAE

NOMENCLATUREExample: OMAJB1S/T ASC2 24 50/60

OMA JB 1 S/T ASC2 24 50/60

Alco Oil Management Control

JB - Junction BoxMA - Stress Relief Connector

1 - TraxOil2 - Oil Watch

Oil InletFTG 1/4″ SAES/T - StraightANG - Angle

Solenoid Coil ModelNumber, Voltage, Frequency (Included)

ORDERING INFORMATION FOR OMA TRAXOIL

Standard Product Offering.*Product Code Number.†7-1/2 - 15 HP.

**6 HP and smaller. NOTE: An adapter kit is required for new installations.

PCN* DESCRIPTION

TRAXOIL

064340 OMA-JB1 S/T ASC 2 24/50-60 - STD

064341 OMA-MO1 ANG ASC 2 24/50-60 - Hussmann Protocol

ADAPTERS (TO ATTACH TRAXOIL TO COMPRESSORFOR NEW INSTALLATIONS ONLY)

063678 OMA-ACB ADAPTER (Copeland Scroll ZF, ZS ZB)† - KS30349

063520 OMA-ACA ADAPTER (Copeland Scroll ZF, ZS, ZB)** - KS30350

063521 OMA-AUA ADAPTER (Semi Hermetic Universal) - KS30348

SERVICE PARTS

048638 Inlet Flare Screen - X11176-7

064811 Sight Glass and O-Ring - KS30367

064812 O-Rings (3 pieces) - KS30368

Page 14: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

737

OIL CONTROL SYSTEMS

OMA TRAXOIL

OMA OIL WATCHThe Alco OMA-JB2 Oil Watch is designed to monitor a compressor’s oil level and signal an alarm if the oillevel is not adequate. The OMA-JB2 can be used to shut-down the compressor in addition to its alarmcapability. For use on single compressor applications without oil separators.

FEATURES

• Self contained unit.

• SPDT alarm output.

• Installs directly over compressor sight glass.

• Junction box standard.

• UL recognized.

ORDERING INFORMATION FOR OMA OIL WATCH

PCN DESCRIPTION063841 OMA-JB2

oma-aua

oma-aca

oma-acb

OMA - AUA - 063521 Includes: (3) O-Rings, 3 Bolts, 3 Washers and 3 Nuts• Flange Adapter 3/4″• 3 holes (.26″)• 4 holes (.26″)• O-ring seal (1.3″ x 1″)

OMA - ACA - 063520 Includes:Sight Glass, (2) O-Rings and 3 Bolts• Screw Adapter 3/4″-14 NPTF• Thread NPTF male• Teflon seal• Additional flange ring for adapter/base unit

connection (included)

OMA - ACB - 063678 Includes:Sight Glass, (2) O-Rings and 3 Bolts• Screw Adapter 1-1/8″-12 UNF• Thread UNF• O-ring seal (.86″ x 1″)• Additional flange ring for adapter/base

unit connection (included)

NOTE: Sight Glass PCN 064811 required for Bitzer 4-holepattern compressor.

Semi-HermeticUniversal Adapter

Semi-HermeticUniversal Adapter

Semi-HermeticUniversal AdapterCopeland Scroll

ZF, ZS, ZB (2 - 6 Hp)

Semi-HermeticUniversal AdapterCopeland Scroll

ZF, ZS, ZB (7-1/2 - 15 Hp)

Page 15: ACCUMULATORS - dms.hvacpartners.comdms.hvacpartners.com/docs/1006/Public/04/ACCUMU-RECEIV-SEPS-2… · accumulator should have an adequate liquid holding capacity, which can vary

738

OIL LEVEL REGULATOR ADAPTER KIT/CONTROL COMP.

AC&R OIL LEVEL REGULATOR ADAPTER KITSIGHT GLASS

OIL LEVEL

COMPRESSOR MANUFACTURER

SIGHT GLASS CONFIGURATION

ADAPTER KIT PART NUMBER

1/4 Copeland (older model) 4 Bolt 2-1/8 B.C. 3-033-2071/2 Vilter 1-1/2 NPT Thread 3-033-2081/2 Vilter 2″ NPT Thread 3-033-2091/4 Copeland (model “8R”) 3 Bolt 1-7/8 B.C. 3-033-2121/2 Prestcold (C,E,R,L, & LG) 42mm Thread 3-033-2181/2 Trane (model “K”) 3/4 NPT Thread 3-033-2181/2 Schancke-Grasso 1-1/4 NPT Thread 3-033-2191/2 Grasso Thermtrol 1″ NPT Thread 3-033-2281/2 Bristol 15/16 - 20 Thread 3-033-2421/2 Bock 4 Bolt 1-31/32 B.C. 3-033-2441/2 Maneurop 1-1/8 - 18 thread 3-033-2461/2 Bitzer 4 Bolt 2″ B.C. 3-033-253* KIT 3-033-201 INCLUDED WITH ALL OIL LEVEL REGULATORS

NOTE: For compressors not listed above, a universal adapter kit is available Part No. 3-033-217. This adapter kit has a 3-hole flange to mount to the regulator. The compressor end of the kit is a 1-1/4″ OD steel tube. The existing compressor sight glass gland or flange must be bored out or bushed down to accept the 1-1/4″ tube. The tube is then brazed or welded to the reworked gland or flange and installed on the compressor. A sight glass, seals, & hardware are included in the kit.

SIGHT GLASS

OIL LEVEL

COMPRESSOR MANUFACTURER

SIGHT GLASS CONFIGURATION

ADAPTER KIT PART NUMBER

1/2 Dunham-Bush Big 4 3 Bolt 1-7/8 B.C. 3-033-201*1/2 Trane 3 Bolt 1-7/8 B.C. 3-033-201*1/2 York 3 Bolt 1-7/8 B.C. 3-033-201*1/4 Carrier (models EA & ER) 3 Bolt 1-7/8 B.C. 3-033-201*1/4 Copeland (over 5 tons) 3 Bolt 1-7/8 B.C. 3-033-201*1/2 Copeland (under 5 tons) 1-1/8 - 12 Thread 3-033-2021/2 Prestcold (model “K”) 1-1/8 - 12 Thread 3-033-2021/2 Dunham-Bush (model “D”) 4 Bolt 2-1/8 B.C. 3-033-2031/4 Carrier (DA,DR,5F,5H & 06D) 1-1/2 - 18 Thread 3-033-2041/2 Schnacke-Grasso 2” x 16 Thread 3-033-2051/2 Trane 5 Bolt 2-1/2 B.C. 3-033-206

AC&R OIL LEVEL CONTROL COMPONENTSPRESSURE VALVE

PART NUMBER

PRESSURE SETTING

SIZE CONNECTION

S-9104 5 lbs3/8″ Female x

3/8″ Male Flare

S-9104H 20 lbs3/8″ Female x

3/8″ Male Flare

STRAINER

PART NUMBER

CONNECTION SIZE.

SCREENDATA

S-9105 3/8″ Flare100 Meshx 11 sq. in.

SHUT-OFF BRASS VALVES

PART NUMBER

A B TYPE

S-9106A 3/8″ ODS 3/8″ Fem. Flare VerticalS-9106E 1/4″ Flare 1/4″ Fem. Flare VerticalS-9106H 3/8″ Flare 3/8″ Fem. Flare VerticalS-9106V 3/8″ Flare 3/8″ Fem. Flare Horizontal

EQUALIZATION ADAPTER KIT 3-033-226

B

AA

INLETINLET

(SWIVELCONNECTION)

B (SWIVELCONNECTION)

Horizontal TypeVertical Type

2.47"

5"

3/8 ODS connections available by ordering with an “X” suffix (i.e., S-9105X)

1/4" FLARE

3.25"

3 BOLT1 7/8" B.C.

P1160

P1161P1159

P1162