3/28/2016 According to the IEC 60909 Open Electrical http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 1/14 According to the IEC 60909 From Open Electrical Contents 1 Introduction 1.1 Why do the calculation? 1.2 When to do the calculation? 2 Calculation Methodology 2.1 Step 1: Construct the System Model and Collect Equipment Parameters 2.2 Step 2: Calculate Equipment Short Circuit Impedances 2.2.1 Network Feeders 2.2.2 Synchronous Generators and Motors 2.2.3 Transformers 2.2.4 Cables 2.2.5 Asynchronous Motors 2.2.6 Fault Limiting Reactors 2.2.7 Static Converters 2.2.8 Other Equipment 2.3 Step 3: Referring Impedances 2.4 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location 2.5 Step 5: Calculate Balanced ThreePhase Short Circuit Currents 2.5.1 Initial Short Circuit Current 2.5.2 Peak Short Circuit Current 2.5.3 Symmetrical Breaking Current 2.5.4 DC Short Circuit Component 2.6 Step 6: Calculate SinglePhase to Earth Short Circuit Currents 3 Worked Example 3.1 Step 1: Construct the System Model and Collect Equipment Parameters 3.2 Step 2: Calculate Equipment Short Circuit Impedances 3.3 Step 3: Referring Impedances 3.4 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location 3.5 Step 5: Calculate Balanced ThreePhase Short Circuit Currents 3.5.1 Initial Short Circuit Current 3.5.2 Peak Short Circuit Current 4 Computer Software 5 What Next? Introduction This article looks at the calculation of short circuit currents for bolted threephase and singlephase to earth faults in a power system. A short circuit in a power system can cause very high currents to flow to the fault

Upload: nilesh-mahajan

Post on 14-Jul-2016

119 views

Category:

Documents


29 download

DESCRIPTION

dadfaf

TRANSCRIPT

Page 1: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 1/14

According to the IEC 60909From Open Electrical

Contents1 Introduction

1.1 Why do the calculation?1.2 When to do the calculation?

2 Calculation Methodology2.1 Step 1: Construct the System Model and Collect Equipment Parameters2.2 Step 2: Calculate Equipment Short Circuit Impedances

2.2.1 Network Feeders2.2.2 Synchronous Generators and Motors2.2.3 Transformers2.2.4 Cables2.2.5 Asynchronous Motors2.2.6 Fault Limiting Reactors2.2.7 Static Converters2.2.8 Other Equipment

2.3 Step 3: Referring Impedances2.4 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location2.5 Step 5: Calculate Balanced Three­Phase Short Circuit Currents

2.5.1 Initial Short Circuit Current2.5.2 Peak Short Circuit Current2.5.3 Symmetrical Breaking Current2.5.4 DC Short Circuit Component

2.6 Step 6: Calculate Single­Phase to Earth Short Circuit Currents3 Worked Example

3.1 Step 1: Construct the System Model and Collect Equipment Parameters3.2 Step 2: Calculate Equipment Short Circuit Impedances3.3 Step 3: Referring Impedances3.4 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location3.5 Step 5: Calculate Balanced Three­Phase Short Circuit Currents

3.5.1 Initial Short Circuit Current3.5.2 Peak Short Circuit Current

4 Computer Software5 What Next?

Introduction

This article looks at the calculation of short circuit currents for bolted three­phase and single­phase to earthfaults in a power system. A short circuit in a power system can cause very high currents to flow to the fault

Page 2: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 2/14

Figure 1. Lightning arc

location. The magnitude of the short circuit currentdepends on the impedance of system under short circuitconditions. In this calculation, the short circuit current isestimated using the guidelines presented in IEC 60909.

Why do the calculation?

Calculating the prospective short circuit levels in apower system is important for a number of reasons,including:

To specify fault ratings for electricalequipment (e.g. short circuit withstandratings)To help identify potential problems andweaknesses in the system and assist insystem planningTo form the basis for protectioncoordination studies

When to do the calculation?

The calculation can be done after preliminary system design, with the following pre­requisite documentsand design tasks completed:

Key single line diagramsMajor electrical equipment sized (e.g. generators, transformers, etc)Electrical load scheduleCable sizing (not absolutely necessary, but would be useful)

Calculation Methodology

This calculation is based on IEC 60909­0 (2001, c2002) (https://webstore.iec.ch/publication/3886) , "Short­circuit currents in three­phase a.c. systems ­ Part 0: Calculation of currents" and uses the impedance method(as opposed to the per­unit method). In this method, it is assumed that all short circuits are of negligibleimpedance (i.e. no arc impedance is allowed for).

There are six general steps in the calculation:

Step 1: Construct the system model and collect the relevant equipment parametersStep 2: Calculate the short circuit impedances for all of the relevant equipmentStep 3: Refer all impedances to the reference voltageStep 4: Determine the Thévenin equivalent circuit at the fault locationStep 5: Calculate balanced three­phase short circuit currentsStep 6: Calculate single­phase to earth short circuit currents

Step 1: Construct the System Model and Collect Equipment Parameters

Page 3: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 3/14

The first step is to construct a model of the system single line diagram, and then collect the relevantequipment parameters. The model of the single line diagram should show all of the major system buses,generation or network connection, transformers, fault limiters (e.g. reactors), large cable interconnectionsand large rotating loads (e.g. synchronous and asynchronous motors).

The relevant equipment parameters to be collected are as follows:

Network feeders: fault capacity of the network (VA), X/R ratio of the networkSynchronous generators and motors: per­unit sub­transient reactance, rated generator capacity(VA), rated power factor (pu)Transformers: transformer impedance voltage (%), rated transformer capacity (VA), ratedcurrent (A), total copper loss (W)Cables: length of cable (m), resistance and reactance of cable ( )Asynchronous motors: full load current (A), locked rotor current (A), rated power (W), fullload power factor (pu), starting power factor (pu)Fault limiting reactors: reactor impedance voltage (%), rated current (A)

Step 2: Calculate Equipment Short Circuit Impedances

Using the collected parameters, each of the equipment item impedances can be calculated for later use inthe motor starting calculations.

Network Feeders

Given the approximate fault level of the network feeder at the connection point (or point of commoncoupling), the impedance, resistance and reactance of the network feeder is calculated as follows:

Where   is impedance of the network feeder (Ω)

 is resistance of the network feeder (Ω) is reactance of the network feeder (Ω) is the nominal voltage at the connection point (Vac) is the fault level of the network feeder (VA)

 is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV,1.1 for voltages >1kV)

 is X/R ratio of the network feeder (pu)

Page 4: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 4/14

Synchronous Generators and Motors

The sub­transient reactance and resistance of a synchronous generator or motor (with voltage regulation)can be estimated by the following:

Where   is the sub­transient reactance of the generator (Ω)

 is the resistance of the generator (Ω) is a voltage correction factor ­ see IEC 60909­0 Clause 3.6.1 for more details (pu) is the per­unit sub­transient reactance of the generator (pu)

 is the nominal generator voltage (Vac) is the nominal system voltage (Vac) is the rated generator capacity (VA)

 is the X/R ratio, typically 20 for   100MVA, 14.29 for   100MVA, and 6.67 for

all generators with nominal voltage   1kV is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV,

1.1 for voltages >1kV) is the power factor of the generator (pu)

For the negative sequence impedance, the quadrature axis sub­transient reactance   can be applied inthe above equation in place of the direct axis sub­transient reactance  .

The zero­sequence impedances need to be derived from manufacturer data, though the voltage correctionfactor   also applies for solid neutral earthing systems (refer to IEC 60909­0 Clause 3.6.1).

Transformers

The positive sequence impedance, resistance and reactance of two­winding distribution transformers can becalculated as follows:

Page 5: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 5/14

Where   is the positive sequence impedance of the transformer (Ω)

 is the resistance of the transformer (Ω) is the reactance of the transformer (Ω) is the impedance voltage of the transformer (pu) is the rated capacity of the transformer (VA) is the nominal voltage of the transformer at the high or low voltage side (Vac) is the rated current of the transformer at the high or low voltage side (I) is the total copper loss in the transformer windings (W)

For the calculation of impedances for three­winding transformers, refer to IEC 60909­0 Clause 3.3.2. Fornetwork transformers (those that connect two separate networks at different voltages), an impedancecorrection factor must be applied (see IEC 60909­0 Clause 3.3.3).

The negative sequence impedance is equal to positive sequence impedance calculated above. The zerosequence impedance needs to be derived from manufacturer data, but also depends on the windingconnections and fault path available for zero­sequence current flow (e.g. different neutral earthing systemswill affect zero­sequence impedance).

Cables

Cable impedances are usually quoted by manufacturers in terms of Ohms per km. These need to beconverted to Ohms based on the length of the cables:

Where   is the resistance of the cable {Ω)

 is the reactance of the cable {Ω) is the quoted resistance of the cable {Ω / km) is the quoted reactance of the cable {Ω / km) is the length of the cable {m)

The negative sequence impedance is equal to positive sequence impedance calculated above. The zerosequence impedance needs to be derived from manufacturer data. In the absence of manufacturer data, zerosequence impedances can be derived from positive sequence impedances via a multiplication factor (assuggested by SKM Systems Analysis Inc) for magnetic cables:

Asynchronous Motors

Page 6: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 6/14

An asynchronous motor's impedance, resistance and reactance is calculated as follows:

Where   is impedance of the motor (Ω)

 is resistance of the motor (Ω) is reactance of the motor (Ω)

 is ratio of the locked rotor to full load current is the motor locked rotor current (A)

 is the motor nominal voltage (Vac) is the motor rated power (W)

 is the motor full load power factor (pu) is the motor starting power factor (pu)

The negative sequence impedance is equal to positive sequence impedance calculated above. The zerosequence impedance needs to be derived from manufacturer data.

Fault Limiting Reactors

The impedance of fault limiting reactors is as follows (note that the resistance is neglected):

Where   is impedance of the reactor (Ω)

 is reactance of the reactor(Ω) is the impedance voltage of the reactor (pu) is the nominal voltage of the reactor (Vac) is the rated current of the reactor (A)

Positive, negative and zero sequence impedances are all equal (assuming geometric symmetry).

Static Converters

Static converters and converter­fed drivers (i.e. feeding rotating loads) should be considered for balancedthree­phase short circuits. Per IEC 60909­0 Clause 3.9, static converters contribute to the initial and peakshort circuit currents only, and contribute 3 times the rated current of the converter. An R/X ratio of 0.1should be used for the short circuit impedance.

Page 7: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 7/14

Other Equipment

Line capacitances, parallel admittances and non­rotating loads are generally neglected as per IEC 60909­0Clause 3.10. Effects from series capacitors can also be neglected if voltage­limiting devices are connectedin parallel.

Step 3: Referring Impedances

Where there are multiple voltage levels, the equipment impedances calculated earlier need to be convertedto a reference voltage (typically the voltage at the fault location) in order for them to be used in a singleequivalent circuit.

The winding ratio of a transformer can be calculated as follows:

Where   is the transformer winding ratio

 is the transformer nominal secondary voltage at the principal tap (Vac) is the transformer nominal primary voltage (Vac) is the specified tap setting (%)

Using the winding ratio, impedances (as well as resistances and reactances) can be referred to the primary(HV) side of the transformer by the following relation:

Where   is the impedance referred to the primary (HV) side (Ω)

 is the impedance at the secondary (LV) side (Ω) is the transformer winding ratio (pu)

Conversely, by re­arranging the equation above, impedances can be referred to the LV side:

Step 4: Determine Thévenin Equivalent Circuit at the Fault Location

The system model must first be simplified into an equivalent circuit as seen from the fault location,showing a voltage source and a set of complex impedances representing the power system equipment andload impedances (connected in series or parallel).

The next step is to simplify the circuit into a Thévenin equivalent circuit(http://en.wikipedia.org/wiki/Th%C3%A9venin%27s_theorem) , which is a circuit containing only avoltage source ( ) and an equivalent short circuit impedance ( ).

Page 8: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 8/14

Figure 2. Thévenin equivalent circuit

This can be done using the standard formulae for series andparallel impedances, keeping in mind that the rules ofcomplex arithmetic must be used throughout.

If unbalanced short circuits (e.g. single phase to earth fault)will be analysed, then a separate Thévenin equivalent circuitshould be constructed for each of the positive, negative andzero sequence networks (i.e. finding ( ,   and 

).

Step 5: Calculate Balanced Three­Phase ShortCircuit Currents

The positive sequence impedance calculated in Step 4represents the equivalent source impedance seen by a balanced three­phase short circuit at the faultlocation. Using this impedance, the following currents at different stages of the short circuit cycle can becomputed:

Initial Short Circuit Current

The initial symmetrical short circuit current is calculated from IEC 60909­0 Equation 29, as follows:

Where   is the initial symmetrical short circuit current (A)

 is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV,1.1 for voltages >1kV)

 is the nominal system voltage at the fault location (V) is the equivalent positive sequence short circuit impedance (Ω)

Peak Short Circuit Current

IEC 60909­0 Section 4.3 offers three methods for calculating peak short circuit currents, but for the sake ofsimplicity, we will only focus on the X/R ratio at the fault location method. Using the real (R) and reactive(X) components of the equivalent positive sequence impedance  , we can calculate the X/R ratio at thefault location, i.e.

The peak short circuit current is then calculated as follows:

 (for non­meshed networks)

Page 9: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 9/14

or

 (for meshed networks ­ see clause 4.3.12b)

Where   is the peak short circuit current (A)

 is the initial symmetrical short circuit current (A)

 is a constant factor, 

Symmetrical Breaking Current

The symmetrical breaking current is the short circuit current at the point of circuit breaker opening (usuallysomewhere between 20ms to 300ms). This is the current that the circuit breaker must be rated to interruptand is typically used for breaker sizing. IEC 60909­0 Equation 74 suggests that the symmetrical breakingcurrent for meshed networks can be conservatively estimated as follows:

Where   is the symmetrical breaking current (A)

 is the initial symmetrical short circuit current (A)

For close to generator faults, the symmetrical breaking current will be higher. More detailed calculationscan be made for increased accuracy in IEC 60909, but this is left to the reader to explore.

DC Short Circuit Component

The dc component of a short circuit can be calculated according to IEC 60909­0 Equation 64:

Where   is the dc component of the short circuit current (A)

 is the initial symmetrical short circuit current (A) is the nominal system frequency (Hz) is the time (s)

 is the X/R ratio ­ see more below

The X/R ratio is calculated as follows:

Where   and   are the reactance and resistance, respectively, of the equivalent source impedance atthe fault location (Ω)

Page 10: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 10/14

 is a factor to account for the equivalent frequency of the fault. Per IEC 60909­0 Section 4.4,

the following factors should be used based on the product of frequency and time (  ):

<1 0.27

<2.5 0.15

<5 0.092

<12.5 0.055

Step 6: Calculate Single­Phase to Earth Short Circuit Currents

For balanced short circuit calculations, the positive­sequence impedance is the only relevant impedance.However, for unbalanced short circuits (e.g. single phase to earth fault), symmetrical components come intoplay.

The initial short circuit current for a single phase to earth fault is as per IEC 60909­0 Equation 52:

Where   is the initial single phase to earth short circuit current (A)

 is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV,1.1 for voltages >1kV)

 is the nominal voltage at the fault location (Vac) is the equivalent positive sequence short circuit impedance (Ω) is the equivalent negative sequence short circuit impedance (Ω) is the equivalent zero sequence short circuit impedance (Ω)

Worked Example

In this example, short circuit currents will be calculated for a balanced three­phase fault at the main 11kVbus of a simple radial system. Note that the single phase to earth fault currents will not be calculated in thisexample.

Step 1: Construct the System Model and Collect Equipment Parameters

The system to be modelled is a simple radial network with two voltage levels (11kV and 415V), andsupplied by a single generator. The system model is shown in the figure to the right. The equipment andcable parameters were collected as follows:

Page 11: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 11/14

Figure 3. System model for short circuit example

Equipment Parameters

Generator G1

 = 24,150 kVA = 11,000 V = 0.255 pu = 0.85 pu

Generator CableC1

Length = 30mSize = 2 parallel circuitsof 3 x 1C x 500 mm2

(R = 0.0506 Ω\km, X = 0.0997Ω\km)

Motor M1

 = 500 kW = 11,000 V = 200.7 A

 = 6.5 pu = 0.85 pu = 0.30 pu

Motor Cable C2

Length = 150mSize = 3C+E 35 mm2

(R = 0.668 Ω\km, X = 0.115 Ω\km)

Transformer TX1

 = 2,500 kVA = 11,000 V = 415 V

 = 0.0625 pu = 19,000 W = 0%

Transformer CableC3

Length = 100mSize = 3C+E 95 mm2

(R = 0.247 Ω\km, X = 0.0993Ω\km)

Page 12: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 12/14

Motor M2

 = 90 kW = 415 V = 1,217.3 A

 = 7 pu = 0.8 pu = 0.30 pu

Motor M3

 = 150 kW = 415 V = 1,595.8 A

 = 6.5 pu = 0.85 pu = 0.30 pu

Step 2: Calculate Equipment Short Circuit Impedances

Using the patameters above and the equations outlined earlier in the methodology, the followingimpedances were calculated:

Equipment Resistance (Ω) Reactance (Ω)

Generator G1 0.08672 1.2390

Generator Cable C1 0.000759 0.001496

11kV Motor M1 9.4938 30.1885

Motor Cable C2 0.1002 0.01725

Transformer TX1 (Primary Side) 0.36784 3.0026

Transformer Cable C3 0.0247 0.00993

415V Motor M2 0.0656 0.2086

415V Motor M3 0.0450 0.1432

Step 3: Referring Impedances

We will model a fault on the main 11kV bus, so all impedances must be referred to 11kV. The two lowvoltage motors need to be referred to this reference voltage. Knowing that the transformer is set at principaltap, we can calculate the winding ratio and apply it to refer the 415V motors to the 11kV side:

Page 13: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 13/14

The 415V motor impedances referred to the 11kV side is therefore:

Equipment Resistance (Ω) Reactance (Ω)

415V Motor M2 46.0952 146.5735

415V Motor M3 31.6462 100.6284

Step 4: Determine Thévenin Equivalent Circuit at the Fault Location

Using standard network reduction techniques, the equivalent Thévenin circuit at the fault location (main11kV bus) can be derived. The equivalent source impedance is:

Step 5: Calculate Balanced Three­Phase Short Circuit Currents

Initial Short Circuit Current

The symmetrical initial short circuit current is:

 kA

Peak Short Circuit Current

The constant factor   at the fault location is:

Therefore as it is a simple radial system (non­meshed), the symmetrical peak short circuit current is:

 kA

Computer Software

Page 14: According to the IEC 60909 - Open Electrical

3/28/2016 According to the IEC 60909 ­ Open Electrical

http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 14/14

Short circuit calculations are a standard component of power systems analysis software (e.g. ETAP, PTW,DIgSILENT, etc) and the calculations are far easier to perform with software than by hand. Howevermanual calculations could be done as a form of verification to confirm that the software results arereasonable.

What Next?

The results from the short circuit calculations can be used to specify the fault ratings on electricalequipment (e.g. switchgear, protective devices, etc) and also for protection coordination studies.

Short Circuit Calculation