accessories - anixter – wire and cable, networking ... · pdf fileaccessories...

44
ACCESSORIES Introduction to Glands............................................................................. 12:2 I.P Ratings for Cable Glands.................................................................... 12:4 A1/A2 Brass Gland with Outer Seal........................................................ 12:6 CX Brass Gland with Outer Seal.............................................................. 12:7 CXT Brass Gland with Outer Seal .......................................................... 12:8 Ultech Nylon Gland................................................................................... 12:9 LSF Standard Cable Gand for Non Armoured Cable............................. 12:11 Technical Data........................................................................................... 12:12 Index EMC Nickel Plated Gland for Braid Screened Cable................... 12:13 CW Brass Gland with Outer Seal............................................................. 12:14 BW Brass Gland........................................................................................ 12:16 E1W Brass Gland with Inner & Outer Seal.............................................. 12:17 Low Smoke & Fume Gland Kits............................................................... 12:18 BW Brass Gland – LSF............................................................................. 12:19 CW Brass Gland with Outer LSF Seal..................................................... 12:20 Selecting Glands for Hazardous Areas................................................... 12:21 A2F Flameproof Gland with Outer Seal.................................................. 12:22 E1WF Flameproof Gland with Inner & Outer Seal.................................. 12:23 E1XF Flameproof Gland with Inner & Outer Seal................................... 12:24 “Excelplus” Deluge Proof Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................... 12:25 Universal Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................................................. 12:26 E2WF (RTLF) Flameproof Gland with Inner & Outer Seal..................... 12:27 Universal Explosion Proof Barrier Glands............................................. 12:28 Brass Earth Tags...................................................................................... 12:29 High Performance Sealing Washers....................................................... 12:30 Glavanised Serrated Washers................................................................. 12:30 Steel, Brass & Aluminium Locknuts....................................................... 12:31 PCP/PVC Shrouds........................................................................ ............ 12:32 Lugs........................................................................................................... 12:33 Telcleats - Black Polythene & Grey LSF................................................. 12:36 “PUJ” Straight Cable Joints..................................................................... 12:37 Claw & Two Bolts Cleats - Aluminium Alloy........................................... 12:38 Cable Tiles & Warning Tapes...................................................... .............12:39 11kV Indoor Termination Kits...................................................................12:40 3M Inline (Straight) Barrier Boot - MB63................................................. 12:42 3M Pre-Moulded Right Angle Barrier Boot..............................................12:43 Heat Shrinkable Tubing............................................................................ 12:44 CONTENTS

Upload: vuongquynh

Post on 30-Mar-2018

218 views

Category:

Documents


3 download

TRANSCRIPT

ACCESSORIES

Introduction to Glands............................................................................. 12:2I.P Ratings for Cable Glands....................................................................12:4A1/A2 Brass Gland with Outer Seal........................................................ 12:6CX Brass Gland with Outer Seal..............................................................12:7CXT Brass Gland with Outer Seal .......................................................... 12:8Ultech Nylon Gland................................................................................... 12:9LSF Standard Cable Gand for Non Armoured Cable............................. 12:11Technical Data........................................................................................... 12:12Index EMC Nickel Plated Gland for Braid Screened Cable................... 12:13CW Brass Gland with Outer Seal............................................................. 12:14BW Brass Gland........................................................................................ 12:16E1W Brass Gland with Inner & Outer Seal..............................................12:17Low Smoke & Fume Gland Kits............................................................... 12:18BW Brass Gland – LSF............................................................................. 12:19CW Brass Gland with Outer LSF Seal..................................................... 12:20Selecting Glands for Hazardous Areas................................................... 12:21A2F Flameproof Gland with Outer Seal.................................................. 12:22E1WF Flameproof Gland with Inner & Outer Seal.................................. 12:23E1XF Flameproof Gland with Inner & Outer Seal................................... 12:24“Excelplus” Deluge Proof Flameproof & Increased SafetyGland with Inner & Outer Seals............................................................... 12:25Universal Flameproof & Increased Safety Gland with Inner& Outer Seals.............................................................................................12:26E2WF (RTLF) Flameproof Gland with Inner & Outer Seal..................... 12:27Universal Explosion Proof Barrier Glands............................................. 12:28Brass Earth Tags...................................................................................... 12:29High Performance Sealing Washers....................................................... 12:30Glavanised Serrated Washers................................................................. 12:30Steel, Brass & Aluminium Locknuts........................................... ............ 12:31PCP/PVC Shrouds........................................................................ ............ 12:32Lugs........................................................................................................... 12:33Telcleats - Black Polythene & Grey LSF................................................. 12:36“PUJ” Straight Cable Joints.....................................................................12:37Claw & Two Bolts Cleats - Aluminium Alloy...........................................12:38Cable Tiles & Warning Tapes...................................................... .............12:3911kV Indoor Termination Kits...................................................................12:403M Inline (Straight) Barrier Boot - MB63................................................. 12:423M Pre-Moulded Right Angle Barrier Boot..............................................12:43Heat Shrinkable Tubing............................................................................ 12:44

CONTENTS

12:2 ®

12

Glands

Cable glands are designed to provide some or all of the following functions in a cabling system:

• Mechanical connection: Locate and anchor cable.

• Earth continuity: Armour termination.

• Ingress Protection: Protect against dust and liquids.

• Hazardous area: Flameproof protection.

The design of cable glands are covered by BS6121, which covers size, finish, materials,performance, etc. The gland designs are basically a combination of compatibility with cable andinstallation requirements.

GLAND TYPES

There are several distinct gland types covered in BS6121 Part 1;

A Type

B Type

C Type

D1 Type

E1 Type

D2 Type

E2 Type

Suffixes are used to identify the type of armour on a cable:

W = single wire armour

X = wire braid armour

Y = aluminium wire armour

Z = steel tape armoured

Hence, CW would be a single wire armour, whereas CX would be for a braid armour. The onlydifference is in the armour lock which caters for the physical size of the armour.

ACCESSORIES

12

ACCESSORIES

12:3®

Gland Type Application/Use

A1/A2 Indoor/outdoor brass gland for use with unarmoured cable.

BW Indoor, low-cost, two-part brass gland for use with single wire armoured cable.

CW Indoor/outdoor brass glands for use with single wire armoured cable.Provides seal on outer sheath of cable and separate armour locking ring.

NB: Aluminium gland available for aluminium wire armoured cable.

CX Indoor/outdoor brass gland for use with braid armoured cables. Providesseal on outer sheath of cable and separate armour locking ring.

E1W Indoor/outdoor brass gland for use with single wire armour cable. Providesseal on inner and outer sheaths of cable, and has separate armour locking ring.

LSF Glands

BW Indoor, low cost, two-part brass gland for use with LSF single wirearmoured cables.

CW Indoor/outdoor brass gland for use with LSF single wire armoured cables.Provides LSF seal onto outer sheath of cable and separate armour locking ring.

Glands for Hazardous Areas

A2F Indoor/outdoor brass gland for use with unarmoured cables. For use withflameproof or increased safety equipment (E.Exd or E.Exe)

E1WF Indoor/outdoor brass gland for use with single wire armoured cable.Provides seal on inner and outer sheaths of cable, and has separate lockingring. For use with flameproof or increased safety equipment (E.Exd or E.Exe)

E1XF Indoor/outdoor brass gland for use with braid armoured cable. Providesseal on inner and outer sheaths of cable, and has separate armour lockingring. For use with flameproof or increased safety equipment (E.Exd or E.Exe).

E2WF Indoor/outdoor brass gland for use with single wire armoured and leadsheathed cables (eg. EEMUA types, BS5308 PT1/Type 3). Provides sealonto outer sheath of cable. Inner seal grips and provides earth continuity tolead sheath. Design has separate armour locking ring. For use withflameproof or increased safety equipment (E.Exd or E.Exe).

BARR-X Indoor/outdoor brass barrier gland for use with a braid armoured cable.Provides seal on outer sheath of cable, and solid setting compoundsqueezed into the interstices of cable when installed to prevent escape ofgases through centre of cable. For use with explosion proof equipment.

12:4 ®

12

I.P Ratings for Cable Glands

I.P. (Ingress Protection) Ratings detail the degree of protection against solidbodies and liquids, and is tested against IEC 144.

Generally any seal has a rating of IP66.

However, since they are tested in isolation, when they are in conjunction with apiece of equipment this needs to be taken into consideration.

Generally the following can be taken:-

1. Gland used in Plain Entry with Backnut - IP54.

2. Gland used in Plain Entry with sealing washer between gland and equipmentinterface - IP66.

3. Gland used in Tapped Entry - IP65.

4. These can be uprated by the use of Sealing washers and Thread Sealants.

5. Special designs of Gland are available which can achieve an IP Rating ofIP68. (NB. Interface with equipment then becomes critical.)

ACCESSORIES

12

12:5®

Degree of Protection IEC 144 I.P. RatingsFirst ProtectionDigit (Against solid bodies)

0 No protection

1 Protected against solid bodies larger than 50mm, eg, accidentalcontact with hand.

2 Protected against solid bodies larger than 12mm, eg, finger.

3 Protected against solid bodies larger than 2.5mm, eg, tools and wires.

4 Protected against solid bodies larger than 1.0mm, eg, fine tools andsmall wires.

5 Protected against dust (no harmful deposits).

6 Completely protected against dust.

Second ProtectionDigit (Against Liquids)

0 No protection.

1 Protected against vertically falling drops of water (condensation).

2 Protected against drops of water falling at up to 150 from the vertical.

3 Protected against rain falling at 600 from vertical.

4 Protected against splashes of water from all directions.

5 Protected against jets of water from all directions.

6 Protected against jets of water of similar force to heavy seas.

7 Protected against the effects of temporary immersion.

8 Protected against prolonged effects of immersion under pressure.

ACCESSORIES

12:6 ®

12

A1/A2 Brass Gland with Outer Seal

• To BS6121: Part 1.• Suitable for unarmoured, plastic or

rubber sheathed cables.• Suitable for most indoor and outdoor

applications.• Seal rated to IP66

Glands are supplied in kit form, complete with locknuts and shrouds.Up to size 25:- 2 per kitSize 32 and above:- 1 per kit

CABLE & GLAND DETAILS

E1AW-A1/A2-20SS Pirelli 20SS 3.5 8.5

E1AW-A1/A2-20S Pirelli 20S 8.0 11.5

E1AW-A1/A2-20 Pirelli 20 11.0 13.5

E1AW-A1/A2-25 Pirelli 25 13.0 19.5

E1AW-A1/A2-32 Pirelli 32 19.0 25.5

E1AW-A1/A2-40 Pirelli 40 25.0 32.0

E1AW-A1/A2-50S Pirelli 50S 31.5 37.0

E1AW-A1/A2-50 Pirelli 50 36.5 43.0

E1AW-A1/A2-63S Pirelli 63S 42.5 50.0

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Overall diameterMin Max

ACCESSORIES

12

12:7®

CX Brass Gland with Outer Seal

• BS6121: Part 1• Suitable for wire braid armoured, plastic or rubber

sheathed cables.• Outer seal grips sheath of cable.• Weatherproof and water proof.• Seal rated to IP66.• Design has separate armour locking ring.• Gland rated to IP66 with use of suitable sealing

washer or thread sealant at gland interface

Glands are supplied in kit form, complete with locknuts, earthtags and shrouds.Up to size 25:- 2 per kitSize 32 and above:- 1 per kit

CABLE & GLAND DETAILS

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

E1AH-CX-20SS Pirelli 20SS - 8.6 8.0 13.2

E1AH-CX-20S Pirelli 20S - 11.6 8.0 15.8

E1AH-CX-20 Pirelli 20 - 13.9 12.9 20.8

E1AH-CX-25 Pirelli 25 - 19.9 17.0 27.2

E1AH-CX-32 Pirelli 32 - 26.2 23.5 33.5

E1AH-CX-40 Pirelli 40 - 32.1 29.0 39.9

ACCESSORIES

ACCESSORIES

12:8 ®

12

CXT Brass Gland with Outer Seal

• Gland reference not specified in BS6121:Part 1. However, gland complies in all other respects with the design and test requirements of Type A2 cable glands.

• Suitable for wire braid armoured/screened, plastic or rubber sheathed cables.• Outer seal grips sheath of cable.• Weatherproof and water proof.• Seal rated to IP66.• Integral knurled armour lock.• Gland rated to IP66 with use of suitable sealing

washer or thread sealant at gland interface

Glands are supplied in kit form, complete with locknuts, earthtags and shrouds.Up to size 32:- 2 per kitSize 40 and above:- 1 per kit

CABLE & GLAND DETAILS

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

OverallMin Max

E1AH-CXT-20S CMP 20S 6.1 11.6

E1AH-CXT-20 CMP 20 6.5 13.9

E1AH-CXT-25 CMP 25 11.1 19.9

E1AH-CXT-32 CMP 32 17.0 26.2

E1AH-CXT-40 CMP 40 22.0 32.1

12:9

12

ACCESSORIES

®

Ultech® Nylon Gland with Outer Seal For non-armoured cable

• Suitable for unarmoured, plastic or rubber sheathed cables.• Polyamide 6 nylon gland with neoprene seal.• Compact “skin-top” design• Quick and easy assembly• Halogen free and UL94-V2 flammability rated.• Seal rated IP68 at 5 bar.• Temperature range: -30°C to +80°C• Grey RAL 7001 colour• ISOMETRIC thread.• 10mm thread length for gland sizes 16-25, 18mm for gland size 32.Ultech® is a registered trade name of Elkay International

Glands are supplied in kit form, complete with nylon washer and locknut. Allsizes: 2 per kit.NB: Mini-size polyamide 6.6 standard nylon gland is also available for IP66 ratednitrile seal for small diameter cable. Details as follows:-

CABLE & GLAND DETAILS

E1AV-ULT-16 Elkay 270-8011 16 5.0 10.0

E1AV-ULT-20S Elkay 270-8021 20S 6.0 12.0

E1AV-ULT-20 Elkay 270-8031 20 10.0 14.0

E1AV-ULT-25 Elkay 270-8061 25 13.0 18.0

E1AV-ULT-32 Elkay 270-8071 32 18.0 25.0

Anixter Part Gland Gland Manf. Gland Size Cable DimensionsNumber Manf. Part Number accommodated (mm)

Overall diameter

Minimum Maximum

ACCESSORIES

12:10 ®

12

Mini - Gland

• Halogen free and UL94-V2 flammability rated.• -20°C to +90°C temperature range.• Grey RAL 7001 colour.• ISOMETRIC thread.• 8mm thread length.

Glands are supplied in kit form with nylon washer and locknut – 2 per kit.

CABLE & GLAND DETAILS

E1AV-MINI-13 Elkay 239-B M13 2.0 5.0

Anixter Part Gland Gland Manf. Gland Size Cable DimensionsNumber Manf. Part Number accommodated (mm)

Overall diameter

Minimum Maximum

12

ACCESSORIES

12:11®

“LSF” Standard Cable Gland for Non-Armoured Cable

• Suitable for unarmoured plastic or rubber sheathed cables.• Polyamide 6.6 nylon gland with nitrile rubber seal.• Quick and easy assembly.• Halogen free and UL94-V2 flammability rated.• Seal rated at IP66.• -20°C to +90°C temperature range.• Black RAL 9005 colour.• ISO METRIC thread.• 11mm thread length• LSF glands meet following standards:- BS6853 App B5.1, BS7878, BS2782

M141, IEC 60754-1, IEC 60754-2, BS6425, NES713/Iss 3.

Glands are supplied in kit form, complete with washer and locknut.

CABLE & GLAND DETAILS

E1AV-LSF-20SS Elkay 249-LSF 20SS 4.0 6.0

E1AV-LSF-20S Elkay 251-LSF 20S 7.0 10.0

E1AV-LSF-20 Elkay 252-LSF 20 8.0 13.0

Anixter Part Gland Gland Manf. Gland Size Cable DimensionsNumber Manf. Part Number accommodated (mm)

Overall diameter

Minimum Maximum

ACCESSORIES

12:12 ®

12

TECHNICAL DATA

ASTM Oil No. 2 SAcetaldehyde LAcetic acid (10%) LAcetic acid (glacial) LAcetone SAmmonium Hydroxide (35%) SBenzene SBenzyl Alcohol LBromine (liquid) UButyl Alcohol SButyl Acetate SButylamine SCarbon Tetrachloride SChlorine Gas UCitric acid (10%) SCresols UCyclohexane SDiesel oil SDiethyl ether SEthanol SEthylamine LEthylene glycol SFormaldehyde SHexane SHydrochloric acid (10%) UHydrochloric acid (conc) UHydrogen peroxide (35%) L

Chemical Agent Nylon

Hydrogen sulphide (gas) SIso-octane SIso-propanol SLubricating oil SMethanol LNitric acid (10%) UNitric acid (conc) UOzone (gas) LParaffin oil SPetrol SPhenol USilicone oils SSodium hydroxide (60%) SSodium hypochlorite (bleach) LStyrene SSulphur dioxide (gas) USulphuric acid (10%) USulphuric acid (70%) UToluene STransformer oil STrichloroethylene LTricresyl phosphate (SKYDROL) STurps SWhite spirit SXylene SZinc chloride U

Chemical Agent Nylon

APPLICABLE TO NYLON GLANDS - CHEMICALRESISTANCE

Listed below is the general chemical resistanceinformation for the materials used to manufacture themajority of products in this catalogue.S = SuitableL = Limited suitabilityU = Unsuitable

12

ACCESSORIES

12:13®

Index EMC Nickel Plated Brass Gland forBraid Screened Cable

11

12

13

14

15

16

FEATURES.• 1. Compression Nut• 2. Santoprene Seal• 3. Endless Spring• 4. Tapered Ring• 5. O Ring• 6. Gland Body

• For use with braid screened cable to connect screen to the enclosure system.• Two tapered rings applying force onto an endless spring washer ensure positive

and intimate contact for efficient screening.• Screen can continue into enclosure.• Suitable for systems conforming to EN50082.• Nickel plated brass gland body with santoprene rubber seal.• Seal rated IP68 at 1 bar.• -40 to +135°C temperature range.• ISO METRIC thread with exception of gland for 4-6mm diameter cable which has

P.G.7 thread to DIN40430.

Glands are supplied in kit form complete with locknut. All sizes: 2 per kit.

E1AH-EMC-7 Elkay 261-1000 PG7 1.5 4.0 4.0 6.0

E1AH-EMC-16 Elkay 260-1000 M16 3.0 7.0 6.0 8.0

E1AH-EMC-20 Elkay 260-1250 M20 4.0 8.5 8.0 10.5

E1AH-EMC-25SSS Elkay 260-1400 M25 6.5 10.0 10.0 11.5

E1AH-EMC-25SS Elkay 260-1450 M25 8.0 12.0 11.0 14.0

E1AH-EMC-25S Elkay 260-1500 M25 8.0 12.0 14.0 16.6

E1AH-EMC-25 Elkay 260-1600 M25 12.5 17.5 17.0 20.0

E1AH-EMC-32S Elkay 260-1650 M32 15.0 21.0 19.0 23.0

E1AH-EMC-32 Elkay 260-1700 M32 15.0 21.0 22.0 27.0

Anixter Part No. Gland Gland Gland Cable Dimensions Accommodated (mm)

Manf. Manf. Part Size Over Screen Cable Diameter

No. Min. Max. Min. Max.

ACCESSORIES

12:14 ®

12

CW Brass Gland with Outer Seal

• BS6121: Part 1• Suitable for wire armoured, plastic or rubber

sheathed cables.• Outer seal grips sheath of cable.• Weatherproof and water proof.• Seal rated to IP66.• Design has separate armour locking ring (Pirelli glands only).• Gland rated to IP66 with use of suitable

sealing washer or thread sealant at gland interface

Brass glands are provided with steel locknuts and aluminium glands are providedwith aluminium locknuts. For more corrosive environments brass locknuts maybe supplied.

Glands are supplied in kit form complete with locknuts, earthtags and shrouds.

Pirelli Up to size 25: - 2 per kitSize 32 and above:- 1 per kit

CMP Up to size 32:- 2 per kitSize 40 and above:- 1 per kit

12

ACCESSORIES

12:15®

CABLE & GLAND DETAILS

E1AG-CW-20SSC Pirelli 20SS - 8.6 8.0 13.2

E1AG-CW-20SS CMP 20SS* - 8.6 8.0 13.4

E1AG-CW-20SC Pirelli 20S - 11.6 8.0 15.8

E1AG-CW-20S CMP 20S - 11.6 11.4 15.9

E1AG-CW-20C Pirelli 20 - 13.9 12.9 20.8

E1AG-CW-20 CMP 20 - 13.9 15.0 20.9

E1AG-CW-25C Pirelli 25 - 19.9 17.0 27.2

E1AG-CW-25 CMP 25 - 19.9 20.3 27.4

E1AG-CW-32C Pirelli 32 - 26.2 23.5 33.5

E1AG-CW-32 CMP 32 - 26.2 26.0 33.9

E1AG-CW-40C Pirelli 40 - 32.1 29.0 39.9

E1AG-CW-40 CMP 40 - 32.1 31.0 40.4

E1AG-CW-50SC Pirelli 50S - 38.1 38.0 46.2

E1AG-CW-50S CMP 50S - 38.1 36.5 46.7

E1AG-CW-50C Pirelli 50 - 44.0 39.5 52.6

E1AG-CW-50 CMP 50 - 44.0 43.0 53.1

E1AG-CW-63S CMP 63S - 50.0 48.9 59.4

E1AG-CW-63C Pirelli 63 - 55.9 51.3 65.3

E1AG-CW-63 CMP 63 - 55.9 58.0 65.9

E1AG-CW-75C Pirelli 75 - 67.9 62.5 78.0

E1AG-CW-75 CMP 75 - 67.9 64.9 78.5

Aluminium CW glands for aluminium wire armoured cable

E1DN-CW-25 Pirelli 25 - 19.9 17.0 27.2

E1DN-CW-32 Pirelli 32 - 26.2 23.5 33.5

E1DN-CW-40 Pirelli 40 - 32.1 29.0 39.9

E1DN-CW-50SC CMP 50S - 38.1 36.5 46.7

E1DN-CW-50 Pirelli 50 - 44.0 39.5 52.6

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

NB Pirelli glands have separate armour locking rings.CMP glands have integral knurled armour lock.

* Also known as 20/16 (CMP only),

ACCESSORIES

12:16 ®

12

BW Brass Gland

• BS6121: Part 1• Suitable for single wire armoured,

plastic or rubber sheathed cables.• For use in dry, indoor situations.• Low-cost two-part design.• IP54• Shroud may be used for additional

ingress protection

Glands are supplied in kit form complete with locknuts, earthtags and shrouds.Pirelli Up to size 25: - 2 per kit

Size 32 and above:- 1 per kitCMP Up to size 32:- 2 per kit

Size 40 and above:- 1 per kit

CABLE & GLAND DETAILS

E1AJ-BW-20SC Pirelli 20S - 11.6 - 15.8

E1AJ-BW-20S CMP 20S - 11.6 - 16.1

E1AJ-BW-20C Pirelli 20 - 13.9 - 20.8

E1AJ-BW-20 CMP 20 - 13.9 - 21.1

E1AJ-BW-25C Pirelli 25 - 19.9 - 27.2

E1AJ-BW-25 CMP 25 - 19.9 - 27.4

E1AJ-BW-32C Pirelli 32 - 26.2 - 33.5

E1AJ-BW-32 CMP 32 - 26.2 - 34.4

E1AJ-BW-40C Pirelli 40 - 32.1 - 39.9

E1AJ-BW-40 CMP 40 - 32.1 - 42.4

E1AJ-BW-50S CMP 50S - 38.1 - 50.1

E1AJ-BW-50C Pirelli 50 - 44.0 - 52.6

E1AJ-BW-50 CMP 50 - 44.0 - 55.7

E1AJ-BW-63C Pirelli 63 - 55.9 - 65.3

E1AJ-BW-63 CMP 63 - 55.9 - 68.2

E1AJ-BW-75C Pirelli 75 - 67.9 - 78.0

E1AJ-BW-75 CMP 75 - 67.9 - 82.9

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

12

ACCESSORIES

12:17®

E1W Brass Gland with Inner andOuter Seals

• BS6121: Part 1• Suitable for single wire armoured, plastic

or rubber sheathed, extruded bedded cables.• Outer seal grips sheath of cable.• Inner seal grips bedded layer of cable.• Weatherproof and waterproof.• Inner and outer seal rated to IP66• Gland rated to IP66 with use of suitable sealing washer or thread sealant at

gland interface.

Glands are supplied in kit form complete with locknuts, earthtags and shrouds.Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kitCMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kitNB Pirelli glands have separate armour locking rings.CMP glands have integral knurled armour lock.

CABLE & GLAND DETAILS

E1BA-E1W-20S Pirelli 20S 8.7 11.6 8.0 15.8

E1BA-E1W-20SC CMP 20S 6.1 11.6 11.4 15.9

E1BA-E1W-20 Pirelli 20 11.7 13.9 12.9 20.8

E1BA-E1W-20C CMP 20 6.5 13.9 15.0 20.9

E1BA-E1W-25 Pirelli 25 13.0 19.9 17.0 27.2

E1BA-E1W-25C CMP 25 11.1 19.9 20.3 27.4

E1BA-E1W-32 Pirelli 32 20.0 26.2 23.5 33.5

E1BA-E1W-32C CMP 32 17.0 26.2 26.0 33.9

E1BA-E1W-40 Pirelli 40 26.3 32.1 29.0 39.9

E1BA-E1W-40C CMP 40 22.0 32.1 31.0 40.4

E1BA-E1W-50S Pirelli 50S 32.2 38.1 38.0 46.2

E1BA-E1W-50SC CMP 50S 29.5 38.1 36.5 46.7

E1BA-E1W-50 Pirelli 50 38.2 44.0 39.5 52.6

E1BA-E1W-50C CMP 50 35.6 44.0 43.0 53.1

E1BA-E1W-63 Pirelli 63 50.1 55.9 51.3 65.3

E1BA-E1W-63C CMP 63 47.2 55.9 58.0 65.9

E1BA-E1W-75S Pirelli 75S 56.0 61.9 62.0 71.6

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

ACCESSORIES

12:18 ®

12

Low Smoke and Fume Gland Kits

• Convenient ready to use kits.• Contain everything necessary to terminate an LSF cable run - gland(s) with

LSF seal(s), backnuts(s), earth tag(s) and LSF shroud(s).• Zero halogen.• Complies with the test criteria of BS6724, BS6853 category 1.• Continuous operating temperature of -500C to 1500C• Resists most chemicals, solvents, acids, alkalis, oils, moisture, steam and UV

light.• Excellent tear resistance.

NOTE: The materials utilised in these kits are noted for the absence of smokegenerating constituents, particularly halogens (flourine, bromine and chlorine)thus avoiding the hazards of highly irritant and toxic fumes emitted by standardmaterials such as PCP and PVC when exposed to flame.

12

ACCESSORIES

® 12:19

BW Brass Gland - LSF

• To BS6121: Part 1.• Suitable for single wire armoured,

plastic or rubber sheathed cables.• For use in dry, indoor situations.• Low cost two-part design.• IP54.• LSF shroud may be used for additional

ingress protection.

Glands are supplied in kit form, complete with locknuts and shrouds.Up to size 25:- 2 per kitSize 32 and above:- 1 per kit

CABLE & GLAND DETAILS

E1AJ-BW-20SLSF Pirelli 20S - 11.6 - 15.8

E1AJ-BW-20LSF Pirelli 20 - 13.9 - 20.8

E1AJ-BW-25LSF Pirelli 25 - 19.9 - 27.2

E1AJ-BW-32LSF Pirelli 32 - 26.2 - 33.5

E1AJ-BW-40LSF Pirelli 40 - 32.1 - 39.9

E1AJ-BW-50LSF Pirelli 50 - 44.0 - 52.6

E1AJ-BW-63LSF Pirelli 63 - 55.9 - 65.3

E1AJ-BW-75LSF Pirelli 75 - 67.9 - 78.0

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

ACCESSORIES

12:20 ®

12

CW Brass Gland with Outer LSF Seal

• To BS6121: Part 1.• Suitable for single wire armoured, plastic

or rubber sheathed cables.• Outer LSF seal grips sheath of cable.• Weatherproof and waterproof.• Seal rated to IP66• Design has separate armour locking ring.• Gland rated to IP66 with use of suitable sealing

washer or thread sealant at gland interface.

Glands are supplied in kit form, complete with locknuts and LSF shrouds.Up to size 25:- 2 per kitSize 32 and above:- 1 per kit

CABLE & GLAND DETAILS

E1AG-CW-20SSLSF Pirelli 20SS - 8.6 8.0 13.2

E1AG-CW-20SLSF Pirelli 20S - 11.6 8.0 15.8

E1AG-CW-20LSF Pirelli 20 - 13.9 12.9 20.8

E1AG-CW-25LSF Pirelli 25 - 19.9 17.0 27.2

E1AG-CW-32LSF Pirelli 32 - 26.2 23.5 33.5

E1AG-CW-40LSF Pirelli 40 - 32.1 29.0 39.9

E1AG-CW-50SLSF Pirelli 50S - 38.1 38.0 46.2

E1AG-CW-50LSF Pirelli 50 - 44.0 39.5 52.6

E1AG-CW-63LSF Pirelli 63 - 55.9 51.3 65.3

E1AG-CW-75LSF Pirelli 75 - 67.9 62.5 78.0

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

12

ACCESSORIES

® 12:21

Selecting Glands for Hazardous AreasZONE CLASSIFICATION

Zone 0 (Division 0)Explosive gas/air mixture is continuously present or for long periods. Noequipment should be terminated in this zone.

Zone 1 (Division 1)Explosive gas/air mixture is likely to occur in normal operation.

Zone 2 (Division 2)Explosive gas/air mixture is not likely to occur and if so, only for a short period of time.

Increased Safety Glands(E.Exe) For use in hazardous environments and comply with EN50014 and EN 50019(BS5501 Part 1 and Part 6). These glands can only be used where no parts ofthe electrical equipment can produce sparks/arcing or exceeds the gas ignitiontemperature. E.Exe glands are normally recommended for Zone 2 applicationsbut can be used in Zone 1, i.e. indirect entry situations.

Flameproof (E.Exd) GlandsFor use in hazardous environments and comply with EN50014 and EN50018(BS5501 Part 1 and Part 5). These glands are approved for direct entry applications in Zone 1 areas, IIA, IIB or IIC gas groups with the exception of A2Fglands which are for IIA and IIB groupings - may also be used in Zone 2 areas.

Explosion Proof Barrier GlandsFor use in hazardous environments and comply with EN50014 and EN 50018(BS5501 Part 1 and Part 5). These glands are approved for direct entry applications in Zone 1 areas, IIA, IIB, or more commonly IIC gas groups.

Selecting Barrier Glands as opposed to Conventional Flameproof GlandsThe main applications for the specification of barrier glands in accordance withthe relevant codes of practice, can be summarised as follows:

• with enclosures containing an ignition source and installed in Group IIC gas areas• with an enclosure containing an ignition source and in a Zone 1 area where

the volume of the enclosure exceeds 2 litres• with cables other than those specified in BS5308, BS5467, BS6116, BS6346

and 6883• where 'cold flow' of cable installation is considered a possibility• to prevent gas migration from one area to another• to prevent moisture migration in cables• where the user assessment considers a barrier gland essential for safety

ACCESSORIES

12:22 ®

12

A2F Flameproof Gland with Outer Seal

• Suitable for unarmoured, plastic or rubber sheathed cables.• Suitable for most indoor and outdoor applications.• Seal rated to IP66.• Complies with IIB hazardous atmospheres

EN50014 and EN50018 (BS5501 Part 1 and Part 5).

• Zone 1 and Zone 2 applications.• For use with flameproof or increased safety

equipment (E.Exd or E.Exe)• BASEEFA Approved.

Glands are supplied in kit form complete with locknuts, earthtags and shrouds.Up to size 25: - 2 per kit Size 32 and above:- 1 per kitHawke glands are supplied as gland only

CABLE & GLAND DETAILS

E1AT-A2F-16H-A HAWKE 16 3.0 8.0

E1AT-A2F-20SS Pirelli 20SS 3.5 8.5

E1AT-A2F-20S Pirelli 20S 8.0 11.5

E1AT-A2F-20SH-A HAWKE 20S 7.5 11.9

E1AT-A2F-20 Pirelli 20 11.0 13.5

E1AT-A2F-20H-A HAWKE 20 11.0 14.3

E1AT-A2F-25S Pirelli 25S 13.0 16.5

E1AT-A2F-25 Pirelli 25 16.0 19.5

E1AT-A2F-25H-A HAWKE 25 13.0 20.2

E1AT-A2F-32 Pirelli 32 19.0 25.5

E1AT-A2F-32H-A HAWKE 32 19.0 26.5

E1AT-A2F-40 Pirelli 40 25.0 32.0

E1AT-A2F-40H-A HAWKE 40 25.0 32.5

E1AT-A2F-50S Pirelli 50S 31.5 37.0

E1AT-A2F-50 Pirelli 50 36.5 43.0

E1AT-A2F-50H-A HAWKE 50 31.5 44.4

E1AT-A2F-63S Pirelli 63S 42.5 50.0

E1AT-A2F-63H-A HAWKE 63 42.5 56.3

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Overall

Min Max

12

ACCESSORIES

® 12:23

CABLE & GLAND DETAILS

E1BN-E1WF-20SS Pirelli 20SS 3.81 8.74 8.0 13.2

E1BN-E1WF-20S Pirelli 20S 8.0 11.79 8.0 15.8

E1BN-E1WF-20 Pirelli 20 11.79 14.15 12.9 20.8

E1BN-E1WF-25 Pirelli 25 14.0 20.12 17.0 27.2

E1BN-E1WF-32 Pirelli 32 19.7 26.55 23.5 33.5

E1BN-E1WF-40 Pirelli 40 26.55 32.42 29.0 39.9

E1BN-E1WF-50 Pirelli 50 38.39 44.33 39.5 52.6

E1BN-E1WF-63 Pirelli 63 50.27 56.24 51.3 65.3

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

E1WF Flameproof Gland with Inner & Outer Seals

• Suitable for single wire armoured, plastic or rubber sheathed, extruded bedded cables.• Outer seal grips sheath of cable.• Inner seal grips bedded layer of cable.• Weatherproof and waterproof.• Inner and outer seal rated to IP66• Design has separate outer locking ring.• Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.• For use with flameproof equipment or increased safety equipment.• Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501

Part 1 and Part 5).• BASEEFA Approved.• Zone 1 and Zone 2 applications.

Pirelli glands are supplied in kit form completPirellie with locknuts, earthtags and shrouds.Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

ACCESSORIES

12:24 ®

12

CABLE & GLAND DETAILS

E1BP-E1XF-16 Pirelli 16 3.81 8.74 8.0 13.2

E1BP-E1XF-20SS Pirelli 20SS 3.81 8.74 8.0 13.2

E1BP-E1XF-20S Pirelli 20S 8.0 11.79 8.0 15.8

E1BP-E1XF-20 Pirelli 20 11.79 14.15 12.9 20.8

E1BP-E1XF-25 Pirelli 25 14.0 20.12 17.0 27.2

E1BP-E1XF-32 Pirelli 32 19.7 26.55 23.5 33.5

E1BP-E1XF-40 Pirelli 40 26.55 32.42 29.0 39.9

E1BP-E1XF-50S Pirelli 50S 32.42 38.39 38.0 46.2

E1BP-E1XF-50 Pirelli 50 38.39 44.33 39.5 52.6

E1BP-E1XF-63S Pirelli 63S 44.33 50.27 50.0 58.9

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

E1XF Flameproof Gland with Inner & Outer Seals

• Suitable for wire braid armoured, plastic or rubber sheathed, extruded bedded cables.• Outer seal grips sheath of cable.• Inner seal grips bedded layer of cable.• Weatherproof and waterproof.• Inner and outer seal rated to IP66• Design has separate outer locking ring.• Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.• For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe).• Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501

Part 1 and Part 5).• BASEEFA Approved.• Zone 1 and Zone 2 applications.

Pirelli glands are supplied in kit form complete with locknuts, earthtags and shrouds.Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

12

ACCESSORIES

® 12:25

CABLE & GLAND DETAILS

E1BP-EXC-20S-A Pirelli 20S 7.0 12.0 9.0 16.0

E1BP-EXC-20-A Pirelli 20 8.0 14.4 11.5 21.0

E1BP-EXC-25-A Pirelli 25 10.5 20.2 18.5 27.5

E1BP-EXC-32-A Pirelli 32 15.5 26.5 21.0 34.0

E1BP-EXC-40-A Pirelli 40 23.0 32.5 31.0 41.5

E1BP-EXC-50-A Pirelli 50 28.5 44.5 36.0 52.5

E1BP-EXC-63-A Pirelli 63 44.0 56.5 50.0 65.5

E1BP-EXC-75-A Pirelli 75 53.0 68.5 59.0 78.0

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

“Excelplus” Deluge Proof Flameproof & IncreasedSafety Gland with Inner & Outer Seals

• Suitable for wire braid and single wire armoured, plastic or rubber sheathed, extruded bedded cables.

• Outer seal grips sheath of cable.• Inner seal grips bedded layer of cable.• Weatherproof, waterproof and deluge proof.• Inner and outer seal rated to IP67.• Design has separate armour locking ring and

additional locking ring to ensure integrity ofarmour lock under vibrating conditions.

• Gland rated to IP67 with use of suitable sealing washer or thread sealant at gland interface.• For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe).

Dual certified.• Complies with group II C hazardous atmospheres EN50014, EN50018 and

EN50019 (BS5501 Part 1, Part 5 and Part 6).• BASEEFA Approved.• Zone 1 and Zone 2 applications.

Supplied as gland only.

ACCESSORIES

12:26 ®

12

CABLE & GLAND DETAILS

E1DZ-UNI-20S HAWKE 20S 7.5 11.9 9.5 16.0

E1DZ-UNI-20 HAWKE 20 9.4 14.3 12.5 20.5

E1DZ-UNI-25 HAWKE 25 12.1 20.2 16.9 26.0

E1DZ-UNI-32 HAWKE 32 17.6 26.5 22.0 33.0

E1DZ-UNI-40 HAWKE 40 23.1 32.5 28.0 41.0

E1DZ-UNI-50 HAWKE 50 28.9 44.4 36.0 52.6

E1DZ-UNI-63 HAWKE 63 39.9 56.3 46.0 65.3

E1DZ-UNI-75 HAWKE 75 50.5 68.2 57.0 78.0

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

Universal Flameproof & Increased SafetyGland with Inner & Outer Seals

• Suitable for wire braid, single wire, steel tape and strip armoured plastic orrubber sheathed, extruded bedded cables.

• Outer seal grips sheath of cable.• Inner seal grips bedded layer of cable.• Weatherproof and waterproof.• Inner and outer seal rated to IP66• Design has separate outer locking ring.• Gland rated to IP66 with use of suitable sealing washer or thread sealant at

gland interface.• For use with flameproof equipment or increased safety equipment (E.Exd or

E.Exe).• Complies with group II C hazardous atmospheres EN50014, EN50018 and

EN50019 (BS5501 Part 1, Part 5 and Part 6).• BASEEFA Approved.• Zone 1 and Zone 2 applications.• Incorporates external boot seal which offers protection against moisture

ingress to the armour.

Glands are supplied in kit form complete with locknut, earthtag, shroud, nylonwasher and serrated washers.All sizes: 1 per kit

12

ACCESSORIES

® 12:27

E2WF (RTLF) Flameproof Gland withInner & Outer Seals

• Suitable for SWA, plastic or rubber oversheathed, lead inner sheath cables.• Outer seal grips sheath of cable.• Inner seal grips and provides earth continuity to lead sheath.• Weatherproof and waterproof.• Inner and outer seal rated to IP66• Design has separate outer locking ring.• RTLF for use with flameproof equipment or increased safety equipment.• Complies with group II C hazardous atmospheres EN50014 and EN50018

(BS5501 Part 1 and Part 5).• BASEEFA Approved.• Zone 1 and Zone 2 applications.

CABLE & GLAND DETAILS

E1CF-RTLF-20SH-A HAWKE 20S 7.0 9.6 10.5 16.0

E1CF-RTLF-20H-A HAWKE 20 8.0 12.0 12.9 20.9

E1CF-RTLF-25H-A HAWKE 25 11.5 17.0 17.0 27.1

E1CF-RTLF-32SH-A HAWKE 32S 15.0 19.0 25.0 33.3

E1CF-RTLF-32H-A HAWKE 32 18.0 23.0 25.0 33.3

E1CF-RTLF-40SH-A HAWKE 40S 20.0 25.0 33.0 42.9

E1CF-RTLF-40H-A HAWKE 40 23.0 29.0 33.0 42.9

E1CF-RTLF-50SH-A HAWKE 50S 29.0 35.0 39.5 52.6

E1CF-RTLF-50H-A HAWKE 50 34.0 40.0 39.5 52.6

Glands are supplied as gland only.

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Over lead sheath OverallMin Max Min Max

ACCESSORIES

12:28 ®

12

Universal Explosion Proof Barrier Glands

• For plastic or rubber insulated cables with wire braid, single wire, steel tape or strip armour, having extruded or taped bedding.

• Solid setting compound is squeezed into the interstices of the cable whengland is installed.

• Compound forms a barrier around individual cores so preventing escape ofgases through centre of cable.

• Sealing arrangements are rated to IP66.• Weatherproof and waterproof.• For use with explosion proof equipment in Zone 1 hazardous areas.• Complies with group II C qualifies the gland for use under the most onerous

conditions.• BASEEFA Approved.• Approved to EN50014 and EN50018 (BS5501 Part 1 and Part 5)

CABLE & GLAND DETAILS

E1BS-UNI-20S-A HAWKE 20S - 10.0 9.5 16.0

E1BS-UNI-20-A HAWKE 20 - 12.5 12.5 20.5

E1BS-UNI-25-A HAWKE 25 - 18.4 16.9 26.0

E1BS-UNI-32-A HAWKE 32 - 24.7 22.0 33.0

E1BS-UNI-40H-A HAWKE 40 - 29.7 28.0 41.0

E1BS-UNI-50H-A HAWKE 50 - 41.7 36.0 52.6

Glands are supplied body only with 2 compound mixes.

Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

Under armour OverallMin Max Min Max

12

ACCESSORIES

12:29®

Brass Earth Tags

• Ensure earth continuity is maintained between the gland and the equipment.• Aluminium earth tags should be used with aluminium glands.

NOTE:Earth bond connections are specified in IEE wiring regulations and relevantCodes of Practice.

TAG DETAILS

Anixter ISO Entry Bolt HolePart No. Thread Diameter Diameter

(mm) (mm)

E1BG-20R 20 7.2

E1BG-25R 25 10.3

E1BG-32R 32 11.9

E1BG-40R 40 13.5

E1BG-50R 50 13.5

E1BG-63R 63 13.5

E1BG-75R 75 13.5

ACCESSORIES

12:30 ®

12

High Performance Sealing Washers

• Improve the IP rating between the gland and the equipment i.e. IP66.

• Fibre or Nylon available according to customer preference.

SEALINGWASHER

EQUIPMENTINTERFACE

WASHER DETAILS

Anixter ISO Entry WasherPart No. Thread Diameter Material

(mm)

E1DS-20R 20 NYLON

E1DS-25R 25 NYLON

E1DS-32R 32 NYLON

E1DS-40R 40 NYLON

E1DS-50R 50 NYLON

E1DS-63R 63 NYLON

E1DS-75R 75 NYLON

E1DT-20 20 FIBRE

E1DT-25 25 FIBRE

E1DT-32 32 FIBRE

E1DT-40 40 FIIBRE

E1DT-50 50 FIBRE

E1DT-63 63 FIBRE

E1DT-75 75 FIBRE

Galvanised Serrated Washers

• Used to prevent loosening of locknut

• Mild steel zinc plated

WASHER DETAILS

Anixter ISO EntryPart No. Thread Diameter

(mm)

E1DY-20 20

E1DY-25 25

E1DY-32 32

E1DY-40 40

E1DY-50 50

12

ACCESSORIES

12:31®

Steel, Brass & Aluminium Locknuts

• Used to secure gland body to the equipment where entry hole is not tapped.• Brass backnuts recommended for most corrosive environments.• Aluminium backnuts should be used with aluminium glands.• Steel backnuts are primarily for dry, low humidity environments.

Steel and aluminium locknuts are available when required.

LOCKNUT DETAILS

Anixter ISO Entry LocknutPart No. Thread Diameter Material

(mm)

E1BK-20R 20 BRASS

E1BK-25R 25 BRASS

E1BK-32R 32 BRASS

E1BK-40R 40 BRASS

E1BK-50R 50 BRASS

E1BK-63R 63 BRASS

E1BK-75R 75 BRASS

ACCESSORIES

12:32 ®

12

PC P/PVC Shrouds

• For fitting over cable glands where additional protection against onerousweather conditions and corrosion is required.

• Provide an effective seal onto both gland and cable oversheath.• PCP shrouds are particularly recommended for outdoor and the most hostile

conditions and are not affected by ultravoilet rays contained in sunlight.• PVC shrouds for use in dry indoor and most outdoor situations.

SHROUD DETAILS

Anixter To Suit ShroudPart No. Gland Size Material

(mm)

E1BF-20SH 20S PCP

E1BF-20H 20 PCP

E1BF-25H 25 PCP

E1BF-32H 32 PCP

E1BF-40H 40 PCP

E1BF-50H 50 PCP

E1BF-63H 63 PCP

E1BF-75H 75 PCP

E1DR-20SH 20S PVC

E1DR-20H 20 PVC

E1DR-25H 25 PVC

E1DR-32H 32 PVC

E1DR-40H 40 PVC

E1DR-50H 50 PVC

E1DR-63H 63 PVC

E1DR-75H 75 PVC

12

ACCESSORIES

12:33®

Lugs for Medium Voltage Cables

These compression lugs are based on the standard tin plated connectors manufactured by Pirelli, and are suitable for indoor and outdoor applications.Connections are manufactured from thickwall copper tubing and incorporate single hole palm. The base of the compression barrel is effectively waterblockedvia incorporation of a waterproof seal during manufacture.

LUG DETAILS

Anixter To Suit StudPart No. Conductor Size Size

(mm2) (mm)

E1AE-BTHW-70-C12 70 12

E1AE-BTHW-95-C16 95 16

E1AE-BTHW-120-C16 120 16

E1AE-BTHW-150-C16 150 16

E1AE-BTHW-185-C16 185 16

E1AE-BTHW-240-C20 240 20

ACCESSORIES

12:34 ®

12

Lugs

The use of compression lugs for securing conductors to terminals has long been recognised as offering the optimum combination of electrical integrity, reliability andspeedy installation. Single hole, two hole and four hole palm lugs available.

The compression system ensures a high level of termination when used in associationwith tooling supplied by the same manufacturer ensuring that the completed installationcomplies with the standards laid down in BS4579 Part 1 (Compression joints in copperconductors). Anixter stocks uninsulated compression lugs, manufactured by PirelliComponents, produced from high conductivity electrolytic copper having a tin plated finish for operating temperatures up to 1500C and also to prevent corrosion.

12

ACCESSORIES

12:35®

Anixter To Suit StudPart No. Conductor Size Size

(mm2) (mm)Flex Str.

E1AE-BT-150-C12 120 150 12E1AE-BT-150-C16 16E1AE-BT-185-C10 10E1AE-BT-185-C12 150 185 12E1AE-BT-185-C16 16E1AE-BT-185-C20 20E1AE-BT-240-C12 12E1AE-BT-240-C16 185 240 16E1AE-BT-240-C20 20E1AE-BT-300-C12 240 300 12E1AE-BT-300-C16 16E1AE-BT-300-C20 20E1AE-BT-400-C16 300 400 16E1AE-BT-500-C20 400 500 20E1AE-BT-630-C20 500 630 20Two Hole PalmE1AE-BT-150-C12B2 120 150 12E1AE-BT-185-C12B2 150 185 12E1AE-BT-240-C12B2 185 240 12E1AE-BT-300-C12B2 240 300 12E1AE-BT-400-C12B2 300 400 12E1AE-BT-500-C12B2 400 500 12Four Hole PalmE1AE-BT-300-C8B4 240 300 8E1AE-BT-400-C8B4 300 400 8E1AE-BT-500-C8B4 400 500 8E1AE-BT-630-C8B4 500 630 8

Anixter To Suit StudPart No. Conductor Size Size

(mm2) (mm)Flex Str.

Single Hole PalmE1AE-BT-6-C5 4.0 5E1AE-BT-6-C6 to 6E1AE-BT-6-C8 6.0 8E1AE-BT-6-C10 10E1AE-BT-10-C5 10 5E1AE-BT-10-C6 6E1AE-BT-10-C8 8E1AE-BT-10-C10 10E1AE-BT-10-C12 12E1AE-BT-16-C5 10 16 5E1AE-BT-16-C6 6E1AE-BT-16-C8 8E1AE-BT-16-C10 10E1AE-BT-16-C12 12E1AE-BT-25-C6 16 25 6E1AE-BT-25-C8 8E1AE-BT-25-C10 10E1AE-BT-25-C12 12E1AE-BT-35-C6 25 35 6E1AE-BT-35-C8 8E1AE-BT-35-C10 10E1AE-BT-35-C12 12E1AE-BT-50-C6 35 50 6E1AE-BT-50-C8 8E1AE-BT-50-C10 10E1AE-BT-50-C12 12E1AE-BT-70-C8 50 70 8E1AE-BT-70-C10 10E1AE-BT-70-C12 12E1AE-BT-70-C16 16E1AE-BT-95-C10 70 95 10E1AE-BT-95-C12 12E1AE-BT-95-C16 16E1AE-BT-120-C10 10E1AE-BT-120-C12 95 120 12E1AE-BT-120-C16 16E1AE-BT-120-C20 20E1AE-BT-150-C10 10

ACCESSORIES

12:36 ®

12

Telcleats - Black Polythene & Grey LSF

• Range taking and self adjusting• Just 8 sizes cover from 10mm to

51mm diameter• Ultraviolet and weather resistant• Low cost• Versatile• One piece• Single fixing• LSF cleats are low smoke and fume

emission and zero halogen• Coloured grey to distinguish from black coloured Telcleat• Meets requirements of BS6853 and LUL specification E1042 with regards to

temperature index, smoke emission and toxicity ratings.

CLEAT DETAILS

Anixter Cable DimensionsPart No. Accomodated

Min (mm) Max (mm)

Black Polythene

E1D-A01 10 15

E1D-A02 12 17

E1D-A03 15 20

E1D-A04 18 24

E1D-A05 22 29

E1D-A06 26 34

E1D-A07 32 42

E1D-A08 39 51

Grey LSF

E1D-A01LSF 10 15

E1D-A02LSF 12 17

E1D-A03LSF 15 20

E1D-A04LSF 18 24

E1D-A05LSF 22 29

E1D-A06LSF 26 34

E1D-A07LSF 32 42

E1D-A08LSF 39 51

®

Anixter To Suit Conductor Size Shell Internal To SuitCable

DiameterPart No. Length Diameter

(mm) (mm) (mm)

SJK1

Two Core

(mm2)

1.5 to 4.0

6.0 to 25.0

35, 50

70, 95

120, 150, 185

240, 300

400

Three Core

(mm2)

1.5 to 4.0

6.0, 10.0

16, 25

35, 50

70, 95, 120

150, 185, 240

300, 400

Four Core

(mm2)

1.5, 2.5

4.0 to 10.0

16

25, 35, 50

70, 95, 120

150, 185

240, 300, 400

190

260

360

400

530

705

900

36

47

55

70

100

125

150

14.0 - 22.0

14.0 - 30.0

20.0 - 37.0

25.0 - 42.0

33.0 - 55.0

45.0 - 74.0

50.0 - 90.0

SJK2

SJK3

SJK4

SJK5

SJK6

SJK7

SJK3 and SJK4 kits.

12

ACCESSORIES

12:37

Straight Cable JointsPolyurethane Resin Encapsulation Suitable for 2, 3, 4 core

XLPE/PVC SWA Copper Conductor Cables

• Joints comply with BS6910 Part 1.

• Transparent shell to allow inspection ofjoint before application of resin. Jointsutilise Two-Part Polyurethane resin toencapsulate, insulate and protect thejointed conductors.

• Resin and hardener are separated by a ‘centre peelable seal’ in Twin Pack Laminated Sachet (completely enclosed mixing).

• Unmixed ingredients have shelf life of 24 months based on average UK temperature.• Compression connectors for relevant conductor size are SJK1, SJK2,

• Armour bonds included in all kits.• Simple to use - no special tools required.• Supplied in resealable box.

ACCESSORIES

12:38 ®

12

Claw & Two Bolt Cleats -Aluminium Alloy

• Claw cleats for cable dimensions up to 51mm diameter.• Two bolt cleats for cable dimensions 51mm and above.

CLEAT DETAILS

Anixter Cable DimensionsPart No. Accomodated

Min (mm) Max (mm)

Claw Cleats

E1B-BA01 10 13

E1B-BA02 13 16

E1B-BA03 16 19

E1B-BA04 19 22

E1B-BA05 22 25

E1B-BA06 25 32

E1B-BA07 32 38

E1B-BA08 38 44

E1B-BA09 44 51

Two Bolt Cleats

E1B-BA10 51 57

E1B-BA11 57 64

E1B-BA12 64 70

E1B-BA13 70 76

E1B-BA14 76 83

E1B-BA15 83 89

12

ACCESSORIES

12:39®

Cable Tiles & Warning Tapes

Plastic warning cable tiles and warning tapes for buried cables and have thefollowing warning legend:

CAUTION • CAUTION

ELECTRIC CABLE BELOW

CABLE TILE DETAILS

Anixter TilePart No. Dimensions (mm)

500315 1000 x 152 x 12

500314 1000 x 244 x 12

500313 1000 x 300 x 12

WARNING TAPE DETAILS

Anixter TilePart No. Dimensions (mm)

515319 150mm wide x 100 microns thick

(365m roll)

ACCESSORIES

12:40 ®

12

11kV Indoor Termination Kits for 3 Core PILC/PICAS Cables

• Scotchcast™ termination kits for use on11kV indoor terminations for 3 core paperinsulated, belted, lead sheath and corrugated aluminium sheath cables.

• Inorganic cold shrink silicone insulator.

• Cold pour Scotchcast™ resin to insulate and fill crotch area.

• Light weight assembly

• No special tools necessary

• Cold shrink technology, no heating required

• 11kV rated voltage

• 95kV nominal impluse withstand voltage

• 700C maximum operating temperature (accelerated ageing test to VDE0278)

• 1600C overload temperature (accelerated ageing test to VDE0278)

• Track resistance on silicone insulator as per ASTM [email protected] - 30 hours @3.5kV - 10 hours

Contents list of kit:

- EPDM rubber pre-stretched tubes- Silicone Glove- Silicone pre-stretched tubes- Polyetherurethane resin- Self amalgamating tapes:

- Stress control tape- EPR rubber tape- Silicone tape

- Core separator- Cable cleaner- Gloves- Drawing instructions

Scotchcast is a registered Trade Mark of 3M.

Anixter 3M Suitable Approx.Part No. Part No. for Conductor Kit

Sizes Weight(mm2) (kg)

E1DW-MT16 MT16 70-400 3.5

12

ACCESSORIES

12:41®

11kV Indoor Termination Kits for 3 Core Polymeric Cables

• Scotchcast™ termination kits for use on11kV indoor terminations for 3 cores XLPE or EPR insulated cables.

• Inorganic cold shrink silicone insulator.

• Light weight assembly

• No special tools necessary

• Cold shrink technology, no heating required

• 11kV rated voltage

• 95kV nominal impluse withstand voltage

• 950C maximum operating temperature (accelerated ageing test to VDE0278)

• 2500C overload temperature (accelerated ageing test to VDE0278)

• Track resistance on EPDM insulator as per ASTM [email protected] - 5 hours

Contents list of kit:

- EPDM rubber pre-stretched tubes- EPDM Rubber Glove- Self amalgamating tapes:

- Semi-conducting tape- EPR rubber tape

- Copper earth braid with integral lug- Constant force springs- Cable cleaner- Drawing instructions

Scotchcast is a registered Trade Mark of 3M.

Anixter 3M Suitable Approx.Part No. Part No. for Conductor Kit

Sizes Weight(mm2) (kg)

E1DW-MT46 MT46 35-70 3.0

E1DW-MT47 MT47 95-185 2.5

E1DW-MT48 MT48 240-400 3.0

ACCESSORIES

12:42 ®

12

3M Inline (Straight) Barrier Boot - MB63

• Installation of cable termination to bushing connections in switchgear andcable end boxes for straight (in-line) applications.

• Suitable for paper or polymeric cables

• No special tools necessary

• Quick and simple installation

• Cold shrink technology, no heating required

• 11kV rated voltage (75kV BIL)

• Track resistant EPDM material

• For use on conductor sizes up to 630mm2

Dimensions of cable box and bushing dimensions should meet the following criteria:

Dimension Description Min Max(mm) (mm)

“A” Phase - Earth clearance 18 76*“B” Phase - Phase clearance 36 127*“C” Bushing diameter 50mm up bushing 24 66“D” Bushing length 50 127*

* For dimensions greater than these no boots are required.NB: 3 barrier boots are provided in each kit.

Anixter 3M Suitable Approx.Part No. Part No. for Conductor Kit

Sizes Weight(mm2) (kg)

E1DW-MB63 MB63 Up to 630 0.8

"A""B"

"C"

"D"

12

ACCESSORIES

12:43®

3M Pre-Moulded Right Angle Barrier Boot

• Installation of cable termination to bushing connections inswitchgear and cable end boxes for right angleapplications. Consists of one large tubular opening tofit a porcelain bushing, and a smaller stepped tubularopening to cover the cable lugs and fit over the cableterminations. A sealing cover is also included whichallows the connection bolts to be accessed after barrierboot has been slipped onto the bushing andtermination. The sealing cover guarantees anelectrical sealing of the live parts and is re-enterable.

• Suitable for paper or polymeric cables

• No special tools necessary

• Quick and simple installation

• Re-enterable design

• No heating required

• 11kV rated voltage (95kV BIL)

• Track resistant EPDM material

• For use in conductor sizes 35 - 300mm2

Dimensions of cable box and bushing dimensions should meet the following criteria:

Dimension Description Min Max(mm) (mm)

“A” Phase - Earth clearance 30 76*“B” Phase - Phase clearance 70 127*“C” Bushing length 110 127*“D” Bushing diameter at length “C” (circular bushing) 45** 50“E” Bushing circumference at length “C” 140** 157

(eliptical bushing)* For dimensions greater than these no boots are required.** Bushings below these minumum dimensions can be catered for using 3M’s MB64/Ssupplementary kit(s) in conjunction with the standard MB 64 kit.NB: 3 barrier boots are provided in each kit.

"B" "A"

Anixter 3M Suitable Approx.Part No. Part No. for Conductor Kit

Sizes Weight(mm2) (kg)

E1DW-MB64 MB64 35 - 300 1.05

"C"X

X

"D"

Section XX

Circular Bushing

Elliptical Bushing

"E"

Heat Shrinkable Tubing

(PICTURE UNAVAILABLE)

• General purpose heat-shrinkable polyolefin tubing. To identify and insulate

cable cores on LV power cables.

• –55 to +120°C operating temperature.

• 120°C minimum shrink temperature.

• 20 kV/mm dielectric strength as per IEC60243

• Standard 2:1 shrink ratio

• Flame retardant

• Good resistance to chemicals

AnixterPart No.E1CU-

Colour Min.Expanded

Diameter (D)

Max.Recovered

Diameter (d)

NominalWall

Thickness

To suitstandard LV

core sizemm mm mm mm2

CTW127-02 Black 12.7 6.4 0.64 25 - 35CTW127-06 Blue 12.7 6.4 0.64 25 - 35CTW254-02 Black 25.4 12.7 0.89 50 – 150CTW254-06 Blue 25.4 12.7 0.89 50 – 150CTW380-02 Black 38.0 19.1 1.02 185 – 300CTW380-06 Blue 38.0 19.1 1.02 185 – 300CTW510-02 Black 51.0 25.4 1.14 400 – 630CTW510-02 Black 51.0 25.4 1.14 400 – 630

12

ACCESSORIES

12:44