CAC ACCESSORIES
LG AIR CONDITIONERS
CAC Accessories 1
LG Airconditioners Product Data
TABLE OF CONTENTS
Table of contents Page
• Wireless Remote Control............................................................................................3
• General Central Control..............................................................................................5
• Zone Control ...............................................................................................................8
• Tele Control...............................................................................................................12
• Low Ambient Kit........................................................................................................14
• Low Static Motor .......................................................................................................17
• Drain Pump...............................................................................................................18
• Electric Heater-Duct Split .........................................................................................23
• Electric Heater- Single Package ...............................................................................26
• Plasma Air purifier ....................................................................................................29
• Electronic Thermostat...............................................................................................31
• Manual Hood ............................................................................................................34
• RF Remote Control...................................................................................................37
• Air Guide...................................................................................................................40
• Elevation Grille kit .....................................................................................................41
• Branch Distributor .....................................................................................................42
• Y Branch ...................................................................................................................47
• Header ......................................................................................................................48
• Dry Contact module..................................................................................................52
2 CAC Accessories
CAC Accessories 3
Wireless Remote Control
Accessory Name Wireless Remote Control
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
Installation Procedure :- Mounting on the wall
• It provides control flexibility.
• Wireless Remote Control .......................1EA
• Installation Manual .................................1EA
• Applicable to Ceiling Cassette, Ceiling Concealed Duct, Ducted Split & SinglePackage (6.25~25RT).
1. Mount the remote control stand on the wall with the help of screw dri-ver and screw purchased locally.
2. Insert the remote control in the stand.
Type Simple Deluxe(LCD Type)
Cooling only General For Ducted Split & Single Package AHWRCD
Heat Pump AHWRHS AUWRHS AHWRHD
AHWRHSAUWRHS
AHWRCDAHWRHD
FunctionsAir circulation / Fan operationRoom temperature checkingSleep mode operationTemperature settingsOperation mode selectionAir-swing & Jet cool (Cassette Only)On/Off Timer settings
Deluxe Simple
4 CAC Accessories
Wireless Remote Control
How to insert batteries :
How to Use :
For Ceiling Cassette :
Point the signal transmitter towards the front panel of the cassette indoor unit (for C, D, E, F Chassis models) and press any function key. For B chassis point the signal transmitter towards the wired remotecontrol and press any function key.
For Ceiling Concealed Duct, Ducted Split & Single Package :
Point the signal transmitter towards the wired remote control and press any function key.
1. Remove the battery cover from the remote control. Slide the coverin the direction of arrow.
2. Insert two batteries. Take care about the polarity(+/-) and batteriesshould be new.
3. Re-place the cover by sliding it back into position.
Remarks 1. Do not use rechargeable batteries for wireless remote control .
2. Remove the batteries from the remote control if the air conditioner is notgoing to be used for long time.
CAC Accessories 5
General Central Control
Accessory Name Central Control
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
• Individual On/Off Function
• Individual Operating monitor (LED Display)
• Total On/Off Function
• Diagnostic Funciton
• Lock Funciton (Individual, Total Lock)
• Sequential starting to prevent over current
AQCC
• Factory Supplied :- Central Control .......................1EA- *Sub PCB .............................16EA- PCB Supporter .....................64EA - Lead Wire Assembly...............1EA - Installation Manual..................1EA- **Terminal Block ...................16EA
• Purchased Locally :
- Lead Wire ...............................7EA- Screw......................................4EA
• Applicable to Ceiling Cassette, Ceiling Concealed Duct, Floor Standing, DuctedSplit & Single Package.
* : For Ceiling Cassette, Ceiling Concealed duct, Floor Standing** : For Ducted Split, Single Package
On/Off display LED (Total 16EA)• If pressing individual on/off button, display the present operation state. -Operation : green. -Stop : off -Error mode : blinking
Power display LED• Indicate the state of DC Power supply in central controller unit. -On : red -Off : no signal - Error mode : blinking
Individual On/Off button• Control ON/OFF of a unit.
Total Off button • Stop all linked units sequentially.
Total On button• Operate all linked units sequentially.
6 CAC Accessories
General Central Control
R66
1 2 3 4
ON
OFF 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4
ON
OFF 1 2 3 4 1 2 3 4 1 2 3 4
CH1
S1 S2
CH1TB
TA
CH2
Range of Control
DIP S/WSetting Method
DIP S/WSetting Method
Range of Control
1~16 Set
60~80 Set
17~32 Set
81~96 Set
33~48 Set
97~112Set
49~64 Set
113~128 Set
1. Hold the control as shown in the picture than pushthe front case slightly and pull front & rear cases infront & rear direction to separate the case.
2. Set screws to the holes of case.
3. Set the dip switch according to Range of Control asexplained in table.When linking more than 2 sets,eliminate R66(1Ω) resistorfrom PCB of controls con-trolling 17th ~128th indoor unit. Don't remove resis-tor of control controlling 1st ~ 16th units.
4. Also set the dip switch on main PCB assemblyaccording to setting order.
5. Connect the terminal referring below table.
6. After attaching the supply wire to terminal, link theconnecting wire . Cut the indicated rounded parts offront case to draw the lead wire, if necessary. Afterthat Push the front case to the rear case to assem-ble.
7. Supply the power to check control operation.
TERMINAL WIRE COLOR CONNECTING TERMINALTA Red ↔ DC 12Vof indoor unit
TB Black ↔ DC Ground of indoor unit, TB terminal of the other control
CH1 Blue ↔ Signal port of indoor unitCH2 White ↔ CH2 of the other control
Installation Procedure :
CAC Accessories 7
General Central Control
Sub1
Sub2
Sub16
M1
M2
M16
Sub17
Sub18
Sub32
M17
M18
M32
Sub113
Sub114
Sub128
M113
M114
M128
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#1
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#2
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#8
T/B1
T/B2
T/B16
M1
M2
M16
T/B17
T/B18
T/B32
M17
M18
M32
T/B113
T/B114
T/B128
M113
M114
M128
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#1
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#2
CH
1
TB TA
CH
2
CENTRALCONTROLLER
#8
(T/B: Terminal Block)
Wiring Schematic :
- Ceiling Cassette- Ceiling Concealed Duct- Floor Standing
- Ducted Split- Single Package
Remarks 1. Avoid installing control nearby computer, automatic door & elevator.
2. Avoid installing control nearby extremely humid area.
3. Avoid installing control under direct Sun- rays.
8 CAC Accessories
Zone Control
Accessory Name Zone Control
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
1) Operation Summary- A device which senses temperature of each zone controls operation of each dif-
fuser, so temperature of each zone can be controlled.
2) Specific Operation- If every zone (diffuser) is closed, Comp and outer fan become turned off to
protect compressor.
* Zone controller requires diffuser temperatures and controllers available locally.
Operating Scene- The temperature of all zones are con-
trolled individually (makes energy savings)- Controlled by the signal of every zones induct system (By connecting the thermostat and VAV Diffuser to Main PCB,comp. & fan)
• Diffuser and Thermostat are locallysourced
- Connected to Another Apparatus, Controlit Freely
ABZCA
• Factory Supplied :- Zone Control PCB ..................1EA - Trans ......................................1EA- Case .......................................1EA- Cover ......................................1EA- Main lead wires.......................1EA- Screws....................................4EA- Holder .....................................4EA- Installation Manual..................1EA
• Purchased Locally :
- Damper Motor- Thermostat- Damper
• Applicable to Ceiling Concealed Duct type air conditioners.
Zone Control PCB
Trans
Case Main lead wires
Zone A Zone B
Zone DZone C
CAC Accessories 9
Zone Control
Installation Procedure :-• The control should be mounted to control panel using 4 screws sup-
plied.
• Fasten it to any holes on control panel as long as there is enoughspace to install. If necessary drill holes to install on proper position.
• When drilling, ensure that metal swarf does not foul any electroniccomponents.
Wiring Diagram :
• Connect main lead wires between main PCB and Zone Control.
• Connect thermostat to Zone Control according to thermostat maker's manuals.
• Connect Damper Motor to Zone Control according to Damper Motor maker's manuals.
10 CAC Accessories
Zone Control
Indoor Unit
MainPCB
DamperMotor
#1
DamperMotor
#2
DamperMotor
#3
DamperMotor
#4CH1CH2CH3CH4
COMCOMCOMCOM
AC 24V 24V 24V 24V
Trans
Trans : 12VA(24V/130mA*4)
AC220~240V 50/60Hz
ZoneControllerPCB N
L L L L
N N N
Thermostat #1Thermostat #2Thermostat #3Thermostat #4
DamperMotor
#1
DamperMotor
#2
DamperMotor
#3
DamperMotor
#4N
S S S S
N N N
Thermostat #1Thermostat #2Thermostat #3Thermostat #4
AC(L) AC(N)
Power Input
Indoor Unit
MainPCB
CH1CH2CH3CH4
COMCOMCOMCOM
AC 24V 24V 24V 24V
Trans
Trans : 12VA(24V/130mA*4)
AC220~240V 50/60Hz
L : LiveN : NeutralS : Signal
ZoneControllerPCB
AC(L) AC(N)
Power Input
HVAC
By-pass damper
24 VCApower supply
Return Supply
Staticpressure control
40 VAtransformer NC NO
Pressure controller
Closed
Common
3-Canle damper motor
Open
1
2 3
Wiring also depends upon the type of the damper actuators.
• Spring Return Damper Actuators
• Non Spring Return Damper Actuators
By Pass Damper System :-
To maintain an adequate flow of air and static pressure through the HVAC system, a by-pass systemcan be used that is equipped with a motorized damper and a static pressure control.
CAC Accessories 11
Zone Control
When the area dampers open or close, the static pressure control will open or close the by-pass damper soas to maintain the adequate static pressure. Dimensions of the by-pass damper depends on the coolingcapacity of the unit.
Remarks • Turn off the Power before installation or maintenance.
Btu/h Size of the by-pass (ø)36K 250 mm42K 250 mm48K 300 mm60K 300 mm91K 350 mm120K 350 mm
12 CAC Accessories
Tele Control
Accessory Name Tele Control
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
Installation Procedure :
• It provides ease of control.
• Air conditioner can be switched on/off by the telephone. It saves time &energy.
AQTCA
- Tele Control PCB.................................................................................1EA
- Connecting wire between main PCB and Tele control ........................1EA
- Telephone Line(10m)...........................................................................1EA
- Installation Manual...............................................................................1EA
• Applicable to Ceiling Concealed Duct & Floor Standing type of air conditioner.
1. Connect the tele control PCB with mainPCB of Indoor unit through the connectingwire provided. Tele-Control
PCB ASM
Main PCB
Socket
3 Wire
CAC Accessories 13
Tele Control
2. Connect the tele control PCB to the telephone line with amulti plug.
System Schematic :-
Remarks Turn off the Power before installation or maintenance.
Tele-ControlPCB ASM
Socket
Multi Plug Telephone Line
Telephone Line Plug
Tele-ControlPCB ASM
Main PCB
Indoor unit
Socket
3 Wire
Multi Plug Telephone Line
Telephone Line Plug
Normal & ARS Telephone
Telephone Line
Condition may not be same
14 CAC Accessories
Low Ambient Kit
Accessory Name Low Ambient Kit
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
Wiring Diagram : (For Cooling Only type)
• Even when the outdoor temperature reaches low ambient with low ambient kityou can get cooling operation.
• As the ambient air temperature rises and falls, the outdoor fan speed increasesand slows down, to produce the variable cooling effect needed to give constantpressure.
- AQLA Fan Speed Control.........(1EA)- Sensor Assembly .....................(1EA)- Buckle-clip ................................(3EA)- Adhesive Insulation, 20mm x 80mm
.................................................(1EA)
- Tie Wrap,100mm......................(2EA)- Instruction Manual ....................(1EA)- Screw ......................................(3EA)
• Applicable to Convertible, Ceiling Cassette & Ceiling Concealed Duct.
Low Ambient Controller
AQLA
CAC Accessories 15
Low Ambient Kit
MAIN INPUT
(MOTOR)
SUPPLY TO FAN(S)
FROM 4 WAY VALVE
Sensor
L 123456789
1 = Live input2 = Neutral input3 = Neutral output (to motor)4 = Live output (to motor)5 = Do not use6 = Live from 4 way valve7 = Neutral from 4 way valve8 = sensor9 = sensor
P1
NN
L
P.C.B.ROOM
PIPE
P2
SW01F
Low Ambient Controller(For Heat - Pump type)
Installation Procedure :- Fixing : - The control should be mounted to control panel within the condensing unit using two screws sup-
plied. Fasten it to any holes on control panel as long as there is enough space to install.
If necessary, drill holes to install on proper position.
Electrical Connections :-
Some condensing units are equipped with two fans. In that case, connect the lead wire of each motor to ter-minal numbers 3 and 4. But some condensing units also require a separate control for each fan.
Heat Pump Models : - When the Low Ambient Control is to be used with a Heat Pump, the condenser fanneeds to run at full speed during the heating mode, and is only modulated duringthe cooling mode.When fitted to a Heat Pump, terminal numbers 6 and 7 should be wired directly tothe reversing solenoid valve ; in all cases both live and neutral side of solenoidvalve should be connected to the control.
16 CAC Accessories
Low Ambient Kit
Fig. 2: Rotary S/W P2(default:8)
Fig. 1: Rotary S/W P1(default:4)
Fig. 3: S/W SW01F(default: PIPE )
PIPE Opt A
ROOM
12
345
6789
AB
CD
E F 012
345
6789
AB
CD
E F 0
Rotating part (use a proper tool to rotate)
Opt 0
Opt F
0
10
20
30
40
50
60
70
80
90
100
Pres
et Te
mp.-0
˚CPr
eset
Temp
.-1˚C
Pres
et Te
mp.-2
˚CPr
eset
Temp
.-3˚C
Pres
et Te
mp.-4
˚CPr
eset
Temp
.-5˚C
Pres
et Te
mp.-6
˚CPr
eset
Temp
.-7˚C
Pres
et Te
mp.-8
˚CPr
eset
Temp
.-9˚C
Pres
et Te
mp.-1
0˚CPr
eset
Temp
.-11˚C
Pres
et Te
mp.-1
2˚CPr
eset
Temp
.-13˚C
Pres
et Te
mp.-1
4˚CPr
eset
Temp
.-15˚C
Pres
et Te
mp.-1
6˚CPr
eset
Temp
.-17˚C
Opt 0Opt 1Opt 2Opt 3Opt 4Opt 5Opt 6Opt 7Opt 8Opt 9Opt AOpt BOpt COpt DOpt EOpt F
Spee
drat
io(%
)
Preset temperature (¡C)Graph : Speed ratio(%) ; Controlled by rotating P2
PRESET TEMP
FAN OFF TEMP
FAN ON TEMP
Opt 0
19°C
2°C
4°C
Opt 1
20.5°C
3.5°C
5.5°C
Opt 2
22°C
5°C
7°C
Opt 3
23.5°C
6.5°C
8.5°C
Opt 4
25°C
8°C
10°C
Opt 5
26.5°C
9.5°C
11.5°C
Opt 6
28°C
11°C
13°C
Opt 7
29.5°C
12.5°C
14.5°C
Opt 8
31°C
14°C
16°C
Opt 9
32.5°C
15.5°C
17.5°C
Opt 10
34°C
17°C
19°C
Opt 11
35.5°C
18.5°C
20.5°C
Opt 12
37°C
20°C
22°C
Opt 13
38.5°C
21.5°C
23.5°C
Opt 14
40°C
23°C
25°C
Opt 15
41.5°C
24.5°C
26.5°C
Table : Setting Temperatures ; Controlled by rotating P1
Cooling Only Models : - On cooling only units, where a reversing valve is not fitted, terminal numbers 6 and7 Should be left unconnected.
Fitting the Sensor : - Locate a return bend, two or three bends above a convenient liquid line exit from theCondenser. This should ideally be chosen with its temperature closest to that of dis-charge saturation temperature.
Setting the Control : - First check whether switch SW01F is towards pipe or not. If not than slide it towardspipe.
Preset temperature at the condenser outlet can be set by switch S/W P1 and accordingly the fan on /
off temperature will be as follows :
According to preset temp. - 0 or 1 or 2,.........17, you can read the % speed ratiofrom graph. The variation in % speed ratio ischanged by position of switch S/W P2.
Remarks
- Disconnect all power supplies before starting installation or maintenance work.
- The control & sensor are to be safely enclosed within the condensing unit.
- All electrical wiring must be carried out by a competent person, and must followthe local & National Electric code.
CAC Accessories 17
Low Static Motor
Accessory Name Low Static Motor
Functions
Picture
Parts Supplied
Remarks
Applicable Models
Installation Procedure :-
• To maintain same air flow irrespective of static pressure.
- Motor ..........................................1EA
- Capacitor ...................................2EA
- Mounted Motor ...........................1EA
- Installation Manual......................1EA
• Applicable to Ceiling Concealed Duct Models.
Replace the already installed motor with low static motor.
• Turn off the Power before installation or maintenance.
Accessory Model Name
Ceiling concealed Duct
ABLME488ABLME608
Capacity
48k Btu/h
60k Btu/h
V/Hz/Ø
220-240/50/1
220-240/50/1
High40 (1413)
45 (1589)
Middle35 (1236)
40 (1413)
Air Volume[CMM(CFM)]
Low30 (1059)
35 (1236)
18 CAC Accessories
Drain Pump
Accessory Name Drain Pump
Functions
Picture
Parts Supplied
Applicable Models
• To remove the condensed water from the indoor unit.
• In some of the places where natural drainage is not possible Drain Pump is veryuseful to remove condensed water.
Factory Supplied PartsParts needed for servicing
(Factory Supplied)
For D,E&F Chassis Models - Drain Pump Assembly
(AC220~240,50/60Hz,400CMM) 1EA
- Elbow (ø32) ................................1EA
- Hose ...........................................1EA
- Tie Wrap ....................................2EA
- Screw........................................10EA
- Rubber ........................................1EA
- Installation Manual......................1EA
For G&H Chassis Models :- Drain Pump Assembly
(AC220~240,50/60Hz,400CMM) 1EA
- Screw..........................................4EA
- Cap .............................................1EA
- Installation Manual......................1EA
For D, E&F Chassis Models :
For G&H Chassis Models :
• Applicable to D,E,F,G,H Chassis Ceiling Concealed Duct Models.
Part Name Part No.Water Pump 5858A10001L
Switch Assy, Float 6601A20001E
Part Name Part No.Water Pump 5858A10001L
Switch Assy, Float 6601A20001E
Ceiling Concealed Duct
Accessory Model Name D, F Chassis G, H Chassis E Chassis
ABDPD ABDPG ABDPE
ABDPD/ABDPE ABDPG
CAC Accessories 19
Drain Pump
Installation Procedure : - For D,E&F Chassis Models
Step 1. Separate the filter. Step 2. Open the top cover.
Step 5. Connect the hose and tie wrap. Step 6. Connect two lead wires to control box.
Connect two lead wires to control box, One wire isfor float switch and other Wire is for power supply todrain pump.
Step 7. Assemble the top cover. Step 8. Close the drainage hole with the providedrubber cap.
Step 3. Assemble the drain pump assembly.
Tighten 4 screws to the channel.
Tighten 2 screws to the Side Panel.
Step 4. Attach the elbow to the side panel.
20 CAC Accessories
Drain Pump
Installation Procedure : - For G & H Chassis Models
Step 1. Separate the filter. Step 2. Open the top cover.
Step 5. Connect two lead wires to control box.
Connect two lead wires to control box (One wire isfor float switch and other Wire is for power supply todrain pump.)
Step 6. Close the drainage hole with the providedcap.
Step 7. Assemble the top cover. Step 8. Insert the filter.
Step 3. Remove the knock-out from the side panel. Step 4. Assemble the drain pump assembly.
Tighten 4 screws to the Side Panel.
CAC Accessories 21
Drain Pump
INDOOR ELECTRIC CIRCUIT
INDOORMOTOR
DRAINPUMP
BR
BR
YL
OR
RD
BL
BL
RD
BK
BL
BL
BK
GN
/YL
GN/YL
CO
MP
4 W
AY
FUSE250V10A
TE
MP
.T
HE
RM
IST
OR
PIPETHERMISTOR
FLOAT S/W
REMOTECONTROL
ZONECONTROL
Drain Pump Assy
TERMINALBLOCK
1(L
)2
(N)
4 3
5TO
OU
TD
OO
R U
NIT
INDOOR ELECTRIC CIRCUIT
Drain Pump Assy
VE
NT
INDOORMOTOR
DRAINPUMP
YL
BR
OR
BR
BK
BL
RD
BK
BRBL
BL
BL
GN
/YL
GN/YL
CO
MP
4 W
AY
FUSE250V 8A
TE
MP
.T
HE
RM
IST
OR
PIPETHERMISTOR
FLOAT S/W
REMOTECONTROL
ZONECONTROL
TELECONTROL/CENTRAL CONTROL
A/CL UNIT
OPTION
TERMINALBLOCK
1(L
)2
(N)
4 3
5TO
OU
TD
OO
R U
NIT
TRIAC
VENTILATOR
T/B
Wiring Diagram :
For D,E&F Chassis Models :
For G & H Chassis Models :
22 CAC Accessories
Drain Pump
MAX 700mm
Drain Pipe
Drain Pump
1/50~1/1001/50~1/100
Drainage Hole
Cap
Drainage holeMake sure to be closed.
Unit
Correct Incorrect
Drainage pipe(Local supply)
Thermal insulator(Local supply)
Functions
Remarks
• Be sure that there should not be any leakageafter closing the drainage hole with the cap.
For D,E,F,G&H Chassis Models :
- Possible drain-head height is up to 700mm.So, installation must be below 700mm.
- Keep the drain hose inclined downward with aslope of 1/50~1/100.
- Prevent upward or reverse flow.
- To prevent condensate forming over the drainpipe minimum 5mm thick insulation should beapplied.
- Upward rounding is not allowed.
• Disconnect the power supply before installation & maintenance.
• Check the drain pump for normal operation and abnormal noise after elec-trical wiring.
CAC Accessories 23
Electric Heater-Ducted Split
Accessory Name Electric Heater-Ducted Split
Functions
Accessory ModelName
Picture
Parts Supplied - Electric Heater ...........................1EA - Installation Manual ..................1EA
- Hexagonal bolt M6, L14............16EA - Hexagonal Nut..........................6EA
Applicable Models
• To provide quick heating.
• To provide additional heat with cycle heat.
• ANEH(Refer to Electrical Data)
• Applicable to Ducted Split type Air Conditioner.
24 CAC Accessories
Electric Heater-Ducted Split
1. First remove the flanges on the top cover incase of 15RT and 20RT models.
2. Assemble the electric heater with the help ofscrews provided with electric heater.
3. Assemble the duct flange to the electric heateras shown in the figure.
Installation Procedure :
Flange
Duct Flange (In the filter assy kit)
To Unit Control BoxGround
Power Supply(High Voltage)
Electrical Wiring :Control Wiring :
1. Connect control wires(brown) on terminal block(on PCB) as shown on wiring diagram attached oncontrol box cover.
Power Wiring :
2. Connect the wires to high voltage terminal block.Refer wiring diagram supplied with heater.
3. Fuse should be checked for correct specifications.
4. Replace control box cover using screws.
CAC Accessories 25
Electric Heater-Ducted Split
Remarks 1. Disconnect the power supply before starting installation or maintenance work .
2. Installation must be carried out by a competent person, and must follow thelocal & National Electric code.
Electric Heater for Ducted Split type air conditioner
ANEH0521A ANEH1021A ANEH09B1B ANEH18B1B ANEH18B1C ANEH36B1C ANEH36B2C
a 295.4 295.4 270.4 270.4 370.4 370.4 370.4
b 381.2 381.2 440 440 534 534 534
c 381.6 381.6 729 729 860.6 860.6 860.6
d 234.6 234.6 524 524 615.6 615.6 615.6
e 325.6 325.6 370 370 454 454 454
f 25.4 25.4 25.4 25.4 25.4 25.4 25.4
e
f
d
c
Hole for High VoltagePower Supply
Removable Panel
b
a
ApplicableModel(Ton)
3~5RT
3~5RT
6.25~12.5RT
6.25~17.5RT
15~20RT
15~20RT
HeaterModel No.
ANEH0521A
ANEH1021A
ANEH09B1B
ANEH18B1B
ANEH18B1C
ANEH36B2C
HeaterKw Rating
3.6/5.0
7.2/10.0
7.8/9.0
15.6/18.0
31.2/36.0
31.2/36.0
HeaterKw
5
10
9
18
18
18+18
Power Supply(Phase, Voltage)
1ø, 208~240V
1ø, 208~240V
3ø, 208~240V
3ø, 208~240V
3ø, 208~240V
3ø, 208~240V
ControlStages
1
1
1
1
1
2
ApplicableModel(Ton)
3~5RT
3~5RT
6.25~12.5RT
6.25~12.5RT
15~20RT
6.25~12.5RT
15~20RT
HeaterModel No.
ANEH0581A
ANEH0981A
ANEH0981B
ANEH1881B
ANEH1881C
ANEH3682B
ANEH3682C
HeaterKw Rating
5.0
9.0
9.0
18.0
18.0
36.0
36.0
HeaterKw
5
9
9
18
18
36
18+18
Power Supply(Phase, Voltage)
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
ControlStages
1
1
1
1
1
1
2
Electrical Data :
Dimensional Drawing:
Note : Heater kW ratings are at 415V.
Note : Heater kW ratings are at 240V.
26 CAC Accessories
Electric Heater-Single Package
Accessory Name Electric Heater
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
Installation Procedure :
• To provide quick heating.
• To provide additional heat with cycle heat.
LKAEH(Refer to Electric Data)
- Electric Heater ..................................1EA - Installation Manual ..........1EA
- Heater Control Box ...........................1EA - Screws
• Applicable to Single Package type of air conditioner.
1. Loosen the screws that secures heatercompartment access panel. Lift up and pullpanel towards outside.
2. Remove 4 screws from block off panel toexposure heater cavity and heater's backsupporting bracket . Keep the screws forinstalling heater later.
Heater Access PanelCompressor Access Panel
SupportBracket
Block off panel
Heater Cavity
CAC Accessories 27
Electric Heater-Single Package
Heater Control Box
SupportingBracket
SupportingBracket
Heater
L3
L2
3. Insert heater into the opening hole of heater control box.
4. Align holes and secure screws to the control box asshown in figure.
Single Bank Heater Installation :
5. Place the heater control assembly in the heater cavity.Make sure that the heater arm slides into heater's sup-porting bracket.
6. Secure the heater control assembly on heater cavityusing four screws.
Two Bank Heater Installation :
5. Place the heater control assembly in the heater cavity.Make sure that the heater arm slides into heater's sup-porting bracket.
6. Secure the heater control assembly on heater cavityusing four screws.
7. From the heater terminal posts marked L1, L2 and L3remove the nut, lock washer and flat washer.
8. Connect wiring from control box panel to the respectiveterminal post as mentioned on heater's wiring diagram.The sequence of assembling various parts is1) WireConnector 2) Flat washer 3) Locking Washer and 4) Nut.Do not over tighten the nuts on the heater terminals toprevent ceramic insulation from damage.
28 CAC Accessories
Electric Heater-Single Package
To Unit Control Box.
Ground
Power Supply
Terminal Block9. Connect control wires(Brown) on terminal block
(and PCB) as shown on wiring diagram attachedon compressor access panel.
10. Connect power supply wires to high voltage ter-minal block.Refer to wiring diagram supplied with heater.
Remarks 1. Disconnect the power supply before starting installation or maintenance work .
2. Installation must be carried out by a competent person, and must follow the local& National Electric code.
ApplicableModel(Ton)
HeaterModel No.
HeaterKw Rating
HeaterKw
Power Supply(Phase, Voltage)
ControlStages
ApplicableModel(Ton)
HeaterModel No.
HeaterKw Rating
HeaterKw
Power Supply(Phase, Voltage)
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
3ø, 380~415V
ControlStages
3~5RT
3~5RT
5RT
6.25~12.5RT
6.25~17.5RT
15~17.5RT
20~25RT
LKAEH0521
LKAEH1021
LKAEH05B
LKAEH09B
LKAEH18B
LKAEH36B
LKAEH36BL
3.6/5.0
7.2/10.0
4.3/5.0
7.8/9.0
15.6/18.0
31.2/36.0
31.2/36.0
5
10
5
9
18
18+18
36
1
1
1
1
1
2
2
5RT
6.25~12.5RT
6.25~17.5RT
6.25~17.5RT
20~25RT
LKAEH058
LKAEH098
LKAEH188
LKAEH368
LKAEH368L
4.2/5.0
7.5/9.0
15.1/18.0
30.2/36.0
30.2/36.0
5
9
18
18+18
36
1
1
1
2
2
1ø, 208~240V
1ø, 208~240V
3ø, 208~240V
3ø, 208~240V
3ø, 208~240V
3ø, 208~240V
3ø, 208~240V
Electrical Data :
Note : Heater kW ratings are at 415V.
Note : Heater kW ratings are at 240V.
CAC Accessories 29
Plasma Air Purifier
Accessory Name Plasma Air Purifier
Functions
Accessory Model Name
Picture
Parts Supplied
Applicable Models
• To provide odor free, dust free, allergy free, clean & healthy air.
• It not only removes microscopic contaminants & dust but it also removes housemites, pollen, and pet fur to help prevent allergic diseases like asthma.
Plasma Air Purifier Kit ........................1EA Installation Manual.................1EA
Screws M4 .....................................12EA Wired Remote Control ...........1EA
• Applicable to Ceiling Concealed Duct type of air conditioner.
ABPAHHABPAHCABPAGHABPAGCABPAEHABPAECABPAEZ
Type
Heat PumpCooling OnlyHeat Pump
Cooling OnlyHeat Pump
Cooling OnlyH/P + E/H
Capacity (Btu/h)18K 24K 30K 36K 42K 48K 60K
ABPAGH(C)
ABPAHH(C)
ABPAEH(C)
30 CAC Accessories
Plasma Air Purifier
Remarks Turn off the Power before installation or maintenance.
Installation Procedure :
Dimensional Drawing :
1. Disassemble the angle attached at the return of the indoor unit.
2. Fasten the Plasma Air purifier kit using supplied Screws (M4).
3. Do the wiring as per the wiring diagram provided with Plasma Air Purifier kit.
4. Confirm there is no gap between the indoor unit and Plasma Air Purifier Kit.
5. Reassemble detached angle to the back side of the plasma Air Purifier Kit box.
Model
ABPAHHABPAHCABPAGHABPAGCABPAEHABPAECABPAEZ
H
230
260
350
D
180
180
180
Dimension (mm)
W
785
1,092
1,235
CAC Accessories 31
Electronic Thermostat
Mode
°C
FanSelect
Timer
1 9
10
11
3 12
13
14
15
4
5
6
7
8
2
SET/ROOM TEMPERATURE DISPLAY
IR RECEIVER
SET TEMPERATURE BUTTON (DECREASE)
SET TEMPERATURE BUTTON (INCREASE)
OPERATION MODE SELECT BUTTON
ROOM TEMPERATURE DISPLAY BUTTON
TIMER BUTTON
FAN SELECT BUTTON
OPERATION ON/OFF BUTTON
COOL OPERATION LED
FAN OPERATION LED
HEATER ON OPERATION LED
FAN ON OPERATION LED
FAN AUTO OPERATION LED
TIMER LED
Mode
Cool
Set Temp
Room(°C)Mode
Timer
On/Off
Fan
Fan
Heater
On
Auto
°C
FanSelect
Timer
1 9
10
11
3 12
13
14
15
4
5
6
7
8
2
SET/ROOM TEMPERATURE DISPLAY
IR RECEIVER
SET TEMPERATURE BUTTON (DECREASE)
SET TEMPERATURE BUTTON (INCREASE)
OPERATION MODE SELECT BUTTON
ROOM TEMPERATURE DISPLAY BUTTON
TIMER BUTTON
FAN SELECT BUTTON
OPERATION ON/OFF BUTTON
COOL OPERATION LED
FAN OPERATION LED
HEATER ON OPERATION LED
FAN ON OPERATION LED
FAN AUTO OPERATION LED
TIMER LED
Accessory Name Electronic Thermostat
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
• It provides ease of control.
AQETC (Applicable only to Cooling Only model or Cooling Only model withElectric Heater)
Electronic Thermostat........................1EA Hexagonal Nut .......................6EA
Manual ..............................................1EA
Note : Both the thermostat are same. Function of the keys are also same only dif-ference between the two is marking in words and with symbol.
• Applicable to Ducted Split (3~5RT Cooling only 50~60Hz) and Single Package(60Hz 3~5RT Cooling only, 50Hz 3~4RT Cooling only) type.of airconditioner.
32 CAC Accessories
Electronic Thermostat
Remotecontroller
body
Lower carefully the under plate and open
it using a screw driver, etc.
Front case
The lower part
Face of wallUpper notch
Lower notchSwitch box(Local supply)
Under plateRemotecontrol unit
Remotecontrol cord
Screw(Local supply)
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
1
2THERMOSTAT
AC24V(L)
AC24V(N)
FAN
COOL
HEAT
R
C
G
Y1
W1
24V TRANS
COMP1 RELAY
INDOOR FAN RELAY
HEATER1 RELAY
AC230V(L)
AC230V(N)
AC24V(L)
AC24V(N)
FAN
COOL
HEATER
R
C
G
Y1
W1
Main UNIT
Wiring Diagram :-
Installation Procedure :-
Step1. Open the under plate carefully using a screw driver.
Installation (When Cord Buried)
Step 2. Fix the under plate on the switch box by locally sup-plied screw. Take care of deformation of under plate during fixing.
Step 3. Take out the electronic thermostat cord through thefittings & switch box.
Step 4. Connect the wiring to the terminal block of the ther-mostat.
Step 5. Now, fix the thermostat on under plate.
CAC Accessories 33
Electronic Thermostat
Cordclamp
Face of wall
Upper flange
Under plateThermostat
cord
Remotecontrol unit
Tapping screw(Accessory)
Installation (When Cord Exposed)
Step 2. Fix the under plate on the wall by self tappingscrew.
Step 3. Round the cord as shown in the figure.
Step 4. Hook the thermostat unit on the under plate.
Fixing of cord :
Step 5. Fix the cord clamps on the wall by Ø3 tapping screwsupplied locally.
Step 6. Fix the electronic thermostat cord.
Remarks
1. Electronic thermostat should be installed at a place away from direct sunlight,high humidity & direct supply of cold air.
2. Keep the electronic thermostat cord away from the refrigerant piping & thedrain piping.
3. Wiring must follow local and national code and installation should be done bytrained person.
34 CAC Accessories
Manual Hood
Accessory Name Manual Hood
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
The manual fresh air adjustment panel with the hood is designed to provide up to 25% percent outside air.
Once the adjustable panel is set and the hood is installed, they will allow a fix quantity of outside air to beintroduced into the conditioned space.
• To supply fresh air to maintain good IAQ.
AKHDA
- Manual Hood ..................................1EA Installation Manual ................1EA
- Screws M5 ....................................30EA
• Applicable to Single Package type of air conditioner.
Table 1. Maximum Allowable Fresh Air for the Unit
Unit Max CFM Unit Max CFM
LK-06B0CH 625 LK-0880CH(HH) 650
LK-08B0CH 750 LK-1080CH(HH) 850
LK-09B0CH 850 LK-1380CH 1100
LK-10B0CH 1000 LK-1580CH(HH) 1325
LK-13B0CH 1250 LK-1880CH 1550
LK-15B0CH 1500 LK-2080CH 2000
LK-18B0CH 1750 LK-2580CH 2375
LK-20B0CH 2000
LK-25B0CH 2500
CAC Accessories 35
Manual Hood
Inches Open Returen Static -- inch W. G
-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9 -1
1 80 159 195 221 277 292 352 383 378 438
2 197 296 361 415 498 511 586 636 656 717
3 318 432 528 610 720 731 819 890 933 997
4 431 569 694 804 941 950 1053 1143 1211 1276
5 471 680 830 959 1086 1174 1289 1404 1458 1573
6 511 791 965 1113 1231 1398 1525 1659 1705 1870
7 598 910 1095 1268 1422 1592 1731 1886 1958 2115
w/Open 707 1058 1258 1462 1661 1835 1989 2170 2275 2422
Table 2. Accessory Hood Flow Rate Data
Note: Before utilizing CFM mentioned in the shaded area, refer to Table 1 for maximum allowablefresh air for the unit.
Installation Procedure :- 1. Remove screws securing the fresh air adjustment
panel to the unit panel.
2. Adjust the amount of fresh air desired by changingthe position of the fresh air panel. refer to Table 2 todetermine the correct opening for the specifiedamount of fresh air, based on the operating returnstatic pressure.
3. Secure the fresh air adjustment panel to the unit endpanel with 2 screws.
4. Using the provided screws, assemble the fresh airhood, as illustrated in Figure 1.
5. Install the filter into the fresh air hood as illustratedin Figure 2.
6. Install the fresh air hood onto end panel of the unitusing the 12 screws. (Installer can secure the hoodby punching on the unit end panel )
7. Turn on the power and start the supply fan.
For CFM OpeningRefer to Table 1
Unit end panel
Fresh Air Damper
Figure 1
Figure 2
36 CAC Accessories
Manual Hood
Remarks
8. Measure the full load amps of the supply fan motor. If theamperage exceeds the full load amps, system CFM maybe too high.Make the necessary adjustments to lower the motoramperage by ; readjusting the fresh air damper or adjust-ing the fan RPM.
9. In case of installing a different type filter, you can assem-ble it by provided screws through the holes in the sidepanel as illustrated in Figure 3.
Dimensional Drawing:
• Turn off the Power before installation or maintenance.
Figure 3
A
B
C
D
Unit : Inch (mm)
24.98 (634.5)
28.11 (714)
25.91 (658)
19.35 (491.5)
CAC Accessories 37
RF Remote Control
RF Receiver
PQRFA0
• Anyway Control
- LBNH1861BL- LBNH2461BL- LBNS3061BL- LBNG3061BL- LBNK3661BL- LBNK4261BL
- LBNK4881BL- LBNL6081BL- LBNM7281BL- LBNM9081BL- LBNM1081BL
- ABNW366KSA0- ABNW426KSA0- ABNW486KSA0- ABNW606LTA0
- RF remmote controller can be possible to control the air-conditioner with Boundless & through a wall. (It help you to control the unit anywhere you are!)
- Max reciving length is 20m
• Ceiling Concealed Duct type
Accessory Name RF Remote Control
Functions
Accessory ModelName
Picture
Parts Supplied
Applicable Models
PQRFA0
- Remote Control.............................1EA
- RF Control.....................................1EA
- Installation Manual .......................1EA
- Battery...........................................2EA
38 CAC Accessories
RF Remote Control
Remove the battery cover from the remote controller.• Slide the cover according to the arrow direction.
Insert the two batteries.• Be sure that the (+) and (-) directions are correct.• Be sure that both batteries are new.
Re-attach the cover.• Slide it back into position.
• Do not use rechargeable batteries such batteries differ from standard dry cells in shape dimensions and per-formance.• Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.
Select the password.
The password can be selected from (0001-9999).
Enter your password in the remote controller.
The password can be selected using the
Up Down buttons as shown in the figure
next page example.
NOTE:If you change the battery then you have to set the password again, in condition of test operation mode (Push simultaneously hour + room-temperature key over 3 seconds in wired remote controller.)
1. Insert batteries
2. Set Password
Installation
1. How to Install Password
CAC Accessories 39
RF Remote Control
First power off the Air - Conditioner.
Open the control box cover.
Insert the cable into CN-DISP of main P.C.B.
Close the control box cover.
Fix the receiver position at your desired location.
Insert the other part of cable into receiver.
Supply power to the Air - Conditioner.
Finally, You have to install password to operate RF remote controller.
Control terminal board
Control box
Control box cover(On which the Electric
Wiring Connection is put)
Cable
A A view
Remotecontrol cord
Connection cord between the indoor unit and the outdoor unit
Cord clamper
1
1
11
22
33
44
55
66
77
88
2. How to Install RF Control
40 CAC Accessories
Air Guide
Accessory Name Air Guide
Accessory ModelName PQAGA
Functions
Picture
• It is an air guide that specially fits the Outdoor design.
• Air discharge can be changed by a simple installation.
• With one outdoor unit top discharge and front discharge
are available simultaneously.
Parts supplied
Applicable Models• Applicable to the outdoor unit of Multi V system.
• Air Guide 1EA
CAC Accessories 41
Elevation Grille Kit
Accessory Name Elevation Grille Kit
Accessory ModelName
PT-CEE/F PT-CFE/F PT-CDE/F
Functions
Picture
• Auto elevation grill will help easy clean and maintenance.
• With a Grill down button, front grill comes down.
• With a Grill up button, front grill goes up.
• With a grill stop button, front grill stops at the point.
• When the grill comes down, it does not affect the fan.
Parts supplied
Applicable Models• Applicable to Ceiling Cassette type airconditioners.
• Front panel assembly 1EA
• Screw 4EA
• Manual 1EA
• Remote controller 1EA
Cooling Only
PT-CEE/F PT-CFE/F PT-CDE/FHeat Pump
42 CAC Accessories
Branch Distributor
Accessory Name Branch Distributor
Accessory ModelName
For R410A model
Functions
Picture
• LG MPS Multi provides simple piping with using distributors
• Easy Installation with various distributors (for 2,3,4 Indoors)
• Connecting with Flare and Nuts Installers can connect pipes to outdoor units,
indoor units, branches and distributors without brazing
Parts supplied
Applicable Models • Applicable to Multi F DX, Tropical Multi system.
• Factory Supplied :
- BD(Banch Distributor) unit….1EA
- Hanger metal…………………4EA
- Screws ………………………12EA
- Installation Manual…………. 1EA
2 indoor units
For R22 model
3 indoor units
4 indoor units
PMBD3620
PMBD3630/7230
PMBD3640
PMBD5420L
PMBD5430L
PMBD5440L
(Shown PMBD3640)
• Purchased Locally : - Connecting wires (H05VV, 4 wires, 0.75mm or 1.2mm) - Installation Parts (Hanging bolts:4 x M10 orM8, Nuts : 12, flat washers :8) - Screws for wall-mounting : 6 x M5 - Insulation, Brass cap, Aluminum tape
CAC Accessories 43
Branch Distributor
Specifications :
ModelConnectable Indoor Units Number of Indoor Units
Capacity Btu/hCasing colorPowre SourcePower Consumption WRuning Current ADimensions W*H*D inch(mm)Packing Dimension W*H*D inch(mm)Net Weight kgConnecting Cable Direction Indoor Unit No. * mm2
Direction Outdoor Unit No. * mm2
Piping Connection Liquid inch(mm)(To Outdoor Unit) Gas inch(mm)Piping Connection Liquid inch(mm)(To Indoor Unit) Gas inch(mm)Piping length mPiping Elevation mDrain hoseHeat InsulationAccessories Hanger EA
Screw EAManual EA
1~4 1~3 1~2 1~37k/9k/12k/18k/24k 7k/9k/12k/18k/24k 7k/9k/12k/18k/24k 18k/24k/30k/36k
Paintingless Paintingless Paintingless PaintinglessØ1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V
10 10 10 100.05 0.05 0.05 0.05
11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)
5.0 4.9 4.8 5.04*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)3/4(19.05) 3/4(19.05) 3/4(19.05) 3/4(19.05)
1/4 (6.35)*4EA 1/4 (6.35)*3EA 1/4 (6.35)*2EA 1/4 (6.35)*3EA3/8 (9.52)*4EA 3/8 (9.52)*3EA 3/8 (9.52)*2EA 1/2 (12.7), 3/8 (15.88)*2EA
- - - -- - - -
UnusableBoth Liquid and Gas pipes
4 4 4 48 8 8 81 1 1 1
PMBD3640 PMBD3630 PMBD3620 PMBD7230
R410A
R22
Model
Connectable Indoor UnitsCombination(Min~Max.) Btu/hCasing colorPowre SourcePower Consumption WRuning Current ADimensions W*H*D inch(mm)Packing Dimension W*H*D inch(mm)Net Weight kgConnecting Cable Direction Indoor Unit No. * mm2
Direction Outdoor Unit No. * mm2
Piping Conntcion Liquid inch(mm)(To Outdoor Unit) Gas inch(mm)Piping Conntcion Liquid inch(mm)(To Indoor Unit) Gas inch(mm)Piping Length mPiping Elevation mDrain hoseHeat InsulationAccessories Hanger EA
Screw EAConnector EAManual EA
1~4 1~3 1~212000~54000 12000~54000 12000~54000Paintingless Paintingless Paintingless
Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V10 10 10
0.05 0.05 0.0511.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)
16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)5.0 4.9 4.8
4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
3/8 (9.52) 3/8 (9.52) 3/8 (9.52)3/4(19.05) 3/4(19.05) 3/4(19.05)
1/4 (6.35)*4 1/4 (6.35)*3 1/4 (6.35)*21/2 (12.7)*4 1/2 (12.7)*3 1/2 (12.7)*2
- - -- - -
UnusableBoth Liquid and Gas pipes
4 4 48 8 8- - -1 1 1
PMBD5440L PMBD5430L PMBD5420L
Note :
1. BD unit ↔ BD unit, Indoor Unit ↔ Indoor Unit : Max. Height - 10mSet up the BD unit and Indoor Unit in 15m.
2. The piping connection must be suit the piping sizes of the indoor unit which will be connected. (If need, use the connector which is included in the indoor unit)
3. The BD unit should be installed inside the building.
44 CAC Accessories
Branch Distributor
(298
)
250 Ø9.52
Main Pipe
Ø19.05
Cover ControlBranch Pipe
Suspension bolt pitch.
Refer to modelspecifications
Refer to modelspecifications
245(3
37)
505050
505050(56)
50(3
8)
(36) 5030
(111
)
Min 400
Min
30
Min 400
6030072
(150
)
Inspection opening
(Servicing space)
Min
300
A
B
C
Installation Procedure :
• This unit may be installed suspended from the ceiling or mounted on the wall.• This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up)
However, it may be freely installed in any direction forward or back, and to the sides.• Be sure to leave a 600mm square opening for service and inspection as shown in the diagram below, for
both ceiling - suspended installation and wall-mounted installation.• This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure piping
insulation.• Service direction is the side B and C• The piping for the indoor unit may be led around in direction A• The inclination of side B must be within ±5°C degrees forward or back or to the sides.
CAC Accessories 45
Branch Distributor
:
• This unit has two different installation types:(1) Ceiling-suspended type and (2) wall-mounted type.
• Choose the proper installation pattern according to thelocation of installation.
• The installation location for printed wiring board can bechanged.Follow the procedure specified in the "CONNECTINGTHE WIRING" section to change the location.
NOTICE
(1) Ceiling-suspended type
(2) Wall-mounted type
Screws(M5)(locally procude)Screws(M5)(locally procude)
15.00
BD unit
Flat washerFlat washer
Hanger metalHanger metal
Hanging boltHanging bolt(M10 or M8)
Six-sided Nut(M10 or M8)Six-sided Nut(M10 or M8)
Procedure(1) Fix the fumished hanger metal with two screws.(4 locations in
total).(2) Using an insert-hole-in- anchor, hang the hanging bolt.(3) Install a hexagon nut and a flat washer (locally-procured)to
the hanging bolt as shown in the figure in the left, and ift themain unit to hang on the hanger metal.
(4) After checking with a level that the unit is level, tighten thehexagon nut.* The tilt of the unit should be within ±5° in front/back and
left/right.
Procedure(1) Fix the fumished hanger metal with two screws.
(3 locations in total).
(2) After checking with a level that the unit is level, fix the unitwith the furnished wood screws.* The tilt of the unit should be within ±5° in front/back and
left/right.
CAUTIONS• Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again
or cover it with alumium tape.(This is to prevent condensation)• Be sure to install the unit with the ceiling-sie up.• Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be
audible.
(1) Ceiling-suspended type (2) Wall-mounted type
46 CAC Accessories
Branch Distributor
Connection of Wiring :• Connect refrigerant pipes and connection wires to the appropriate ports maked with matching
alphabets (A, B and C) on this unit.
• Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoorunits to terminal board numbers.(1, 2 and 3) Always fix each ground wire separately with a groundscrew.(See the figure below.)
• After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clampon indoor unit side is furnished. Follow the procedure below to install.
• Refer to the circuit diagram on the control cover inside outdoor unit.
: The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.
NOTICE
Warning
Do not use tappedwires, stand wires,extensioncords, orstarbust connections,as they may causeovertheating, electricalshock, or fire.
C room
B room
A room
A
B
C
CN-PWR
Connection wire for indoor units(H05VV, 4wires, 0.75mm)
Connection wire for outdoor units(H05RV, 4wires, 1.2mm)
In Case of 3 rooms
(1) Remove the control cover. Loosen the twoscrews, and slide the cover in the direction ofthe arrow.
(2) Perform wiring with reference the wiring dia-gram on a control cover of outdoor unit.Allow 300 mm for the pulling-out section ofharness. Fix the wires completely with wireclamps(4 locations).
(3) Put in the cover in the direction of the arrowthen tighten the screws.
CAC Accessories 47
Y Branch
Accessory Name Y Branch
Accessory ModelName
Picture
Parts supplied
Applicable Models • Applicable to Multi V system.
- Y Banch(Gas side, Liquid side)….1EA
- Installation Manual……..…………. 1EA
ARBL052SARBL052L
ARBL102SARBL102LARBL102G
ARBL202SARBL202LARBL202M
ARBL302SARBL302L
Pipe fitting :
Y Branch
Y branch
A B
To Outdoor Unit
To Branch Piping or Indoor Unit
A
B
Facingupwards
Facingdownwards
Within 3 Within 3
Viewed from point Ain direction of arrow
Horizontalplane
Within +/- 10
A
Insulator(included with kit)
Liquid and Gaspipe joints
Insulator forfield piping
Tape
(field supply)
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the sizeof the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
48 CAC Accessories
Y Branch
Y branch pipe
Models Gas pipe Liquid pipe
ARBL102G
ARBL202S
ARBL202L
ARBL202M
ARBL302S
ARBL302L
ARBL302M
ARBL102L
ø44.5 ø38.1 ø38.1 ø31.8
ø28.58
ø25.4ø28.58ø31.8
ø22.2 ø19.05 ø19.05 ø15.88
ø12.7
ø12.7ø15.88 ø9.52
ø44.5 ø38.1 ø38.1 ø31.8
ø28.58
ø25.4ø28.58ø31.8
ø22.2 ø19.05 ø19.05ø22.2
ø15.88
ø19.05ø22.2
ø15.88
ø15.88ø12.7
ø38.1 ø31.8 ø38.1 ø31.8 ø19.05 ø15.88 ø19.05 ø15.88
ø28.58
ø12.7
ø15.88ø19.05ø25.4
ø12.7
ø6.35ø9.52ø12.7
ø38.1 ø31.8 ø38.1 ø31.8
ø28.58
ø19.05ø25.4
ø19.05 ø15.88 ø19.05 ø15.88
ø28.58
ø12.7
ø6.35ø9.52ø12.7
ø38.1 ø38.1ø31.8
ø19.05ø25.4
ø19.05 ø15.88 ø19.05 ø15.88
ø28.58ø28.58
ø28.58
ø25.4ø12.7
ø12.7
ø6.35ø9.52ø12.7
ø25.4 ø19.05 ø19.05ø15.88
ø15.88 ø12.7
ø12.7 ø12.7 ø9.52
ø9.52 ø6.35
ARBL052S
ø15.88 ø15.88
ø15.88
ø12.7
ø12.7
ø9.52 ø9.52
ø9.52
ø6.35
ø6.35
ø19.05
ARBL102S
ø15.88 ø15.88
ø15.88
ø12.7
ø12.7 ø12.7
ø12.7 ø9.52
ø9.52
ø6.35
ø19.05 ø19.05
ø28.58 ø25.4 ø28.58 ø25.4 ø15.88 ø9.52
ø9.52 ø6.35ø15.88 ø12.7
ø12.7
ø12.7
ø12.7
ø19.05ø19.05
ø28.58 ø25.4 ø28.58 ø25.4
ø15.88
ø15.88 ø12.7 ø15.88 ø12.7
ø9.52
ø9.52
ø6.35ø12.7
ø12.7
ø19.05ø19.05
[unit:mm]
ø44.5 ø38.1 ø44.5 ø38.1 ø22.2 ø19.05 ø22.2 ø19.05
ø15.88
ø6.35ø9.52ø12.7
ø31.8
ø12.7
ø15.88ø19.05ø25.4
ARBL052L
Speciications :
CAC Accessories 49
Header
Accessory Name Header
Accessory ModelName
Picture
Parts supplied
Applicable Models • Applicable to Multi V system.
- Header(Gas side, Liquid side)….1EA
- Installation Manual……..…………. 1EA
4 branch
ARBL1010ARBL2010
Pipe fitting :
7 branch 10 branch
ARBL054ARBL104
ARBL057ARBL107
Header Branch
A
B
Header To outdoor unit
To indoor unit
A
B
C
• When the number of pipes to be connected issmaller than the number of header branches,install a cap to the unconnected branches.
• The Indoor Unit having larger capacity must beinstalled closer to than smaller one.
• If the diameter of the refrigerant piping selectedby the procedures described is different fromthe size of the joint, the connecting sectionshould be cut with a pipe cutter.
Pipe cutter
50 CAC Accessories
Header
• When the number of Indoor Units to be connected to the branch pipes is less than the number of branchpipes available for connection then cap pipes should be fitted to the surplus branches.
• Fit branch pipe lie in a horizontal plane.
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape included in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as describedabove.
B
Piched pipe
Horizontal plane
View from point B in the direction of the arrow
Insulate the header usingthe insulationmaterial attached to thebranch pipe kitas shown in the figure.
Insulator
Insulator of field pipe
Tape
TapeCap pipe
Insulator for cap pipe
CAC Accessories 51
Header
Header
Ø15.88
Ø12.7Ø15.88Ø12.7
Ø19.05
Ø15.88
Ø12.7
Ø15.88
Ø12.7
Ø19.05
[unit:mm]
4 branch
ARBL054
7 branch
ARBL057
4 branch
ARBL104
7 branch
ARBL107
10 branch
ARBL1010
10 branch
ARBL2010
Ø9.52 Ø9.52
Ø6.35Ø6.35
Ø12.7
Ø9.52Ø6.35
Ø9.52Ø6.35
Ø12.7
Ø15.88
Ø12.7
Ø28.58
Ø19.05
Ø15.88
Ø9.52Ø6.35
Ø9.52Ø12.7
Ø6.35
Ø15.88
Ø12.7
Ø28.58
Ø19.05
Ø15.88
Ø9.52Ø6.35
Ø9.52Ø12.7
Ø6.35
Ø15.88
Ø12.7
Ø28.58
Ø19.05Ø15.88 Ø9.52Ø6.35
Ø9.52 Ø12.7
Ø6.35
Ø15.88Ø15.88
Ø19.05 Ø6.35
Ø9.52
Ø9.52 Ø6.35
Ø15.88
Ø19.05
Ø31.8
Ø38.1
Ø12.7
Models Gas pipe Liquid pipe
Specifications :
52 CAC Accessories
Dry Contact module
Accessory Name Dry Contact module
Accessory ModelName
Functions
Picture
Parts supplied
Applicable Models • Applicable to all LG airconditioners.
PQDSA [Without case]PQDSB [With case]
• PQDSA kit ………………………… 1EA
• Installation Manual……..…………. 1EA
1
2
3 4 5 6
CN-POWER : AC 220V Connector
CN-CC : MAIN PCB Connector
CN_DRY (L) : DRY CONTROLLER Connector
CN_DRY ( SIG ) : DRY CONTROLLER Connector
CN_DRY (ERROR CHECK) : ERROR Check Display Connector
CN_DRY( OPER STATE): Operation DisplayConnector
1
234
5
6
It toggles into On/OFF of Automatic Operation when pressing the Reservation Cancel button of the Wireless Remote Controller in a series of 3 times within 3 minutes, with it facing to the main body. At first, the Automatic Operation is not set.
1. When it is on the Automatic Operation,• It(Air-conditioner) operates when the contact of controller is ON during its stop.
At this time, it is possible to stop/operate it by using controller.• It stops when the contact of controller is OFF during its operation.
At this time, it is not possible to control with the controller as it stops and at once converts into the Lock mode.
• RY1 becomes OFF during the operation and RY1 becomes OFF during the stop. (However, RY1 can repeat its ON/OFF when generating error, depending on the model.)
• RY2 becomes ON when generating error and RY2 becomes OFF in case of no error.
2. When it is not on the Automatic Operation,• It(Air-conditioner) is possible its operation when the contact of controller is ON during its stop.
At this time, it is possible to stop/operate it by using controller.• It stops when the contact of controller is OFF during its operation.
At this time, it is not possible to control with the controller as it stops and at once converts into the Lock mode.
• RY1 becomes ON during the operation and RY1 becomes OFF during the stop. (However, RY1 can repeat its ON/OFF when generating error, depending on the model.)
• RY2 becomes ON when generating error and RY2 becomes OFF in case of no error.
CAC Accessories 53
Dry Contact module
432
432
1 1
22
11
DRY CONTACT SUB PCB
MAIN PCB
CN-CC CN-CC
AC 220V
432
432
1 1
22
11
DRY CONTACT SUB PCB
MAIN PCB
CN-CC CN-CC
AC 220V
Connection PCB(6871A30056A)
PI485 PCB : Special purchase forCentral Control(Ex : PHNFP14A0 or PSNFP14A0...)
S1
BR1
TANS01Y
ZNR01Y
U02YU04YU03Y
SWITCH
LED
1LE
D01
GLE
D02
GLE
D03
G
OS
C01
BL0
2DL0
1D C01
A
IC01
A
CN_COMM
C03
Y
C04
Y
ON
L1 2 3 4
2 . Connect CN_DRY with Control Unit .
(Fix SUB PCB into the proper location.)
- To apply power source through PCB - To apply power source from the outside
Dry contactController
432
432
1 1
22
11
LN
DRY CONTACT SUB PCB
INPUTAC 220V
RY1 RY2
Operation DisplayError Check DisplayCN-CC
Dry contactController
432
432
1 1
22
11
LN
DRY CONTACT SUB PCB
AC 220V
RY1 RY2
Operation DisplayError Check DisplayCN-CC
1 . Connect CN-CC with Main PCB by the cable(provided)
- Connection of Dry contact only
- Connection of Dry contact & LG Central Controller
Installation Procedure :