![Page 1: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/1.jpg)
AC CORROSION ISSUES
PREDICTION & MITIGATION
By
Allen Carlile
www.arkengineering.com
![Page 2: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/2.jpg)
![Page 3: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/3.jpg)
Introduction
Although not all aspects of the AC Corrosion mechanism have been fully clarified, experience has reached a level from which general guidelines have been developed.
AC Corrosion Risk Assessment, AC corrosion mitigation , and AC corrosion monitoring.
![Page 4: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/4.jpg)
Overview
NACE - Task Group 430 – Issued a document titled: “Alternating Current Corrosion on Cathodically Protected Pipelines: Risk Assessment, Mitigation, and Monitoring” in May 2018.
NACE SP21424-2018
This standard practice presents guidelines and procedures for use during risk assessment, mitigation, and monitoring.
![Page 5: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/5.jpg)
NACE Standard SP21424-2018
AC Corrosion on a cathodically protected underground pipeline is commonly the result of a combined action of the AC voltage, the CP conditions, a coating defect, and the chemical and physical conditions of the soil.
If the AC component is removed or limited, the corrosion will be mitigated.
![Page 6: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/6.jpg)
NACE Standard SP21424-2018
AC Corrosion is also influenced by DC current. It can also be reduced by adjusting the DC component through the CP system.
An AC Corrosion evaluation process includes an analysis to develop the following strategies:
![Page 7: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/7.jpg)
Evaluation Process
Analysis – Risk Assessment
Mitigation Strategy
Monitoring Strategy
On-going monitoring to determine safe or unsafe conditions
Used for new pipelines, new interference source, or existing pipelines
![Page 8: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/8.jpg)
AC Interference vs. AC
Corrosion Inductive and conductive effects as a result
of AC current flowing in electric circuits.
AC voltage and currents are induced upon the pipeline.
Where these AC currents leave the pipeline through coating defects, they can cause AC corrosion effects.
The intensity is measured in A/m2
![Page 9: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/9.jpg)
![Page 10: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/10.jpg)
Overview
Induced AC voltage may be a cause of corrosion at coating defects where AC current escapes the pipe.
Small rather than large coating defects are susceptible to AC corrosion since the spread resistance (in Ω-m2) associated with the defects increases with increasing area
![Page 11: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/11.jpg)
Spread Resistance
The spread resistance RS is controlled by factors relating to the resistance of the soil, porosity, and geometric factors in the interface between the soil and the coating defect.
Spread resistance is approximately the proportionality factor between AC voltage and AC density.
![Page 12: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/12.jpg)
Spread Resistance
![Page 13: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/13.jpg)
Spread Resistance
A non-coated surface results in only a soil resistance value.
A coated surface with a defect results in both soil resistance and spreading resistance values. A large IR drop develops near the vicinity of the pipe to soil interface where the coating defect is present.
A geometrical spread effect is produced as a result of concentrated current flux lines.
![Page 14: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/14.jpg)
Effect of Surface Area
The surface area of the pipe at a coating holiday is important since the corrosion rate increases with increasing current density.
Large holidays would have a lower current density than small holidays if both were exposed to the same soil conditions.
![Page 15: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/15.jpg)
![Page 16: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/16.jpg)
AC Corrosion Risks
The following factors increase AC corrosion risks:
A low level of cathodic protection (low DC current density) with a high level of AC current density
Small size coating defects
Low soil resistivity
![Page 17: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/17.jpg)
Signs of Coating Failure and AC Corrosion –
Polyethylene Coating
Pushed up coating due to corrosion
by product
![Page 18: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/18.jpg)
Nodule Out Side of
Polyethylene Coating
![Page 19: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/19.jpg)
Risk Assessment
AC Corrosion Evaluation – If an AC Corrosion risk is present, then AC interference calculations (analysis), AC survey, evaluation of historic CP data and abnormalities, DC interference, ILI results, other relevant data should be reviewed.
New AC circuits or DC interference sources may cause additional risk
![Page 20: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/20.jpg)
AC Corrosion By Products
Coating Break Down
Magnetite
Pushed Up
Coating
![Page 21: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/21.jpg)
Elevated pH
![Page 22: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/22.jpg)
Circular Morphology, Magnetite
![Page 23: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/23.jpg)
Elevated pH
![Page 24: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/24.jpg)
Coating Distortion
![Page 25: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/25.jpg)
Risk Assessment
New pipelines with interfering AC systems
Pipeline Corrosion History Records may require re-evaluation in view of AC corrosion characteristics.
AC Voltage measurements
DC CP Potentials – Inadequate or Excessive
Soil Resistivity Measurements
![Page 26: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/26.jpg)
Risk Assessment
Soil resistivity surveys – the spread resistance is influenced by the soil resistivity.
The following soil resistivity parameters can be applied as a risk guideline:
Below 25 Ω-m: very high risk
Between 25 Ω-m and 100 Ω-m: high risk
Between 100 Ω-m and 300 Ω-m: Medium
![Page 27: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/27.jpg)
Circular Morphology
Active AC
Corrosion
![Page 28: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/28.jpg)
Risk Assessment
DC Interference Effects
Coupon or Corrosion Rate Probe Data –AC & CP Densities or Significant Corrosion Rates
![Page 29: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/29.jpg)
AC Corrosion - pH is Always 13-14
pH 13-14
Previous coating repair
areas jeeped in inspection
at 12:00
![Page 30: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/30.jpg)
Criteria
AC Voltage – mitigated to a level where the current densities are met.
AC Density – recommended not to exceed:
30 A/m2 – if DC Density exceeds 1 A/m2
100 A/m2 – if DC Density less than 1 A/m2
Less than 0.025 mm/y corrosion rate using weight loss coupons or probes
![Page 31: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/31.jpg)
Criteria
Consecutive use of inspection tools may be used to quantify corrosion attacks
AC and DC current densities are measured at coupons installed along the pipeline
The above criteria should be documented for a representative period of time accounting for variations in the influencing parameters.
![Page 32: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/32.jpg)
Research Studies
AC Voltage required to produce a current density of 100A/m2 in 1000 ohm-cm soil at a 1 cm2 holiday:
iac = 8 Vac / p π d
Where:
iac = ac current density (A/m2)
Vac = pipe ac voltage to remote earth (V)
p = soil resistivity (ohm-m)
![Page 33: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/33.jpg)
Research Studies
d = diameter of a circular holiday having a 1 cm2 surface area = 0.0113 m
Then: for iac = 100A/m2 and p = 10 ohm-m
Vac = 100A/m2 • 10 ohm-m • 3.14 • 0.0113m
8
Vac = 4.4 V
![Page 34: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/34.jpg)
Results
The calculation indicates that CP protected pipelines subjected to AC voltages that are below the NACE recommended maximum safe level of 15 volts (NACE SP0177) can suffer from AC corrosion at holiday sites having a surface area of approximately 1 cm2 in a soil resistivity of 3000 ohm-cm or less.
![Page 35: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/35.jpg)
Mitigation
AC Voltage Mitigation – Reference NACE Standard SP0177-2104
CP System Condition – Create uniform polarized potentials along the pipeline and minimize voltage drops. Minimize the risk of inadequate CP and excessive CP.
DC Interference effects – Reference NACE Standard SP0169
![Page 36: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/36.jpg)
Proving Effectiveness
![Page 37: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/37.jpg)
Other Factors
Mitigation wire provides a benefit in the mitigation of AC corrosion. For a coating holiday located in the vicinity of the mitigation wire, the effective resistance of the holiday is increased due to the mutual resistance between the holiday and the mitigation wire, thereby reducing the AC current density at the holiday.
![Page 38: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/38.jpg)
Monitoring Strategies
Test Stations and Monitoring Locations –Selected where the risk analysis indicates a risk of AC corrosion:
High AC voltages
Low Soil Resistivity
Excessive CP conditions or DC intf.
Previous ILI or excavation locations
Coupon or Probe locations of high values
![Page 39: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/39.jpg)
![Page 40: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/40.jpg)
Coupon Test Station
![Page 41: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/41.jpg)
Monitoring Strategies
Coupon Test Stations
Corrosion Rate Measurements
Data Loggers
Remote Monitoring Units
![Page 42: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/42.jpg)
Coupon T/S - DCD – Remote Monitor
![Page 43: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/43.jpg)
Coupons or Probe Installation
Coupon test stations or ER Probes are installed on the pipeline, at specific intervals to measure the DC potentials, AC potentials, and current densities.
This test equipment provides the necessary data to assess the likelihood that AC interference is contributing to the observed corrosion.
![Page 44: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/44.jpg)
Long Term Monitoring
Monitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information.
This monitoring will determine safe or unsafe locations. Unsafe locations are areas where the parameters have been exceeded and require a renewed risk assessment analysis or a renewed mitigation strategy, in an iterative process.
![Page 45: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/45.jpg)
Thank You! Any Questions
![Page 46: AC CORROSION ISSUES PREDICTION & MITIGATION Corrosion Issues_2019.pdfMonitoring AC corrosion is a dynamic process, to provide AC corrosion criteria information. This monitoring will](https://reader035.vdocuments.site/reader035/viewer/2022081601/60ff187a4c803c0cf74918bc/html5/thumbnails/46.jpg)
www.arkengineering.com