FUEL STORAGEAboveground Tank
Application and Installation Guidelines
formerly titled Motor Vehicle Fuel Storage and Dispensing Guidelines
Introduction
The intent of this document is to provide a user friendly resource of the requirements for the installation of above-
ground flammable and combustible liquid storage tanks for MOTOR VEHICLE FUEL DISPENSING for fire
service, the general public, and industry in the State of Oregon.
We hope that you will find this guideline to be a useful resource to the installation and use of above-ground
flammable and combustible liquid tanks for fuel dispensing.
Background – Regulations for storage and dispensing of motor vehicle fuels from above-ground storage tanks
(ASTs) within the State of Oregon are found in the 2014 Oregon Fire Code, which is an amended version of the
2012 International Fire Code.
Building Department Requirements – Consult with the local planning and building department for additional
requirements that may apply.
Plan Review Requirements – Prior to installation and operation when an AST has a capacity of more than 1,000
gallons, single or aggregate, two sets of plans shall be submitted to the Office of State Fire Marshal for review.
Plans shall include details for all applicable provisions.
Inspection Requirements – When tank installation is complete, a final inspection is required prior to filling.
Contact Office of State Fire Marshal for an appointment.
Questions for farm installations, construction projects, vaults or requests for additional information can be
directed to:
Office of State Fire Marshal, Codes and Technical Services Unit, 3565 Trelstad Ave SE, Salem, OR 97317
Ph. (503) 934-8204
TABLE OF CONTENTS
STATE FIRE MARSHAL APPLICATION TO INSTALL
ABOVE GROUND TANKS ........................................................................................... Section 1
STATE FIRE MARSHAL INSTALLATION GUIDELINES .................................... Section 2
ABOVE GROUND TANK ILLUSTRATIONS……………………………………… Section 3
APPLICATION TO INSTALL Flammable/Combustible Liquid Aboveground TanksFlammable/Combustible Liquids - To install tanks for the storage of flammable or combustible liquids above-ground in excess of 1,000 gallons in either individual or aggregate quantities as specified in Oregon Fire Code Section 5701.6
Incomplete applications will automatically be rejected ALL INFORMATION MUST BE PROVIDED AND ALL NECESSARY SIGNATURES MUST BE OBTAINED
Flammable Liquids:
LOCATED ON PREMISES KNOWN AS:
SITE ADDRESS
ZIP
Street
PLANNING-ZONING
PRINT name of Planning/Zoning Official
Mailing Address of Planning/Zoning Official
City, State, Zip Code Telephone #
SIGNATURE of Planning/Zoning Official Date
FIRE DEPARTMENT
PRINT Fire Department Name
Mailing Address of Fire Department
City, State, Zip Code Telephone #
INSTALLER INFORMATION
PRINT name of Company Installing Tank
Mailing Address
City, State, Zip Code Telephone #
Email address
APPLICANT INFORMATION
PRINT name of Applicant Applying for Permit
Mailing Address of Applicant
City, State, Zip Code
Telephone Number
SIGNATURE of Fire Chief or Fire Marshal Date SIGNATURE of Applicant Date
NOTE: It is the responsibility of the applicant to ensure that this installation shall be in full compliance with applicable
statutes of the state of Oregon and any local codes and ordinances.
Email address Email address
Email address
OFFICE of STATE FIRE MARSHAL 3565 Trelstad Avenue SE, Salem, Oregon 97317 [email protected] Phone: 503-934-8256
Required Items to Submit: TWO (2) SETS of plans shall accompany this application to include: Necessary specification or cutsheets, documents and drawings showing details of design and construction including support, structures, piping, valves, tank capacities, spill and drainage control, secondary containment, fire protection, physical protection and security.
Nearest Cross Street / Road
City County
Submit completed application packet to:
Combustible Liquids: Quantity in gal
Note: Flammable liquids have a flash point below 100°F. Combustible liquids have a flash point at or above 100 F.
Select Appropriate Responsefrom Drop down
Quantity in gal
Revised 6-2017
INSTALLATION GUIDELINES
Tank Design Criteria – Above-ground storage tanks shall be designed, fabricated and constructed in
accordance with nationally recognized standards. For the purpose of the Oregon Fire Code, the following
standards are recognized:
UL 142 – Non-protected Tanks
UL 2085 – Protected Tanks
Piping
All piping is required to be designed and fabricated from suitable materials having adequate strength and
durability to withstand the pressure, structural stresses and exposure to which they can be subjected.
All piping is required to be tested before being placed in service. Hydrostatic testing is required to be
150 % of the maximum anticipated pressure of the system, or pneumatic testing is required to be 110 %
of the maximum anticipated pressure of the system when operating, but not less than 3 psi and not more
than 5 psi.
All under ground piping shall be properly designed, installed and maintained, and protected from
corrosion by either a cathodic protection system or by being constructed of corrosion-resistant materials.
Quantity Of Fuel To Be Stored
UL 142 (Non-protected Tanks) – 6,000 gallons individual shell or 18,000 gallon aggregate capacity.
UL 2085 (Protected Tanks) – 12,000 gallons individual shell or 48,000 gallons aggregate capacity.
NOTE: Tanks containing Class II or III-A liquids may be of greater capacity as approved by the
fire code official.
Vehicle Impact Protection – Protection shall be provided when tanks are subject to vehicle impact. When
guard posts are installed, the posts shall be:
Constructed of steel, not less than 4 inches in diameter, and concrete filled.
Spaced not more than 4 feet between posts on center.
Set not less than 3 feet deep in a concrete footing of not less than a 15 inch diameter.
Set with the top of the post not less than 3 feet above ground, and
Located not less than 3 feet from the protected object.
Separation Of LP-Gas Tanks – The minimum horizontal separation between an LP-gas container and a Class
I, II or III-A liquid storage tank shall be 20 feet.
Separation Requirements
NON–PROTECTED TANKS – UL 142
Tank Capacity
(Gallons)
Property lines or opposite
side of a public way
(feet)
Near side of public way or
important building
(feet)
Distance between tanks
(feet)
ALL 100 50 3
PROTECTED TANKS – UL 2085
Tank Capacity
(Gallons)
Property lines or opposite
side of a public way
(feet)
Near side of public way or
important building
(feet)
Distance between tanks
(feet)
Less than or equal to
6000
15 5 3
Greater than 6000 25 15 3
Overfill Prevention – Tanks shall not be filled in excess of 95 % of their capacity. An overfill prevention
system shall be provided that shall:
Provide an independent means of notifying the person filling the tank that the fluid has reached 90
percent of tank capacity by providing an audible or visual alarm signal, providing a tank level gauge
marked at 90 percent of tank capacity, or other approved means, and
Automatically shut off the flow of fuel to the tank when the quantity of liquid in the tank reaches 95
percent of tank capacity or other approved method of overfill prevention.
A permanent sign shall be provided at the fill point for the tank documenting the filling procedure and
the tank calibration chart. The filling procedure shall require the person filling the tank to determine the
gallonage required to fill it to 95 percent of capacity before commencing the fill operation.
Spill Containment – A spill container having a capacity of not less than 5 gallons shall be provided for each fill
connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to
the tank and equipped with a manual drain valve that drains into the primary tank. For tanks with a remote fill
connection, a portable spill container shall be provided.
Venting (normal and emergency)
Vent pipe outlets for tanks storing Class I, II or III-A liquids shall be located such that the vapors are
released at a safe point outside of buildings and not less than 12 feet above the adjacent ground level.
Vapors shall be discharged upwards or horizontally away from closely adjacent walls to assist in vapor
dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or
other obstructions and shall be at least 5 feet from building openings or property lines of properties that
can be built on.
Stationary above ground tanks shall be provided with additional venting that will release excessive
internal pressure caused by exposure to fire. Emergency vents for Class I, II and III-A liquids shall not
discharge inside buildings.
Exception: Tanks larger than 12,000 gallons in capacity storing Class III-B liquids which are not
within the diked area or the drain age path of Class I or II liquids do not require emergency relief
venting.
Warning Signs – Warning signs shall be conspicuously posted within sight of each dispenser in the fuel-
dispensing area and shall state the following:
- No smoking
- Shut off motor
- Discharge your static electricity before fueling by touching a metal surface away from the nozzle
- To prevent static charge, do not reenter your vehicle while gasoline is pumping
- If a fire starts, do not remove nozzle – use emergency shut off
- It is unlawful and dangerous to dispense gasoline into unapproved containers
- No filling of portable containers in or on a motor vehicle. Place container on ground before
filling.
Markings – Above-ground stationary tanks shall be marked by visible hazard identification signs as specified in
NFPA 704 for the specific material contained. Signs shall be placed on above-ground tanks and at the entrances
to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit
and at specific entrances and locations designated by the fire code official.
Dispenser Specifications and Location(s)
Dispensing devices shall be located as follows:
1) Ten feet or more from property lines.
2) Ten feet or more from buildings having combustible exterior wall surfaces or buildings having
noncombustible exterior wall surfaces that are not part of a 1-hour fire-resistance-rated assembly
or buildings having combustible overhangs.
Exception: Canopies constructed in accordance with the Building Code providing
weather protection for the fuel island.
3) Such that all portions of the vehicle being fueled will be on the premises of the motor fuel-
dispensing facility.
4) Such that the nozzle, when the hose is fully extended, will not reach within 5 feet of building
openings.
5) Twenty feet or more from fixed sources of ignition.
Dispensing devices except those installed on top of a protected above ground tank that qualifies as
vehicle-impact resistant, shall be protected against physical damage by mounting on a concrete island 6
inches or more in height or by other approved methods.
Dispensing devices shall be installed and securely fastened to their mounting surface in accordance with
the dispenser manufacturer’s instructions.
Dispenser hoses shall be a maximum of 18 feet in length unless approved. Dispenser hoses shall be
listed and approved. When not in use, hoses shall be reeled, racked or otherwise protected from damage.
Dispenser hoses for Class I and II liquids shall be equipped with a listed emergency breakaway device
designed to retain liquid on both sides of a breakaway point.
Emergency Disconnect Switches – An approved clearly identified and readily accessible emergency disconnect
switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of
a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located
within 100 feet of but not less than 20 feet from the fuel dispensers. For interior fuel-dispensing operations, the
emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled
as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Secondary Containment
Secondary containment for outdoor storage areas shall be designed to contain a spill from the largest
individual vessel. If the area is open to rainfall, secondary containment shall be designed to include the
volume of a 24-hour rainfall as determined by a 25-year storm and provisions shall be made to drain
accumulations of ground water and rain water.
An approved monitoring method shall be provided to detect hazardous materials in the secondary
containment system. The monitoring method is allowed to be visual inspection of the primary or
secondary containment, or other approved means. Where secondary containment is subject to the
intrusion of water, a monitoring method for detecting water shall be provided. Where monitoring
devices are provided, they shall be connected to approved or audible alarms.
Drainage Control and Diking
The area surrounding a tank or group of tanks shall be provided with drainage control or shall be diked
to prevent accidental discharge of liquid from endangering adjacent tanks, adjoining property or reaching
waterways.
Exceptions:
1) The fire code official is authorized to alter or waive these requirements based on a
technical report which demonstrates that such tank or group of tanks does not constitute a
hazard to other tanks, waterways or adjoining property, after consideration of special
features such as topographical conditions, nature of occupancy and proximity to buildings
on the same or adjoining property, capacity and construction of proposed tanks and
character of liquids to be stored, and nature and quantity of private and public fire
protection provided.
2) Drainage control and diking is not required for listed secondary containment tanks.
Fire Extinguishers – Approved portable fire extinguishers with a minimum rating of 2-A:20-B:C shall be
provided and located such that an extinguisher is not more than 75 feet from pumps, dispensers or storage tank
fill-pipe openings.
Sources of Ignition – Smoking and open flames shall be prohibited within 25 feet of fueling operations. The
engine of vehicles being fueled shall be shut off during fueling. Electrical equipment shall be in accordance with
NFPA 70.
Unsupervised Dispensing (Cardlock/Fleet)
A telephone not requiring a coin to operate or other approved, clearly identified means to notify the fire
department shall be provided on the site in a location approved by the fire code official.
An approved emergency procedure sign, in addition to other required signs, shall be posted in a
conspicuous location and shall read:
IN CASE OF FIRE, SPILL OR RELEASE
1.) USE EMERGENCY PUMP SHUT OFF
2.) REPORT THE ACCIDENT!
FIRE DEPARTMENT TELEPHONE NO. ______________
FACILTY ADDRESS ______________________
Dispenser operating instructions shall be conspicuously posted in approved locations on every dispenser
and shall indicate the location of the emergency controls.
Dispensing equipment used at unsupervised locations shall comply with one of the following:
1) Dispensing devices shall be programmed or set to limit uninterrupted fuel delivery to 40
gallons and require a manual action to resume delivery.
Exception: Class II or III-A liquid may be programmed or set to limit uninterrupted fuel
delivery of up to 250 gallons.
2) The amount of fuel being dispensed shall be limited in quantity by a preprogrammed card as
approved.
Contact the Office of State Fire Marshal for additional rules regarding cardlock operations.
NOTE: Compliance with the Oregon Fire Code does not automatically constitute compliance with EPA or
other federally mandated rules, and further research may be necessary. It is the responsibility of the
applicant to ensure that all installations are in full compliance with applicable statutes of the State of Oregon
and any local codes and ordinances.
Information in this guideline may not include every above ground storage tank and fuel dispensing
requirement as per the Oregon Fire Code. If a discrepancy is discovered the Oregon Fire Code shall be the
governing document.