abb ttr 4x mv medium voltage mv current transformers ct's - abb medium voltage current...

4
Description Highest voltage for equipment TTR 4x. xx Indoor Bushing Current Transformer Medium Voltage Product The TTR 4x.xx current transformers are cast in epoxi resin and designed for insulation voltages up to 12 kV. The TTR 4x.xx transformers are configurated as bar-type, with only one or more ratios (secondary side to be changeover) and perform the function of a bushing when installed in the switchboard. The transformer is designed with either 1 or 2 secondary windings and, depending on the combi- nation of parameters (accuracy class, burden, short- circuit current, overcurrent factor…) with the possibili- ty to choose from various sizes of the transformer. The secondary windings are used for measurement or protection purposes. One terminal of each secondary winding in use and one terminal of short-circuited and not used winding have to be earthed during the trans- former operation.The secondary windings are lead out into a cast-type secondary terminal board, covered with plastic cover which may be sealed.The transformer can be mounted in any position. The transformer position is fixed by using four screws. [kA] [A] [kV] [kV] [kV] [VA/cl] Secondary reconnectible for 1 core type Rated primary voltage ...3.6 kV; 7.2 kV; 12 kV Rated primary currents 100;150;200;300;400;500;600;750;1000;1250;1500; 2000;2500 A Primary currents different from the above can also be agreed upon with the customer. Rated secondary currents...5 A; 1 A (possibility to combine different values in one transformer) Rated frequency ... 50 Hz; 60 Hz The transformers are manufactured conformably to the following requirements and standards: IEC, VDE, ANSI, BS,GOST and ČSN 12 28 75 100 - 2500 60 -100 5- 30 / 0.2 - 1/5P;10P Power frequency test voltage, 1 min. Lighting impulse test voltage Rated continous thermal current Rated short-time thermal current Burdens, classes Reconnectible Basic marking TTR 4 x . x x 1...up to 600 A (smaller parameters) 2...up to 600 A (higher parameters) 3...up to 1250 A 4...up to 1500 A 5...up to 2000 A 6...up to 2500 A Insulation levels of TTR 4x.xx transformer V k 5 7 / 8 2 / 2 1 V k 0 6 / 7 2 / 2 . 7 V k 5 4 / 1 2 / 6 . 3 V k 0 6 / 0 2 / 2 . 7 V k 0 4 / 0 1 / 6 . 3 1...bar-type outlet 1...model series

DESCRIPTION

ABB Medium Voltage MV Indoor Bushing Current Transformers CT's ABB TTR 4x MV Medium Voltage MV Current Transformers CT's 3.3kV/3.6kV - 11kV/12kV Medium Voltage MV Bushing Current Transformers ABB Power Products ABB TTR6x medium voltage current transformers are cast in epoxy resin for MV insulation up to 25kV - ABB TTR6x medium voltage transformers are configured as bar-type, with either one or more transformer ratios (possibility to change over the meddium voltage MV secondary side) and perform the function of a bushing when installed on the switchboard. The ABB TTR6x indoor bushing current transformer is designed with either 1 or 2 secondary transformer windings and depending on the combinagtion of parameters (accuracy class, burden, short circuit current, overcurrent factor) with the possibility to choose from various sizes of the medium voltage transformer. The secondary MV transformer windings are used for measurement or protection purposes - one transformer terminal of each secondary transformer winding in use and one terminal of short-circuited and not used medium voltage winding have to be earthed during the transformer operation. The seoondary windings are lead out into a cast-type secondary terminal board, covered with plastic cover which may be sealed. The ABB transformer can be mounted in any position for efficient and reliable MV medium voltage performance. The ABB transformer is fixed by using four screws. ABB TTR 4x Current Transformers CT ABB Medium Voltage MV Indoor Bushing Current Transformers CT's - ABB TTR Features Transformer rated primary medium voltages : 17.5kV to 25kV Transformer rated current : 100, 150, 200, 300, 400, 500, 600, 750, 1000, 1250, 1500, 2000 and 2500Amps Transformer rated frequency : 50 Hz ; 60 Hz (Herz) ABB indoor bushing current transformers for MV medium voltage service are conformant to following specifications : IEC, VDE, ANSI, BS, GOST and CSN.

TRANSCRIPT

Page 1: ABB TTR 4x MV Medium Voltage MV Current Transformers CT's - ABB Medium Voltage Current Transformers

Description

Highest voltage for equipment

TTR 4x. xxIndoor Bushing Current Transformer

Medium Voltage Product

The TTR 4x.xx current transformers are cast in epoxi resin and designed for insulation voltages up to 12 kV.The TTR 4x.xx transformers are configurated as bar-type, with only one or more ratios (secondary side to be changeover) and perform the function of a bushing when installed in the switchboard.The transformer is designed with either 1 or 2 secondary windings and, depending on the combi-nation of parameters (accuracy class, burden, short-circuit current, overcurrent factor…) with the possibili-ty to choose from various sizes of the transformer.The secondary windings are used for measurement or protection purposes. One terminal of each secondary winding in use and one terminal of short-circuited and not used winding have to be earthed during the trans-former operation.The secondary windings are lead out into a cast-type secondary terminal board, covered with plastic cover which may be sealed.The transformer can be mounted in any position. The transformer position is fixed by using four screws.

[kA]

[A]

[kV]

[kV]

[kV]

[VA/cl]

Secondary reconnectiblefor 1 core type

Rated primary voltage ...3.6 kV; 7.2 kV; 12 kVRated primary currents 100;150;200;300;400;500;600;750;1000;1250;1500;2000;2500 A Primary currents different from the above can also be agreed upon with the customer.Rated secondary currents...5 A; 1 A (possibility to combine different values in one transformer)Rated frequency ... 50 Hz; 60 HzThe transformers are manufactured conformably to the following requirements and standards: IEC, VDE, ANSI, BS,GOST and ČSN

12

28

75

100 - 2500

60 -100

5- 30 / 0.2 - 1/5P;10P

Power frequency test voltage, 1 min.

Lighting impulse test voltage

Rated continous thermal current

Rated short-time thermal current

Burdens, classes

Reconnectible

Basic marking

TTR 4 x . x x

1...up to 600 A (smaller parameters)2...up to 600 A (higher parameters)3...up to 1250 A4...up to 1500 A5...up to 2000 A 6...up to 2500 A

Insulation levels of TTR 4x.xx transformer Vk 57 / 82 / 21Vk 06 / 72 / 2.7Vk 54 / 12 / 6.3

Vk 06 / 02 / 2.7Vk 04 / 01 / 6.3

1...bar-type outlet

1...model series

Page 2: ABB TTR 4x MV Medium Voltage MV Current Transformers CT's - ABB Medium Voltage Current Transformers

Dimensions

)cngised eroc-elbuoD )bngised eroc-elgniS )a ,ngised eroc-elgniSreconnectable on the secondary side

Marking of current transformer outlets

thgieWsnoisnemiD tnerruc detaRepyT noitalusnI

voltage [kV] [A] A B C D E F G H H I ØØ ØJ K∞ L [kg]

TTR 41.11 to 600 402 214 170 120 162 60 30 16 6 71 156 136 160 10.0

TTR 42.11 to 300 500 214 170 220 162 60 30 16 6 71 156 136 160 17.0

12TTR 43.11 750-1250 472 214 170 120 162 95 30 20 10 71 156 136 160 11.0

TTR 44.11 1500 482 252 208 120 162 100 30 16 20 110 192 174 196 15.0

TTR 45.11 2000 482 252 208 120 162 100 30 20 20 110 192 174 196 21.0

TTR 46.11 2500 502 252 208 120 162 110 30 20 20 110 192 174 196 24.0

c)

Page 3: ABB TTR 4x MV Medium Voltage MV Current Transformers CT's - ABB Medium Voltage Current Transformers

Type Ratio I thn Burden accuracy FS/ALF Type Ratio I thn Burden accuracy FS/ALF[ A ] [ kA ] [ VA ] [ A ] [ kA ] [ VA ]

41.11 100//5 60 5 1 541.11 100//5 60 15 3 541.11 100//5 60 10 10P 541.11 125//5 60 5 1 541.11 125//5 60 15 3 541.11 125//5 60 5 10P 1041.11 125//5 60 10 10P 541.11 150//5 60 10 0,5 541.11 150//5 60 15 3 541.11 150//5 60 5 10P 1041.11 150//5 60 10 10P 541.11 200//5 60 15 0,5 541.11 200//5 60 30 3 541.11 200//5 60 5 10P 1541.11 200//5 60 15 10P 541.11 200//5/5 60 10/10 3/10P 5/541.11 200//5/5 60 5/10 0.5/10P 5/541.11 250//5 60 15 0.5 541.11 250//5 60 45 3 541.11 250//5 60 10 10P 1041.11 250//5 60 15 10P 541.11 250//5/5 60 5/5 0.5/10P 5/1041.11 250//5/5 60 5/10 0.5/10P 5/541.11 250//5/5 60 10/5 3/10P 5/1041.11 250//5/5 60 10/10 3/10P 5/541.11 300//5 60 30 0.5 541.11 300//5 60 60 3 541.11 300//5 60 5 5P 2541.11 300//5 60 15 5P 1041.11 300//5/5 60 5/5 0.5/10P 5/1041.11 300//5/5 60 5/10 0.5/10P 5/541.11 300//5/5 60 10/5 3/10P 5/1041.11 300//5/5 60 10/10 3/10P 5/541.11 400//5 60 30 0.5 541.11 400//5 60 60 1 541.11 400//5 60 15 5P 1041.11 400//5 60 30 5P 541.11 400//5/5 60 10/5 0.5/10P 5/1541.11 400//5/5 60 10/15 0.5/10P 5/541.11 400//5/5 60 15/5 3/10P 5/1541.11 400//5/5 60 15/15 3/10P 5/541.11 500//5 60 30 0.5 541.11 500//5 60 90 1 541.11 500//5 60 15 5P 1541.11 500//5 60 30 5P 541.11 500//5/5 60 15/5 0.5/5P 5/2041.11 500//5/5 60 15/10 0.5/5P 5/1041.11 500//5/5 60 15/15 0.5/5P 5/541.11 500//5/5 60 15/5 3/5P 10/2041.11 500//5/5 60 15/10 3/5P 10/1041.11 500//5/5 60 15/15 3/5P 10/541.11 600//5 60 30 0.5 541.11 600//5 60 120 1 541.11 600//5 60 15 5P 1541.11 600//5 60 30 5P 1041.11 600//5/5 60 15/5 0.5/5P 10/2041.11 600//5/5 60 15/10 0.5/5P 10/1041.11 600//5/5 60 15/30 0.5/5P 10/541.11 600//5/5 60 30/5 5/5P 5/2041.11 600//5/5 60 30/10 5/5P 5/1041.11 600//5/5 60 30/30 5/5P 5/5

42.11 100//5 60 10 10P 1042.11 100//5 60 15 10P 542.11 100//5/5 60 5/5 1/10P 5/1042.11 100//5/5 60 5/10 1/10P 5/542.11 100//5/5 60 15/5 3/10P 5/1042.11 100//5/5 60 15/10 3/10P 5/542.11 125//5 60 10 10P 1042.11 125//5 60 15 10P 542.11 125//5/5 60 5/5 1/10P 5/1042.11 125//5/5 60 5/10 1/10P 5/542.11 125//5/5 60 15/5 3/10P 10/1042.11 125//5/5 60 15/10 3/10P 10/542.11 150//5 60 15 10P 1042.11 150//5 60 30 10P 542.11 150//5/5 60 10/5 0.5/10P 5/1542.11 150//5/5 60 10/15 0.5/10P 5/542.11 150//5/5 60 15/5 3/10P 5/1542.11 150//5/5 60 15/15 3/10P 5/542.11 200//5 60 15 10P 1542.11 200//5 60 30 10P 542.11 200//5/5 60 15/10 0.5/10P 5/1042.11 200//5/5 60 15/15 0.5/10P 5/542.11 200//5/5 60 15/10 3/10P 10/1042.11 200//5/5 60 15/15 3/10P 10/542.11 250//5 60 15 10P 1542.11 250//5 60 30 10P 1042.11 250//5/5 60 15/10 0.5/10P 10/1042.11 250//5/5 60 15/15 0.5/10P 10/542.11 250//5/5 60 15/10 3/10P 10/1042.11 250//5/5 60 15/15 3/10P 10/542.11 300//5 60 15 10P 2042.11 300//5 60 30 10P 1042.11 300//5/5 60 30/10 0.5/10P 5/1542.11 300//5/5 60 30/15 0.5/10P 5/1042.11 300//5/5 60 15/10 3/10P 10/1542.11 300//5/5 60 15/15 3/10P 10/10

43.11 750//5 100 60 1 1043.11 750//5 100 30 5P 1043.11 750//5/5 100 15/30 0.5/5P 5/543.11 1000//5 100 60 0.5 1043.11 1000//5 100 30 5P 1043.11 1000//5/5 100 30/15 0.5/5P 5/1043.11 1000//5/5 100 30/30 0.5/5P 5/543.11 1250//5 100 120 0.5 543.11 1250//5 100 30 5P 1543.11 1250//5/5 100 30/15 0.5/5P 5/1043.11 1250//5/5 100 30/30 0.5/5P 5/5

44.11 1500//5 150 120 0.5 1044.11 1500//5 150 60 5P 1044.11 1500//5/5 150 60/30 0.5/5P 5/1044.11 1500//5/5 150 60/60 0.5/5P 5/5

45.11 2000//5 200 120 0.5 1045.11 2000//5 200 60 5P 1045.11 2000//5/5 200 60/30 0.5/5P 5/1045.11 2000//5/5 200 60/60 0.5/5P 5/5

46.11 2500//5 250 120 0.5 1046.11 2500//5 250 60 5P 1546.11 2500//5/5 250 60/30 0.5/5P 5/1546.11 2500//5/5 250 60/60 0.5/5P 5/5

Standartized transformers

Page 4: ABB TTR 4x MV Medium Voltage MV Current Transformers CT's - ABB Medium Voltage Current Transformers

1VLC

0005

22 -

Rev

1,

en 2

010.

xx.x

xABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602