ABB
Technical Catalog
ACS 100 Adjustable
ACS 140 Frequency
ACS 400 Drives
ABB Automation Inc.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
ACS 100
1/6 - 3 HP, 200 - 240 V both Single and Three Phase Protected Chassis Standard with Optional NEMA 1 Enclosure Kit Available Operator Panel Standard Flange, Wall or DIN Rail Mounting Heatsinkless Models
ACS 140
1/6 - 3 HP, 200 - 240 V both Single and Three Phase 1/2 - 3 HP, 380 - 480 V Protected Chassis Standard with Optional NEMA 1 Enclosure Kit Available Operator Panel Standard Flange, Wall or DIN Rail Mounting Heatsinkless Models RS232 Modbus Serial Communications PID Setpoint Control Standard
ACS 400
3 - 40 HP, 200 - 240 V 3 - 50 HP, 380 - 480 V NEMA 1 Enclosure Standard with Optional NEMA 4 and NEMA 12 Enclosures Available
RS485 Modbus Serial Communication Standard PID Setpoint Control standard
The ACS 100, ACS 140 and ACS 400 are microprocessor-based pulse width modulated (PWM) adjustable frequency AC drives. These drives take advantage of sophisticated microprocessor control and advanced IGBT power switching technology to deliver excellent performance control of AC motors for a wide range of applications.
Product Overview
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Standard Features
Input PowerVoltage: (ACS 100, ACS 140) 1-phase and 3-phase,
200 to 240 V, ±10 %, (ACS 140, ACS 400)
3-phase, 380 to 480 V, ±10 %
Frequency: 48 to 63 Hz
Power Factor: approx. 0.98
Motor connectionVoltage: 3-phase, from 0 to U
SUPPLY
Frequency: (ACS 100/140) 0 to 300 Hz,
(ACS 400) 0 to 250 Hz
Continuous loading capability (constant torque at a max. ambient temperature of 40°C): Rated output current I2.
Overload capacity (at a max. ambient temp. of 40°C):
at constant torque 1.5 x I2N
, for 1 minute every
10 minutes
at constant torque 1.25 x I2N
, for 2 minutes every
10 minutes
Switching frequency:(ACS 100/140) Standard 4 kHz, Low-noise 8 kHz,
Silent 16 kHz*,
(ACS 400) Standard 4 kHz, Low-noise: 8 kHz
Acceleration time: 0.1 to 1800 s
Deceleration time: 0.1 to 1800 s
Programmable control connectionsTwo analog inputs (only one in ACS 100): Voltage signal: 0 (2) to 10 V, 200 kΩ single-ended
Current signal: 0 (4) to 20 mA, 500 Ω single-ended
Potentiometer reference value:
10 V ±2 % max. 10 mA, 1 kΩ ≤ R ≤ 10 kΩ
Response time: ≤ 60 ms
Resolution: 0.1 %
Accuracy: ±1 %
Analog output (ACS 140/400): 0 (4) to 20 mA, load <500 Ω
Auxiliary voltage (ACS 100/140): 12 V DC, max. 100 mA
(ACS 400): 24 V, max. 250 mA
Five digital inputs (only three in ACS100): 12 V… 24 V DC with internal or external supply,
PNP and NPN
In ACS 100 ABB standard, 3-wire or alternate
Input impedance: 1.5 kΩ
Response time: ≤ 9 ms
Two relay outputs (only one fault relay in ACS 100): Switching voltage: 12 to 250 VAC or max 30 VDC/0.5 A
Maximum continuous current: 10 mA to 2 A
Control Panel
Environmental limitsAmbient temperatures: Output current = I
2, f
switch = 4 kHz: 0 to 40 °C
ACS 100/140 additionally: Output current = 0,8 · I
2, f
switch = 4 kHz: 0 to 50 °C
Output current = I2, f
switch = 8 kHz: 0 to 30 °C
Output current = 0.9 · I2, f
switch = 8 kHz: 30 to 40 °C
Output current = 0.75 · I2, f
switch = 16 kHz: 0 to 30°C 1)
ACS 400 additionally: Output current = 0.9 · I
2, f
switch = 4 kHz: 0 to 50 °C
Output current = 0.8 · I2, f
switch = 8 kHz: 0 to 40 °C
Altitude: Output current = I
2: 0 to 1000 m
Output current reduced by 1 % per 100 m over 1000 m
to 2000 m
Relative humidity: less than 95 % (non-condensing)
Protection class: (ACS 100/140) Protected Chassis,
(ACS 400) NEMA 1
Paint color: NCS 1502-Y, RAL 9002, PMS 420 C
Contamination levels: no conductive dust, corrosive liquids
or gases (IEC 721-3-3)
Product compliance Low Voltage Directive 73/23/EEC with supplements
EMC Directive 89/336/EEC with supplements
Quality assurance system ISO 9001 and ISO 14001
CE, UL, cUL and C-Tick approvals
Options
NEMA 1 Enclosure Kit for ACS 100 and ACS 140
NEMA 4 and NEMA 12 Enclosures for ACS 400
Extended Control Panel Cable
EMC input fi lters for First Environment
Braking units and choppers
ACS 140/400: RS 485/232 adapter
DriveWindow Light ACS 400:
DDCS adapter for fi eldbus modules
1) Except ACS 143-1K1-3 and ACS 143-2K1-3 where
output current = 0.55 x I2 , f
SWITCH =16 kHz: 0 to 30 °C
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Specifi cations
Input ConnectionVoltage (VIN): 230 V Units (ACS 100/140 1/6 - 3 HP) - 1 Phase 200 - 240 V ±10%
230 V Units (ACS 100/140 1/6 - 3 HP) - 3 Phase 200 - 240 V ±10%
230 V Units (ACS 400 3 - 40 HP) - 3 Phase 200 - 240 V ±10%
480 V Units (ACS 140 1/2 - 3 HP, ACS 400 3 - 40 HP) - 3 Phase 380 - 480 V ±10 %
Frequency: 48 to 63 Hz
Power Factor (for Fundamental): 0.98
Motor connectionVoltage: 3-phase, from 0 to V
IN(V
MAX at Field Weakening Point)
Output Frequency: 0 to 250 Hz (ACS 100/140 - 300 Hz)
Frequency Resolution: 0.1 Hz Digital, 10 bit Analog Input 1 & 2
Switching Frequency fS: 4.0, 8.0 or 16.0 kHz
Continuous Output Current: Constant Torque: Rated IN (IN: Rated Current), fs = 4kHz
Overload Capacity: Constant Torque: 1.5 X IN, for 1 minute every 10 minutes
Field Weakening Point: (ACS 400) 30 to 250 Hz, (ACS 100/140) 300 Hz
Acceleration Time: 0.1 to 1800 seconds
Deceleration Time: 0.1 to 1800 seconds
Enclosure: (ACS400) NEMA Type 1, NEMA Type 12 and NEMA Type 4,
(ACS100/140) Protected Chassis
Environmental Limits:Ambient Operating Temperature (fS = 4 kHz): Variable Torque (NEMA Type 1 & NEMA Type 12): 32 to 104 °F (0 to 40 °C)
Storage Temperature: 4 to 158 °F (-20 to 70 °C)
Cooling Method: (ACS 400) Integral Fan(s), (ACS 100/140) Natural Convection up to 1.5 HP
Relative Humidity: max 95%, no condensation allowed
Altitude Maximum: 3300 ft. (1000 m) above sea level (100% load) 1 % derating every 330 ft. above 3300 ft.
Agency Approval: UL, cUL, CE
External Control ConnectionsTwo Programmable Analog Inputs (ACS 140/400): Voltage Reference: 0 (2) to 10 V, 200 k, Single Ended
Current Reference: 0 (4) to 20 mA, 500 , Single Ended
Potentiometer: 10 VDC, 10 mA (1k to 10 k)
Auxiliary Voltage: (ACS 400) 24 VDC, max 250 mA, (ACS 100/140) 12 VDC, max 100 mA
Five Programmable Digital Inputs: (ACS 400) 24 VDC, (ACS 100/140) 12 VDC
Response Delay: < 8 ms
One Programmable Analog Output: (ACS 140/400) 0 (4) to 20 mA, 500 max.
Two Programmable Relay (Form C) Outputs: (ACS 100) One Fault Relay Output
Max. Switching Voltage: 30 VDC / 250 VAC
Max. Switching Current: 8 A / 24 VDC, 8 A / 250 VAC
Max. Switching Power: 2000 VA / 250 VAC
Max. Continuous Current: 2 A
Response Delay: < 10 ms
Protections: Overcurrent Trip Limit: 3.5 x IN instantaneous (ACS 100 1.5 x IN, ACS 140 2.25 x IN)
Adjustable Current Regulation Limit: 1.1 x IN (RMS) max
Overvoltage Trip Limit: 1.35 x VR
Undervoltage Trip Limit: 0.65 x VN
Overtemperature (Heatsink): 203 °F (95 °C) (ACS 100/140: 194 °F (90 °C))
Auxiliary Voltage: Short Circuit Protected
Ground Fault: Protected
Short Circuit: Protected
Microprocessor Fault: Protected
Motor Stall Protection: Protected
Motor Overtemperature Protection (I2t): Protected
Input Power Loss of Phase: Protected
Loss of Reference: Protected
Short Circuit Current Rating: 65,000 RMS Symmetrical Amperes (ACS 400 ONLY)
Input Line Impedance: 3% with Standard Internal Reactors (ACS 400 ONLY)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
standard feature ACS 100 ACS 140 ACS 400
Functions
Start; normal/fl ying/torque boost
Start; premagnetizing
IR compensation
Stop; ramp/coasting
Stop; DC brake
DC hold
U/f -ratio; linear/square
Acceleration/deceleration 1 (s) 0.1 … 1800 0.1 … 1800 0.1 … 1800
Acceleration/deceleration 2 (s) 0.1 … 1800 0.1 … 1800
S-ramp; fast/medium/slow
Preset speeds 1 7 7
Critical frequencies 2 2
Slip compensation
Application Macros
Factory
ABB Standard
3-wire
Alternate
Motor potentiometer
Hand/Auto Control
PID Control (process)
Premagnetize
Pump and Fan Control (PFC)
Protection, fault functions
Overload protection
Stall protection
Output overcurrent
Output short circuit
Ground fault, motor cable
Under load
Network failure
Low input signal level (AI<min)
Panel fault
Over voltage
Under voltage
External fault
Automatic fault reset, under voltage
Automatic fault reset, over voltage, over current, AI<min
Fault history 1 3 3
Supervision functions (programmable) 1)
Speed
Current
Torque
Output power
Reference setpoint
1) Many other signals can also be monitored, please refer to the appropriate user's manual.
Parameters, Macros and Protection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Technical Data1-phase Supply Voltage 200 - 240 V ± 10 %
Mounting options, standard series
In addition to the conventional wall mounting and
time-saving DIN rail mounting, ACS 100/140 Drives
also offer fl ange-mounting. The heat sink is located
outside the enclosure and the majority of the power
loss is external to the enclosure, thus reducing the size
of the enclosure signifi cantly.
wall mountingmounting on DIN rail
Nominal ratings Over- Power losses
Order Nominal Frame Input Output Max. Over- temp. Line Power Control
code motor size/ current current output current (heat fuse2) circuit circuit
ACS 101- P N 3) weight I 1N I 2N current (peak) sink)
ACS 141- HP lbs. A A A4) A oC A W W
H18-1 0.16 H/1.76 2.7 1.0 1.5 3.2 90 6 7 8
H25-1 0.25 H/1.76 4.4 1.4 2.1 4.5 90 6 10 10
H37-1 0.33 H/1.76 5.4 1.7 2.6 5.5 90 10 12 12
H75-1 0.5 H/1.76 3.2 2.2 3.3 7.1 90 10 13 14
1H1-1 0.75 H/1.76 9.0 3.0 4.5 9.7 90 10 19 16
1H6-1 1.0 H/1.76 10.8 4.3 6.5 13.8 90 16 27 17
Nominal ratings Over- Power losses
Order Nominal Frame Input Output Max. Over- temp. Line Power Control
code motor size/ current current output current (heat fuse2) circuit circuit
ACS 101- P N 3) weight current (peak) sink)
ACS 141- HP lbs. A A A4) A oC A W W
K18-1 0.16 A/1.98 2.7 1.0 1.5 3.2 90 6 7 8
K25-1 0.25 A/1.98 4.4 1.4 2.1 4.5 90 6 10 10
K37-1 0.33 A/1.98 5.4 1.7 2.6 5.5 90 10 12 12
K75-1 0.5 A/1.98 3.2 2.2 3.3 7.1 90 10 13 14
1K1-1 0.75 A/1.98 9.0 3.0 4.5 9.7 90 10 19 16
1K6-1 1.0 B/2.64 10.8 4.3 6.5 13.8 90 16 27 17
2K1-1 1.5 C/3.52 14.8 5.9 8.9 19.0 95 16 39 18
2K7-1 2.0 C/3.52 18.2 7.0 10.5 23.5 95 20 48 19
4K1-1 3.0 D/4.18 22.0 9.0 13.5 34.5 95 25 70 20
Standard series
Heatsinkless series
The Drives in the heatsinkless series are minimized
in volume in order to save space. They are built with
a base plate and need to be installed on an external
sink to dissipate the heat generated, please refer to the
power circuit losses table below.
These drives are typically used in machines, where
space is limited or increased fl exibility in installations
is required.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Technical Data3-phase Supply Voltage 200 - 240 V ± 10 %
1) Heatsinkless versions also available, see page 7.
Order code type: ACS 141-xHx-1.
2) Fuse type: UL class CC or T (symbol KTK-R, JJN or JJS). For non-UL installations IEC269 gG.
Use 140 °F (60 °C) rated power cable (164 °F (75 °C) if Tamb
above 113 °F (45 °C)).
3) The power ratings in HP apply to most 2- and 4-pole motors. The current ratings are the same
regardless of the supply voltages. The rated current of the Drive must be higher than or equal to
the rated motor current to achieve the rated motor power given in the table.
4) Overload current allowed for one minute every 10 minutes.
Nominal ratings Protection limits
Nominal Frame Input Cont. Max Nominal Input Cont. Max Line Power losses
Order motor size/ current output output motor HP current output output fuse2) Power Control
code HP 3) weight current current Constant current current circuit circuit
Variable VT torque CT
Torque
ACS 143-1) HP lbs. A A A HP A A A A W W
K75-1 0.5 A/1.76 3.2 2.2 3.3 0.5 3.2 2.2 3.3 6 13 14
1K1-1 0.75 A/1.76 4.2 3.0 4.5 0.75 4.2 3.0 4.5 6 19 16
1K6-1 1.0 B/2.42 5.3 4.3 6.5 1.0 5.3 4.3 6.5 6 27 17
2K1-1 1.5 C/3.30 7.2 5.9 8.9 1.5 7.2 5.9 8.9 10 39 18
2K7-1 2.0 C/3.30 8.9 7.0 10.5 2.0 8.9 7.0 10.5 10 48 19
4K1-1 3.0 D/3.74 12.0 9.0 13.5 3.0 12.0 9.0 13.5 16 70 20
ACS 401-
0004-2-X 3.0 R1/12.8 10.6 10.6 11.7 2.0 7.5 7.5 11.3 15 70 6
0005-2-X 5.0 " 16.7 16.7 18.4 3.0 10.6 10.6 15.9 25 110 6
0006-2-X 7.5 R2/14.8 24.2 24.2 26.2 5.0 16.7 16.7 25.1 30 165 6
0009-2-X 10.0 " 30.8 30.8 33.9 7.5 24.2 24.2 36.3 40 220 6
0011-2-X 15 R3/40.8 46.2 46.2 50.8 10.0 30.8 30.8 46.2 60 330 6
0016-2-X 20 " 59.4 59.4 65.3 15.0 46.2 46.2 69.3 80 450 6
0020-2-X 25 R4/59.5 74.8 74.8 82.3 20.0 59.4 59.4 89.1 100 600 6
0030-2-X 30 " 88.0 88.0 96.8 25.0 74.8 74.8 112.2 110 740 6
0041-2-X 40 " 114.0 114.0 125.4 30.0 88.0 88.0 132 150 900 6
Switching frequency (in kHz):
ACS 143-: 4 (Standard), 8 (Low-noise), 16 (silent)
ACS 401-: 4 (Standard), 8 (Low-noise)
Protection limits/Overvoltage
Trip limits
- Running V DC: 842 (corr. to 595 V input)
- Start inhibit V DC: 661 (corr. to 380 - 415 V input)
765 (corr. to 440 - 480 V input)
Protection limits/Undervoltage:
- Running V DC: 333 (corr. to 247 V input)
- Start inhibit V DC: 436 (corr. to 380 - 415 V input)
505 (corr. to 440 - 480 V input)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Technical Data3-phase Supply Voltage 380 - 480 V ± 10 %
1) Heatsinkless versions also available, see page 7.
Order code type: ACS 143-xHx-3.
2) Fuse type: UL class CC or T (symbol KTK-R, JJN or JJS). For non-UL installations IEC269 gG.
Use 140 °F (60 °C) rated power cable (164 °F (75 °C) if Tamb
above 113 °F (45 °C)).
3) The power ratings in HP apply to most 2- and 4-pole IEC 34 motors. The current ratings are the
same regardless of the supply voltages. The rated current of the Drive must be higher than or
equal to the rated motor current to achieve the rated motor power given in the table.
4) Overload current allowed for one minute every 10 minutes.
Nominal ratings Protection limits
Nominal Frame Input Cont. Max Nominal Input Cont. Max Line Power losses
Order motor size/ current output output motor HP current output output fuse2) Power Control
code HP weight current current Constant current current circuit circuit
Variable VT torque CT
torque
ACS 143-1) HP lbs. A A A HP A A A A W W
K75-3 0.5 A/1.76 2.0 1.2 1.8 0.5 2.0 1.2 1.8 6 14 14
1K1-3 0.75 A/1.76 2.8 1.7 2.6 0.75 2.8 1.7 2.6 6 20 16
1K6-3 1.0 B/2.64 3.6 2.0 3.0 1.0 3.6 2.0 3.0 6 27 17
2K1-3 1.5 C/4.84 4.8 2.8 4.2 1.5 4.8 2.8 4.2 6 39 18
2K7-3 2.0 C/4.84 5.8 3.6 5.4 2.0 5.8 3.6 5.4 10 48 19
4K1-3 3.0 D/6.05 7.9 4.9 7.4 3.0 7.9 4.9 7.4 10 70 20
ACS 401-
0004-3-X 3.0 R1/17.8 6.2 6.6 7.3 2.0 4.7 4.9 7.4 10 90 6
0005-3-X 5.0 " 8.3 8.8 9.7 3.0 6.2 6.6 9.9 10 120 6
0006-3-x 7.5 " 11.1 11.6 12.8 5.0 8.8 8.8 13.2 16 170 6
0009-3-X 10.0 R2/19.8 14.8 15.3 16.8 7.5 11.1 11.6 17.4 16 230 6
0011-3-X 15 " 21.5 23 25.3 10.0 14.8 15.3 23 25 330 6
0016-3-X 20 R3/40.8 29 30 33 15.0 21.5 23 34 35 450 6
0020-3-X 25 " 35 38 42 20.0 29 30 45 50 560 6
0025-3-X 30 R4/59.5 41 44 48 25 35 38 57 50 660 6
0030-3-X 40 " 56 59 65 30 41 44 66 60 900 6
0041-3-X 50 " 68 72 79 40 56 59 88 80 1100 6
Switching frequency (in kHz):
ACS 143-: 4 (Standard), 8 (Low-noise),16 (silent)
ACS 401-: 4 (Standard), 8 (Low-noise)
Protection limits/Overvoltage
Trip limits
- Running V DC: 842 (corr. to 595 V input)
- Start inhibit V DC: 661 (corr. to 380 - 415 V input)
765 (corr. to 440 - 480 V input)
Protection limits/Undervoltage:
- Running V DC: 333 (corr. to 247 V input)
- Start inhibit V DC: 436 (corr. to 380 - 415 V input)
505 (corr. to 440 - 480 V input)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Technical DataConnection Diagrams ACS 100 & ACS 140
DI confi guration
ABB standard
DI confi guration
3-wire
The supply voltage may be switched on only after the cover has been refi tted and snapped into place.
Please refer to the appropriate User’s Manual for detailed connection instructions.
ACS 100 ACS 140
Frequency reference value
from an external current
source
DI confi guration
default (0)
DI confi guration
default (1)
Frequency reference value
from an external current
source
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Technical DataConnection Diagrams ACS 400
ACS 400
X3
RS485 Multidrop application
J2
RS485
interf.
Other Modbus
devices
The supply voltage may be switched on only after the cover has been refi tted and snapped into place.
Please refer to the ACS 400 User’s Manual for detailed connection instructions.
ACS 400 ACS 400
DI confi guration
NPN connected (sink)
DI confi guration
PNP connected (source)
Signal termination is
selected by jumper J2
not terminated.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
ACS100-PAN control panel for
ACS 100/140/400
ACS 100/140 drives are provided with a detachable
control panel as standard.
The ACS-100-PAN can also be used for copying
parameters from one ACS 100 to another or from one
ACS 140 to another. Firmware versions for each drive
must be the same.
OptionsControl Panels
control
modes
fault
indicator
display
modes
start/stop
direction
units
shaft
direction
menu
enter
up/down
ACS-PAN-A control panel for
ACS 400
ACS-PAN-A is a detachable multi-lingual alphanu-
meric control panel with LCD display. The control
panel can be used for copying parameters between
ACS 400 drives. Firmware versions for each drive
must be the same.
control modes
display
modes
menu
green LED
red LED
reset
run
indicator
shaft
direction
up/down
enter
start/stop
LOC/REM direction
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
This option includes:
Gasket, 10 ft. (3 m) connection
cable ACS...panel, drilling
template and all materials
needed to mount the panel.
Mounting Plate or Door
Mounting Screws
with Sleeve
Clamp for Cable
Control Panel
GasketCable Hole
Plastic Clamp with Tape
Panel Extension Cable Kit for ACS 100/140/400
OptionsDriveWindow Light
Comp-AC set-up and control tool - Win95, Win98, WinNT compatible
Windows-based, user-friendly
ABB's DriveWindow Light is an easy-to-use tool for
commissioning and control of drives.
It provides even more fl exibility and operating
possibilities for the ACS 140 and ACS 400. It
has features for programming, monitoring, trouble
shooting and maintenance. It is also an excellent
training tool. DriveWindow Light is free of charge and
can be downloaded.
DriveWindow Light operates both off- and on-line.
No additional PC hardware required. DriveWindow
Light uses the PC's RS-232/485 port and Modbus
serial communication protocol.
DriveWindow Light features
• All software included for drive to screen
operation in one package.
• Off- and on-line viewing and changing of
drive parameters.
• Backup and restore parameters. In a fault
situation the parameters can be reloaded
resulting in time savings.
• Monitoring of actual signal values.
• Datalogger for fast and accurate
measurements.
• Fault logger. DriveWindow Light indicates
the reason for the fault, and also collects
fault history data from the drive.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
RS485 terminal X2
RS485 bus
termination
jumpers S2
and S3
RS232/RS485
mode select jumper
S5
communication
speed setting
DIP-switch S1
RS232 terminal X4
RS485 terminal X3
LEDs:RxDTxDpower
3 (A)
2 (C)
1 (B)
3 (A)
2 (C)
1 (B)
15
OptionsFieldbus Control
Fieldbus Control Highlights
Greater Manufacturing Flexibility
Drive ControlThe drive Control Word (16 bit) provides a wide vari-
ety of functions from Start, Stop and Reset to Ramp
Generator control. Typical setpoint values like Speed
and Torque can be transmitted to the drive with 15
bit accuracy.
Drive MonitoringFrequency and current can be monitored and used to
provide control data for the manufacturing process.
Drive DiagnosticsAccurate and reliable diagnostic information can be
obtained via the drive Alarm and Fault Words, help-
ing to cut drive down-time and production losses.
Drive Parameter HandlingTotal integration of the drives into the production
process is achieved by drive parameter reading and
writing.
Reduced Installation and Engineering Effort
Connection
A single twisted pair replaces the large amount of
control cabling required in conventional systems.
This reduces costs and increases system reliability.
Commissioning and Assembly
The modular machine confi guration allows pre-
commissioning of single machine sections and
provides easy and fast assembly of the complete
installation.
ABB AC Drives can connect to all major automa-
tion systems. This is achieved with a dedicated gate-
way concept between the fi eldbus systems and ABB
Distributed Drive Communication System1) (DDCS).
DDCS is a high speed optical link combining fast data
transfer and excellent noise immunity.
The wide range of fi eldbus gateways means that the
automation system can be chosen independently of
the drives.
1) Available as an option for ACS 400
RS232/485 adapter for ACS 140/400
When an RS 232/485 adapter is used, several
ACS 140 or ACS 400 drives can be controlled using
Modbus protocol.
ACS 140 Gateways
RS 232/485
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Gateway Module Technical Data
Power supplySupply voltage: 24 VDC ±10 %
Current consumption: 60..160 mA
ConnectionsBus-line: Screw terminals
Drive link: Fiber optics
Environmental limitsAmbient temperature: 0..50 °C
Altitude: up to 2000 m ASL
EnclosureDegree of protection: IP 20
Drive interfaceProtocol: DDCS
Baudrate: 4 Mbit/s
N.A. = Not Applicable
Fieldbus
Profi bus
InterBus-S
Modbus
Modbus Plus1)
DeviceNet
CANopen2)
Protocol Mode
FMS. DP
I/O. PCP
RTU
N.A.
N.A.
N.A.
Device Profi le
Adjustable Speed
Drives
ABB Drives
ABB Drives
ABB Drives
AC Drives,
DC Drives
Drives and Motion
Control
Baudrate
(min.-max.)
9.6-1500 kbit/s
500 kbit/s
1.2-19.2 kbit/s
1000 kbit/s
125-500 kbit/s
1000 kbit/s
Service Channel
(Parameter R/W)
Supported
Supported
Supported
Supported
Supported
Supported
DDCS adapter for ACS 400 allows
connection of fi eldbus modules.
The ACS 400 provides a Modbus RS 485 connection.
In addition, the following gateways are available for
use with the optional DDCS module.
1) Software version 1.3 or later is compatible with ACS 400.2) Fieldbus module version 1.2 or later is compatible with ACS 400.
DDCS
OptionsACS 400 Gateways
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
OptionsEMC Filters
Series ACS 100/140-IFxx-x
ABB ACS 100, ACS 140 and ACS 400 drives meet the
requirements of the Second Environment as standard.
An appropriate EMC fi lter is required only when oper-
ating in the First Environment.
Product Standard EN6180003 defi nes the First Envi-
ronment as an installation that includes domestic prem-
ises. It also includes establisments connected directly,
without intermediate transformers, to a low voltage
power supply network which supplies buildings used
for domestic purposes. A Second Environment instal-
lation includes all others than those connected directly
to a low voltage power supply network which supports
buildings used for domestic purposes.
Filters are provided in a fi nger-safe protected chassis (IP 20)
Drive Model # Filter Model # A B C D E F G H I Max. Motor Cable length ft./m
ACS 101/141- in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm Switching Frequency
4 kHz 8 kHz 16 kHz
K18-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 7.09/180 1.65/42 90/30 60/20 30/10
K25-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 7.09/180 1.65/42 90/30 60/20 30/10
K37-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 7.09/180 1.65/42 90/30 60/20 30/10
K75-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 7.09/180 1.65/42 90/30 60/20 30/10
1K1-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 7.09/180 1.65/42 90/30 60/20 30/10
1K6-1 ACS 100/140-1FAB-1 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.19/81 7.37/186 8.48/217 1.65/42 90/30 60/20 30/10
2K1-1 ACS 100/140-1FCD-1 2.28/58 10.71/272 1.0/25 2.28/58 8.19/208 3.19/81 11.26/2867.37/200 1.65/42 90/30 60/20 30/10
2K7-1 ACS 100/140-1FCD-1 2.28/58 10.71/272 1.0/25 2.28/58 8.19/208 3.19/81 11.26/2867.37/200 1.65/42 90/30 60/20 30/10
4K1-1 ACS 100/140-1FCD-1 2.28/58 10.71/272 1.0/25 2.28/58 9.25/235 3.19/81 11.26/2868.15/207 1.65/42 90/30 60/20 30/10
1-phase supply voltage 200 - 240 V, 0.16 - 3 HP
3-phase supply voltage 380 - 480 V, 0.5 - 3 HP
Drive Model # Filter order code A B C D E F G H I Max. Motor Cable length ft./m
ACS 143- in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm Switching Frequency
4 kHz 8 kHz 16 kHz
K75-3 ACS 140-1FAB-3 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.14/81 7.32/186 7.52/191 1.65/42 90/30 60/20 30/10
1K1-3 ACS 140-1FAB-3 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.14/81 7.32/186 7.52/191 1.65/42 90/30 60/20 30/10
1K6-3 ACS 140-1FAB-3 2.28/58 6.77/172 1.0/25 2.28/58 5.35/136 3.14/81 7.32/186 8.98/228 1.65/42 90/30 60/20 30/10
2K1-3 ACS 140-1FAB-3 2.28/58 10.71/272 1.0/25 2.28/58 8.19/208 3.14/81 11.26/286 8.31/211 1.65/42 90/30 60/20 30/10
2K7-3 ACS 140-1FCD-3 2.28/58 10.71/272 1.0/25 2.28/58 8.19/208 3.14/81 11.26/286 8.31/211 1.65/42 90/30 60/20 30/10
4K1-3 ACS 140-1FCD-3 2.28/58 10.71/272 1.0/25 2.28/58 9.25/235 3.14/81 11.26/286 8.58/218 1.65/42 90/30 60/20 30/10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Selection table and dimensions for IP 20 EMC fi lters
3-phase supply voltage 380 - 480 V, 3.0 - 37 kW
OptionsEMC Filters
Series ACS 400-IFx1-3
Always use RFI Ferrite ACS-CHK-A or ACS-CHK-C with series ACS400-IFx1-3 EMC fi lters. The
motor cable, including the shield, must be fed through the hole in the ferrite. Ferrites ACS-CHK-A
or ACS-CHK-C are supplied in the same package as the input fi lter.
Selection table and
dimensions for
NEMA 1 (IP 21) /
NEMA 12 (IP 54)
EMC fi lter covers
EMC fi lter type NEMA 12 protection Cable J K L M N
ACS 401- cover model # diameter in/mm in/mm in/mm in/mm in/mm
-IF11-3 IFC-99-001 9-16 1.38/35 1.77/45 max. 1.50/38 max. 1.50/38 max. 21/533.5
IFC-99-002 13-20
-IF21-3 IFC-99-002 13-20 1.38/35 1.77/45 max. 1.50/38 max. 1.50/38 max. 24.92/633
IFC-99-003 18-25
-IF31-3 IFC-99-004 13-20 2.56/65 3.35/85 max. 1.85/47 max. 1.85/47 max. 23.39/594
IFC-99-005 18-25
IFC-99-006 25-31
-IF41-3 IFC-99-005 18-25 2.56/65 3.35/85 max. 1.85/47 max. 1.85/47 max. 25.35/644
IFC-99-006 25-31
IFC-99-007 32-38
Drive Filter Model # A B C D E F G H H I Max.1) Motor Cable length ft./m
Model # ACS 401- NEMA 1 NEMA 12 Switching Frequency
ACS 401- in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm 4 kHz 8 kHz
0004 IF11-3 3.54/90 14.25/362 1.38/35 3.86/98 12.52/318 4.72/120 14.88/378 10.59/269 11.81/300 2.36/60 300/100 -
0005 IF11-3 3.54/90 14.25/362 1.38/35 3.86/98 12.52/318 4.72/120 14.88/378 10.59/269 11.81/300 2.36/60 300/100 -
0006 IF11-3 3.54/90 14.25/362 1.38/35 3.86/98 12.52/318 4.72/120 14.88/378 10.59/269 11.81/300 2.36/60 300/100 -
0009 IF21-3 3.54/90 18.15/461 1.38/35 3.86/98 16.42/417 4.72/120 18.78/477 11.06/281 12.32/313 2.36/60 300/100 300/100
0011 IF21-3 3.54/90 18.15/461 1.38/35 3.86/98 16.42/417 4.72/120 18.78/477 11.06/281 12.32/313 2.36/60 300/100 300/100
0016 IF31-3 5.51/140 12.99/330 1.97/50 3.86/98 20.79/528 6.69/170 13.78/350 - - 3.15/80 300/100 300/100
0020 IF31-3 5.51/140 12.99/330 1.97/50 3.86/98 20.79/528 6.69/170 13.78/350 - - 3.15/80 300/100 300/100
0025 IF41-3 6.30/160 14.96/380 1.97/50 3.86/98 24.37/619 7.87/200 15.75/400 - - 3.15/80 300/100 300/100
0030 IF41-3 6.30/160 14.96/380 1.97/50 3.86/98 24.37/619 7.87/200 15.75/400 - - 3.15/80 300/100 300/100
0041 IF41-3 6.30/160 14.96/380 1.97/50 3.86/98 24.37/619 7.87/200 15.75/400 - - 3.15/80 300/100 300/100
Converter A B C D Max motor cable length
type fsw = 4 kHz, fsw = 8 kHz
ACS 401- in/mm in/mm in/mm in/mm ft./m
0004 17.83/453 4.02/102 3.43/87 4.57/116 30/10
0005 17.83/453 4.02/102 3.43/87 4.57/116 30/10
0006 17.83/453 4.02/102 3.43/87 4.57/116 30/10
0009 21.77/553 4.49/114 3.43/87 4.57/116 30/10
0011 21.77/553 4.49/114 3.43/87 4.57/116 30/10
Series ACS 400-IF22-3
Dimensions for regular NEMA 1/
IP 21 EMC fi lter for ACS 400
frequency converter
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
OptionsDynamic Braking Units
Braking unit Frequency converter Resistor Continuous Max. output
order code input voltage OHM output W 20 s W
ACS-BRK-A 200 – 240 VAC 400 150 350
380 – 480 VAC 1000
ACS-BRK-B 200 – 240 VAC 150 400 1000
380 – 480 VAC 2400
ACS-BRK-C 200 – 240 VAC 32 2000 4500
380 – 480 VAC 12000
ACS-BRK-D 200 – 240 VAC 10.5 7000 14000
380 – 480 VAC 42000
ACS-BRK-F 200 – 240 VAC 50 400 2400
–
Braking unit technical data
Braking unit Width Height Depth H1 W1 Weight
order code in/mm in/mm in/mm in/mm in/mm lbs./kg
ACS-BRK-A 3.54/90 9.45/240 7.09/180 7.72/196 2.64/67 2.65/1.2
ACS-BRK-B 3.54/90 11.81/300 11.22/285 9.06/230 2.64/67 3.31/1.5
ACS-BRK-C 5.91/150 19.69/500 13.66/347 19.13/486 3.35/136 16.53/7.5
ACS-BRK-D 10.63/270 23.62/600 17.72/450 22.91/582 9.92/252 45.19/20.5
ACS-BRK-F 3.54/90 11.81/300 11.22/285 9.06/230 2.64/67 3.31/1.5
Dimensions
Compact-sized
braking units with
braking chopper
and resistor.