abb ach550 hvac vsd commissioning - control … more information call 1800 557 705 or email...

2
for more information call 1800 557 705 or email [email protected] www.control-logic.com.au industrial. electrical. automation. tech tip ABB ACH550 HVAC VSD COMMISSIONING Have you ever wondered which parameters to set when trying to commission an ABB ACH550 HVAC VSD to maintain a pressure in a building stairwell? Simply use this guide below to short cut the learning process and make your life a bit easier next time. Summary... PRODUCT/SERVICE HOW THIS WILL ASSIST ABB ACH550 HVAC VSD Know what parameters to set to maintain a pressure in a building stairwell Peter Tennent | September 2016

Upload: nguyentruc

Post on 02-May-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

for more information call 1800 557 705 or email [email protected]

industrial.electrical.

automation.

tech tip

ABB ACH550 HVAC VSDCOMMISSIONINGHave you ever wondered which parameters to set when trying to commission an ABB ACH550 HVAC VSD to maintain a pressure in a building stairwell?

Simply use this guide below to short cut the learning process and make your life a bit easier next time.

Summary...

PRODUCT/SERVICE

HOW THIS WILL ASSIST

ABB ACH550 HVAC VSD

Know what parameters to set to maintain a pressure in a building stairwell

Peter Tennent | September 2016

for more information call 1800 557 705 or email [email protected]

industrial.electrical.

automation.

tech tip

Note 1Analogue input 1 DIP switch selector is by default set to voltage so if the transducer has a 0 to 10 volt output then leave this switch in the left hand side position. If however the transducer output is mA then move this switch to the right hand side position.

ABB ACH550 HVAC VSD