ABB ACH550 HVAC VSDCOMMISSIONINGHave you ever wondered which parameters to set when trying to commission an ABB ACH550 HVAC VSD to maintain a pressure in a building stairwell?
Simply use this guide below to short cut the learning process and make your life a bit easier next time.
Summary...
PRODUCT/SERVICE
HOW THIS WILL ASSIST
ABB ACH550 HVAC VSD
Know what parameters to set to maintain a pressure in a building stairwell
Peter Tennent | September 2016
for more information call 1800 557 705 or email [email protected]
industrial.electrical.
automation.
tech tip
Note 1Analogue input 1 DIP switch selector is by default set to voltage so if the transducer has a 0 to 10 volt output then leave this switch in the left hand side position. If however the transducer output is mA then move this switch to the right hand side position.