version 01 20 इरिसेट Page 1/12 IRISET/ESL MTKYO-09 इरिसेट विद् युत वसगनवग योगशाा योग : एमटीकेिाईओ 09 IRISET ELECTRICAL SIGNALLING LABORATORY EXPERIMENT NO.: MTKYO - 09 नाम Name : _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ अनुमाक Roll No : _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ पाठय़म Course : _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ दिनाक Date : _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ात अक Marks Awarded : अनुिेशक का अधाि Instructor Initial : STUDY OF COMMUNICATION NETWORK OF K5BMC DISTRIBUTED ELECTRONIC INTERLOCKING SYSTEM AND COMMUNICATION FAILURES K5BMC Electronic Interlocking System is a fail-safe Interlocking system designed to meet CENELEC SIL-4 Standards. K5BMC system can be configured as centralized or as well as distributed interlocking system. It is very much suitable for distributed type electronic interlocking system. It is very much effective in Auto section / IBH concept of signalling. It is based on Two Out of Two (2oo2) architecture with a hot standby provision and automatic change-over facility. Logic sub rack (LK7-C) uses two independent channels for computing the vital interlocking. Hot standby with automatic change-over facility is provided. Redundant optical fiber communication provided between LK7-C and Field units (ET/EP-5 sub rack) & CCIP (ET/EM-6 sub rack. In Logic Sub-rack for handling communication 2 communication cards (FSIO and FSIO-EX) used for each system. In generally FSIO card used for communication between Logic sub rack and Field units (ET/EP-5) and FSIO-EX cards used for communication between Logic sub rack and CCIP & operator VDU.LK7-C to Field units & LK7-C to CCIP units connected in daisy chain topology. ET/EP-5 sub rack provides interface between filed gears and logic sub rack. ET/EP-5 Sub rack consist of Input & output card (ETPIO2) and Power Supply and communication card (LINE2B). LINE2B cards used for communication between field gears and logic sub rack. LINE2B card have 2 optical fiber channels for communication. ET/EM-6 sub rack provides interface between CCIP and logic sub rack. ET/EP-6 sub rack consist of Input & output card (MMIF2) and Power Supply and communication card (LINEM2).

Upload: others

Post on 22-Aug-2021

3 views

Category:

Documents


0 download

TRANSCRIPT


: – 09
IRISET

STUDY OF COMMUNICATION NETWORK OF K5BMC DISTRIBUTED ELECTRONIC
INTERLOCKING SYSTEM AND COMMUNICATION FAILURES
K5BMC Electronic Interlocking System is a fail-safe Interlocking system designed to meet
CENELEC SIL-4 Standards. K5BMC system can be configured as centralized or as well as
distributed interlocking system. It is very much suitable for distributed type electronic interlocking
system. It is very much effective in Auto section / IBH concept of signalling. It is based on Two Out
of Two (2oo2) architecture with a hot standby provision and automatic change-over facility.
Logic sub rack (LK7-C) uses two independent channels for computing the vital interlocking.
Hot standby with automatic change-over facility is provided. Redundant optical fiber
communication provided between LK7-C and Field units (ET/EP-5 sub rack) & CCIP (ET/EM-6 sub
rack. In Logic Sub-rack for handling communication 2 communication cards (FSIO and FSIO-EX)
used for each system. In generally FSIO card used for communication between Logic sub rack
and Field units (ET/EP-5) and FSIO-EX cards used for communication between Logic sub rack
and CCIP & operator VDU.LK7-C to Field units & LK7-C to CCIP units connected in daisy chain
topology.
ET/EP-5 sub rack provides interface between filed gears and logic sub rack. ET/EP-5 Sub
rack consist of Input & output card (ETPIO2) and Power Supply and communication card
(LINE2B). LINE2B cards used for communication between field gears and logic sub rack. LINE2B
card have 2 optical fiber channels for communication.
ET/EM-6 sub rack provides interface between CCIP and logic sub rack. ET/EP-6 sub rack
consist of Input & output card (MMIF2) and Power Supply and communication card (LINEM2).
version 01 20
Page 2/12 IRISET/ESL –MTKYO-09
LINEM2 cards used for communication between Panel and logic sub rack. LINEM2 card have 2
optical fiber channels for communication.
Logic sub rack to Operator VDU, Maintenance VDU, and Journal Module connected through
optical fiber. In Opera VDU and Maintenance VDU one communication interface card (INIO2) used
to connect to logic sub rack. Datalogger connected to Logic sub rack to through Journal Module,
Journal consist of optical to electrical conversion cards.
LOGIC SUB RACK Communication Modules:
FSIO & FIO7 [P] cards:
• Each logic sub rack consists of one FSIO card which is placed next to F486-4I card. The FI07
[P] board is connected to the FSIO card; it is placed on the rear side of logic sub rack.
• FSIO card together with FI07 (P) card is used for communication of F486-4I with ET/EP5 sub
racks and MTC.FI07 [P] acts like electrical to optical converter for FSIO board.
• FIO7 [P] has 5 multimode fiber optic communication channels in that 3 channels are used for
communication with ET/EP5 sub racks and 1 channel is used for communication with MTC, 1
Channel is reserved.
• To one channel a maximum of 15 I/O boards of ET sub racks can be connected
• The data transmission rate between MTC & FSIO is 307.2Kbps and ET/EP5 sub rack & FSIO
is 31.2Kbps
FSIO-EX & EXT-FI07 [P] cards:
• Each logic sub rack consists of one FSIO-EX card which is placed next to FSIO card. The EXT-
FI07 [P] board is connected to the FSIO-EX card; it is placed on the rear side of logic sub rack.
• FSIO-EX card together with EXT FIO7 [P] card is used for communication between Logic sub
rack and operator VDU/Control panel. Ext FIO7P is a electrical to optical converter for FSIO-Ex
board
• EXT-FI07 [P] has 3 multimode fiber optic communication channels; in that two channels are
meant for communication with Operator VDU and /or EM6 (Panel processor) .One channel is
kept reserved.
• Data transmission rate of FSIO –Ex and Ext FIO7P is 31.2 kbps
DID Card:
• Each system is provided with one DID Card which is placed in rear of the logic sub rack
• It is used for data transmission between CPU cards of system I & system II
ET SUB RACK Communication Modules:
LINE2B modules:
• It is the communication cum power supply card in ET sub rack. In each ET sub rack two number
of LINE2B cards are provided.
• This card has two multimode optical channels for communication with Logic sub rack and other
ET sub racks.
• It transmits data in serial transmission method with a data rate of 31.2kbps using optical cables.
EM6 SUB RACK Communication Modules:
LINEM2:
• First two slot of EM6 Rack is allotted for LINEM2 card of S1 & S2 respectively.
• LINEM2 card is used for the communication between logic rack and EM6 sub rack.
• LINEM2 card is also act as a Power Supply Card for EM6 sub rack.
• LINEM2 card is having two optical channels. One channel is for Input connection from Logic
Sub rack and the other channel is used to connect with other EM6 Sub rack.
OTHER COMMUNICATION MODULES:
SPHC-TT:
• SPHC-TT is the optical splitter card. It’s used to divide one communication line into 2 lines.
• In generally it is used to communicate between logic sub rack with MTC and Journal module.
version 01 20
SPHC-PA:
• SPHC-PA is the optical convertor card. It is used to convert multi mode to single mode and
vice versa.
• K5BMC All communication modules (FIO7 [P], EXT-FIO7 [P], LINE2B, LINEM2) interface is
multimode optical fiber. To transmit data to long distance multimode is converted to single
mode using SPHC-PA and used.
INIO2:
• INIO2 is a communication card for operator console and maintenance console to logic sub
rack. INIO2 is having two optical connectors to connect with System1 and System2. Two
types of INIO2 cards are available.
INIO2-ET (OPC)
INIO2-MT (MTC)
• Single INIO2-ET card is enough to drive the OPC communication. But for MTC
communication 2 no of INIO2-MT cards are required.
DATALOGGER CONNECTION:
• External Data logger connected to Logic sub-rack using Journal Module and Protocol
convertor, Without Journal module external data logger can be directly connected to Data
logger also.
• When External Data logger connected using Journal module, Logic sub Rack FIO7 [P]
cards Maintenance Line optical channel will be used for connecting Maintenance terminal
and external data Logger.
• Journal Module consist of optical to electrical convertor card (ZNIO2) which receives optical
data from Logic sub rack converts it to electrical data. Electrical data will sent to Protocol
convertor and data logger through ZSIO2 card.
• When External Data logger connected without Journal module, in Logic sub Rack EXT -
FIO7 [P] cards serial communication port (CN5) will be used. CN5 is the Serial
Communication port supports which supports RS-485 interface.
• To prevent surges at Logic sub rack side and protocol convertor side Optical to Electrical
and vice versa convertor cards used
• CN5 will be connected to electrical (serial) to optical convertor and optical data transmitted
to protocol convertor.
• At protocol convertor received optical data will be converted to electrical data using optical
to electrical (serial) convertor.
FIG.1 TYPICAL SYSTEM CONFIGURATION
FIG.2 TYPICAL K5BMC DISTRIBUTED ELECTRONIC INTERLOCKING SYSTEM CONFIGURATION DIAGRAM USING JOURNAL MODULE
version 01 20
FIG.3 TYPICAL K5BMC DISTRIBUTED ELECTRONIC INTERLOCKING SYSTEM CONFIGURATION DIAGRAM WITHOUTJOURNAL MODULE
version 01 20
-/ - 09 Page 8/12 IRISET/ MTKYO - 09 IRISET/ESL –53
FSIO CARD INDICATIONS
FSIO-EX CARD INDICATIONS
Show status of ET SIO lines Blink = Have transfer data, OFF= No transfer data 1 T: Line 1 Self SYS Sending 1 R(left): Line 1 Self SYS Receiving 1 R(right): Line 1 Other SYS Receiving 2 T: Line 2 Self SYS Sending 2 R(left): Line 2 Self SYS Receiving 2 R(right): Line 2 Other SYS Receiving 3 T: Line 3 Self SYS Sending 3 R(left): Line 3 Self SYS Receiving 3 R(right): Line 3 Other SYS Receiving
Show status of ET SIO lines. Blink = Have transfer data, OFF= No transfer data 1 T: Line 4 Self SYS Sending 1 R(left): Line 4 Self SYS Receiving 1 R(right): Line 4 Other SYS Receiving 2 T: Line 5 Self SYS Sending 2 R(left): Line 5 Self SYS Receiving 2 R(right): Line 5 Other SYS Receiving 3 T: Reserved 3 R(left): Reserved 3 R(right): Reserved
LINE2B CARD INDICATIONS
LED5 Meaning ----5V power supply normal Indication status----ON for normal
LINEM2 CARD INDICATIONS
NORMAL Meaning ---- 5V power supply normal Indication status---- ON for normal, OFF for fault
RXD Meaning ---- Reception from safety system Indication status---- ON during reception
TXD Meaning ---- Transmission to safety system Indication status---- ON during transmission
LED4 Not Used
LED5 Not Used
version 01 20
-/ - 09 Page 9/12 IRISET/ MTKYO - 09 IRISET/ESL –53
INI02 CARD INDICATIONS
SA Lighted when transmission data exist in A channel
RA Lighted when reception data exist in A channel
SB Lighted when transmission data exist in B channel
RB Lighted when reception data exist in B channel
Ach-SD FC type optical connector for transmission of A channel
Ach-RD FC type optical connector for reception of A channel
Bch-SD FC type optical connector for transmission of B channel
Bch-RD FC type optical connector for reception of B channel
version 01 20
-/ - 09 Page 10/12 IRISET/ MTKYO - 09 IRISET/ESL –53
Review Questions Q1.Draw IRISET Distributed Electronic interlocking system configuration diagram?
version 01 20
-/ - 09 Page 11/12 IRISET/ MTKYO - 09 IRISET/ESL –53
Q2.South cabins S1 home signal cleared for Main Line, after clearing the signal north cabins
ET/EP-5 sub rack losses communication with logic sub rack. What is the condition of S1
signal and note all the observations on VDU?
Q3. Central cabin – in Logic sub rack System1 is in ONLINE. North cabins S30 signal cleared for
up loop line, after clearing the signal power supply failed to North cabins system1 LINE2B
card. What is the condition of the signal and note all the observations on VDU?
Q4. Central cabin- in Logic sub rack System1 is in ONLINE, system2 is Power OFF condition.
After clearing the North cabins signal, North cabins system1 LINE2B card failed. What is the
condition of the signal and note all the observations on VDU?
Q5.Why external Datalogger is required? How External Datalogger is connected to Logic sub
rack system?