a study material on unit-i fundamentals of …

17
SWITCHGEAR AND PROTECTION-15EE53T DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 1 A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF PROTECTION-7 Hours PREPARED BY KEDARNATH .Y LECTURER IN E & E GOVERNMENT POLYTECHNIC RAICHUR

Upload: others

Post on 10-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 1

A STUDY MATERIAL ON

UNIT-I

FUNDAMENTALS OF PROTECTION-7 Hours

PREPARED BY

KEDARNATH .Y

LECTURER IN E & E

GOVERNMENT POLYTECHNIC RAICHUR

Page 2: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 2

1

UNIT-I

FUNDAMENTALS OF PROTECTION

1.1

Sources of Fault Power, Illustrate the Phenomena of Short Circuit

with the help of a general circuit diagram

1.2

Types of faults & Harmful Effects of short circuit current,

Symmetrical Faults on Three Phase Systems

1.3

Importance of calculation of Short Circuit Current, Define

Percentage reactance and Base KVA, Meaning of Reactor

1.4

Use of current limiting reactors & their arrangements, List the steps

for Symmetrical Fault Calculations

1.5 Simple Problems on Symmetrical Fault Calculations.

1.6

Causes of over voltages, Lighting phenomena &over voltage due to

lightning, Types of lightning arresters

1.7

Lightning arresters & surge absorbers & their Construction &

principle of operation.

Page 3: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 3

UNIT-I

FUNDAMENTALS OF PROTECTION

SOURCES OF FAULT POWER

Mainly there are three sources which can feed into the short circuit of motors

in the power system. The sources are:-

1. Generators.

2. Synchronous Motors and Synchronous Condensers.

3. Induction Motors.

Source 1. Generators as a Source of Fault Power:

The generators are driven by prime movers and when the short circuit occurs, the

generators continue to run at normal speed and the excitation is also maintained.

Thus the normal voltage is continued to be generated, and due to this generated

voltage an enormous current is fed to the fault point which is limited by the

impedance of the generator and that of the circuit up to the fault point.

Source 2. Synchronous Motor as a Source of Fault Power:

Synchronous motors are similar to synchronous generators in construction. They

have dc excitation and draw ac power from the power system and convert it into

mechanical power. On occurrence of a short circuit, the system voltage is

considerably reduced (almost to zero) and so supply of electrical power to the

motor is stopped.

As a result, the motor starts slowing down, but the flywheel and inertia of the

motor prevents it from slowing down instead drives it as a prime mover. As the dc

excitation is maintained, the synchronous motor starts operating as a

Synchronous generator.

Mechanical energy stored in the flywheel and the rotor is thus converted into

electrical energy and fed to the fault point. The magnitude of short circuit current

which it can supply to the fault point depends on the output kW, reactance and

voltage rating of the motor.

Source 3. Induction Motor as a Source of Fault Power:

Like synchronous motor the induction motor also behaves like a generator at the

time of short circuit. The difference between them is that the induction motor does

Page 4: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 4

not have dc excitation, but during normal operation the flux from the stator

appears to be as if is being produced from the dc winding.

On occurrence of a short circuit on a system, the terminal voltage across the

motor terminals drops to almost zero suddenly, the flux cutting the rotor does not

change instantaneously, and the inertia of the motor continues to drive it, thus it

also behaves as a generator and starts feeding the fault point until the stator flux

decays.

Although, synchronous motors and induction motors act as generators only for a

short intervals; but they definitely produce sufficient power to cause momentary

duty on the circuit breakers.

ILLUSTRATE THE PHENOMENA OF SHORT CIRCUIT WITH THE

HELP OF GENERAL CIRCUIT DIAGRAM

SHORT-CIRCUIT

Whenever a fault occurs on a network such that a large current flows in one or more

phases, a short-circuit is said to have occurred.

When a short circuit occurs, a heavy current called short circuit current flows

through the circuit.This can be beautifully illustrated by referring to Fig. 16.6 where a single

phase generator of voltage( V) and internal impedance( Z i) is supplying to a load Z .

Under normal conditions, the current in the circuit is limited by *load impedance (Z).

However, if the load terminals get shorted due to any reason,the circuit impedance is

reduced to a very low value being (Z i) in this case. As (Z i) is very small, therefore, a large

current flows through the circuit. This is called short-circuit current.

TYPES OF FAULTS IN A POWER SYSTEM

A fault occurs when two or more conductors that normally operate with a potential

difference come in contact with each other. These faults may be caused by sudden failure of

a piece of equipment or short-circuit to overhead lines or by insulation failure resulting from

lightning surges.

The faults in a 3-phase system can be classified into two main categories viz.

Page 5: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 5

(i) Symmetrical faults

(ii) Unsymmetrical faults

(i) Symmetrical faults. That fault which gives rise to symmetrical fault currents (i.e.

equal faults currents with 120o displacement) is called a symmetrical fault. The most

common example of symmetrical fault is when all the three conductors of a 3-phase line are

brought together simultaneously into a short-circuit condition.

(ii) Unsymmetrical faults.

Those faults which give rise to unsymmetrical currents (i.e. un-equal line currents

with unequal displacement) are called unsymmetrical faults. The unsymmetrical faults may

take one of the following forms :

(a) Single line-to-ground fault(L-G)

(b) Line-to-line fault(L-L)

(c) Double line-to-ground fault(LL-G)

The great majority of faults on the power system are of unsymmetrical nature; the most

common type being a short-circuit from one line to ground.

HARMFUL EFFECTS OF SHORT-CIRCUIT CURRENT

When a short-circuit occurs, the current in the system increases to an abnormally high value

while the system voltage decreases to a low value.

(i) The heavy current due to short-circuit causes excessive heating which may result in

fire or explosion. Sometimes short-circuit takes the form of an arc and causes considerable

damage to the system.

(ii) An arc on a transmission line not cleared quickly will burn the Conductor severely

causing it to break, resulting in a long time interruption of the line.

(iii) The low voltage created by the fault has a very harmful effect on the service

rendered by the power system.

iv) If the voltage remains low for even a few seconds, the consumers’ motors may be

shutdown and generators on the power system may become unstable.

SYMMETRICAL FAULTS ON THREE PHASE SYSTEM:-

That fault on the power system which gives rise to symmetrical fault currents (i.e. equal fault

currents in the lines with 120o displacement) is called a symmetrical fault.

Page 6: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 6

The symmetrical fault occurs when all the three conductors of a 3-phase line are brought

together simultaneously into a short circuit condition as shown in the above figure. This type

of fault gives rise to symmetrical currents i.e. equal fault currents with 120o displacement.

Thus referring to the above figure,fault currents IR, IY and IB will be equal in magnitude with

120o displacement among them. Because of balanced nature of fault, only one phase need

be considered in calculations since condition in the other two phases will also be similar. The

following points may be particularly noted :

(i) The symmetrical fault rarely occurs in practice as majority of the faults are of

unsymmetrical in nature

(ii) The symmetrical fault is the most severe and imposes more heavy duty on the circuit

breaker.

IMPORTANCE OF CALCULATION OF SHORT CIRCUIT CURRENTS

Most of the failures on the power system lead to short-circuit fault and cause heavy current

to flow in the system.

(i) A short-circuit on the power system is cleared by a circuit breaker or a fuse. It is

necessary,therefore, to know the maximum possible values of short-circuit current so that

switchgear of suitable rating may be installed to interrupt them.

(ii) The magnitude of short-circuit current determines the setting and sometimes the types

and location of protective system.

(iii) The magnitude of short-circuit current determines the size of the protective reactors

which must be inserted in the system so that the circuit breaker is able to withstand the

fault current.

(iv) The calculation of short-circuit currents enables us to make proper selection of the

associated apparatus (e.g. bus-bars, current transformers etc.) so that they can withstand

the forces that arise due to the occurrence of short circuits.

Page 7: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 7

Percentage Reactance

The reactance of generators, transformers, reactors etc. is usually expressed in percentage

reactance to permit rapid short circuit calculations.

The percentage reactance of a circuit is defined as under :

It is the percentage of the total phase-voltage dropped in the circuit when full-load current is

flowing i.e.,

%X =(IX/v)*100.

Where I = full-load current

V = phase voltage

X = reactance in ohms per phase

Alternatively,

percentage reactance (%X) can also be expressed in terms* of kVA and kV as under

%X =( KVA*X)/10*(KV)2

where X is the reactance in ohms.

If X is the only reactance element in the circuit, then short-circuit current is given by ;

ISC = I *( 100/%X)

i.e. short circuit current is obtained by multiplying the full-load current by 100/(% X)

Percentage Reactance and Base KVA

Percentage reactance of an equipment depends upon its kVA rating. Generally, the various

equipments used in the power system have different kVA ratings.Therefore, it is necessary

to find the percentage reactances of all the elements on a common kVA rating. This common

kVA rating is known as base kVA. The value of this base kVA is quite unimportant and may be

(i) equal to that of the largest plant

(ii) equal to the total plant capacity

(iii) any arbitrary value

The conversion can be effected by using the following relation :

% age reactance at base kVA =(Base kVA)/(rated KVA )* ( % age reactance at Rated kVA)

Page 8: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 8

Short circuit KVA

Although the potential at the point of fault is zero, it is a normal practice to express the

short-circuitcurrent in terms of short-circuit kVA based on the normal system voltage at the

point of fault.

The product of normal system voltage and short-circuit current at the point of fault

expressed in kVA is known as short-circuit kVA.

Let V = normal phase voltage in volts

I = full-load current in amperes at base kVA

%X = percentage reactance of the system on base kVA upto the fault point

Short-circuit current, ISC = I* (100/%X)

∴ Short-circuit kVA for 3-phase circuit=(3*V*Isc)/1000.

=(3*VI)/1000*(100/%X)

= Base kVA × (100/%X)

short-circuit kVA is obtained by multiplying the base kVA by 100/(% X).

REACTOR CONTROL OF SHORT CIRCUIT CURRENT

Generally, the reactance of the system under fault conditions is low and fault currents may

rise to a dangerously high value. If no steps are taken to limit the value of these short-circuit

currents, not only will the duty required of circuit breakers be excessively heavy, but also

damage to lines and other equipment will almost certainly occur.

In order to limit the short-circuit currents to a value which the circuit breakers can handle,

additional reactances known as reactors are connected in series with the system at suitable

points.

DEFINITION OF A REACTOR:-

A reactor is a coil of number of turns designed to have a large inductance as compared to its

ohmic resistance.

Advantages

(i) Reactors limit the flow of short-circuit current and thus protect the equipment from

over-heating as well as from failure due to destructive mechanical forces.

(ii) Troubles are localised or isolated at the point where they originate without

communicating their disturbing effects to other parts of the power system. This

increases the chances ofcontinuity of supply.

(iii) They permit the installation of circuit breakers of lower rating.

Page 9: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 9

Location of Reactor

Short circuit current limiting reactors may be connected

(i) in series with each generator

(ii) in series with each feeder and

(iii) in bus-bars.

(1) Generator reactors

When the reactors are connected in series with each generator, they are known as

generator reactors. In this case, the reactor may be considered as a part of leakage

reactance of the generator ; hence its effect is to protect the generator in the case of any

short-circuit beyond the reactors.

Disadvantages

(i) There is a constant voltage drop and power loss in the reactors even during normal

operation.

(ii) If a bus-bar or feeder fault occurs close to the bus-bar, the voltage at the bus-bar will be

reduced to a low value, thereby causing the generators to fall out of step.

(iii) If a fault occurs on any feeder, the continuity of supply to other is likely to be affected.

(2) Feeder reactors:-

When the reactors are connected in series with each feeder, they are known as

feeder reactors (see Fig. 17.5). Since most of the short-circuits occur on feeders, a large

numberof reactors are used for such circuits.

Two principal advantages are claimed for feeder reactors.

Firstly, if a fault occurs on any feeder, the voltage drop in its reactor will not affect

the bus-bars voltage so that there is a little tendency for the generator to lose synchronism.

Page 10: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 10

Secondly, the fault on a feeder will not affect other feeders and consequently the effects of

fault are localised.

Disadvantages

(i) There is a constant power loss and voltage drop in the reactors even during normal

operation.

(ii) If a short-circuit occurs at the bus-bars, no protection is provided to the generators.

(iii) If the number of generators is increased, the size of feeder reactors will have to be

increased to keep the short-circuit currents within the ratings of the feeder circuit breakers.

Page 11: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 11

(3) Bus-bar reactors. The above two methods of locating reactors suffer from the

disadvantage that there is considerable voltage drop and power loss in the reactors even

during normal operation. This disadvantage can be overcome by locating the reactors in the

bus-bars. There are two methods for this purpose, namely Ring system and Tie-Bar system.

(i) Ring system. In this system, bus-bar is divided into sections and these sections are

connected through reactors as shown in Fig. 17.6. Generally,one feeder is fed from one

generator only. Under normal operating conditions, each generator will supply its own

section of the load and very little power will be fed by other generators. This results in low

power loss and voltage drop in the reactors.

However, the principal advantage of the system is that if a fault occurs on any feeder, only

one generator (to which the particular feeder is connected)mainly feeds the fault current

while the current fed from other generators is small due to the presence of reactors.

Therefore, only that section of bus-bar is affected to which the feeder is connected, the

other sections being able to continue in normal operation.

(ii) Tie-Bar system. Fig. 17.7 shows the tie-bar system. Comparing the ring system with

tie-bar system,it is clear that in the tie-bar system, there are effectively two reactors in

series between sections so that reactors must have approximately half the reactance of

those used in a comparable ring system. Another advantage of tie-bar system is that

additional generators may be connected to the system without requiring changes in the

existing reactors. However, this system has the disadvantage that it requires an additional

bus-bar i.e. the tie-bar.

STEPS FOR SYMMETRICAL FAULT CALCULATIONS

(i) Draw a single line diagram of the complete network indicating the rating, voltage

and percentage reactance of each element of the network.

(ii) Choose a numerically convenient value of base kVA and convert all percentage

reactances to this base value.

Page 12: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 12

(iii) Corresponding to the single line diagram of the network, draw the reactance

diagram showing one phase of the system and the neutral. Indicate the percentage

reactances on the base kVA in the reactance diagram. The transformer in the

system should be represented by a reactancein series.

(iv) Find the total percentage reactance of the network upto the point of fault.

Let it be X%.

(v) Find the full-load current corresponding to the selected base kVA and the normal

system voltage at the fault point. Let it be I.

(vi) Then various short-circuit calculations are :

Short-circuit current, ISC = I × (100/%X)

Short-circuit kVA = Base kVA ×( 100/%X)

CAUSES OF OVERVOLTAGES

The overvoltages on a power system may be broadly divided into two main categories

1. Internal causes

(i) Switching surges (ii) Insulation failure (iii) Arcing ground (iv) Resonance

2. External causes i.e. lightning

Internal causes do not produce surges of large magnitude. Experience shows that

surges due to internal causes hardly increase the system voltage to twice the normal

value. Generally, surges due to internal causes are taken care of by providing proper

insulation to the equipment in the power system.

However, surges due to lightning are very severe and may increase the system voltage

to several times the normal value. If the equipment in the power system is not

protected against lightning surges, these surges may cause considerable damage.

Internal causes of overvoltages on the power system are primarily due to oscillations

set up by the sudden changes in the circuit conditions. This circuit change may be a

normal switching operation such as opening of a circuit breaker, or it may be the fault

condition such as grounding of a line conductor..

We shall briefly discuss the internal causes of overvoltages.

1. Switching Surges. The overvoltages produced on the power system due to

switching operations are known as switching surges. A few cases will be discussed by

way of illustration :

(i) Case of an open line.

(ii) Case of a loaded line.

Page 13: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 13

(iii) Current chopping.

2. Insulation failure.

3. Arcing ground.

4. Resonance.

LIGHTNING

An electric discharge between cloud and earth, between clouds or between the charge

centres of the same cloud is known as lightning.

PROTECTION AGAINST OVER VOLTAGE DUE TO LIGHTNING

The earthing screen and ground wires can well protect the electrical system against

direct lightning strokes but they fail to provide protection against travelling waves

which may reach the terminal apparatus. The lightning arresters or surge diverters

provide protection against such surges.

DEFINITION OF LIGHTNING ARRESTER:-

A lightning arrester or a surge diverter is a protective device which conducts the high

voltage surges on the power system to the ground.

Fig. 24.8 (i) shows the basic form of a surge diverter. It consists of a spark gap in

series with a non-linear resistor. One end of the diverter is connected to the terminal

of the equipment to be protected and the other end is effectively grounded. The length

of the gap is so set that normal line voltage is not enough to cause an arc across the

gap but a dangerously high voltage,will break down the air insulation and form an arc.

Page 14: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 14

The action of the lightning arrester or surge diverter is as under :

(i) Under normal operation, it conducts no current to earth or the gap is non-

conducting.

(ii) On the occurrence of overvoltage, the air insulation across the gap breaks down

and an arc is formed, providing a low resistance path for the surge to the ground. In

this way, the excess charge on the line due to the surge is harmlessly conducted

through the arrester to the ground instead of being sent back over the line.

(iii). After the surge is over, the resistor offers high resistance to make the gap non-

conducting.

Two things must be taken care of in the design of a lightning arrester.

Firstly, when the surge is over, the arc in gap should cease. If the arc does not go out,

the current would continue to flow through the resistor and both resistor and gap may

be destroyed.

Secondly, I R drop (where I is the surge current) across the arrester when carrying

surge current should not exceed the breakdown strength of the insulation of the

equipment to be protected.

TYPES OF LIGHTNING ARRESTER

1. Rod gap arrester

2. Horn gap arrester

3. Multigap arrester

4. Expulsion type lightning arrester

5. Valve type lightning arrester

Page 15: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 15

1. Rod Gap Arrester.:-

It is a very simple type of diverter and consists of two 1·5 cm rods which are bent at

right angles with a gap in between as shown in Fig. 24.9. One rod is connected to the

line circuit and the other rod is connected to earth. The distance between gap and

insulator (i.e. distance P) must not be less than one-third of the gap length so that the

arc may not reach the insulator and damage it. Generally, the gap length is so adjusted

that breakdown should occur at 80% of spark- over voltage in order to avoid

cascading of very steep wave fronts across the insulators. The string of insulators for

an overhead line on the bushing of transformer has frequently a rod gap across it. Fig.

24.9 shows the rod gap across the bushing of a transformer.

Under normal operating conditions, the gap remains non-conducting.

On the occurrence of a high voltage surge on the line, the gap sparks over and the

surge current is conducted to earth. In this way, excess charge on the line due to the

surge is harmlessly conducted to earth.

Limitations

(i) After the surge is over, the arc in the gap is maintained by the †normal supply

voltage,leading to a short-circuit on the system.

(ii) The rods may melt or get damaged due to excessive heat produced by the arc.

(iii) The climatic conditions (e.g. rain, humidity, temperature etc.) affect the

performance of rod gap arrester.

(iv) The polarity of the surge also affects the performance of this arrester.

Due to the above limitations, the rod gap arrester is only used as a ‘back-up’

protection in case of main arresters.

SURGE ABSORBERS CONSTRUCTION AND WORKING PRINCIPLE

Page 16: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 16

The travelling waves set up on the transmission lines by the surges may reach the

terminals apparatus and cause damage to it. The amount of damage caused not only

depends upon the amplitude of the surge but also upon the steepness of its wave front.

The steeper the wave front of the surge, the more the damage caused to the

equipment. In order to reduce the steepness of the wave front of a surge, we generally

use surge absorber..

A surge absorber is a protective device which reduces the steepness of wave front of a

surge by absorbing surge energy. Although both surge diverter and surge absorber

eliminate the surge, the manner in which it is done is different in the two devices. The

surge diverter diverts the surge to earth but the surge absorber absorbs the surge

energy. A few cases of surge absorption are discussed below :

(i) A condenser connected between the line and earth can act as a surge absorber. Fig.

24.14 shows how a capacitor acts as surge absorber to protect the transformer

winding. Since the reactance of a condenser is inversely proportional to frequency, it

will be low at high frequency and high at low frequency. Since the surges are of high

frequency, the ***capacitor acts as a short circuit and passes them directly to earth.

However, for power frequency, the reactance of the capacitor is very high and

practically no current flows to the ground….

Page 17: A STUDY MATERIAL ON UNIT-I FUNDAMENTALS OF …

SWITCHGEAR AND PROTECTION-15EE53T

DEPARTMENT AF ELECTRICAL AND ELECTRONICS ENGINEERING Page 17