AUGUST 2010 FAX 989-846-9231 989-846-4583 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 BULLETIN ACV, REV. #7 C-1 DESCRIPTION AND OPERATION The Globe Model H-1, H-2 and H-3 Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water through their bodies (non-return) and also provide for the use of a hydraulic fire alarm which is not dependent upon an electrical power supply for its operation. Through the use of a hydraulic retard chamber a time delay is provided to eliminate potential false alarms caused by fluctuating water supply pressures. Where constant pres- sure water supplies are used the retard chamber (time delay) is not necessary. By incorporating the use of electrical pressure switches, other supplemental alarms, annunciators etc. may also be used. A unique feature found on the Globe 3", 4" and 6" Alarm Valves is the clapper being hinged to the handhole cover for extreme ease of removal for inspection and service. Globe Model H-1, H-2 and H-3 Alarm Check Valves may be installed in both vertical and horizontal positions and trim can be provided for both variable and constant water supply pressures in either of these positions. The body of the Alarm Check Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling. All interior operating parts are machined from highly corrosive-resistant alloys, each having high strength and good wear resistance. Rubber parts are of selective materials which have good abrasive resistance and long life expectancy in terms of resiliency. ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE Water Working Pressure Rating - 175 psi (12 bars) (see below for more specific rating approvals). 4" Model "H-1" cULus Listed with DIN Class 16 flanges has a pressure rating of 16 bars. 4" and 6" Model "H-1" LPCB Approved for a 16 bar pressure rating with DIN Class 16 flanges and for a 20 bar pressure rating with DIN Class 25 Flanges. Factory tested hydrostatically at twice the rated work- ing pressure. Equivalent feet of pipe: 3" Valve = 12.2 feet, 4" Valve = 9.7 feet, 6" Valve = 17 feet. TECHNICAL DATA APPROVALS MODEL H-3 MODEL H-1 MODEL H-2 cULus Listed LPCB Approved - H1 & H3 FM Approved NYC - DOB MEA 325-91-M 3" 4" 6" 3" 4" 3" 4" 6" Overall Length 9" 9" 10" 10" 10" 9¼" 9½" 11" 34 lbs. 42 lbs. 69 lbs. 20 lbs. 22 lbs. 28 lbs. 37 lbs. 59 lbs. 81 lbs. 89 lbs.114 lbs. 57 lbs. 69 lbs. 75 lbs. 84 lbs. 100 lbs. Weight of Valve Complete with Verticle Variable Pressure Trimmings PHYSICAL DATA MODEL / SIZE H-1 H-2 H-3

Upload: others

Post on 10-Mar-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

AUGUST 2010

FAX 989-846-9231989-846-45834077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658

BULLETIN ACV, REV. #7C-1

DESCRIPTION AND OPERATION

The Globe Model H-1, H-2 and H-3 Alarm Check Valvesare used in wet pipe fire sprinkler systems. They primarilyserve a dual purpose in that they prevent a reverse flow ofwater through their bodies (non-return) and also provide forthe use of a hydraulic fire alarm which is not dependentupon an electrical power supply for its operation. Throughthe use of a hydraulic retard chamber a time delay isprovided to eliminate potential false alarms caused byfluctuating water supply pressures. Where constant pres-sure water supplies are used the retard chamber (timedelay) is not necessary. By incorporating the use ofelectrical pressure switches, other supplemental alarms,annunciators etc. may also be used. A unique feature found on the Globe 3", 4" and 6" AlarmValves is the clapper being hinged to the handhole coverfor extreme ease of removal for inspection and service. Globe Model H-1, H-2 and H-3 Alarm Check Valvesmay be installed in both vertical and horizontal positionsand trim can be provided for both variable and constantwater supply pressures in either of these positions. The body of the Alarm Check Valve is constructed ofhigh tensile strength cast iron having considerable ductilityto reduce damage in field handling. All interior operating parts are machined from highlycorrosive-resistant alloys, each having high strength andgood wear resistance. Rubber parts are of selective materials which havegood abrasive resistance and long life expectancy interms of resiliency.

ALARM CHECK VALVE3", 4" & 6" MODEL H-1

FLANGE/FLANGE3" & 4" MODEL H-2GROOVE/GROOVE

3", 4" & 6" MODEL H-3FLANGE/GROOVE

Water Working Pressure Rating - 175 psi (12 bars)

(see below for more specific rating approvals).

4" Model "H-1" cULus Listed with DIN Class 16

flanges has a pressure rating of 16 bars.

4" and 6" Model "H-1" LPCB Approved for a 16 bar

pressure rating with DIN Class 16 flanges and for a

20 bar pressure rating with DIN Class 25 Flanges.

Factory tested hydrostatically at twice the rated work-

ing pressure.

Equivalent feet of pipe: 3" Valve = 12.2 feet,

4" Valve = 9.7 feet, 6" Valve = 17 feet.

TECHNICAL DATA

APPROVALS

MODEL H-3

MODEL H-1

MODEL H-2

cULus Listed LPCB Approved - H1 & H3

FM Approved NYC - DOB MEA 325-91-M

3" 4" 6" 3" 4" 3" 4" 6"

Overall Length 9" 9" 10" 10" 10" 9¼" 9½" 11"

34 lbs. 42 lbs. 69 lbs. 20 lbs. 22 lbs. 28 lbs. 37 lbs. 59 lbs.

81 lbs. 89 lbs.114 lbs.57 lbs. 69 lbs. 75 lbs. 84 lbs. 100 lbs.

Weight of Valve

Complete with

Verticle Variable

Pressure Trimmings

PHYSICAL DATA

MODEL / SIZE

H-1 H-2 H-3

FAX 989-846-9231

www.globesprinkler.com

PRINTED U.S.A.

4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658

989-846-4583

1-800-248-0278

BULLETIN ACV, REV. #7AUGUST 2010

GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own

manufactured products found to be defective in material

or workmanship for a period of one year from date of

shipment.

For specific details of our warranty please refer to

Price List Terms and Conditions of Sale (Our Price List).

ORDERING INFORMATIONSPECIFY

Quantity Model Number Size

Factory Trimmed and Leak Tested Hydrostatically or

Loose Trim for Customer Installation.

Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation

instructions, and maintenance.

LEFT SIDE VIEW TOP VIEW

MODEL H-1

CROSS SECTIONS

ITEM DESCRIPTION MAT'L 3" P/N 4" P/N 6" P/N ITEM DESCRIPTION MAT'L 3" P/N 4" P/N 6" P/N

1 Body - H-1 Cast Iron 323803 323502 323562 9 Clapper Facing Disc EPDM 323815 323511 323571

Body H-2 Cast Iron 323827 323552 ------ 10 Disc Retainer Stainless 323816 323512 323572

Body - H-3 Cast Iron 323807 323542 323592 11 Lock Nut Stainless 323514 323514 323514

2 Cover Bolt Steel 323408 323509 323569 12 Disc Retainer Bolt Stainless 323817 323513 323573

3 Seat Ring Bronze 323809 323504 323564 13 Sealing Washer Hard Fiber 323515 323515 323515

4 Cover Cast Iron 323805 323507 323567 14 Hinge Pin Bushing Bronze 323819 323518 323518

5 Clapper Stainless 323814 323510 323570 15 Name Plate Aluminum 323480 323480 323480

6 Retaining Ring Stainless 323527 323517 323517 16 Drive Screw Stainless 323520 323520 323520

7 Hinge Pin Stainless 323818 323516 323516 17 Torsion Spring Stainless 323528 323528 323565

8 Cover Gasket Vellumoid 323810 323508 323568 18 Spring Bushing Brass ------ ------ 323579

ALARM CHECK VALVE3", 4" & 6" MODEL H-1FLANGE/FLANGE3" & 4" MODEL H-2GROOVE/GROOVE3", 4" & 6" MODEL H-3FLANGE/GROOVE

MAY 2003

FAX 989-846-9231989-846-45834077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658

BULLETIN ACV-8H, REV. #2C-2

ALARM CHECK VALVE

8" MODEL H-1FLANGE / FLANGE

8" MODEL H-3FLANGE / GROOVE

MODEL H-3

ALARM CHECK VALVE

Water Working Pressure Rating - 175 psi (12 bars).

Factory tested hydrostatically to 350 psi (24 bars).

Equivalent feet of pipe: 8" Valve = 21 feet.

TECHNICAL DATA

cULus Listed FM Approved

APPROVALS

DESCRIPTION AND OPERATION

The Globe Model H-1 and H-3 8" Alarm CheckValves are used in wet pipe fire sprinkler systems. Theyprimarily serve a dual purpose in that they prevent areverse flow of water through their bodies (non-return)and also provide for the use of a hydraulic fire alarmwhich is not dependent upon an electrical power supplyfor its operation. Through the use of a hydraulic retardchamber a time delay is provided to eliminate potentialfalse alarms caused by fluctuating water supply pres-sures. Where constant pressure water supplies areused the retard chamber (time delay) is not necessary.By incorporating the use of electrical pressure switches,other supplemental alarms, annunciators etc. may alsobe used. Globe 8" Model H-1 and H-3 Alarm Check Valvesmay be installed in the vertical position and trim can beprovided for both variable and constant water supplypressures. The body of the Alarm Check Valve is constructed ofhigh tensile strength cast iron having considerable duc-tility to reduce damage in field handling. All interior operating parts are machined from highlycorrosive-resistant alloys, each having high strengthand good wear resistance. Rubber parts are of selective materials which havegood abrasive resistance and long life expectancy interms of resiliency.

MODEL H-1

ALARM CHECK VALVE

PHYSICAL DATAMODEL

H-1 H-3

Overall Length 13 7/8" 15 1/8"

Weight of Valve

Complete with Vertical

Variable Pressure

Trimmings

150 lbs.

200 lbs.

130 lbs.

180 lbs.

FAX 989-846-9231

www.globesprinkler.com

PRINTED U.S.A.

4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658

989-846-4583

1-800-248-0278

MAY 2003 BULLETIN ACV-8H, REV. #2

ALARM CHECK VALVE

8" MODEL H-1FLANGE / FLANGE

8" MODEL H-3FLANGE / GROOVE

GLOBE® PRODUCT WARRANTY

Globe agrees to repair or replace any of its own

manufactured products found to be defective in mate-

rial or workmanship for a period of one year from date

of shipment.

For specific details of our warranty please refer to

Price List Terms and Conditions of Sale (Our Price List).

ORDERING INFORMATION

Quantity Model Number Size

Factory Trimmed and Leak Tested Hydrostatically or

Loose Trim for Customer Installation.

MODEL H-1

CROSS SECTION

FRONT VIEW

Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation

instructions, and maintenance.

ITEM DESCRIPTION MAT'L P/N ITEM DESCRIPTION MAT'L P/N

1 Body - H-1 Cast Iron 323832 7 Clapper Disc EPDM 323842

Body - H-3 Cast Iron 323851 8 Disc Retainer Stainless 323843

2 Cover Cast Iron 323835 9 Disc Retainer Bolt Stainless 323838

3 Cover Gasket Rubber 323833 10 Hinge Pin Stainless 323845

4 Cover Bolt Steel 323839 11 Hinge Pin Bushing Bronze 323846

5 Seat Ring Bronze 323837 12 Name Plate Aluminum 323480

6 Clapper Bronze 323841 13 Drive Screw Stainless 323420

TOP VIEW

SPECIFY

JUNE 2002

FAX 989-846-9231989-846-45834077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658

BULLETIN RET.CHM., REV. #2D-1

DESCRIPTION AND OPERATION

The Globe Model H Retarding Chamber is an acces-sory which is used with variable pressure wet sprinklersystems where water motor alarms and / or pressureswitches are used in conjunction with Globe's AlarmCheck Valves. It serves primarily as a hydraulic timedelay to prevent most false alarms associated withfluctuating water supply pressures. In situations whereexcessive water pressure surges occur, the Model HRetarding Chamber is needed to collect excess waterfrom the Alarm Check Valve and feed water back intothe main drain, before activating the alarm. An addi-tional retarding chamber could be needed if pressuresurges exceed the capacity of one retarding chamber. Water enters the retarding chamber through the 1/2"NPT Inlet and automatically flows through a restrictedorifice and to drain; when the drain capacity is ex-ceeded, as when the alarm check valve clapper re-mains open or when the system is being tested, theretarding chamber capacity is reached, and water thenflows through the Outlet to the water motor alarm and /or electric alarm switch. The body of the Retarding Chamber has consider-able ductility to reduce damage in field handling. All interior operating parts are machined from highlycorrosive-resistant alloys, each having high strengthand good wear resistance.

RETARDING CHAMBERMODEL H

Water Working Pressure Rating - 175 psi (12 bars).Factory tested hydrostatically to 350 psi (24 bars).Capacity - 1 Gallon (3.785 liters)Body - High Tensile Cast Iron

TECHNICAL DATA

cULus ListedFM ApprovedLPCB Approved

APPROVALS

MODEL HRETARD CHAMBER

FAX 989-846-9231www.globesprinkler.com

PRINTED U.S.A.

4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658989-846-45831-800-248-0278

BULLETIN RET.CHM., REV. #2JUNE 2002

RETARDING CHAMBERMODEL H

GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its ownmanufactured products found to be defective in mate-rial or workmanship for a period of one year from dateof shipment. For specific details of our warranty please refer toPrice List Terms and Conditions of Sale (Our Price List).

ORDERING INFORMATIONSPECIFY

Quantity Model Number

Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installationinstructions, and maintenance.

ITEM DESCRIPTION MAT'L P/N 1 Outlet Bushing Cast Iron 323354 2 Machined Body Cast Iron 323352 3 Hex Head Machine Screw Brass 323357 4 Cup Brass 323356 5 Strainer Screen Brass 323355 6 Drain Bushing Brass 323353

CROSS SECTIONDIMENSIONS

4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 FAX 989-846-9231989-846-4583

AUGUST 2002 BULLETIN WMN-1

Globe's Model WM and WM-2 Water MotorAlarms are hydraulically operated indoor and out-door alarms for use with fire protection systems.They are lightweight yet durable, and can be usedin conjunction with alarm check, dry pipe, deluge,and preaction valves to sound a local alarm. Thiswater-powered system eliminates the need for anelectrical alarm and will operate even if electricalpower is lost. Globe's Model WM Water Motor Alarm featuresa one- gong system which sounds an alarm outsidethe building. Globe's Model WM-2 Water MotorAlarm features a unique two-gong system whichprovides an audible fire alarm both inside andoutside the building. The Water Motor Alarms are suitable for mount-ing to any type of rigid wall and can accomodate awall thickness up to 16" (406.4 mm). They areprovided with a listed and approved strainer foruse in the alarm line. The Gong, Gong Mount, andWater Motor Housing are fabricated from corro-sion-resistant cast aluminum. The polymer drivebearings do not require lubrication. The WM and WM-2 utilize a lightweight, impellerdesign which can produce a very high decibelsound level. As water passes through the watermotor, the impeller turns and the shaft rotates. Therotating shaft drives a striker assembly which ringsthe gong, sounding a continuous alarm as long asthe water flow continues.

WATER MOTOR ALARMMODEL WM

MODEL WM-2

DESCRIPTION AND OPERATION

MODEL WMWATER MOTOR ALARM

MODEL WM-2WATER MOTOR ALARM

TECHNICAL DATABody - cast aluminumFinish - red

60

70

80

90

100

110

10 30 50 70 90 110 130 150 170

10 ft

100 ft

TYPICAL DECIBEL SOUND LEVELS - WM, WM-2

FLOWING PRESSURE (PSI)

SO

UN

D L

EV

EL

(db)

50 ft

APPROVALScULus ListedFM ApprovedNYC-DOB MEA 326-91-M

FAX 989-846-9231www.globesprinkler.com

PRINTED U.S.A.

4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658989-846-45831-800-248-0278

AUGUST 2002 BULLETIN WM

Quantity Model Number

WATER MOTOR ALARMMODEL WMMODEL WM-2

CROSS SECTIONS

GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its ownmanufactured products found to be defective in mate-rial or workmanship for a period of one year from dateof shipment. For specific details of our warranty please refer toPrice List Terms and Conditions of Sale (Our Price List).

ORDERING INFORMATIONSPECIFY

MODEL WM MODEL WM-2

ITEM DESCRIPTION MAT'L WM P/N WM-2 P/N ITEM DESCRIPTION MAT'L WM P/N WM-2 P/N1 Gong Shell Aluminum 325506 325506 9 Threaded Pipe Galvanized Pipe 325517 3255172 Hex Head Cap Screw Zinc 325521 325521 10 Striker Arm Mild Steel 325510 3255103 Gong Mounting Bracket Aluminum 325504 325504 11 Cap Screw Zinc Plated 325520 3255204 Motor Cover Aluminum 325509 ------ 12 Knocker Phenolic 325513 325513

Inside Gong Backing Plate Aluminum ------ 325532 13 Knocker Retaining Washer Stainless Steel 325516 3255165 Impeller Housing Aluminum 325502 325502 14 Knocker Retaining Rivet Stainless Steel 325514 3255146 Impeller Delrin 325507 ------ 15 Bearing-Thompson Type 6 Nylon 325518 325518

Impeller - Inside Gong Delrin ------ 32533 16 3/8 Helical Spring Lock Washer Steel 325522 3255227 Striker Shaft Delrin 325508 325508 17 Backing Plate Gasket Velumoid 325511 3255118 Drive Shaft Aluminum 325515 325515 18 Wall Plate Mild Steel 325528 325528

Refer to Globe's Water Motor Alarm Installation and Maintenance Guide (Bulletin WMA-I) for trim set-up, installationinstructions, and maintenance.

4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658PHONE 989-846-4583 800-248-0278

FAX 989-846-9231 800-846-9211www.globesprinkler.com

[email protected]

3", 4", 6" & 8"Model H Series

Alarm Check ValveInstallation

andMaintenance Guide

APRIL 2004 BULLETIN ACVIM, REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

Page i

Table of Contents

APRIL 2004 BULLETIN A.C.V.I.M., REV. #11

Globe Alarm Check Valves 1General Description 1Physical Data 2

3", 4" & 6" Alarm Check Valve Assembly and Parts List 38" Alarm Check Valve Assembly and Parts List 3

3" Model H Series Vertical Position / Variable Pressure Trim 63" Model H Series Vertical Position / Constant Pressure Trim 73" Model H Series Horizontal Position / Variable Pressure Trim 83" Model H Series Horizontal Position / Constant Pressure Trim 9

4" Model H Series Vertical Position / Variable Pressure Trim 104" Model H Series Vertical Position / Constant Pressure Trim 114" Model H Series Horizontal Position / Variable Pressure Trim 124" Model H Series Horizontal Position / Constant Pressure Trim 13

6" Model H Series Vertical Position / Variable Pressure Trim 146" Model H Series Vertical Position / Constant Pressure Trim 156" Model H Series Horizontal Position / Variable Pressure Trim 166" Model H Series Horizontal Position / Constant Pressure Trim 17

8" Model H Series Vertical Position / Variable Pressure Trim 188" Model H Series Vertical Position / Constant Pressure Trim 19

Optional Alarm Pressure Switch Trim 20Pressure Relief Valve for Use in Gridded Systems 20

Testing 4Maintenance 5

APRIL 2004 Page 1 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

IMPORTANT NOTES

1. Any alarm check valve should be carefully tested, examined, and cleaned periodically in accordance with NFPA 25. 2. It is most important to ensure a clean water supply free of debris and solid particles such as sand, gravel, or mud. 3. If, during the annual inspection of alarm check valves, sediment or free particles of matter are noted, a further examination of internal valve parts becomes necessary. 4. All deposits should be removed from all operating parts and ports. Vent holes through seat ring, Items 3 and 2 (Page 4), should be throroughly cleaned and flushed with clean water. 5. Where difficulty in performance is experienced, the manufacturer or his authorized representative shall be contacted if any field adjustment is to be made.

GENERAL DESCRIPTION

Globe Fire Sprinkler Corporation Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water through their bodies (non-return) and also provide for the use of a hydraulic fire alarm which is not dependent upon an electrical power supply for its operation. Through the use of a hydraulic retard chamber a time delay is provided to eliminate potential false alarms caused by fluctuating water supply pressures. Where constant pressure water supplies are used the retard chamber (time delay) is not necessary. By incorporating the use of electrical pressure switches, other supplemental alarms, annunciators, etc. may also be used. Globe Alarm Check Valves are designed and manufactured to the standards and/or requirements of Underwrit-ers Laboratories Inc., Factory Mutual Approvals, The Loss Prevention Certification Board and the City of New York Department of Buildings, and they conform to the design/usage requirements of NFPA 13.

APRIL 2004 Page 2 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

PHYSICAL DATA

VERTICAL / VARIABLE

MODEL H-1 H-2 H-3SIZE 3" 4" 6" 8" 3" 4" 3" 4" 6" 8"

Overall Length 9" 9" 10" 14" 10" 10" 9 1/4" 9 1/2" 11" 13 5/8"Center of Valve to Back 10" 11" 12" 13" 10" 11" 10" 11" 12" 13"Center of Valve to Right 13 1/2" 16 1/2" 16 1/2" 16 1/2" 13 1/2" 16 1/2" 13 1/2" 16 1/2" 16 1/2" 16 1/2"Center of Valve to Left 8" 8" 8" 8" 8" 8" 8" 8" 8" 8"Center of Valve to Center of Drain 9 1/4" 8" 8 3/4" 8 3/4" 9 1/4" 8" 9 1/4" 8" 8 3/4" 8 3/4"Weight of ValveComplete with all Trimmings

34 lbs.81 lbs.

42 lbs.89 lbs.

69 lbs.114 lbs.

147 lbs.192 lbs.

20 lbs.57 lbs.

22 lbs.69 lbs.

28 lbs.75 lbs.

37 lbs.84 lbs.

59 lbs.100 lbs.

147 lbs.196 lbs.

VERTICAL / CONSTANT

MODEL H-1 H-2 H-3SIZE 3" 4" 6" 8" 3" 4" 3" 4" 6" 8"

Overall Length 9" 9" 10" 14" 10" 10" 9 1/4" 9 1/2" 11" 13 5/8"Center of Valve to Back 10" 8 3/4" 9 3/4" 12 1/4" 10" 8 3/4" 10" 8 3/4" 9 3/4" 12 1/4"Center of Valve to Right 13 1/2" 15 1/2" 16 1/4" 17" 13 1/2" 15 1/2" 13 1/2" 15 1/2" 16 1/4" 17"Center of Valve to Left 8" 8" 8" 7 1/2" 8" 8" 8" 8" 8" 7 1/2"Center of Valve to Center of Drain 9 1/4" 8" 8 3/4" 9 1/2" 9 1/4" 8" 9 1/4" 8" 8 3/4" 9 1/2"Weight of ValveComplete with all Trimmings

34 lbs.56 lbs.

42 lbs.64 lbs.

69 lbs.89 lbs.

147 lbs.167 lbs.

20 lbs.32 lbs.

22 lbs.44 lbs.

28 lbs.50 lbs.

37 lbs.59 lbs.

59 lbs.75 lbs.

147 lbs.172 lbs.

HORIZONTAL / VARIABLE

MODEL H-1 H-2 H-3SIZE 3" 4" 6" 8" 3" 4" 3" 4" 6" 8"

Overall Length 9" 9" 10" N/A 10" 10" 9 1/4" 9 1/2" 11" N/ACenter of Valve to Back 7 1/2" 27" 20 1/2" N/A 7 1/2" 27" 7 1/2" 27" 20 1/2" N/ACenter of Valve to Right 17 1/2" 17" 18 1/2" N/A 17 1/2" 17" 17 1/2" 17" 18 1/2" N/ACenter of Valve to Left 7 1/4" 8 1/2" 12" N/A 7 1/4" 8 1/2" 7 1/4" 8 1/2" 12" N/ACenter of Valve to Center of Drain 9 1/2" 13 1/2" 14" N/A 9 1/2" 13 1/2" 9 1/2" 13 1/2" 14" N/AWeight of ValveComplete with all Trimmings

34 lbs.89 lbs.

42 lbs.97 lbs.

69 lbs.122 lbs. N/A 20 lbs.

70 lbs.22 lbs.82 lbs.

28 lbs.83 lbs.

37 lbs.92 lbs.

59 lbs.113 lbs. N/A

HORIZONTAL / CONSTANT

MODEL H-1 H-2 H-3SIZE 3" 4" 6" 8" 3" 4" 3" 4" 6" 8"

Overall Length 9" 9" 10" N/A 10" 10" 9 1/4" 9 1/2" 11" N/ACenter of Valve to Back 7 1/2" 24 1/2" 19 1/2" N/A 7 1/2" 24 1/2" 7 1/2" 24 1/2" 19 1/2" N/ACenter of Valve to Right 17 1/2" 16 1/2" 15 1/2" N/A 17 1/2" 16 1/2" 17 1/2" 16 1/2" 15 1/2" N/ACenter of Valve to Left 7 1/4" 8 1/2" 8 3/4" N/A 7 1/4" 8 1/2" 7 1/4" 8 1/2" 8 3/4" N/ACenter of Valve to Center of Drain 12 1/4" 13 1/2" 14" N/A 12 1/4" 13 1/2" 12 1/4" 13 1/2" 14" N/AWeight of ValveComplete with all Trimmings

34 lbs.60 lbs.

42 lbs.68 lbs.

69 lbs.94 lbs. N/A 20 lbs.

70 lbs.22 lbs.53 lbs.

28 lbs.54 lbs.

37 lbs.63 lbs.

59 lbs.85 lbs. N/A

APRIL 2004 Page 3 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

3", 4" & 6" ALARM CHECK VALVE ASSEMBLY

FRONT VIEW TOP VIEW

8" ALARM CHECK VALVE ASSEMBLY

FRONT VIEW TOP VIEW

ITEM DESCRIPTION MAT'L 3" P/N 4" P/N 6" P/N ITEM DESCRIPTION MAT'L 3" P/N 4" P/N 6" P/N1 Body - H-1 Cast Iron 323803 323502 323562 9 Clapper Facing Disc EPDM 323815 323511 323571

Body H-2 Cast Iron 323827 323552 ------ 10 Disc Retainer Stainless 323816 323512 323572Body - H-3 Cast Iron 323807 323542 323592 11 Lock Nut Stainless 323514 323514 323514

2 Cover Bolt Steel 323408 323509 323569 12 Disc Retainer Bolt Stainless 323817 323513 3235733 Seat Ring Bronze 323809 323504 323564 13 Sealing Washer Hard Fiber 323515 323515 3235154 Cover Cast Iron 323805 323507 323567 14 Hinge Pin Bushing Bronze 323819 323518 3235185 Clapper Stainless 323814 323510 323570 15 Name Plate Aluminum 323480 323480 323480

6 Retaining Ring Stainless 323527 323517 323517 16 Drive Screw Stainless 323520 323520 3235207 Hinge Pin Stainless 323818 323516 323516 17 Torsion Spring Stainless 323528 323528 3235658 Cover Gasket Vellumoid 323810 323508 323568 18 Spring Bushing Brass ------ ------ 323579

ITEM DESCRIPTION MAT'L P/N ITEM DESCRIPTION MAT'L P/N1 Body - H-1 Cast Iron 323832 7 Clapper Disc EPDM 323842

Body - H-3 Cast Iron 323851 8 Disc Retainer Stainless 3238432 Cover Cast Iron 323835 9 Disc Retainer Bolt Stainless 3238383 Cover Gasket Rubber 323833 10 Hinge Pin Stainless 3238454 Cover Bolt Steel 323839 11 Hinge Pin Bushing Bronze 3238465 Seat Ring Bronze 323837 12 Name Plate Aluminum 323480

6 Clapper Bronze 323841 13 Drive Screw Stainless 323420

APRIL 2004 Page 4 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

Testing and Maintenance

Reference NFPA 25, Standard for the Inspection, Testing, and Main-tenance of Water-Based Fire Protection Systems.

TESTING Before proceeding with any tests involving water flow, certain precautions need to be taken. 1. Check the location where the test connection discharges to make sure that all is clear and that there is no possibility of the water flow causing damage or injury.

2. Check the end of the test connection to make sure that it is unobstructed. To obtain a satisfactory test, there must be an unrestricted flow of water when the test valve is wide open.

3. Check for alarm connections to a central station or fire department. If such connections are found, give proper notice to the signal receiving station before proceeding with the test.

Note: A main drain test will also operate local fire alarms - unless they are temporarily shut off.

Testing Alarm Valve and Waterflow Alarm Devices

NFPA 25 recommends that the alarm valve and its waterflow alarm devices be tested at least quarterly. The primary way to test this equipment is by opening the Inspectors Test Connection. This connection, generally located at the highest and most remote point on the system in relation to the alarm valve, consists of a test orifice and controlling globe valve. Opening of the globe valve (Inspec-tors Test Valve), and the subsequent discharge of water through the test orifice, simulates the operation of a sprinkler. Therefore, alarm devices should sound and/or operate when the Inspectors Test Valve is opened. An alternate means of testing waterflow alarm devices is to open the Alarm Test Valve provided as part of the alarm valve trim. It must be noted, however, that opening of this valve only tests the alarms; it does not test the operation of the alarm valve since the supply for the alarm test line is taken from a point below the alarm valve clapper (see respective trim drawings). This means of testing, therefore, should only be used when weather conditions or other circumstances pro-hibit using the Inspectors Test Connection.

Note: If alarms connect to a central station or fire depart-ment, notify the signal receiving station when all tests have been completed.

Flow Test at Main Drain Valve (Main Drain Test) NFPA 25 recommends that a water flow test be made quarterly from the main drain valve at the system riser. The purpose of this test is to show whether or not the normal water supply is available to the system. By comparing static and residual pressure readings with those previously estab-lished, a main drain test can indicate the possible presence of closed valves or other obstructions in the supply piping. The procedure for conducting a Main Drain Test is as follows:

1. With the Main Drain Valve closed, note and record the reading on the lower Pressure Gauge at the Alarm Valve.

2. Open the Main Drain Valve slowly until it is wide open. Then, check to make sure that a full steady flow of water is discharging from the main drain pipe.

Note: If a full steady stream is not discharging, check the main drain piping further for possible obstructions.

3. Allow the water to flow until the reading on the lower Pressure Gauge drops and stabilizes. Then, record this reading.

Note: The first and higher pressure reading is the static pressure. The second, lower reading is the residual pressure with a given flow discharging from the main drain pipe.

4. Close the Main Drain Valve slowly.

Caution: If alarms have been temporarily shut off, they must be returned to service. If alarms connect to a central station or fire department, notify the signal receiving station when the test has been completed.

5. Compare both pressure readings with previously estab-lished or normal readings.

Note: If the readings compare favorably, the water supply may be considered satisfactory. If, however, the pressure readings vary to any great extent, the condition should be investigated to determine the cause. Some possible causes are:

Partially or totally closed system control valves. Clogged or frozen water mains. Serious leakage at valves or mains.

APRIL 2004 Page 5 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

MAINTENANCE The Globe Alarm Check Valve and its related equipment should be examined periodically to ensure proper operation and trouble-free service. Several areas to be routinely inspected are:

Clapper Facing. The rubber clapper facing should be checked for wear or damage, and to determine that it is free of dirt and other foreign substances. If found to be worn or damaged (e.g., foreign matter imbedded in the surface), the facing should be replaced. If it is dirty, it should be cleaned, but compounds which could damage the rubber facing must never be used.

Seat Ring. The seat ring should be checked for nicks and for stones, dirt or other foreign matter lodged in the grooves or holes. It should be cleaned thoroughly. If the seat ring is found to be severely damaged, the complete alarm valve assembly should be replaced or returned to Globe for pos-sible reconditioning.

By-Pass Check Valve. The ¾" check valve in the external by-pass should be checked for clapper and seat condition.

Retard Chamber. The outlet plug and drain plug assemblies should be checked for obstructions. The screens should be cleaned thoroughly.

Alarm Line Strainer. The ¾" stainer in the alarm line of the constant pressure trim setup should be checked and cleaned thoroughly.

Alarm Test Valve, Main Drain Valve & Inspectors Test Valve. All controlling valves which are normally closed when the alarm valve is in the set position should be checked to be sure that they are fully closed and not leaking.

Alarm Valve & Trim. The overall setup should be checked for visible leaks and possible physical damage to the valve and connections (e.g., broken gauges).

Resetting of System The Globe Alarm Check Valve is self-setting when testing procedures are followed. When sprinklers operate, however, there are certain procedures which must be followed for restoring the system to service.

1. Close the System Control Valve (OS & Y, PIV or other).

Caution: In the event of a fire, the system control valve is to be closed only after it has been determined, positively, that the

fire has been extinguished.

2. Close the Alarm Control Valve.

3. Open the Main Drain Valve.

Note: It is necessary to drain the system only as required to allow for sprinkler replacement.

4. Replace the sprinklers which have operated.

5. Close the Main Drain Valve

6. Open the Inspectors Test Valve.

Note: This valve is opened to permit air to be vented from the system as it is being filled with water.

7. Slowly open the System Control Valve.

Caution: Open the valve only partially at the start of water flow into the system. Do not open it fully at this point. To do so may cause a water hammer to occur which could either damage the piping or trap large volumes of air within the system.

8. Continue filling the system until water discharges in a continuous stream from the Inspectors Test Connection.

9. Close the Inspectors Test Valve.

10. Turn the System Control Valve to its full open position, at the same time observing the Pressure Gauges.

Note: The system is filled when both gauges are steady and have the same pressure reading.

11. Conduct a Main Drain Test to make sure the water supply is satisfactory (see Flow Test at Main Drain Valve).

12. Open the Alarm Control Valve.

13. Conduct a test of the alarm devices (see Testing Alarm and Waterflow Alarm Devices).

14. Seal, lock, or otherwise secure the System Control Valve and Alarm Control Valve in an open position (per NFPA 25). The system is now ready for service.

15. If alarms connect to a central station or fire department, notify the signal receiving station that the system has been returned to service.

APRIL 2004 Page 6 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

3" MODEL H SERIES VERTICAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd

Det.No. Description Part No. Req'd

Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 6 23 1/2" x 3" Nipple 310304 1 73 1/2" x 2" Galv. Nipple 310302-G 1

3 1/2" Tee 311303 2 31 3 1/2" Water Gauge (0-300psi)

300119 2 74 1/2" x 7 1/2" Galv. Nipple 310313-G 1

4 1/2" Close Nipple 310300 10 33 1/2" x 3 1/2" Nipple 310305 1 83 1 1/2" Angle Valve 311616 1

5 1/2" Ball Valve 311692 2 37 1/2" x 1 1/2" Nipple 310301 1 86 1 1/2" x 1 1/2" x 1/2" Tee 311391 1

15 1/4" 3-Way Valve 311683 2 46 1/2" x 4" Nipple 310306 1 102 1/4" x 1 1/2" Nipple 310101 1

16 1/4" Plug 311001 3 59 Retard Chamber 323350 1 106 1 1/2" x 3 1/2" Nipple 310704 1

19 1/2" x 2" Nipple 310302 1 64 1/4" x 4" Nipple 310106 1 111 1 1/2" x 2 1/2" Nipple 310702 1

20 1/2" Swing Check Valve 311639 2 67 1/2" x 1/4" x 1/2" Tee 311305 3

21 1/2" Union 311403 4 70 1/2" Close Galv. Nipple 310300-G 6

APRIL 2004 Page 7 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

3" MODEL H SERIES VERTICAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 6 30 3/4" x 1/2" x 1/2" Tee 311318 1 70 1/2" Close Galv. Nipple 310300-G 6

3 1/2" Tee 311303 2 31 3 1/2" Water Gauge (0-300 psi) 300119 2 73 1/2" x 2" Galv. Nipple 310303-G 1

4 1/2" Close Nipple 310300 11 32 1/2" Coupling 311423 1 83 1 1/2" Angle Valve 311616 1

5 1/2" Ball Valve 311692 2 33 1/2" x 3 1/2" Nipple 310305 1 86 1 1/2" x 1 1/2" x 1/2" Tee 311391 1

7 1/4" x 1 1/2" Nipple 310101 1 35 Alarm Line Bleeder 320506 1 88 1/2" x 10" Nipple 310320 1

15 1/4" 3-Way Valve 311683 2 36 3/4" Strainer 325535 1 101 1 1/2" Close Nipple 310700 1

16 1/4" Plug 311001 3 46 1/2" x 4" Nipple 310306 1 103 3/4" Close Galv. Nipple 310400-G 1

19 1/2" x 2" Nipple 310302 1 64 1/4" x 4" Nipple 310107 1 106 1 1/2" x 3 1/2" Nipple 310704 1

20 1/2" Swing Check Valve 311639 2 66 1/2" x 7 1/2" Nipple 310313 1

21 1/2" Union 311403 4 67 1/2" x 1/4" x 1/2" Tee 311305 3

APRIL 2004 Page 8 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

3" MODEL H SERIES HORIZONTAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 6 23 1/2" x 3" Nipple 310304 1 74 1/2" x 7 1/2" Galv. Nipple 310313-G 1

3 1/2" Tee 311303 2 31 3 1/2" Water Gauge (0-300 psi) 300119 2 75 1/2" x 12" Galv. Nipple 310318-G 1

4 1/2" Close Nipple 310300 10 33 1/2" x 3 1/2" Nipple 310305 1 83 1 1/2" Angle Valve 311616 1

5 1/2" Ball Valve 311692 2 42 1/4" x 6" Nipple 310110 1 86 1 1/2" x 1 1/2" x 1/2" Tee 311391 1

15 1/4" 3-Way Valve 311683 2 46 1/2" x 4" Nipple 310306 1 107 1 1/2" x 4 1/2" Nipple 310706 1

16 1/4" Plug 311001 3 59 Retard Chamber 323350 1 109 1/4" x 3 1/2" Nipple 310105 1

19 1/2" x 2" Nipple 310302 1 67 1/2" x 1/4" x 1/2" Tee 311305 3 110 1 1/2" x 8" Nipple 310715 1

20 1/2" Swing Check Valve 311639 2 70 1/2" Close Galv. Nipple 310300-G 6

21 1/2" Union 311403 4 73 1/2" x 2" Galv. Nipple 310302-G 1

APRIL 2004 Page 9 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE 3" MODEL H SERIES HORIZONTAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 4 31 3 1/2" Water Gauge (0-300 psi) 300119 2 73 1/2" x 2" Nipple 310302 1

3 1/2" Tee 311303 2 32 1/2" Coupling 311423 1 74 1/2" x 7 1/2" Galv. Nipple 310313-G 1

4 1/2" Close Nipple 310300 9 33 1/2" x 3 1/2" Nipple 310305 1 83 1 1/2" Angle Valve 311616 1

5 1/2" Ball Valve 311692 2 35 1/2" Alarm Line Bleeder 320506 1 86 1 1/2" x 1 1/2" x 1/2" Tee 311391 1

15 1/4" 3-Way Valve 311683 2 36 3/4" Strainer 325535 1 103 3/4" Close Galv. Nipple 310400-G 1

16 1/4" Plug 311001 3 37 1/2" x 1 1/2" Nipple 310301 1 107 1 1/2" x 4 1/2" Nipple 310706 1

19 1/2" x 2" Nipple 310302 1 42 1/4" x 6" Nipple 310110 1 108 1 1/2" x 6" Nipple 310709 1

20 1/2" Swing Check Valve 311639 2 46 1/2" x 4" Nipple 310306 1 109 1/4" x 3 1/2" Nipple 310105 1

21 1/2" Union 311403 4 67 1/2" x 1/4" x 1/2" Tee 311305 3

30 3/4" x 3/4" x 1/2" Tee 311318 1 70 1/2" Close Galv. Nipple 310300-G 6

APRIL 2004 Page 10 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

4" MODEL H SERIES VERTICAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 ½" Elbow 311203 3 17 ¾" Union 311404 2 38 1/4" x 2" Nipple 310103 1

3 1/2" Tee 311303 1 18 3/4" x 2 1/2" Nipple 310402 1 41 ¾" x 1 ½" Nipple 310413 1

4 1/2" Close Nipple 310300 2 19 1/2" x 2" Nipple 310302 1 45 1/4" x 5" Nipple 310108 1

5 1/2" Ball Valve 311692 2 20 1/2" Swing Check Valve 311639 1 46 1/2" x 4 ½" Nipple 310307 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 21 1/2" Union 311403 2 59 Retard Chamber 323350 1

7 3/4" x 3" Nipple 310403 1 22 2" x 3" Nipple 310802 2 67 1/2" x 1/4" x 1/2" Tee 311305 1

8 3/4" Elbow 311204 1 24 3/4" x 4 1/2" Nipple 310406 1 70 1/2" Close Galv. Nipple 310300-G 3

12 3/4" Close Nipple 310400 4 25 2" Angle Valve 311617 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 3

13 3/4" Swing Check 311640 1 27 2" x 2" x 1/2" Tee 311380 1 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

15 1/4" 3-Way Valve 311683 2 31 3 1/2" Water Gauge (0-300 psi) 300119 2 122 1/2" X 1/4" Reducing Bushing 311100 2

16 1/4" Plug 311001 3 37 1/2" x 1 ½" Nipple 310301 2

APRIL 2004 Page 11 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

4" MODEL H SERIES VERTICAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 3 18 3/4" x 2 1/2" Nipple 310402 1 36 3/4" Strainer 325535 1

3 1/2" Tee 311303 1 20 1/2" Swing Check Valve 311639 1 37 1/2" x 1 1/2" Nipple 310301 2

4 1/2" Close Nipple 310300 3 21 1/2" Union 311403 2 38 1/4" x 2" Nipple 310102 1

5 1/2" Ball Valve 311692 2 22 2" x 3" Nipple 310802 1 41 3/4" x 1 1/2" Nipple 310413 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 24 3/4" x 4 1/2" Nipple 310406 1 45 1/4" x 5" Nipple 310108 1

7 3/4" x 3" Nipple 310403 1 25 2" Angle Valve 311617 1 58 2" x 2 1/2" Nipple 310801 1

8 3/4" Elbow 311204 1 27 2" x 2" x 1/2" Tee 311380 1 67 1/2" X 1/4" X 1/2" Tee 311305 1

12 3/4" Close Nipple 310400 5 30 3/4" x 1/2" x 1/2" Tee 311318 1 70 1/2" Close Galv. Nipple 310300-G 4

13 3/4" Swing Check Valve 311640 1 31 3 1/2" Water Gauge (0-300 psi) 300119 2 71 1/2" x 1 1/2" Galv. Nipple 310301-G 2

15 1/4" 3-Way Valve 311683 2 32 1/2" Coupling 311423 1 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 34 1/2" x 12" Nipple 310318 1 122 1/2" x 1/4" Reducing Bushing 311100 2

17 3/4" Union 311404 2 35 Alarm Line Bleeder 320506 1

APRIL 2004 Page 12 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

4" MODEL H SERIES HORIZONTAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 4 18 3/4" x 2 1/2" Nipple 310402 1 42 1/4" x 6" Nipple 310110 2

3 1/2" Tee 311303 1 20 1/2" Swing Check Valve 311639 1 59 Retard Chamber 323350 1

4 1/2" Close Nipple 310300 1 21 1/2" Union 311403 2 60 1/4" Coupling 311402 1

5 1/2" Ball Valve 311692 2 24 3/4" x 4 1/2" Nipple 310406 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 25 2" Angle Valve 311617 1 68 2" x 7 1/2" Nipple 310809 1

7 3/4" x 3" Nipple 310403 1 26 2" x 5" Nipple 310803 1 70 1/2" Close Galv. Nipple 310300-G 3

8 3/4" Elbow 311204 1 27 2" x 2" x 1/2" Tee 311380 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 2

11 1/4" x 6 1/2" Nipple 310115 2 28 1/4" Elbow 311201 2 72 1/2" x 2 1/2" Galv. Nipple 310303-G 1

12 3/4" Close Nipple 310400 4 29 1/4" x 10" Nipple 310136 1 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

13 3/4" Swing Check Valve 311640 1 31 3 1/2" Water Gauge (0-300 psi) 300119 2 75 1/2" x 12" Galv. Nipple 310318-G 1

15 1/4" 3-Way Valve 311683 2 37 1/2" x 1 1/2" Nipple 310301 2 122 1/2" x 1/4" Reducing Bushing 311100 2

16 1/4" Plug 311001 3 39 1/2" x 2 1/2" Nipple 310303 3

17 3/4" Union 311404 2 41 3/4" x 1 1/2" Nipple 310413 1

APRIL 2004 Page 13 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE4" MODEL H SERIES HORIZONTAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 2 20 1/2" Swing Check Valve 311639 1 37 1/2" x 1 1/2" Nipple 310301 5

3 1/2" Tee 311303 1 21 1/2" Union 311403 2 41 3/4" x 1 1/2" Nipple 310413 1

5 1/2" Ball Valve 311692 2 24 3/4" x 4 1/2" Nipple 310406 1 42 1/4" x 6" Nipple 310110 2

6 3/4" x 1/2" x 3/4" Tee 311313 3 25 2" Angle Valve 311617 1 60 1/4" Coupling 311402 1

7 3/4" x 3" Nipple 310403 1 26 2" x 5" Nipple 310803 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

8 3/4" Elbow 311204 1 27 2" x 2" x 1/2" Tee 311380 1 69 2" x 6" Nipple 310808 1

11 1/4" x 6 1/2" Nipple 310115 2 28 1/4" Elbow 311201 2 70 1/2" Close Galv. Nipple 310300-G 3

12 3/4" Close Nipple 310400 4 29 1/4" x 10" Nipple 310136 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 2

13 3/4" Swing Check Valve 311640 1 30 3/4" x 1/2" x 1/2" Tee 311318 1 73 1/2" x 2" Galv. Nipple 310302-G 1

15 1/4" 3-Way Valve 311683 2 31 3 1/2" Water Gauge (0-300 psi) 300119 2 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 32 1/2" Coupling 311423 1 103 3/4" Close Galv. Nipple 310400-G 1

17 3/4" Union 311404 2 35 Alarm Line Bleeder 320506 1 122 1/2" x 1/4" Reducing Bushing 311100 2

18 3/4" x 2 1/2" Nipple 310402 1 36 3/4" Strainer 325535 1

APRIL 2004 Page 14 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

6" MODEL H SERIES VERTICAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 3 18 3/4" x 2 1/2" Nipple 310402 1 41 3/4" x 1 1/2" Nipple 310413 1

3 1/2" Tee 311303 1 19 1/2" x 2" Nipple 310302 1 43 3/4" x 3 1/2" Nipple 310404 1

4 1/2" Close Nipple 310300 3 20 1/2" Swing Check Valve 311639 1 45 1/4" x 5" Nipple 310108 1

5 1/2" Ball Valve 311692 2 21 1/2" Union 311403 2 59 Retard Chamber 323350 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 22 2" x 3" Nipple 310802 2 67 1/2" x 1/4" x 1/2" Tee 311305 1

8 3/4" Elbow 311204 1 24 3/4" x 4 1/2" Nipple 310406 1 70 1/2" Close Galv. Nipple 310300-G 3

12 3/4" Close Nipple 310400 4 25 2" Angle Valve 311617 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 2

13 3/4" Swing Check Valve 311640 1 27 2" x 2" x 1/2" Tee 311380 1 73 1/2" x 2" Galv. Nipple 310302-G 1

15 1/4" 3-Way Valve 311683 2 31 3 1/2" Water Gauge (0-300 psi) 300119 2 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 37 1/2" x 1 1/2" Nipple 310301 1 98 1/2" x 4 1/2" Nipple 310307 1

17 3/4" Union 311404 2 38 1/4" x 2" Nipple 310102 1 122 1/2" x 1/4" Reducing Bushing 311100 2

APRIL 2004 Page 15 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

6" MODEL H SERIES VERTICAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 3 21 1/2" Union 311403 2 41 3/4" x 1 1/2" Niple 310413 1

3 1/2" Tee 310309 1 22 2" x 3" Nipple 310802 1 43 3/4" x 3 1/2" Nipple 310404 1

4 1/2" Close Nipple 310300 1 24 3/4" x 4 1/2" Nipple 310406 1 45 1/4" x 5" Nipple 310108 1

5 1/2" Ball Valve 311692 2 25 2" Angle Valve 311617 1 53 2" Close Nipple 310800 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 27 2" x 2" x 1/2" Tee 311380 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

8 3/4" Elbow 311204 1 30 3/4" x 1/2" x 1/2" Tee 311318 1 70 1/2" Close Galv. Nipple 310300-G 4

12 3/4" Close Nipple 310400 4 31 3 1/2" Water Gauge (0-300 psi) 300119 2 71 1/2" x 1 1/2" Galv. Nipple 310301-G 1

13 3/4" Swing Check Valve 311640 1 32 1/2" Coupling 311423 1 73 1/2" x 2" Galv. Nipple 310302-G 1

15 1/4" 3-Way Valve 311683 2 34 1/2" x 12" Nipple 310318 1 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 35 Alarm Line Bleeder 320506 1 103 3/4" Close Galv. Nipple 310400-G 1

17 3/4" Union 311404 2 36 3/4" Strainer 325535 1 122 1/2" x 1/4" Reducing Bushing 311100 2

18 3/4" x 2 1/2" Nipple 310402 1 37 1/2" x 1 1/2" Nipple 310301 4

20 1/2" Swing Check Valve 311639 1 38 1/4" x 2" Nipple 310102 1

APRIL 2004 Page 16 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

6" MODEL H SERIES HORIZONTAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 4 20 1/2" Swing Check Valve 311639 1 59 Retard Chamber 323350 1

3 1/2" Tee 311303 1 21 1/2" Union 311403 2 60 1/4" Coupling 311402 1

4 1/2" Close Nipple 310300 2 24 3/4" x 4 1/2" Nipple 310406 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

5 1/2" Ball Valve 311692 2 25 2" Angle Valve 311617 1 68 2" x 7 1/2" Nipple 310809 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 27 2" x 2" x 1/2" Tee 311380 1 69 2" x 6" Nipple 310808 1

8 3/4" Elbow 311204 1 28 1/4" Elbow 311201 2 70 1/2" Close Galv. Nipple 310300-G 3

11 1/4" x 6 1/2" Nipple 310115 2 29 1/4" x 10" Nipple 310136 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 1

12 3/4" x Close Nipple 310400 4 31 3 1/2" Water Gauge (0-300 psi) 300119 2 72 1/2" x 2 1/2" Galv. Nipple 310303-G 1

13 3/4" Swing Check Valve 311640 1 37 1/2" x 1 1/2" Nipple 310301 1 73 1/2" x 2" Galv. Nipple 310302-G 1

15 1/4" 3-Way Valve 311683 2 39 1/2" x 2 1/2" Nipple 310303 3 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 41 3/4" x 1 1/2" Nipple 310413 1 75 1/2" x 12" Galv. Nipple 310318-G 1

17 3/4" Union 311404 2 42 1/4" x 6" Nipple 310110 2 122 1/2" x 1/4" Reducing Bushing 311100 2

18 3/4" x 2 1/2" Nipple 310402 1 43 3/4" x 3 1/2" Nipple 310404 1

APRIL 2004 Page 17 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVEINSTALLATION AND MAINTENANCE GUIDE

6" MODEL H SERIES HORIZONTAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 2 20 1/2" Swing Check Valve 311639 1 41 3/4" x 1 1/2" Nipple 310413 1

3 1/2" Tee 311303 1 21 1/2" Union 311403 2 42 1/4" x 6" Nipple 310110 2

4 1/2" Close Nipple 310300 1 24 3/4" x 4 1/2" Nipple 310406 1 43 3/4" X 3 1/2" Nipple 310404 1

5 1/2" Ball Valve 311692 2 25 2" Angle Valve 311617 1 60 1/4" Coupling 311402 1

6 3/4" x 1/2" x 3/4" Tee 311313 3 27 2" x 2" x 1/2" Tee 311380 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

8 3/4" Elbow 311204 1 28 1/4" Elbow 311201 2 69 2" x 6" Nipple 310808 2

11 1/4" x 6 1/2" Nipple 310115 2 29 1/4" x 10" Nipple 310136 1 70 1/2 Close Galv. Nipple 310300-G 2

12 3/4" Close Nipple 310400 4 30 3/4" x 1/2" x 1/2" Tee 311318 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 1

13 3/4" Swing Check Valve 311640 1 31 3 1/2" Water Gauge (0-300 psi) 300119 2 73 1/2" x 2" Galv. Nipple 310302-G 3

15 1/4" 3-Way Valve 311683 2 32 1/2" Coupling 311423 1 74 1/2" x 8 1/2" Galv. Nipple 310316-G 1

16 1/4" Plug 311001 3 35 Alarm Line Bleeder 320506 1 103 3/4" Close Galv. Nipple 310400-G 1

17 3/4" Union 311404 2 36 3/4" Strainer 325535 1 122 1/2" x 1/4" Reducing Bushing 311100 2

18 3/4" x 2 1/2" Nipple 310402 1 37 1/2" x 1 1/2" Nipple 310301 4

APRIL 2004 Page 18 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

8" MODEL H SERIES VERTICAL POSITION / VARIABLE PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 3 20 1/2" Swing Check Valve 311639 1 61 1/2" Angle Valve 311612 1

3 1/2" Tee 311303 1 21 1/2" Union 311403 2 62 1/2" Plug 311016 1

4 1/2" Close Nipple 310300 2 25 2" Angle Valve 311617 1 63 3/4" x 3/4" x 1/2" Tee 311317 1

5 1/2" Ball Valve 311692 1 27 2" x 2" x 1/2" Tee 311380 1 64 1/4" x 4" Nipple 310106 1

6 3/4" x 1/2" x 3/4" Tee 311313 1 31 3 1/2" Water Gauge (0-300 psi) 300119 2 65 1/2" x 6" Nipple 310310 1

8 3/4" Elbow 311204 1 33 1/2" x 3 1/2" Nipple 310305 2 66 2" x 7 1/2" Nipple 310809 1

12 3/4" Close Nipple 310400 3 37 1/2" x 1 1/2" Nipple 310301 1 67 1/2" x 1/4" x 1/2" 311305 1

13 3/4" Swing Check Valve 311640 1 39 1/2" x 2 1/2" Nipple 310303 1 70 1/2" Close Galv. Nipple 310300-G 1

15 1/4" 3-Way Valve 311683 2 42 1/4" x 6" Nipple 310110 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 2

16 1/4" Plug 311001 3 47 3/4" x 2" Nipple 310401 2 72 1/2" x 2 1/2" Galv. Nipple 310303-G 1

17 3/4" Union 311404 2 53 2" Close Nipple 310800 1 87 1/2" x 3" Galv. Nipple 310304-G 1

18 3/4" x 2 1/2" Nipple 310402 2 59 Retard Chamber 323350 1 96 1/2" x 3 1/2" Galv. Nipple 310305-G 1

APRIL 2004 Page 19 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

8" MODEL H SERIES VERTICAL POSITION / CONSTANT PRESSURE TRIM

Det.No. Description Part No. Req'd Det.

No. Description Part No. Req'd Det.No. Description Part No. Req'd

1 1/2" Elbow 311203 3 21 1/2" Union 311403 2 53 2" Close Nipple 310800 1

3 1/2" Tee 311303 1 25 2" Angle Valve 311617 1 61 1/2" Angle Valve 311612 1

4 1/2" Close Nipple 310300 3 27 2" x 2" x 1/2" Tee 311380 1 62 1/2" Plug 311016 1

5 1/2" Ball Valve 311692 1 30 3/4" x 1/2" x 1/2" Tee 311318 1 63 3/4" x 3/4" x 1/2" Tee 311317 1

6 3/4" x 1/2" x 3/4" Tee 311313 1 31 3 1/2" Water Gauge (0-300 psi) 300119 2 64 1/4" x 4" Nipple 310106 1

8 3/4" Elbow 311204 1 32 1/2" Coupling 311423 1 65 1/2" x 6" Nipple 310310 1

12 3/4" Close Nipple 310400 2 34 1/2" x 12" Nipple 310318 1 66 2" x 7 1/2" Nipple 310809 1

13 3/4" Swing Check Valve 311640 1 35 Alarm Line Bleeder 320506 1 67 1/2" x 1/4" x 1/2" Tee 311305 1

15 1/4" 3-Way Valve 311683 2 36 3/4" Strainer 325535 1 70 1/2" Close Galv. Nipple 310300-G 1

16 1/4" Plug 311001 3 37 1/2" x 1 1/2" Nipple 310301 1 71 1/2" x 1 1/2" Galv. Nipple 310301-G 3

17 3/4" Union 311404 1 39 1/2" x 2 1/2" Nipple 310303 1 87 1/2" x 3" Galv. Nipple 310303-G 1

18 3/4" x 2 1/2" Nipple 310402 2 42 1/4" x 6" Nipple 310110 1 96 1/2" x 3 1/2" Galv. Nipple 310305-G 1

20 1/2" Swing Check Valve 311639 1 47 3/4" x 2" Nipple 310401 2 103 3/4" Close Galv. Nipple 310400-G 1

APRIL 2004 Page 20 BULLETIN A.C.V.I.M., REV. #11

GLOBE ALARM CHECK VALVE INSTALLATION AND MAINTENANCE GUIDE

OPTIONAL ALARM PRESSURE SWITCH TRIM FOR USE WHEN SWITCH IS PROVIDED WITH MECHANICAL ALARM.

FOR USE WHEN SWITCH IS PROVIDED WITHOUT MECHANICAL ALARM, TO PREVENT AIR LOCKS.

To Drain

*NOTE: Other pressure switches available upon request. May be substituted depending on application.

(Existing Trim)

(Existing Trim - System Side)

PRESSURE RELIEF VALVE FOR USE IN GRIDDED SYSTEMS

MODEL H VALVES

Det.No. Description Part No. Req'd

1 3/4" x 4 1/2" Nipple 310406 1

2 1/2" x 4" Nipple 310306 1

3 1/2" Elbow 311203 1

4 3/4" x 3/4" x 1/2" Tee 311317 1

5 Pressure Switch* 301650 1

Det.No. Description Part No. Req'd

1 3/4" x 4 1/2" Nipple 310406 1

2 1/2" x 4" Nipple 310306 1

3 1/2" Elbow 311203 1

4 3/4" x 1/2" x 1/2" Tee 311318 1

5 Pressure Switch* 301650 1

6 Alarm Line Bleeder 320506 1

7 1/2" Coupling 311423 1

Det.N o. Descr ipt ion Par t N o. Req'd

1 1/4" Pressure Relief Valve 323640 1

2 1/4" N PT Male x 1/4" TubeElbow 320603 2

3 1/4" Copper Tubing M-320604 2'