95814-3229 water tank replacement
TRANSCRIPT
CALIFORNIA DEPARTMENT OF PARKS AND RECREATION
ACQUISITION AND DEVELOPMENT DIVISION
GENERAL NOTES
SHEET INDEX
WATER TANK REPLACEMENT
BIG BASIN REDWOODS STATE PARK
CO
VE
R S
HE
ET
CSFM # 01-44-11-0008
PARK ADDRESS
BIG BASIN REDWOODS STATE PARK
21600 BIG BASIN WAY
BOULDER CREEK, CA 95006
SANTA CRUZ COUNTY
LAT: 37.180573 N
LONG: -122.225465 W
1. ALL MATERIALS SHOWN OR NOTED ON THE PLANS ARE NEW UNLESS CALLED OUT OTHERWISE.
2. THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS, BUT SHALL RELY ONLY ON THE WRITTEN
DIMENSIONS GIVEN. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING
CONDITIONS SHOWN OR DIMENSIONED HERE. ANY DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE STATE REPRESENTATIVE FOR RESOLUTION BEFORE PROCEEDING WITH
THAT PORTION OF THE WORK.
3. ALL WORK SHALL COMPLY WITH THE CURRENT EDITION AT DATE OF PLAN APPROVAL OF THE
FOLLOWING LISTED CODES, AND ALL OTHERS HAVING JURISDICTION OVER THE WORK.
3.1. 2013 EDITION OF THE CALIFORNIA BUILDING CODE.
3.2. 2013 EDITION OF THE CALIFORNIA ELECTRICAL CODE.
3.3. 2013 EDITION OF THE CALIFORNIA PLUMBING CODE.
3.4. 2013 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3.5. CONDUCT ALL WORK IN ACCORDANCE WITH THE LATEST SAFETY RULES AND REGULATIONS
OF ALL AUTHORITIES AND AGENCIES HAVING JURISDICTION OVER THE WORK. ALL WORK
SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. WHERE DETAILED
INFORMATION OR CLARIFICATION IS REQUIRED THE MATTER SHALL BE REFERRED TO THE
STATE'S REPRESENTATIVE FOR WRITTEN RESOLUTION.
4. CONSTRUCTION ACTIVITIES ARE LIMITED TO SEPTEMBER 16TH THROUGH MARCH 23RD.
PROJECT MAY BE SUBJECT TO OVERSIGHT BY A STATE PARKS ENVIRONMENTAL MONITOR. THE
PROJECT WILL BE SUBJECT TO CONSTRUCTION MILESTONES.
5. MAPS WERE PREPARED USING THE FOLLOWING:
5.1. BIG BASIN REDWOODS STATE PARK WATER SYSTEM IMPROVEMENTS PLANS, SHEET C-20,
DATED JUNE 2007.
5.2. BIG BASIN REDWOODS STATE PARK WATER TREATMENT PLANT VALVELESS FILTER &
STORAGE TANK PLANS, SHEET 6, DATED JUNE 1961.
6. ALL ROADS AND PARKING AREAS ARE DIRT AND DIMENSIONS ARE APPROXIMATE.
7. SITE ACCESS IS LIMITED TO 10' WIDE LOADS DUE TO THE VEHICLE GATES AND SECTIONS OF THE
ROAD ARE LIMITED TO 10 FEET WIDE ACROSS.
8. LOCATION OF ALL UTILITIES ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY THE
LOCATION OF UTILITIES PRIOR TO EARTHWORK.
VICINITY MAP
N
S
W E
LOCATION MAP
N
S
W E
MAIN PARK
ENTRANCE
NOT TO SCALE
NOT TO SCALE
SCOPE
THIS PROJECT INCLUDES THE DESIGN FOR THE FOLLOWING IMPROVEMENTS TO THE CLEARWELL
WATER TANK AT BIG BASIN REDWOODS STATE PARK:
1. REMOVE EXISTING 50,000 GALLON REDWOOD STORAGE TANK;
2. INSTALL TEMPORARY WATER STORAGE IMPROVEMENTS INCLUDING:
2.1. TIE-IN CONNECTION TO THE WATER TREATMENT PLANT (E) TREATED WATER LINE;
2.2. TWO 8,050 GALLON CHLORINE CONTACT TANKS;
2.3. 260 FEET OF 2"Ø PVC ABOVEGROUND WATER LINE; AND
2.4. TIE-IN CONNECTION THE THE (E) 6"Ø DISTRIBUTION MAIN
3. INSTALL ENGINEERED CONCRETE SLAB FOUNDATION;
4. INSTALL ONE (1) 50,000 GALLON STAINLESS STEEL WATER TANK WITH THE FOLLOWING:
4.1. 2"Ø INLET AND 6"Ø OUTLET;
4.2. 4"Ø OVERFLOW AND 4"Ø DRAIN WITH DECHLORINATION SYSTEM;
4.3. 2"Ø RECIRCULATION INLET;
4.4. SIDE ACCESS MANWAY;
4.5. ROOF MANWAY AND INTERIOR ACCESS LADDER;
4.6. GUARD RAIL, EXTERIOR LADDER AND SAFETY CAGE;
4.7. LEVEL INDICATOR;
4.8. ULTRASONIC LEVEL SENSOR;
4.9. TANK VENT;
4.10. INLET MANIFOLD;
4.11. TANK MIXER EDUCTOR AND ASSOCIATED RECIRCULATION SYSTEM; AND
4.12. SAMPLE TAPS
5. INSTALL RECIRCULATION SYSTEM W/ A 2" LINE, PUMP SYSTEM & CHLORINE INJECTION LOCATION;
6. INSTALL 1"Ø FILL LINE TO SUPPLY WATER FOR TANK CLEANING; AND
7. INSTALL ELECTRICAL CONDUIT TO WATER TANK EQUIPMENT AND RECIRCULATION PUMP SYSTEM.
G1.0
1
CONSULTANT INFORMATION
STRUCTURAL ENGINEER:
STREETER GROUP, INC.
CONTACT: BRAD STREETER
2571 MAIN STREET, SUITE C.
SOQUEL, CA 95073
PHONE: 831-477-1781
PROJECT
LOCATION
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
CIVIL ENGINEER:
FALL CREEK ENGINEERING, INC.
CONTACT: PETER HAASE
1525 SEABRIGHT AVENUE
SANTA CRUZ, CA 95062
PHONE: 831-426-9054
GEOTECHNICAL ENGINEER:
BUTANO GEOTECHNICAL ENGINEERING
CONTACT: GREG BLOOM
231 GREEN VALLEY ROAD, SUITE E
FREEDOM, CA 95019
PHONE: 831-724-2612
SHEET INDEX
# SHEET TITLE
1 G1.0
COVER SHEET
2 G2.0
EXISTING SITE PLAN
3 C1.0
DEMOLITION PLAN
4 C2.0
WATER TANK IMPROVEMENTS
5 C2.1
TEMPORARY SITE IMPROVEMENTS
6 C3.0
TANK DETAILS
7 C3.1
TANK DETAILS
8 C3.2
WATERLINE DETAILS
9 S1.0
WATER TANK FOUNDATION PLAN
10 E1 SYMBOLS, ABBREV., CODES, STANDARDS
& SHEET INDEX
11 E2 ELECTRICAL SINGLE LINE DIAGRAM,
PANELBOARD SCHEDULE & DETAILS
12 E3
SITE PLAN
13 E4 GENERAL CONSTRUCTION & GENERAL
DEMOLITION NOTES
30391.001
ELECTRICAL ENGINEER:
AURUM CONSULTING ENGINEERS
CONTACT: CHARLES DENLY, EE
60 GARDEN COURT #20
MONTEREY, CA 93940
PHONE: 831-646-3330
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\1
CO
VER
SH
EET.
dw
g, 9
/2
1/2
01
5 1
0:0
2:4
6 A
M
DW
DW
D
W
D
W
D
W
D
W
D
W
D
W
E
E
W
W
W
X
X
X
X
X
X
X
X
X
X
X
DW
DW
D
W
D
W
D
W
D
W
D
W
D
W
E
E
W
W
W
X
X
X
X
X
X
X
X
X
X
X
(E) WATER TREATMENT
FACILITY
(FF EL 1171')
(E) FACILITY
PARKING
TO (E) WATER
RESERVOIR
TO (E)
PUMP
STATION
(E) 50,000 GALLON
REDWOOD POTABLE
WATER STORAGE TANK
(FLOOR EL. 1161.1')
(E) DIRT ACCESS ROAD
(E) VEHICLE GATE
(E) CONCRETE TANK
FOUNDATION FOOTINGS
(EL. 1156.9')
(E) STAIRWAY
AND HANDRAIL
(LOCATION
APPROX.)
(E) 10,000 GALLON
REDWOOD TREATED
WATER BACKWASH TANK
(PAD EL. 1176')
(E) OVERFLOW
& DRAIN LINES
(E) GATE VALVE
(E) FENCE
(E) ELECTRICAL
LINE
(E) DOMESTIC WATER LINE
(E) WATER LINE
(E) GATE
(E) FILTER SUMP
AND CONCRETE PAD
(FF EL 1157.7')
MAINTAIN
REMAINDER
OF (E)
DRAIN
TO CREEK
(SEE SHEET
C2.0)
(E
) O
FF
IC
E
(E) MICROFILTRATION
SYSTEM
(E) CARBON
FILTER
(E) CONTROL
PANEL
(E) SINK &
WORKTABLE
(E) 4"Ø RAW
WATER LINE
(E) CULVERT INLET
(LOCATION APPROX.)
EX
IS
TIN
G S
IT
E P
LA
N
G2.0
2
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SYMBOLS LEGEND
ABBREVIATIONS
DIMENSION LINE
FACE OF MATERIAL
DETAIL NUMBER
1
SHEET NUMBER
REVISION NUMBER
DIMENSION LINE
CENTER LINE
1
A1
SECTION NUMBER
SHEET NUMBER
A
A1
X'-X"
X'-X"
C
L
(E) DIRT ROAD
(E) BUILDINGS
(E) DOMESTIC WATER LINE
(E) WATER LINE
(E) ELECTRICAL LINE
TO BE ABANDONED
DOMESTIC WATER LINE
WATER LINE
WATER LINE (BGS)
ELECTRICAL LINE
DIRECTION OF FLOW
(E) FENCE
GATE VALVE
CHECK VALVE
PUMP
ORIFICE
EDUCTOR
BLOW OFF
PULL BOX
DW
W
AMERICAN CONCRETE INSTITUTE
ANALOG INPUT
ABOVE GROUND SURFACE
ANALOG OUPUT
APPROXIMATE
AMERICAN SOCIETY FOR TESTING
AND MATERIALS
AMERICAN WATER WORKS
ASSOCIATION
BELOW GROUND SURFACE
CLEAR
CONCRETE
DUCTILE IRON/DIGITAL INPUT
DIAMETER
DIGITAL OUTPUT
DRAWINGS
EXISTING
EACH
ELEVATION
EQUAL
ET CETERA
FINISHED FLOOR
FINISHED GRADE
FOOT OR FEET
GAUGE
GALLON
GALVANIZED
GALLON PER MINUTE
HORIZONTAL TO VERTICAL
INCORPORATED
INVERT
LINEAR
MINIMUM
MANUFACTURER
ON CENTER
OVERFLOW
ORIGINAL GROUND
POINT OF CONNECTION
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POLYVINYL CHLORIDE
REQUIRED
STREETER GROUP INCORPORATED
SQUARE
STAINLESS STEEL
STATION
STANDARD
STORMWATER SOIL LOSS
POLLUTION PREVENTION
TEMPORARY
TO BE ABANDONED
TO BE DETERMINED
TO BE REMOVED
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WITH
WATER TREATMENT PLANT
DIAMETER
ACI
AI
AGS
AO
APPROX.
ASTM
AWWA
BGS
CLR
CONC.
DI
DIA
DO
DWGS
(E)
EA
EL
EQ.
ETC.
FF
FG
FT
GA
GAL
GLV
GPM
H:V
INC.
INV
LN
MIN.
MFG.
O.C.
OF
OG
POC
P.S.F.
PSI
PVC
REQ;D.
SGI
SQ.
SS/SSTL
STA
STD
SWSLPP
(T)
TBA
TBD
TBR
TYP
U.N.O.
VERT
W/
WTP
Ø
SCALE: 1" = 10'
1
EXISTING SITE PLAN
N
S
W E
GRAPHIC SCALE: 1" = 10'
0' 10' 20'
E
X
MATERIALS LEGEND
CONCRETE
GRAVEL
ROAD
EARTH
BASE COURSE
AC PAVEMENT SECTION
FINAL BACKFILL
INITIAL BACKFILL
BEDDING COURSE
DENSE NATIVE MATERIAL
E
DW
30391.002
PB
E
W
BO
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\2
EX
ISTI
NG
SIT
E PLA
N.d
wg
, 9
/2
1/2
01
5 1
0:0
2:5
7 A
M
(E) FILTER
SUMP (TBR)
(E) CONCRETE
PAD (TBR)
DW
DW
D
W
D
W
D
W
D
W
D
W
D
W
E
E
W
W
W
X
X
X
X
X
X
X
X
X
X
X
DW
DW
D
W
D
W
D
W
D
W
D
W
D
W
E
E
W
W
W
X
X
X
X
X
X
X
X
X
X
X
(E) WATER TREATMENT
FACILITY
(FF EL 1171')
(E) FACILITY
PARKING
TO (E) WATER
RESERVOIR
TO (E)
PUMP
STATION
MAINTAIN (E) 10,000 GALLON
REDWOOD TREATED
WATER BACKWASH TANK
(PAD EL 1176')
(E) DIRT ACCESS ROAD
(E) VEHICLE GATE
MAINTAIN (E) STAIRWAY
AND HANDRAIL
(LOCATION APPROX.)
REMOVE FIVE
(E) CONCRETE
FOUNDATION
FOOTINGS
REMOVE (E) 50,000 GALLON
REDWOOD STORAGE TANK
REMOVE (E) FILTER SUMP
AND CONCRETE PAD
REMOVE (E) VALVE BOX
& ABANDON (E) GATE VALVE
ABANDON (E)
DISTRIBUTION MAIN
(~50 FEET)
ABANDON (E) OVERFLOW
AND DRAIN LINES
REMOVE (E) &
REPLACE W/ (N)
ELECTRICAL LINES
MAINTAIN (E) 4"Ø
WATERLINE FROM
WATER TREATMENT PLANT
(LOCATION APPROX.)
MAINTAIN (E)
DISTRIBUTION MAIN
TO PUMP STATION
APPROX. POINT
OF CONNECTION
(E) FENCE
(E) GATE
MAINTAIN REMAINDER OF (E) DRAIN
TO CREEK (SEE SHEET C2.0)
REMOVE & REINSTALL
(E) CHLORINE ANALYZER
ON NEW WATER TANK
CAP (E) DRAIN LINE
FROM FILTER SUMP
MAINTAIN ALL(E) WTP
EQUIPMENT
CAP (E)
DISTRIBUTION MAIN
MAINTAIN (E) CULVERT INLET
(LOCATION APPROX.)
MAINTAIN (E) 4"Ø
RAW WATER LINE
28' DIAMETER
12' HEIGHT
(E) WEIR
(TBR)
(E) 8" PIPE
(TO BE CAPPED)
(E) FILTER
SUMP (TBR)
DE
MO
LIT
IO
N P
LA
N
C1.0
3
30391.003
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: 1" = 10'
1
DEMOLITION PLAN
N
S
W E
GRAPHIC SCALE: 1" = 10'
NOTE:
1. THE CONTRACTOR TO DETERMINE THE EXACT
LOCATION OF THE (E) WATER LINE FROM THE
WATER TREATMENT PLANT AND THE DISTRIBUTION
MAIN IN THE LOCATION OF THE TIE-IN PRIOR TO
TRENCHING.
SCALE: NTS
2
(E) 50,000 GALLON REDWOOD TANK (TBR)
NOTES:
1. THE TANK ROOF IS COMPOSED OF COMPOSITE SHINGLES AND HAS A 2:1 H:V SLOPE.
2. THE CONTRACTOR SHALL SALVAGE REDWOOD PLANKS AND JOISTS FOR PARK REUSE. THE STATE
REPRESENTATIVE SHALL DESIGNATE WHERE THE SAVAGED WOOD SHALL BE TAKEN.
3. THE CONCRETE FOOTING IN THE FRONT OF THE TANK (CLOSEST TO THE CREEK) IS 1' DEEPER THAN THE
OTHER FOOTINGS, WHICH ARE TYPICALLY 3' IN HEIGHT. THE FOOTINGS ARE APPROXIMATELY 2 FEET
ABOVE GROUND SURFACE, EXCEPT FOR THE EASTERN FOOTING LOCATED NEAR THE TOE OF THE SLOPE,
WHERE EROSION HAS RESULTED IN THE FOOTING EXPOSED ONLY 15" ABOVE GROUND SURFACE.
4. THERE ARE FOURTEEN (14) 4" X 10" REDWOOD CHINE JOISTS AT 24" ON CENTER ABOVE AND
PERPENDICULAR TO THE CONCRETE FOOTINGS.
5. THE INFORMATION PROVIDED ON THE EXISTING WATER TANK IS FROM BIG BASIN REDWOODS STATE
PARK WATER TREATMENT PLANT VALVELESS FILTER & STORAGE TANK PLANS, SHEET 6, DATED JUNE 1961.
6. THE CHLORINE ANALYZER SHALL BE INSTALLED ON THE OUTLET OF THE (T) CONTACT TANKS DURING THE
CONSTRUCTION PERIOD. AFTER CONSTRUCTION IS COMPLETE, THE ANALYZER SHALL BE PLACED ON THE
NEW 50,000 GALLON STAINLESS STEEL WATER TANK.
0' 10' 20'
REMOVE AND REINSTALL
(E) CHLORINE ANALYZER
ON NEW 50,000 GAL TANK
REMOVE ALL (E)
ABOVEGROUND
PIPING
(E) DIRT ROAD
(E) BUILDINGS
(E) DOMESTIC WATER LINE
(E) WATER LINE
(E) ELECTRICAL LINE
TO BE ABANDONED
DIRECTION OF FLOW
FENCE
GATE VALVE
DW
W
E
X
LEGEND:
REMOVE (E) LADDER
REMOVE (E)
COMPOSITE ROOF
SCALE: NTS
3
(E) FILTER SUMP & CONRETE PAD (TBR)
NOTES:
1. THE DIMENSIONS OF THE OVEFLOW BASIN ARE
4' WIDE BY 5'-6" LONG BY 2'-6" HIGH WITH 6"
THICK WALLS WITH REINFORCEMENT.
2. THE REINFORCED CONCRETE SLAB IS 8" THICK
WITH AN ADDITIONAL 1' DEEP BY 1' WIDE FOOTING
AROUND THE SLAB BASE AND IN THE CENTER.
3. THE WEIR IS A 3/16" IRON PLATE EMBEDDED 3/4"
INTO THE BASIN WALLS AND BOTTOM.
4. THE 8" CAST IRON PIPE SHALL BE CAPPED 6"
BELOW GROUND SURFACE. CONTRACTOR SHALL
VERIFY THE FITTING REQUIRED AS THERE IS A BEND BELOW THE GROUND SURFACE.
5. THE INFORMATION PROVIDED ON THE OVERFLOW BASIN IS FROM BIG BASIN REDWOODS
STATE PARK WATER TREATMENT PLANT VALVELESS FILTER & STORAGE TANK PLANS,
SHEET 6, DATED JUNE 1961.
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\2
EX
ISTI
NG
SIT
E PLA
N.d
wg
, 9
/2
1/2
01
5 1
0:0
3:0
3 A
M
DW
DW
D
W
D
W
D
W
D
W
D
W
D
W
W
W
W
X
X
X
X
X
X
X
X
X
X
X
E
E
E
E
W
D
W
D
W
D
W
D
W
D
W
DW
DW
DW
DWDW
BO
WATER TANK
IMPROVEMENTS
(E) 10,000 GALLON
REDWOOD TREATED
WATER BACKWASH
TANK
(E
) O
FF
IC
E
TO WATER
RESERVOIR
ROAD TO
(E) PUMP STATION
(E) DIRT ACCESS ROAD
(E) VEHICLE GATE
TIE-IN LOCATION
TO (E) DISTRIBUTION MAIN
DW
DW
(E) WATER
TREATMENT
FACILITY
ELECTRICAL
LINE
D
W
D
W
DW
D
W
80' OF 1"Ø FILL LINE
(CONNECT TO
(E) WATER LINE FROM
PANORAMIC TANK
INDICATED IN IMAGE BELOW)
FILL LINE CONNECTION
(SEE NOTE 2)
(E) 4"Ø RAW
WATER LINE
ABOVEGROUND
(HEIGHT VARIES)
(E) CULVERT INLET
TO BE PROTECTED
(LOCATION APPROX.)
BO
TEMPORARY SITE
IMPROVEMENTS
BO
B
B
A
B
E
F
D
G
GF
A
C
DW
DWDW
DW
DW
DW
D
W
W
W
W
W
E
E
E
E
E
E
EE
E
BO
WATER TANK
FOUNDATION
4"Ø OVERFLOW
& 4"Ø DRAIN
2"Ø INLET
LADDER AND
SAFETY CAGE
(SEE NOTE 3)
MANWAY
(SEE NOTE 3)
50,000 GALLON
WATER TANK
6"Ø OUTLET
2"Ø RECIRCULATION
LINE
6"Ø AIR VENT
WITH CAP
RECIRCULATION
PUMP
GATE VALVE
(SEE NOTE 1)
6"Ø WATER MAIN
CHECK VALVE
DECHLORINATION
SYSTEM
TIE-IN TO (E) DRAIN LINE
(SEE NOTE 2)
CHLORINE
INJECTION
LOCATION
CONNECT CHLORINE ANALYZER
DRAIN LINE TO OVERFLOW
AT AIR GAP
INSTALL (E) CHLORINE
ANALYZER ON PEDESTAL
& CONCRETE PAD
PULL BOX
(TYP)
GUARDRAILS
PER OSHA
STANDARDS
(SEE NOTE 3)
TRENCH
TIE-IN TO VALVE INSTALLED DURING
(T) IMPROVEMENTS (SEE NOTE 4)
BO
2"Ø BLOWOFF
CAP (E) 6"Ø MAIN
WA
TE
R T
AN
K IM
PR
OV
EM
EN
TS
C2.0
4
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: 1" = 10'
1
SITE IMPROVEMENT PLAN
N
S
W E
GRAPHIC SCALE: 1" = 10'
0' 10' 20'
SCALE: 1" = 4'
2
WATER TANK IMPROVEMENTS
N
S
W E
GRAPHIC SCALE: 1" = 4'
0' 4' 8'
NOTES:
1. THE LOCATION OF THE (E) DISTRIBUTION MAIN IS APPROXIMATE. THE CONTRACTOR TO
LOCATE THE EXISTING LINE PRIOR TO TIE-IN CONNECTIONS.
2. THE FILL LINE SHALL TERMINATE ADJACENT TO THE WATER TANK WITH A CHECK VALVE,
GATE VALVE AND PIPE CONNECTION TO MEET STATE REPRESENTATIVE REQUIREMENTS.
NOTES:
1. THE 2" INLET SHALL BE CONNECTED TO THE (E) WATER LINE FROM THE WATER TREATMENT PLANT. CONTRACTOR SHALL LOCATE
AND INTERCEPT THE EXISTING LINE AND CONNECT THE NEW INLET BELOW THE GROUND SURFACE.
2. THE OVERFLOW AND DRAIN LINE SHALL BE CONNECTED TO THE (E) DRAIN TO CREEK. CONTRACTOR SHALL DETERMINE THE
EXACT LOCATION THAT THE (E) DRAIN LINE IS LOCATED TO CONNECT THIS PIPE.
3. LOCATION OF MANWAY, GUARDRAILS AND LADDER AND SAFETY CAGE IS APPROXIMATE AND THE FINAL LOCATION SHALL BE
FIELD VERIFIED AND APPROVED BY STATE REPRESENTATIVE.
4. TIE-IN TO THE DISTRIBUTION SYSTEM SHALL BE TO THE GATE VALVE INSTALLED DURING (T) IMPROVEMENTS SHOWN ON DETAIL 1
OF SHEET C2.1.
LEGEND:
30391.004
PIPE SCHEDULE
LINE PIPE
LENGTH
(FT)
DESCRIPTION
A 1"Ø SCH 40 PVC 80 FILL LINE FROM BACKWASH TANK
B 2"Ø SCH 80 PVC 260
(T) LINE FROM (E) TREATED WATER LINE TO (E) DISTRIBUTION MAIN (AGS)
C 2"Ø SCH 40 PVC 20 RECIRCULATION LINE FROM 6"Ø OUTLET TO TANK EDUCTOR
D 4"Ø C900 PVC 20OVERFLOW/DRAIN LINE FROM 50,000 GALLON WATER TANK
E 6"Ø C900 PVC 30
50,000 GALLON WATER TANK OUTLET TO (E) DISTRIBUTION MAIN
F 1"Ø SCH 40 PVC 90 ELECTRICAL LINE FROM WTP TO RECIRCULATION PUMP
G 1-1/4"Ø SCH 40 PVC 50ELECTRICAL LINE FROM WTP TO 50,000 GALLON WATER TANK
PIPE SCHEDULE NOTES:
1. THE PIPE SCHEDULE DOES NOT INCLUDE PIPE INFORMATION FOR THE PIPES ABOVE GROUND CONNECTED TO THE 50,000
GALLON WATER TANK.
2. LINE B IS AN ABOVE GROUND TEMPORARY LINE THAT SHALL BE REMOVED AFTER CONSTRUCTION IS COMPLETE.
(E) DIRT ROAD
(E) BUILDINGS
(E) DOMESTIC WATER LINE
(E) WATER LINE
(E) ELECTRICAL LINE
TO BE ABANDONED
DOMESTIC WATER LINE
WATER LINE
WATER LINE (BGS)
ELECTRICAL LINE
DIRECTION OF FLOW
(E) FENCE
GATE VALVE
CHECK VALVE
PUMP
BLOW OFF
PULL BOX
DW
W
E
X
DW
E
W
BO
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\3
WA
TER T
AN
K IM
PRO
VEM
ENTS
.dw
g, 9
/2
1/2
01
5 1
0:0
3:1
3 A
M
DW
DW
D
W
W
W
W
X
X
X
X
X
X
W
D
W
D
W
D
W
D
W
D
W
DW
DW
DW
DWDW
TO WATER
RESERVOIR
TWO (2) 8,050 GALLON
(T) CONTACT TANKS
MIN 10'
195' OF (T) 2"Ø PVC
WATER LINE
ABOVEGROUND
(E) 4"Ø RAW
WATER LINE
ABOVEGROUND
(HEIGHT VARIES)
(E) CULVERT INLET
TO BE PROTECTED
(LOCATION APPROX.)
(T) LINE TO
(E) CHLORINE
ANALYZER
MIN 3'
4' MIN.
PROTECT (T) 2"Ø PVC
WITH PIPE RAMP/
SPEED BUMP
(E) REDWOOD
TANK (TBR)BO
(T) WATER TREATMENT
PLANT IMPROVEMENTS
(E) FILTER SUMP AND
CONCRETE PAD (TBR)
TO (E) REDWOOD TANK
(E) MICROFILTRATION
SYSTEM
FROM (E)
CARBON
FILTER
RELOCATE CHLORINE
INJECTION LOCATION
4"Ø BUTTERFLY VALVE
(CLOSED DURING
CONSTRUCTION)
4"Ø X 2"Ø TEE
W/ 2"Ø GATE VALVE
2"Ø PVC TEMP LINE TO
(T) CONTACT TANKS
(E) FITTING
(E) 4"Ø TREATED
WATER LINE
CONNECT TO
(E) CHLORINE
DOSING PUMP
(E) PIPE
STRAP
BO
GATE VALVE
BO
2"Ø BLOWOFF
CAP (E) 6"Ø MAIN
6"Ø
TEE
(E) DISTRIBUTION
MAIN (TBR)
(T) 2"Ø PVC
ABOVEGROUND
(SEE NOTE 3)
30"
W
W
W
D
W
D
W
DWDW
DWDW
DWDW
DW
DW
DW
W
(E) OFFICE
TWO (2) 8,050 GALLON
(T) CONTACT TANKS
(E) MICROFILTRATION
SYSTEM
(E) CARBON
FILTER
APPROX. 65' OF
ABOVEGROUND
(T) 2"Ø PVC
195' OF (T) 2"Ø PVC
WATER LINE
ABOVEGROUND
(E) CONTROL
PANEL
(E) 4"Ø RAW
WATER LINE
ABOVEGROUND
(HEIGHT VARIES)
(E) CULVERT INLET
TO BE PROTECTED
(LOCATION APPROX.)
3
C2.1
C2.1
(E) ELECTRICAL
PANEL
(E) TREATED
WATER PIPE
TEMPORARILY INSTALL
(E) CHLORINE ANALYZER
DURING CONSTRUCTION
(E) SINK & WORK TABLE
(SINK LOCATION APPROX.)
(T) LINE FROM (T) CONTACT TANKS OUTLET &
TO (E) CHLORINE ANALYZER (DRAIN TO SINK)
TO (T) 8,050 GALLON
CONTACT TANKS
(E) MAIN ENTRANCE
2"Ø GATE VALVE
(T) 2"Ø BALL
VALVE
(T) SADDLE FOR (T) CHLORINE
ANALYZER LINE
(T) 2"Ø BALL
VALVE
PROFILE
10'-0" OD TANK
14'-4" S
HE
LL LE
NG
TH
15'-5"
16
'-1" O
VE
RA
LL H
EIG
HT
11 1/2"
R
2
"
INLET
OUTLET
FLEXIBLE
COUPLING
13'-2"
6"
PLAN
0°
60°
90°
120°
180°
240°
270°
300°
11"
2
'
-
0
"
(
2
)
P
L
2
'
-
4
"
(
2
)
P
L
323°
37°
154°
206°
1'-6 3/4"
87°
273°
TE
MP
OR
AR
Y S
IT
E IM
PR
OV
EM
EN
TS
C2.1
5
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: 1" = 10'
2
TEMPORARY WATER TREATMENT PLANT IMPROVEMENTS
30391.005
SCALE: AS DIMENSIONED
3
TEMPORARY 2"Ø CONNECTION TO TREATED WATER LINE
RELOCATE CHLORINE
INJECTION LOCATION
UPSTREAM TO
ACCOMMODATE
TEMPORARY
IMPROVEMENTS
(E) MICROFILTRATION
SYSTEM
(E) 4"Ø TREATED
WATER LINE
8,050 GALLON WATER POLY STORAGE TANK (SCALED AS DIMENSIONED)
4
TEMPORARY CONTACT TANKS
NOTES:
1. THE TANKS AND ALL ASSOCIATED PIPING AND VALVES SHALL BE RATED FOR POTABLE WATER AND MEET
NSF 61 STANDARDS.
2. CONTRACTOR TO LEVEL THE GROUND SURFACE TO ENSURE THAT BOTH TANKS ARE PLUMBED AT THE
SAME ELEVATION AND LEVEL.
3. THE TWO TEMPORARY CONTACT TANKS SHALL BE PLUMBED IN PARALLEL WITH THE OUTLET LOCATED 180°
FROM THE INLET TO PREVENT SHORT CIRCUITING.
4. INSTALL (E) ULTRASONIC LEVEL SENSOR IN ONE OF THE (T) CONTACT TANKS AND CONNECT CONDUIT TO
THE EXISTING WTP CONTROLLER. COORDINATE WITH STATE REPRESENTATIVE TO ENSURE THE EXISTING
CONTROLLER OPERATES PROPERLY AND WITH NEW SET POINTS.
5. A CHLORINE LEVEL OF 3.0 MG/L IS REQUIRED TO MEET CHLORINE CONTACT DURING THE WORSE CASE
SCENARIO AT THE PARK USING TWO OF 8,050 GALLON TANKS.
SCALE: 1" = 10'
1
TEMPORARY SITE IMPROVEMENT PLAN
NOTES:
1. THE CONTRACTOR SHALL PLUMB AND DISINFECT THE TEMPORARY IMPROVEMENTS PRIOR TO TIE-IN CONNECTIONS TO THE WATER SYSTEM AT THE WTP AND THE DISTRIBUTION MAIN.
2. SCHEDULING OF THE TIE-IN CONNECTIONS SHALL BE COORDINATED WITH THE STATE REPRESENTATIVE TO DRAIN THE (E) REDWOOD TANK AND TEMPORARILY SHUT DOWN THE WATER TREATMENT
SYSTEM. THE TIMING SHALL OCCUR TO LIMIT THE DOWN TIME OF THE WATER TREATMENT SYSTEM.
3. AFTER THE TIE-IN AT THE DISTRIBUTION MAIN OCCURS, THE GATE VALVE AND BLOWOFF SHALL REMAIN AS PART OF THE WATER TANK IMPROVEMENTS (SEE DETAIL 2 ON SHEET C2.0). THE GATE
VALVE SHALL REMAIN SHALL BE CLOSED DURING CONSTRUCTION AND THE 2" BLOWOFF TEMPORARILY CONNECTED TO THE (T) 2"Ø PVC ABOVEGROUND WATER LINE FROM THE (T) CONTACT TANKS.
4. THE (T) 2"Ø PVC SHALL BE REMOVED AFTER ALL IMPROVEMENTS HAVE BEEN COMPLETED AND THE (E) CHLORINE ANALYZER MOVED TO THE 50,000 GALLON WATER TANK.
5. SETBACKS INDICATED ON THIS PLAN ARE DESIGNATED TO PROVIDE ADEQUATE ACCESS AND TO PROTECT INFRASTRUCTURE DURING CONSTRUCTION.
GRAPHIC SCALE: 1" = 4'
0' 4' 8'
N
S
W
E
N
S
W E
GRAPHIC SCALE: 1" = 10'
0' 10' 20'
NOTE:
1. AFTER CONSTRUCTION
IS COMPLETE, THE
CONTRACTOR SHALL
CLOSE THE 2"Ø GATE
VALVE AND OPEN THE
4"Ø BUTTERFLY VALVE.
LEGEND:
(E) DIRT ROAD
(E) BUILDINGS
(E) DOMESTIC WATER LINE
(E) WATER LINE
(E) ELECTRICAL LINE
TO BE ABANDONED
DOMESTIC WATER LINE
WATER LINE
WATER LINE (BGS)
ELECTRICAL LINE
DIRECTION OF FLOW
(E) FENCE
GATE VALVE
CHECK VALVE
PUMP
BLOW OFF
PULL BOX
DW
W
E
X
DW
E
W
BO
(E) ULTRASONIC LEVEL SENOR
(TO BE INSTALLED IN ONE OF THE TANKS)
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\3
WA
TER T
AN
K IM
PRO
VEM
ENTS
.dw
g, 9
/2
1/2
01
5 1
0:0
3:1
8 A
M
30" MIN. BURY
TO PARK
DISTRIBUTION
MAIN
REFER TO
GEOTECHNICAL
REPORT
4"Ø DRAIN
20'
2% S
LOP
E FO
R
PO
SITIV
E D
RA
INA
GE
AW
AY
FRO
M TA
NK
2" SLOPE FOR
POSITIVE DRAINAGE
AWAY FROM TANK
PROFILE VIEW
CONCRETE SLAB
FOUNDATION
6" OUTLET
LADDER AND SAFETY CAGE
(OPPOSITE SIDE OF TANK)
MANWAY
LEVEL
INDICATOR
20.5'
12
1
3C3.0
2" INLET
LOCATED 180°
FROM 6" OUTLET
2C3.0
4" OVERFLOW
OUTLET
4C3.0
5C3.0
6C3.0
THRUST
BLOCK
2C3.2
1S1.0
ULTRASONIC
LEVEL SENSOR
(BULKHEAD FITTING)
7C3.0
4C3.0
RECIRCULATION
INLET (SEE NOTE 5)
REINSTATE (E)
CHLORINE ANALYZER
ON PEDESTAL &
CONCRETE PAD
AIR GAP
CONCRETE
BLOCK
PIPE SADDLE
CLAMP
SUPPORT
SECTION B-B'
LOCKABLE HOOP
B
B'
HOOP
BAR
CAGE
DETAIL A
8
7
6
5
4
3
2
1
0
ALUMINUM
CAST
INDICATOR
SSTL CABLE
CLAMP
GAGE BOARD
14 GA GLV STEEL
TOP ANCHOR
ASSEMBLY
TANK TOP
TANK BOTTOM
FRONT VIEW
GAUGE BOARD
14 GA GLV STEEL
INDICATOR
BRACKET
15-1/2"Ø
FLOAT
ALUMINUM 90 DEG
CASTING
ASSEMBLY
GLV NIPPLE
TOP ANCHOR
ASSEMBLY
TANK TOP
GUIDE WIRE
11 GA 316 SSTL
FLOAT CABLE
1
16
" 316 SSTL
17"
SS CABLE CLAMP
SECTION VIEWBACK VIEW
(INSIDE TANK)
LOCKING HASP
1
2
" FLAT WASHER
1
2
" HEX NUT
FLANGE BOX ASSEMBLY
HINGE CLIP
MANWAY COVER
1
2
" X 14" LONG
BOLT
STRIP GASKET
24" SQ INSIDE
4"
2" MIN
CONCRETE
FOUNDATION
1S1.0
TANK WALL
6"Ø COMPANION
FLANGE
6"Ø STEEL
FLANGED PIPE
C200-80
6"Ø FLANGED
FLEXIBLE PIPE
CONNECTOR
6"Ø BRONZED GATE VALVE
8C3.0
SAMPLE TAP
SIDE VIEW
WATER
STORAGE TANK 6"Ø BRONZED CHECK VALVE
18"
PIPE
SUPPORT
SIDE VIEW
WATER
STORAGE TANK
2"Ø SCH
80 GLV STEEL PIPE
TANK WALL
(TYP)
2"Ø UNION
2"Ø BRONZED
BALL VALVE
CONCRETE
FOUNDATION
1S1.0
2"Ø LINE TO
WASTE
2"Ø FLEXIBLE COUPLING
CONNECT TO
(E) 4" PVC INLET BGS
TANK MIXING
IMPROVEMENTS
1C3.1
6"
4"X2"Ø REDUCER
2"Ø BALL
VALVE
SIDE VIEW
WATER
STORAGE
TANK
4"Ø DI SPOOL
TANK WALL
(TYP)
CONCRETE
FOUNDATION
1S1.0
CONNECT 4"Ø SPOOL TO
DECHLORINATION SYSTEM &
(E) DRAIN W/ MIN.1% SLOPE
12"
SPOOL LENGTH TO BE
FIELD VERIFIED (TYP)
4"Ø DI ELBOW
4"Ø DI ELBOW
6"
OVERFLOW
DRAIN
SEE SECTION VIEW ABOVE
AIR GAP ON OVEFLOW
4"Ø GATE VALVE
ON DRAIN
4" DI 90° ELBOW
4" DI SPOOL
SECTION VIEW
4"Ø GATE VALVE
& VALVE BOX
4"Ø DI 90° ELBOW
4"Ø TEE TO
DECHLORINATION
SYSTEM
4"Ø DI 90° ELBOW
OVERFLOW
DRAIN
4"Ø DI 90° ELBOW
3C3.2
SCREENED
AIR GAP
4"X6" REDUCER
DRAIN LINE FROM
CHLORINE ANALYZER
7C3.1
DETAIL A
CARRIAGE
BOLT
HOOP
NUT
BAR CAGE
TA
NK
D
ET
AILS
C3.0
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: 1" = 5'
1
50,000 GALLON WELDED STAINLESS STEEL TANK
SCALE: NTS
2
TYPICAL INLET PIPE CONNECTION
SCALE: NTS
3
TYPICAL OUTLET PLUMBING
SCALE: NTS (SUPPLIED BY TANK MANUFACTURER)
5
TYPICAL BOLTED ACCESS MANWAY
ADJUSTABLE PIPE SADDLE CLAMP SUPPORT NOTES:
1. SIZES VARY BY MANUFACTURER
2. ALL PIPE SUPPORTS SHALL BE STEEL WITH A
CORROSION RESISTANT, GALVANIZED FINISH.
3. EXTENSION PIPE SHALL BE 2" SCH 40
4. SUPPORT SIZE: 6"
5. STRAP SIZE: 1/2" X 2"
6. THREAD STUD: 1" X 6"
7. BASE PLATE: 8" X 8" X 1/4"
8. MIN DIST. TO FLOOR: 7"
9. CLAMP SUPPORT SHALL BE SECURED TO A
PRECAST CONCRETE BLOCK WITH A MINIMUM OF
8" BY 8" TOP DIMENSION TO FIT THE BASE PLATE.
10. THE CONCRETE BLOCK SHALL BE EMBEDDED 12"
INTO NATIVE GROUND.
12" MIN
HEIGHT
VARIES
SCALE: NTS (INSTALL PER MANUFACTURER'S RECOMMENDATIONS)
6
TYPICAL LADDER AND SAFETY CAGE
SCALE: NTS
7
TYPICAL LEVEL INDICATOR
SCALE: AS DIMENSIONED
8
PIPE SUPPORT
6
TO PARK
DISTRIBUTION MAIN
TANK NOTES:
1. WELDED 304 STAINLESS STEEL TANK.
2. DESIGNED IN ACCORDANCE WITH AWWA D100-11
3. SEISMIC ZONE 4, I=1.25, RW=4.50, S=1.50 PER AWWA, 100 MPH
WIND LOAD PER AWWA, 25 PSF LIVE DECK LOAD, FLAT STEEL
BOTTOM.
4. TANK ACCESSORIES TO INCLUDE:
4.1. 6" VENT WITH
1
2
" MESH SCREEN
4.2. 24" SQUARE ROOF MANWAY W/ INTERNAL LADDER
4.3. OUTSIDE STAINLESS STEEL LADDER W/ SAFETY CAGE
AND LOCKABLE ENTRY HOOP
4.4. LIQUID LEVEL INDICATOR W/ BOARD
4.5. 8" INTERNAL OVERFLOW WEIR
4.6. SIDE ACCESS HATCH NOMINAL OPENING, 36" DIA.
5. RECIRCULATION INLET (1-1/2"Ø), SEE DETAIL 3 ON SHEET C3.1.
30391.006
SCALE: NTS
4
TYPICAL OVERFLOW/DRAIN PLUMBING
NOTE:
1. AN INTERIOR LADDER TO BE INSTALLED INSIDE THE MANWAY PER
MANUFACTURER'S RECOMMENDATIONS.
TANK BUILDING ANALYSIS:
1. OCCUPANCY CLASSIFICATION AND USE:
2. BUILDING CONSTRUCTION TYPE:
3. NUMBER OF STORIES:
4. ACTUAL BUILDING HEIGHT:
5. BUILDING AREA:
6. AREA OF PROJECT:
UTILITY & MISC. GROUP U
TYPE IA
ONE
20 FEET*
330 SQUARE FEET*
425 SQUARE FEET*
* THIS ANALYSIS IS BASED ON A TYPICAL 50,000 GALLON STAINLESS STEEL TANK,
VALUES MAY VARY SLIGHTLY BASED ON THE MANUFACTURER SELECTED.
NOTES:
1. LADDER SHALL MEET OSHA STANDARDS.
2. THE STATE REPRESENTATIVE SHALL APPROVE THE
TYPE OF LADDER SELECTED.
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\4
DET
AIL
S.d
wg
, 9
/2
1/2
01
5 1
0:0
3:3
4 A
M
1-1/2"Ø RECIRCULATION
INLET ENTERING TANK
2" INLET
ORIFICES
6"
1-1/2"Ø RECIRCULATION
INLET
2" INLET
1-1/2" TANK
MIXING EDUCTOR
6C3.1
2"X1-1/2"Ø REDUCER
EDUCTOR EFFECTIVE
FLOW FIELD
ORIFICES
2"Ø RECIRCULATION
LINE
45°
CHLORINE INJECTION
5C3.1
6"Ø OUTLET
2"Ø INLET
ORIFICE (TYP)
E
TANK MIXING
EDUCTOR
2"Ø RECIRULATION LINE
RECIRCULATION PUMP
4C3.1
6C3.1
2C3.1
2C3.1
TO PARK
DISTRIBUTION
MAIN
3C3.0
2C3.0
3C3.1
3C3.1
CHLORINE INJECTION
5C3.1
GUARD RAILS
(PER OSHA
STANDARDS)
LADDER AND
SAFETY CAGE
6C3.0
2"Ø BALL VALVE (NC)
HANDLE
FEED TUBE CAP
TABLET
FEED TUBE
INTERNAL BAFFLE
INTERMEDIATE
FLOW TIER
UPPER FLOW TIER
INERT DRAINAGE TIER
OUTLETINLET
2"Ø TEE
2"Ø BALL VALVE (NC)
2"Ø PVC CAP
6" STANDPIPE
(E) CHLORINE
ANALYZER
50,000 GALLON
STORAGE TANK
TO DISTRIBUTION
SYSTEM
ULS
1
LV
1
LV
2
FROM
WTP
RECIRCULATION LINE
P
1
(E) CHLORINE
ANALYZER
CA
1
RECIRCULATION
PUMP
TA
NK
D
ET
AILS
C3.1
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: 1" = 5'
2
SECTION VIEW 1
7
SCALE: 1" = 5'
3
SECTION VIEW 2
SCALE: 1" = 5'
1
TANK MIXING IMPROVEMENTS
A
'
NOTE:
1. EDUCTOR SHALL BE DESIGNED TO HAVE AN
INLET FLOW RATE OF 58 GPM, CIRCULATION
RATE OF 290 GPM, AND EFFECTIVE FLOW
FIELD OF 24 FEET.
SCALE: AS DIMENSIONED
6
1-1/2" TANK MIXING EDUCTOR
TYPICAL CENTRIFUGAL PUMP
PUMP SYSTEM SPECIFICATIONS
PARAMETER PS#1
NUMBER OF PUMPS IN SYSTEM 1
FLOW RATE (GPM)
58
TOTAL DYNAMIC HEAD (FT)
70
PHASE 3
VOLTAGE (V)
230
HORSEPOWER (HP)
3
TOTAL FULL LOAD AMPERAGE (AMPS)
--
SCALE: NTS
4
RECIRCULATION PUMP DETAILS
NOTES:
1. THE RECIRCULATION PUMP SHALL BE ABOVE
GROUND, PLACED ON A 2.5' X 2.5' X 4" CONCRETE
PAD.
2. THE PUMP MOTOR CONTROLLER SHALL
OPERATE THE PUMP ON A TIMER TO MIX THE
WATER IN THE TANK AND PREVENT STAGNATION.
THE PUMP SHALL CYCLE ON FOR 15 MINUTES
EVERY HOUR.
3. THE PUMP SHALL BE RATED FOR POTABLE
WATER AND MEET NSF 61 STANDARDS.
WATER LINE (BGS)
GATE VALVE
CHECK VALVE
PUMP
ORIFICE
EDUCTOR
E
LEGEND:
30391.007
SCALE: AS DIMENSIONED
5
CHLORINE INJECTION
SCALE: NTS
7
DECHLORINATION SYSTEM
NOTES:
1. THE DECHLORINATION SYSTEM
(LOCATED ON THE TANK
DRAIN/OVERFLOW LINE) SHALL
ACCOMMODATE 2-5/8" ASCORBIC
ACID DECHLORINATION TABLETS
THAT ARE NON-TOXIC TO FISH
AND OTHER AQUATIC LIFE.
2. THE DECHLORINATION SYSTEM
TO BE INSTALLED IN VALVE BOX.
3. VALVE BOX SHALL HAVE GOPHER
WIRE AND 3" MIN OF CLEAN
GRAVEL INSTALLED AT BASE.
NOTE:
1. CHLORINE INJECTION SHALL
OCCUR MANUALLY, BY REMOVING
THE CAP, POURING CHLORINE INTO
THE STANDPIPE, REPLACING THE
CAP, AND OPENING THE BALL
VALVE. THE BALL VALVE SHALL BE
CLOSED ONCE THE CHLORINE HAS
ENTERED THE RECIRCULATION
LINE.
SCALE: NTS (FOR (E) CHLORINE ANALYZER)
8
PEDESTAL & CONCRETE PAD
CONTROL POINTS FOR WATER SYSTEM CONTROL PANEL
LABEL DESCRIPTION TYPE OTHER INFORMATION
LV-1 LEVEL FLOAT DI LOW LEVEL BACKUP FLOAT
LV-2 LEVEL FLOAT DI HIGH LEVEL BACKUP FLOAT
ULS-1 ULTRASONIC LEVEL SENSOR AI TANK HEIGHT IS 20'
CA-1 (E) CHLORINE ANALYZER AO EXISTING CHLORINE ANALZYER
P-1 RECIRCULATION PUMP DO 58 GPM, 70' TDH, 3 HP MOTOR
SCALE: NTS
9
PROCESS AND INSTRUMENTATION DIAGRAM
CONTROL SYSTEM NARRATIVE:
1. THE (E) CONTROL SYSTEM SHALL INTEGRATE CONTROL POINTS FROM THE ULTRASONIC LEVEL
SENSOR AND (E) CHLORINE ANALYZER TO OPERATE AS PROGRAMMED PRIOR TO
CONSTRUCTION TO SEND TANK LEVELS AND CHLORINE ANALYZER DATA TO THE OPERATOR.
2. THE SUBCONTROLLER SHALL MONITOR THE TWO BACKUP LEVEL FLOATS & THE RECIRCULATION
PUMP, INTEGRATED INTO THE (E) CONTROL SYSTEM TO ALLOW THE THE OPERATOR TO
MONITOR THE SYSTEM. THE RECIRCULATION PUMP SHALL CYCLE ON 15 MINUTES EVERY HOUR.
3. THE SUBCONTROLLER SHALL HAVE THE FOLLOWING ALARMS:
3.1. LOW LEVEL IN WATER STORAGE TANK
3.2. RECIRCULATION PUMP CYCLE COUNTER NOT LOGGING OVER SET POINT
THE OPERATOR SHALL BE ABLE TO DISABLE/ENABLE ALL ALARMS AND ADJUST ALARM SET
POINTS. ALL ALARMS SHALL HAVE A USER DEFINED DELAY BEFORE ACTIVATION.
4. THE SUBCONTROL SYSTEM SHALL LOG THE FOLLOWING INFORMATION
4.1. RECIRCULATION PUMP CYCLE COUNTER
4.2. TANK HIGH LEVEL OR LOW LEVEL
5. THE SUBCONTROL SYSTEM SHALL MONITOR AND DISPLAY:
5.1. RECCIRCULATION PUMP ON/OFF STATUS (P-1)
5.2. BACKUP FLOATS (LV-1 & LV-2)
6. THE OPERATOR INTERFACE FOR THE WATER SYSTEM MAIN CONTROLLER SHALL BE
ACCESSIBLE VIA AN INTRANET CONNECTION TO ALLOW THE OPERATOR TO MONITOR THE
SYSTEM REMOTELY, VIEW ALARMS, AND LOGS. THE INTERFACE WILL ALLOW FOR ALARM
NOTIFICATION VIA EMAIL OR TEXT MESSAGE.
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\4
DET
AIL
S.d
wg
, 9
/2
1/2
01
5 1
0:0
3:4
5 A
M
PIPE END TO
REMAIN ACTIVE
RESTRAINED FLANGED
COUPLING ADAPTER
BLIND FLANGE
GASKET
FTGS TO MATCH
PIPELINE, TYP
THRUST BLOCK
#4 REBAR LOOPED
AROUND VALVE
FINISHED
GRADE
2"x8"x16" CMU,
TYP ALL SIDES
EXTENSION TO
MATCH FINISHED
GRADE (AS REQ'D)
13"x24" TRAFFIC BOX
EXTENSIONS & COVER
STAMPED "WATER",
H/20 LOADING
2" GROUT,
TYP
PIPELINE
SQUARE
NUT
NOTES:
1. A CHRISTY G-5 VALVE BOX AND C.I. COVER MARKED "WATER"
MAY BE USED FOR VALVES 2" AND SMALLER.
2. ALL VALVE BOXES NOT INSTALLED IN THE ROAD SHALL HAVE A
CONCRETE COLLAR AROUND THE RIM.
NOTE:
1. MECHANICAL RESTRAINED
JOINTS ARE ACCEPTABLE IN LIEU
OF CONCRETE THRUST BLOCKS.
TABLE I
TABLE II
90° BEND 45° BEND
PIPE
SIZE
TEE OR
DEAD END
SAFE BEARING
PER SQ. FT.
LOAD, POUNDSSOIL
2"
3"
4"
6"
8"
10"
12"
14"
16" 23779 33628 18199 9278 4661
284
401 217 111 56
87
127
189
355
733
1261
1897
2683
3604
443
649
962
1810
3739
6433
9677
13685
18385
627
918
1361
2559
5288
9097
13685
19353
26001
339
497
736
1385
2862
4923
7406
10474
14072
173
253
375
706
1459
2510
3776
5340
7174
THRUST(T) AT FITTINGS, IN POUNDS AT 100 PSI WATER PRESSURE
SAFE BEARING LOADS (B)
10000
4000
3000
2000
1000
0
SOUND SHALE
CEMENTED SAND
AND GRAVEL
COARSE AND FINE
COMPACTED SAND
MEDIUM CLAY
(CAN BE SPADED)
SOFT CLAY
MUCK
A =
T
B
P
100
SB
T
X
WHERE:
A
SB
AREA OF BLOCK BEARING
AGAINST UNDISTURBED
TRENCH MATERIAL IN SQ. FT.
THRUST FACTOR FROM TABLE I
IN POUNDS AT 100 PSI
SAFE BEARING LOAD FROM
TABLE II IN POUNDS/SQ. FT.
PRESSURE USED FOR
PIPELINE TEST IN PSI
=
=
=
T
B
P T
T
A
SB
22 1/2°
BEND
11 1/4°
BEND
1 1/2"
2 1/2"
CHRISTY G-5 VALVE BOX
AND C.I. COVER.
VALVE BOX
SDR 35 PVC.
18" MIN.
WATER MAIN
OR 4" X 6"
GALV. PIPE
2" OR 4" ABS THREADED PLUG.
BACK OFF 2 TURNS
FROM HANDTIGHT.
4" SAND BEDDING
THRUST BLOCK
MARKED "B.O."
GALV. NIPPLE
EBBA SERIES 1100 PV
RETAINER GLAND W/
M.J. CAP OR PLUG,
TAPPED 2" OR 4" @
BOTTOM OF CAP
M.J. X M.J. X FLG. TEE
BRANCH AND RUN SAME
SIZE.
BLIND FLANGE TAPPED 2" OR
4" @ BOTTOM OF FLANGE.
IN-LINE APPLICATION
END-OF-MAIN APPLICATION
2" OR 4"
COUPLING
2" X 6"
OR PLUG.
GALVANIZED
2" OR 4"
12"
MIN.
6" MAX.
WITH 12" SAND ENVELOPE ABOVE PIPING
NOTES:
1. ALL GALV. PIPE AND FITTINGS SHALL BE BITUMASTIC PRIMED AND WRAPPED W/ PROTECTO
TAPE IN HALF LAPS.
2. BACKFILL SHALL BE 2-SACK SAND/CEMENT SLURRY.
3. BLOW-OFF ASSEMBLY SHALL DRAIN TO NEAREST STORMWATER CATCH BASIN.
FINISH
GRADE
EXTENSION
2####
(N) PAVEMENT
SECTION,
SEE NOTES
1 & 2
NOTES:
1. UNLESS OTHERWISE SPECIFIED, PERMANENT PAVEMENT SHALL
CONFORM IN QUALITY AND THICKNESS TO THE TYPE OF PAVEMENT
REMOVED; BUT IN NO CASE SHALL BE LESS THAN THREE INCHES
(3") OF ASPHALTIC CONCRETE ON SIX INCHES (6") OF BASE.
2. EXISTING PAVEMENT SHALL BE SAWCUT AND REMOVED IN SUCH A
MANNER SO AS NOT TO TEAR, BULGE OR DISPLACE ADJACENT
PAVEMENT. EDGES SHALL BE CLEAN AND VERTICAL WHEN
PRACTICAL, ALL CUTS SHALL BE PARALLEL OR PERPENDICULAR TO
STREET EDGE OF PAVEMENT.
3. ALL EXCAVATION BACKFILL AND COMPACTION SHALL, CONFORM TO
THE REQUIREMENTS OF DIVISION 31, SECTION 312000 - EARTHWORK
SPECIFICATIONS.
4. NO SOLID BLOCKING PERMISSIBLE BENEATH PIPE.
5. JETTING BACKFILL IS NOT PERMITTED.
6. TRENCH EXCAVATION SHALL CONFORM TO CAL-OSHA STANDARDS.
7. WATER PIPING CAN BE RAN IN THE SAME TRENCH AS THE
ELECTRICAL CONDUIT WITH THE WATER PIPING BELOW THE
ELECTRICAL CONDUIT WITH A TWELVE (12) INCH EARTH
SEPARATION.
8. PROTECT TREE ROOTS PER SPECIFICATION SECTION 015639, HAND
DIG WHERE NECESSARY. TREE PROTECTION ZONE IS 5 TIMES THE
DIAMETER-BREAST-HEIGHT OF THE TREE (TPZ = 5 X DBH).
(E) AC
PAVEMENT
SECTION
SUB-BASE
COURSE
MARKER TAPE, ±12"
BELOW (E) GRADE
MARKER TAPE, ±6"
BELOW BASE COURSE
INITIAL
BACKFILL
BEDDING
COURSE
FINISHED
GRADE
~~
~
PIPE AS SHOWN
ON PLANS
WATER
SEWER
ELECTRICAL CONDUIT
30
VARIES PER PLAN
24
UTILITY
NAME
MINIMUM COVER
(INCHES)
PIPE COVER REQUIREMENTS
FOR PIPES SMALLER THAN 12" Ø
(UNLESS NOTED OTHERWISE)
TELEPHONE CONDUIT 20
SEWER FORCE MAIN 28
FINAL
BACKFILL
~
BASE
COURSE
WA
TE
RLIN
E D
ET
AILS
C3.2
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
SCALE: NTS
3
TYPICAL BURIED VALVE
WATER LINE INSTALLATION NOTES:
1. NEW WATER LINES SHALL BE INSTALLED AT A MINIMUM HORIZONTAL
DISTANCE OF FOUR (4) FEET FROM, AND A MINIMUM VERTICAL DISTANCE OF
ONE (1) FOOT ABOVE EXISTING STORMWATER SEWER LINES.
2. NEW WATER LINES SHALL BE INSTALLED AT A MINIMUM HORIZONTAL
DISTANCE OF TEN (10) FEET FROM, AND A MINIMUM VERTICAL DISTANCE OF
TWO (2) FEET ABOVE EXISTING SANITARY SEWER LINES AND AT A MINIMUM
HORIZONTAL DISTANCE OF TWENTY FIVE (25) FEET FROM SANITARY
LEACHFIELDS.
3. WHERE THE ABOVE SEPARATION CAN NOT BE ACHIEVED, THE HORIZONTAL
AND VERTICAL DISTANCES SHALL BE MAXIMIZED, AND THE SECTIONS OF
WATER LINES INSTALLED CLOSE TO EXISTING STORMWATER AND SANITARY
SEWER LINES SHALL BE PLACED IN SLEEVES TO PROVIDE DOUBLE
CONTAINMENT.
4. WHENEVER POSSIBLE, WATER LINES SHALL BE INSTALLED IN ROADS OR
TRAILS. WATER LINES SHALL BE INSTALLED IN LEFT OR RIGHT SIDE OF ROAD
(NOT CENTER) WHERE SETBACKS FROM SD AND SS PIPES CAN BE
MAINTAINED.
SCALE: NTS
2
THRUST BLOCK SIZING AND LOCATIONS
SCALE: NTS
5
TYPICAL PIPE CAP
SCALE: NTS
4
TYPICAL BLOW-OFF ASSEMBLY
SCALE: NTS
1
TYPICAL TRENCH DETAIL
8
30391.008
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\4
DET
AIL
S.d
wg
, 9
/2
1/2
01
5 1
0:0
3:5
4 A
M
1'-4"
3
1
8
"±
20'-6" TANK DIAMETER
WATER TANK SEE
PLANS BY OTHERS
3
4
" DIA (ASTM A36) THREADED ROD
ANCHOR / HOLD DOWN BY TANK
MANUFACTURER
FIRM NATIVE MATERIAL OR
COMPACTED MATERIAL PER
GEOTECHNICAL ENGR
REPORT
1
2
" CANE FIBER JOINT FILLER (AWWA D100-11)
OR 1" SAND CUSHION WITH 6" WIDE x 1" THICK
HIGH STRENGTH GROUT BELOW PERIMETER OF
TANK
1
4
"x3" SQ PLATE
WASHER W/ HEAVY
HEX NUT EA SIDE
1'-0"
PERIMETER THICKEN
CONCRETE EDGE
BEAM
#5 AT 12" O.C. BOTH
WAYS AT BOTTOM
#5 AT 12" O.C. BOTH
WAYS AT TOP
#5 BAR AT BOTTOM
#5 BAR VERT. AT 12" O.C.
3
4
" CHAMFER
12" CONCRETE SLAB
ON GRADE
#5 VERT AT 18" O.C. W/
STD 90 DEG HOOK
EXTEND INTO SLAB 30"
MIN.
30"
MIN.
MIN.
EQ. EQ.
2
S1.0
11'-7"
TYP
TOP OF SLAB SEE
CIVIL DWGS
23'-2" DIAMETER
TANK SHELL
TANK ANCHORAGE
SEE DETAIL 2/S1.0,
TYP
12" CONCRETE
SLAB ON GRADE
SEE DETAIL 2/S1.0
NOTE: VERIFY ALL TANK
MANUFACTURER
DIMENSIONS WITH
PLANS. NOTIFY STATE
REPRESENTATIVE OF
ANY DISCREPANCIES.
CL
WA
TE
R T
AN
K F
OU
ND
AT
IO
N P
LA
N
S1.0
9
09-11-2015
CJC
PHH
CJC
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
(1
00
% S
UB
MIT
TA
L)
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
Reviewed by Date
Approval of this plan does not authorize or
approve any omission of deviation from
applicable regulations. Final approval is
subject to field inspection. One set of
approved plans shall be available on the
project site at all times.
CALIFORNIA STATE FIRE MARSHAL- APPROVED
SH
EET
TITL
E
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
13
FOUNDATION NOTES:
SCALE: 1/4"-1'-0"
1
TANK FOUNDATION
1. USE GRADE 40 DEFORMED REINFORCING FOR #4 AND SMALLER BARS AND GRADE 60
FOR #5 AND LARGER BARS CONFORMING TO THE REQUIREMENTS OF ASTM A615.
STAGGERED REINFORCING BAR CONTACT SPLICES SHALL LAP 40 DIAMETERS.
SUPPORT HORIZONTAL STEEL AT BOTTOM ON MORTAR BLOCKS. MINIMUM CLEARANCE
SHALL BE 3 INCHES FOR SURFACES POURED AGAINST EARTH AND 1.5 INCHES
ELSEWHERE U.N.O.
2. ALL REINFORCING SHALL BE SECURED IN PLACE AND INSPECTED BY THE ENGINEER
PRIOR TO PLACING ANY CONCRETE OR GROUT.
3. ALL WORK DONE UNDER THIS SECTION SHALL CONFORM WITH THE APPLICABLE
PORTIONS OF ACI 318, LATEST EDITION, PARTICULARLY CHAPTER 7, "DETAILS OF
REINFORCEMENT".
1. POURED IN PLACE CONCRETE WORK SHALL BE CONSTRUCTED OF NORMAL WEIGHT,
PORTLAND CEMENT CONCRETE, HAVING A MINIMUM 28-DAY COMPRESSIVE STRENGTH
OF 3,000 PSI. (DESIGN BASED ON Fc=2500 THEREFORE NO SPECIAL INSPECTION OF
CONC. REQ'D) ALL PORTLAND CEMENT CONCRETE SHALL CONFORM TO THE
REQUIREMENTS OF ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED
CONCRETE", LATEST EDITION. MAXIMUM CONCRETE SLUMP SHALL BE 4 INCHES. THE
USE OF ANY ADMIXTURE IN THE CONCRETE MUST BE APPROVED BY THE ENGINEER.
2. ALL NEWLY PLACED CONCRETE SHALL BE CURED IN ACCORDANCE WITH THE
PROVISIONS IN ACI 308, "STANDARD PRACTICE FOR CURING CONCRETE," LATEST
EDITION. METHOD OF CURING SHALL BE AT THE OPTION OF THE CONTRACTOR WITH
APPROVAL OF THE OWNER.
3. ALL METAL ANCHORAGE DEVICES, ANCHOR BOLTS, ETC. SHALL BE SECURED IN PLACE
AND INSPECTED BY ENGINEER PRIOR TO PLACING CONCRETE.
4. ALL WORK DONE UNDER THIS SECTION SHALL CONFORM WITH THE APPLICABLE
PORTIONS OF ACI 318, LATEST EDITION.
1. FOOTINGS ARE PROPORTIONED PER GEOTECHNICAL ENGINEER'S REPORT FOR AN
ALLOWABLE SOIL PRESSURE OF 2,000 P.S.F. SEE GEOTECHNICAL INVESTIGATION
REPORT BY BUTANO GEOTECCHNICAL ENGINEERING INC. PROJECT NO. 15-114-SC
DATED APRIL 2015.
2. CONTRACTOR SHALL CAREFULLY EXCAVATE ALL MATERIALS NECESSARY OF
WHATEVER NATURE, FOR CONSTRUCTION OF THE WORK. ANY MATERIAL OF AN
UNSUITABLE OR DELETERIOUS NATURE DISCOVERED BELOW THE BOTTOMS OF THE
FOUNDATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE GEOTECHNICAL
ENGINEER BEFORE PROCEEDING WITH THE WORK.
3. ALL EXCAVATIONS SHALL BE INSPECTED BY THE PROJECT GEOTECHNICAL ENGINEER.
4. SEE GEOTECHNICAL ENGINEERS REPORT FOR ADDITIONAL SPECIFICATIONS.
C. REINFORCEMENT
B. CONCRETE
A. EARTHWORK
1. SUBMIT TANK DESIGN BY MANUFACTURER TO STREETER GROUP INC FOR FAVORABLE
REVIEW PRIOR TO FOUNDATION CONSTRUCTION.
D. SUBMIT
SCALE: AS DIMENSIONED
2
WATER TANK SLAB EDGE
30391.009
BSS
BSS
S:\
Pro
ject
s\2
15
04
Wa
ter
Tank
Rep
lace
ment
Big
Ba
sin
SP\C
AD
\S1
Foun
da
tion.
dw
g, 9
/2
1/2
01
5 1
0:0
4:0
3 A
M
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
09-11-2015
CADD
E.O.B.
N.A.
13
60 Garden Court Suite 210 Monterey, CA 93940
T.831.646.3330 F.831.646.3336 www.acemb.com
Project No.
ONTEREY
NGINEERS
ONSULTING
E
M
URUM A C
AY, INC.B
15139.00
HALF SWITCHED RECEPTACLE - DUPLEX
INSTALLATION.
FLOOR MOUNTED DUPLEX RECEPTACLE
J
PANELBOARD - FLUSH MOUNTED.
SIZE PER CODE, TAPE AND TAG WIRES.
PANELBOARD - SURFACE MOUNTED.
EQUIPMENT PANEL - SURFACE MOUNTED
EQUIPMENT PANEL - FLUSH MOUNTED
METER W/ CURRENT TRANSFORMER.
INTERIOR SPEAKERS CEILING MOUNTED.
TV OUTLET
FLOOR MOUNTED VOICE/DATA OUTLET
JUNCTION BOX - CEILING OR WALL MOUNTED,
GFCI CONVENIENCE
RECEPTACLE - DUPLEX
DUPLEX RECEPTACLE MOUNTED
ABOVE COUNTER - FIELD VERIFY
HEIGHT
THERMOSTAT - ROUTE 1/2" CONDUIT TO
UNIT SERVED. VERIFY WITH MECHANICAL
DRAWINGS
POWER OUTLET, SEE PLANS FOR NEMA TYPE
RECEPTACLE DOUBLE DUPLEX
VOICE/DATA WALL OUTLET
VOICE/ WALL OUTLET
CLOCK +8'-0" AFF U.O.N. VERIFY BEFORE
T
PER EQUIPMENT MFGRS NAMEPLATE DATA.
FUSED DISCONNECT SWITCH ELEMENT FUSES SIZED
CONDUIT - UP.
CONDUIT - DOWN.
CONDUIT - TELEVISION
CONDUIT EMERGENCY SYSTEM.
FLEX CONDUIT WITH CONNECTION.
CONDUIT - TELEPHONE
SURFACE METAL OR NON-METALLIC RACEWAY
CONDUIT - CONCEALED IN WALLS OR CEILING.
CONDUIT - EXISTING
CONDUIT - BELOW SLAB OR
UNDERGROUND: 3/4"MIN.
CONDUIT - HOME RUN TO PANEL, TERMINAL CABINET,
ETC. RUNS MARKED WITH CROSSHATCHES INDICATE
NUMBER OF #12 AWG WIRES WHEN MORE THAN TWO.
SIZE CONDUIT ACCORDING TO SPECIFICATIONS AND
APPLICABLE CODE. CROSS HATCHES WITH NUMBER
ADJACENT INDICATES WIRE SIZE OTHER THAN
#12AWG.
GROUND ELECTRODE
NEMA 3R ENCLOSURE UNLESS OTHERWISE SPECIFIED.
MAGNETIC STARTER - NEMA SIZE INDICATED.
NON-FUSED DISCONNECT SWITCH
GROUND ROD WITH GROUNDWELL BOX
CIRCUIT BREAKER.
NORMALLY CLOSED CONTACT.
NORMALLY OPEN CONTACT.
TRANSFORMER - SEE SINGLE LINE FOR SIZE.
MOTOR CONNECTION
COMBINATION STARTER/FUSED DISCONNECT SWITCH;
CONDUIT CONTINUATION.
DETAIL OR SECTION REFERENCE
CAPPED CONDUIT. STUB-OUT
PULLBOX
SYMBOLS & ABBREVIATIONS SHOWN ARE FOR GENERAL USE. DISREGARD THOSE WHICH DO NOT APPEAR ON THE PLANS.
DETAIL NOTE REFERENCE SYMBOL
SEE ASSOCIATED NOTE ON SAME DETAIL
2
1
E3.0
INTERIOR SPEAKERS WALL MOUNTED.
M
LOW VOLTAGE WIRING
FEEDER DESIGNATION;
SEE ASSOCIATED NOTE ON SAME DETAIL
SHEET NOTE REFERENCE SYMBOL;
SEE ASSOCIATED NOTE ON SAME SHEET.
SCHEDULE SYMBOL; SEE ASSOCIATED
NOTE ON SAME SHEET.
SINGLE RECEPTACLE
CONVENIENCE RECEPTACLE - DUPLEX
CEILING MOUNTED
PULL BOXPB
PA
FUTURE
GROUND FAULT
PUBLIC ADDRESS
CHLORIDE
POLYVINYL
REQUIRED
REMOVED
SHEET
SWITCH
HEIGHT
PHASE
PANEL
PVC
PNL
REQD
SWBD
SHT
HT.
(R)
SW
PF
NOTED
WITH
WATT
VOLT
U.O.N.
XFMR
W/
W
WP
V
TYP TYPICAL
GROUND
INTERCOM
PANEL
LIGHTING
MOUNTED
METAL HALIDE
THOUSAND
KILOWATT
KILOVOLT
JUNCTION BOX
INTERRUPTING
LIGHTING CONTROL
KILOVOLT
LOW VOLTAGE
CIRCULAR MILS
MAIN LUGS ONLY
NUMBER
NEW
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
CONTRACT
NOT IN ELECTRICAL
MOUNTING
POWER FACTOR
SWITCHBOARD
UNLESS OTHERWISE
REQUIREMENT(S)
EXISTING TO BE
TRANSFORMER
WEATHERPROOF
GFCI
(F)
AFF
A
ABOVE FINISHED
AMPERE
KVA
LCP
LTG
MTD
KCM
JB
KW
LV
MH
KV
GND, G
MLO
NTS
OC
NIEC
NIC
(N)
NO.
MTG
AWG
ARCH.
BKR
CB
CO
CLG
CTR
CKT
DIM
DIST
CL
(E)
C
EQUIP
FIN
FACP
FA
FL
EMT
FLOOR
METALLIC TUBING
CONTROL PANEL
EQUIPMENT
FIRE ALARM
FINISH
FIRE ALARM
AMERICAN WIRE
CIRCUIT BREAKER
BREAKER
GAUGE
DISTRIBUTION
CIRCUIT
CENTER LINE
CEILING
CONDUIT ONLY
CENTER
DIMENSION
EXISTING
ELECTRICAL
CONDUIT
ARCHITECT
FLOOR
OVERHEADOH
REQMT'S
GALVANIZED RIGIDGRS
STEEL
EM EMERGENCY
(NL) NIGHT LIGHT
MECHANICALMECH.
RECPT'S RECEPTACLES
(RP) REMOVABLE POLE
PWR POWER
UG UNDERGROUND
ALUM./AL ALUMINUM
SINGLE LINE DIAGRAMS.L.D.
FLUOR. FLUORESCENT
OAH OVERALL HEIGHT
PASSIVE INFRAREDPIR
KILOVOLT AMPERES
GENERALGC
PH
PHOTOVOLTAICPV
CONTRACTOR
CATV CABLE TV
CCTV CLOSED CIRCUIT TV
POWER POLE
FUSED DISCONNECT SWITCH.
FUSED WITH DUAL-ELEMENT
FUSES SIZED PER EQUIPMENT
MFGR'S NAMEPLATE DATA.
EC ELECTRICAL
CONTRACTOR
IC
INCANDESCENTINCAND.
TTB TELEPHONE TERMINAL
BACKBOARD
MAIN DISTRIBUTIONMDF
MAIN POINT OFMPOE
INTERMEDIATE IDF
FLOOR MOUNTED BOX
DEDICATED RECEPTACLE WITH
DEDICATED NEUTRAL
D
NOMINALNOM
DETAIL NUMBER
SHEET NUMBER
GFI
DISTRIBUTION FRAME
FRAME
ENTRANCE
ABBREVIATIONS
ELECTRICAL SYMBOLS & ABBREVIATIONS
(EL) EVENING LIGHT
SYSTEMS TERMINATION
CABINET
STC
A
DATA WALL OUTLET NEAR CEILING -
12" BELOW FINISHED CEILING FOR WIFI
+48" A.F.F. MAXIMUM TO TOP OF BOX, U.O.N.
+15" A.F.F. MINIMUM TO BOTTOM OF BOX, U.O.N.
1. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ELECTRONICS INDUSTRIES ASSOCIATION (EIA)
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
UNDERWRITER LABORATORIES (UL)
CALIFORNIA OCCUPATIONAL SAFETY AND HEALTH ACT STANDARDS
(CAL/OSHA)
2.
3.
4.
5.
6.
APPLICABLE CODES & STANDARDS
STANDARDS:
CODES:
E1 SYMBOLS, ABBREVIATIONS, CODES, STANDARDS & SHEET
INDEX.
E2 ELECTRICAL SINGLE LINE DIAGRAM, PANELBOARD
SCHEDULE & DETAILS.
E3 SITE PLAN.
E4 GENERAL CONSTRUCTION & GENERAL DEMOLITION NOTES.
SHEET INDEX
7.
5.
6.
7.
9.
4.
2.
3.
1.2013 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1,
TITLE 24 C.C.R.
2013 CALIFORNIA BUILDING CODE (CBC), BASED ON THE 2012
INTERNATIONAL BUILDING CODE (IBC) VOLUMES 1-2 AND CALIFORNIA
LATEST ADOPTED AMENDMENTS.
2013 CALIFORNIA ELECTRICAL CODE (CEC), BASED ON THE 2011
NATIONAL ELECTRICAL CODE (NEC) AND CALIFORNIA LATEST
ADOPTED AMENDMENTS.
2013 CALIFORNIA FIRE CODE (CFC), BASED ON THE 2012 INTERNATIONAL
FIRE CODE (IFC) AND CALIFORNIA LATEST ADOPTED AMENDMENTS.
2013 CALIFORNIA MECHANICAL CODE (CMC), BASED ON THE 2012
UNIFORM MECHANICAL CODE (UMC) AND CALIFORNIA LATEST
ADOPTED AMENDMENTS.
2013 CALIFORNIA PLUMBING CODE (CPC), BASED ON THE 2012
UNIFORM PLUMBING CODE (UPC) AND CALIFORNIA LATEST
ADOPTED AMENDMENTS.
2013 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE
24 C.C.R.
10.
11.
NATIONAL FIRE ALARM CODE (NFPA 72) 2010.
TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE
MARSHAL REGULATIONS.
8.
2013 CALIFORNIA ENERGY CODE, CALIFORNIA
CODE OF REGULATIONS, TITLE 24, PART 6.
2013 CALIFORNIA GREEN BUILDING STANDARDS
CODE. CALIFORNIA CODE REGULATIONS TITLE 24,
PART II.
SY
MB
OLS
, A
BB
RE
V., C
OD
ES
,
ST
AN
DA
RD
S &
S
HE
ET
IN
DE
X
E1
10
30391.010
Voltage: 120/240V,3ø Bussing:
225A
Wire: 4W 1 2 PANEL WT Feed: TOP
Type:
NEMA 3R
Mounting:
SURFACE
Mains: 100/3A.I.C.
10,000
Load A B C Bkr Ck abc Ck Bkr A B C LoadRECEPTACLE 180 20/1 1 2
20/3
3300 RECIRCULATION PUMP
RECEPTACLE 180 20/1 3 4 3300 RECIRCULATION PUMP
STINGER LEG SPACE ONLY - 5 6 3300 RECIRCULATION PUMP
WATER TANK CONTROL PANEL 500 20/1 7 8 20/1 SPARE
SPARE20/1 9 10 20/1
SPARE
STINGER LEG SPACE ONLY -- 11 12 -
- STINGER LEG SPACE ONLY
4 EXISTING LOAD FROM (E) PANEL20/1 13 14 20/1 500 CHLORINE ANALYZER
4 EXISTING LOAD FROM (E) PANEL20/1 15 16 - SPACE ONLY
SPACE ONLY - 17 18 - SPACE ONLY
SPACE ONLY - 19 20 - SPACE ONLY
SPACE ONLY - 21 22 - SPACE ONLY
SPACE ONLY - 23 24 - SPACE ONLY
SPACE ONLY - 25 26 - SPACE ONLY
SPACE ONLY - 27 28 - SPACE ONLY
SPACE ONLY - 29 30 - SPACE ONLY
680 180 0 3800 3300 3300
1
SUBMITTAL SHALL MATCH EXACT BREAKER LOCATIONS SHOWN.
2 LABEL PANEL FOR SHORT CIRCUIT AMPS AVAILABLE PER CEC 110-22.
3 LABEL PANEL FOR "HIGH STINGER LEG" CLEARLY WITH LAMICOID NAME PLATE ON FACE OF PANEL. NO 120V
CONNECTIONS ALLOWED ON STINGER LEG. STINGER LEG IS 208V.
KVA Phase A 4.5
KVA Phase B 3.5 4 CONNECT (E) 20 AMP CIRCUIT TO BE MOVED FROM (E) PANEL TO THIS NEW PANEL.
Total Connected Load KVA 11.3
KVA Phase C 3.3
Total Load Amperes
27
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
09-11-2015
CADD
E.O.B.
N.A.
13
60 Garden Court Suite 210 Monterey, CA 93940
T.831.646.3330 F.831.646.3336 www.acemb.com
Project No.
ONTEREY
NGINEERS
ONSULTING
E
M
URUM A C
AY, INC.B
15139.00
ELE
CT
RIC
AL S
IN
GLE
LIN
E D
IA
GR
AM
,
PA
NE
LB
OA
RD
S
CH
ED
ULE
& D
ET
AILS
E2
NO SCALE
1
SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM LEGEND
(EXISTING)
(NEW)
AMPACITY CONDUIT & CONDUCTORS SIZES
FEEDER SCHEDULE
DESIGNATION
2" C., 4 #2/0 & 1 #6 GND.100F408
DETAIL NOTES:
NOTE:
U.O.N.; ALL SHOWN IS NEW.
PANEL
"WT"
100/3
1
(E) PANEL
2
3
1. PROVIDE & INSTALL NEW 100 AMP, 3-POLE DISTRIBUTION
BREAKER AT EXISTING PANEL. NEW BREAKER SHALL MATCH
EXISTING IN AIC RATING AND TYPE.
2. PROVIDE & INSTALL 6" x 6" x 4" DEEP NEMA 3R PULL CAN;
SPLICE & EXTEND EXISTING (2) 20 AMP CIRCUITS VIA
3
4
"C.
WHERE NECESSARY FOR SPACE REQUIRED TO INSTALL NEW
100 AMP, 3-POLE BREAKER IN EXISTING PANEL.
3. EXISTING (2) 20 AMP BRANCH CIRCUITS TO BE DISCONNECTED
FROM EXISTING PANEL & EXTEND TO NEW PANEL 'WT'.
F408
3
4
"C., 4 #10 & 1 #10 GND.
FOR (E) 20 AMP CIRCUITS
TO NEW PANEL
NO SCALE
TYPICAL PULLBOX DETAIL
2
1.
TYPICAL TRENCH SECTION
5.
4
NO SCALE
6.
4.
NOTES:
SAW CUT, TRENCH & BACKFILL FOR (N) CONDUITS. PATCH WALKWAY TO MATCH (E)
SURROUNDING SURFACES. CARE SHALL BE TAKEN TO PROTECT EXISTING TREES. RESEED OR
RESOD (E) DISTURBED PLANTED AREAS TO ARCHITECT'S SATISFACTION.
EXISTING A.C. SHALL BE CUT AND REMOVED IN SUCH A MANNER SO AS NOT TO TEAR BULGE OR
DISPLACE ADJACENT PAVEMENT. EDGES SHALL BE CLEAN AND VERTICAL. ALL CUTS SHALL BE
PARALLEL OR PERPENDICULAR TO STREET CENTERLINE, WHEN PRACTICAL.
BASE MATERIAL TO BE REPLACED TO THE DEPTH OF EXISTING BASE AND COMPACTED TO A MIN.
95% RELATIVE COMPACTION. A.C. MAY BE SUBSTITUTED FOR BASE MATERIAL. WHEN USED AS
BACKFILL, CLASS 100-E-100 P.C.C. MAY BE SUBSTITUTED FOR BASE MATERIAL.
A TACK COAT OF ASPHALTIC EMULSION OR PAVING ASPHALT SHALL BE APPLIED TO EXISTING A.C.
AT ALL CONTACT SURFACES, PRIOR TO RESURFACING.
ASPHALTIC CONCRETE RESURFACING:
A. MINIMUM TOTAL THICKNESS SHALL BE
ONE INCH GREATER THAN EXISTING A.C.
B. A.C. SHALL BE HOT PLANT MIX.
ALL A.C. RESURFACING SHALL BE SEAL COATED WITH AN EMULSIFIED ASPHALT AND COVERED
WITH CLEAN SAND.
FINISHED GRADE
GROUT FILL (TYPICAL)
CONDUIT
1. SIZE(S) & MFGR. AS NOTED ON DRAWINGS.
BELL ENDS
12
"
PULL BOX
PROVIDE EXTENSIONS
AS REQUIRED
1
1
2
" MIN. DIA.
DRAIN ROCK
LID LABELED AS NOTED
ON DRAWINGS
SAND BACKFILL
WARNING MARKER TAPE
CONTINUOUS LENGTH
OF TRENCH
30
"
12
"
1
DETAIL NOTES:
CONDUIT, SEE PLANS FOR
QUANTITY, SIZES & USAGE
MIN. 95% COMPACT
EARTH FILL, SEE SPECS
AC PAVING OR CONC.
WHEN OCCURS
FINISHED GRADE
6"
3.
2.
PANELBOARD SCHEDULE
11
100/3
30391.011
3
NO SCALE
UNDERGROUND CONDUIT RISER DETAIL
1. UNISTRUT BRACKET.
2. GALVANIZED RIGID STEEL CONDUIT.
3. SCHEDULE 40 PVC.
4. WRAPPED GALVANIZED RIGID STEEL ELBOW
AND UNDERGROUND RISER.
5. UNISTRUT CHANNEL.
DETAIL NOTES:
5
1
2
34
1. FOR WOOD STUD WALL:
USE
3
8
" LAG BOLT WITH MIN.
3
4
"
EMBEDMENT INTO STUDS.
(ONE AT EACH END OF BRACKET)
2. FOR CONCRETE WALL:
USE
3
8
" WEDGE ANCHOR WITH MIN.
2
1
2
" EMBEDMENT INTO CONCRETE
WALL. (ONE AT EACH END OF
BRACKET)
NOTES:
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
09-11-2015
CADD
E.O.B.
N.A.
13
60 Garden Court Suite 210 Monterey, CA 93940
T.831.646.3330 F.831.646.3336 www.acemb.com
Project No.
ONTEREY
NGINEERS
ONSULTING
E
M
URUM A C
AY, INC.B
15139.00
SIT
E P
LA
N
E3
SHEET NOTES
1. 2 HP, 240V, 3Ø.
2. 1"C., 3 #8 & 1 #10 GND.
3. LOCATE FOR 120V POWER TO TEMPORARY CONTROLS FOR TEMPORARY
WATER TANKS; VERIFY EXACT REQUIREMENTS WITH CIVIL ENGINEER. STUB
1"C.O. OUT TO EACH OF THE TEMPORARY WATER TANKS.
4. MOUNT NEW PANEL WITH UNISTRUT AND P-CHANELS; VERIFY EXACT
MOUNTING LOCATION WITH STATE PARK REPRESENTATIVE ON-SITE.
5. PER GENERAL DEMOLITION NOTES ON SHEET E4, CONTRACTOR SHALL
DISCONNECT EXISTING 4-PLEX RECEPTACLE AND ASSOCIATED CIRCUIT
WHERE EXISTING CONTROL PANEL IS TO BE REMOVED.
6. PROVIDE AND INSTALL NEW WEATHERPROOF 4-PLEX, GFI RECEPTACLE IN
NEW CONTROL CABINET. PROVIDE AND INSTALL (2) 20 AMP, 120V CIRCUITS TO
4-PLEX RECEPTACLE AND (1) 20 AMP, 120V CIRCUIT TO FLOW METER; VERIFY
EXACT LOCATION OF CONTROL CABINET AND METER DEVICES WITH CIVIL
PLANS.
7. PROVIDE AND INSTALL CHRISTY #N16 PULLBOX, LID LABELED "ELECTRICAL".
8. 1
1
4
"C., 6 #10 & 1 #10 GND.
9. 120V. PROVIDE AND INSTALL CORD AND PLUG.
SCALE: 1"=10'-0"
1
SITE PLAN
NORTH
10' 5'0' 10'
12
30391.012
PANEL "WT"
(E) PANEL
J
WP
3
1
E2
4
WT-8
1
E2
GFI
1,3
6
5
RECIRCULATION PUMP 1
WP
7
7
2
4
E2
WT-1,3,-78
WT-2,4,6 2
TYP.
3
E2
WT-2,4,6 2
WT-1,3,-78
8
TYP.
2
E2
WT-1,3-7
CHLORINE ANALYZER 9
WT-14
G:\P
ro
jects\15Jo
bs\15139.00 B
ig
B
asin
R
ed
wo
oks S.P
. W
ater Tan
k\D
wg
s01\15139E3.d
wg
, 9/21/2015 11:39:56 A
M, fern
an
do
BIG
B
AS
IN
R
ED
WO
OD
S S
TA
TE
P
AR
K
WA
TE
R T
AN
K R
EP
LA
CE
ME
NT
SHEET NO.
DRAWING NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
ACQUISITION &
DEVELOPMENT DIVISION
One Capitol Mall
95814-3229
Sacramento, CA
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT
THE DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
22"x
34"
SH
EET.
IF
SH
EET
SIZ
E IS
SM
ALL
ER, TH
EN D
RA
WIN
G H
AS B
EEN
RED
UC
ED.
09-11-2015
CADD
E.O.B.
N.A.
13
60 Garden Court Suite 210 Monterey, CA 93940
T.831.646.3330 F.831.646.3336 www.acemb.com
Project No.
ONTEREY
NGINEERS
ONSULTING
E
M
URUM A C
AY, INC.B
15139.00
GE
NE
RA
L C
ON
ST
RU
CT
IO
N &
G
EN
ER
AL
DE
MO
LIT
IO
N N
OT
ES
E4
GENERAL DEMOLITION NOTES
A. CONTRACTOR SHALL FIELD VERIFY EXTENT OF ELECTRICAL DEMOLITION
AND QUANTITIES OF ELECTRICAL TO BE REMOVED AS DICTATED BY THE
REQUIREMENTS OF THE PROJECT.
B. REMOVAL SHALL INCLUDE WIRING, RACEWAY, BOXES, SWITCHES, LIGHT
FIXTURES, ETC. AS INDICATED ON THE PLANS AND AS REQUIRED BY
THESE DEMOLITION NOTES.
C. RACEWAYS ASSOCIATED WITH ELECTRICAL BEING DEMOLISHED WHICH
ARE CONCEALED IN EXISTING REMAINING WALLS MAY BE ABANDONED IN
PLACE. REMOVE WIRING FROM CONDUIT.
D. RACEWAYS ASSOCIATED WITH ELECTRICAL BEING DEMOLISHED WHICH
ARE EXPOSED SHALL BE REMOVED.
E. WHERE REMOVAL OF EQUIPMENT OR WIRING IS INDICATED, IT SHALL
INCLUDE ALL ASSOCIATED WIRING BACK TO LAST ACTIVE REMAINING
OUTLET, DEVICE, FIXTURE OR PANEL.
F. ELECTRICAL CONTRACTOR SHALL INSURE THAT ALL REMAINING ACTIVE
CIRCUITS, DEVICES, OUTLETS, LIGHT FIXTURES, ETC. HAVE NOT BEEN
DISCONNECTED OR MADE INOPERATIVE DURING DEMOLITION.
ELECTRICAL CONTRACTOR SHALL RESTORE ALL INTERRUPTED OR
DISCONNECTED CIRCUITS TO OPERATION.
G. ELECTRICAL CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL
REMOVED ELECTRICAL EQUIPMENT AND MATERIAL.
H. NO REMOVED EQUIPMENT OR MATERIAL SHALL BE REUSED AS PART OF
NEW WORK, U.O.N.
I. EXISTING FLUSH OUTLETS MAY BE REUSED FOR NEW WORK PROVIDED
THEY MEET ALL REQUIREMENTS OF THE SPECIFICATION FOR NEW WORK,
MEET THE REQUIREMENTS OF THE CURRENT C.E.C. FOR VOLUME AND
COINCIDE WITH LOCATION SHOWN FOR THE NEW WORK.
J. EXISTING WIRING SHOWN HAS BEEN TAKEN FROM OLD PLANS AND IS
ASSUMED TO BE CORRECT. ELECTRICAL CONTRACTOR SHALL FIELD
VERIFY ACTUAL CONDITIONS AND MAKE ADJUSTMENTS TO SUIT ACTUAL
CONDITIONS AND TO MEET THE INTENT OF THE CONTRACT DOCUMENTS.
K. COORDINATE WITH OWNER PRIOR TO START OF DEMOLITION TO
MINIMIZE POWER INTERRUPTIONS, WORK MAY HAVE TO OCCUR DURING
NON-REGULAR BUSINESS HOURS. COORDINATE IN WRITING WITH OWNER
ONE WEEK PRIOR TO PLANNED POWER INTERRUPTIONS.
GENERAL CONSTRUCTION NOTES
1. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES AND
REGULATIONS. MATERIALS AND EQUIPMENT SHALL BE U.L. LISTED
AND LABELED FOR THE APPLICATION.
2. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,
LICENSES AND INSPECTION FEES REQUIRED BY THIS CONTRACT
WORK.
3. CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO BIDDING AND
ALLOW FOR ALL FIELD CONDITIONS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL ELECTRICAL WORK NOTED AND CALLED OUT
ON ALL CONTRACT DOCUMENTS. THE CONTRACTOR SHALL OBTAIN
INFORMATION AND BE FAMILIAR WITH ALL OTHER TRADES WORK. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION BETWEEN
OTHER TRADES ON PROJECT.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF PERSONS
AND PROPERTY AND SHALL PROVIDE INSURANCE COVERAGE AS
NECESSARY FOR LIABILITY AND PERSONAL, PROPERTY DAMAGE, TO
FULLY PROTECT THE OWNER AND ENGINEER FROM ANY AND ALL
CLAIMS RESULTING FROM THIS WORK.
5. CONTRACTOR SHALL MAINTAIN RECORD DRAWINGS AT THE PROJECT
SITE INDICATING ALL MODIFICATIONS TO ELECTRICAL SYSTEMS. THE
CONTRACTOR SHALL AT THE CONCLUSION OF THE PROJECT PROVIDE
ACCURATE "AS-BUILT" DRAWINGS ACCEPTABLE TO THE STATE REP.
6. ALL MATERIALS PROVIDED TO THE PROJECT SHALL BE NEW. THE
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE AND INSTALL ALL
INCIDENTAL MATERIALS REQUIRED FOR A COMPLETE INSTALLATION.
7. CONTRACTOR SHALL PROVIDE TO THE STATE REP. A CONSTRUCTION
SCHEDULE OF ELECTRICAL WORK. THE CONSTRUCTION SCHEDULE
SHALL IDENTIFY ALL SIGNIFICANT MILESTONES WITH COMPLETION
DATES.
8. CONTRACTOR SHALL PROVIDE ALL REQUIRED "CUTTING, PATCHING,
EXCAVATION, BACKFILL AND REPAIRS" NECESSARY TO RESTORE
DAMAGED SURFACES TO EQUAL OR BETTER THAN ORIGINAL
CONDITIONS EXISTING AT START OF WORK.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING ALL EXPOSED
CONDUITS AND ELECTRICAL EQUIPMENT WITH POWDER COATING TO
MATCH EXISTING INFRASTRUCTURE OR AS APPROVED BY STATE
REPRESENTATIVE.
10. ALL ELECTRICAL EQUIPMENT INSTALLED OUTDOORS SHALL BE
WEATHERPROOF. EXTERIOR CONDUITS RUN INTO BUILDINGS SHALL
BE INSTALLED WITH FLASHING, CAULKED AND SEALED. CONDUITS FOR
EXTERIOR ELECTRICAL DEVICES SHALL BE RUN INSIDE BUILDING
UNLESS OTHERWISE NOTED ON DRAWINGS.
11. ALL CONDUITS UNLESS OTHERWISE NOTED ON DRAWINGS SHALL
HAVE AS A MINIMUM: TWO (2) #12s WITH ONE (1) #12 GROUND. "TICK"
MARKS SHOWN ON CIRCUITRY ARE FOR ROUGH ESTIMATING ONLY.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WIRES AND WIRE
SIZES REQUIRED BY LATEST CODE.
12. ALL BRANCH CIRCUITS SHALL HAVE INDIVIDUAL NEUTRALS. SHARED
NEUTRALS ON MULTIWIRE CIRCUITS IS NOT ALLOWED.
13. COORDINATE ALL CONDUIT RUNS, ELECTRICAL EQUIPMENT AND
PANELS WITH ALL OTHER WORK TO AVOID CONFLICTS.
14. CONTRACTOR SHALL PROVIDE IN EVERY NEW EMPTY CONDUIT A
DRAW STRING FOR USE IN FUTURE CONSTRUCTION.
15. ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. CUT AND
PATCH EXISTING WALLS WHERE NECESSARY. WHERE IT IS
NECESSARY TO CUT OR BORE EXISTING STRUCTURAL WALLS FOR
NEW ELECTRICAL WORK OBTAIN PERMISSION FROM THE STATE REP.
PRIOR TO STARTING WORK. REUSE (E) CONDUIT WHERE POSSIBLE.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE TO (E)
UNDERGROUND SYSTEMS (GAS, WATER, TELEPHONE, ELECTRICAL,
SEWER, ETC.). THE CONTRACTOR SHALL REPAIR & PAY ALL EXPENSES
FOR DAMAGE TO (E) UNDERGROUND SYSTEMS AS A RESULT OF (N)
WORK. REPAIR TO DAMAGED UNDERGROUND SYSTEMS SHALL BE TO
THE OWNERS SATISFACTION WITHOUT EXTRA EXPENSE TO THE
OWNER.
17. EXISTING WIRING SHOWN HAS BEEN TAKEN FROM OLD PLANS AND IS
ASSUMED TO BE CORRECT. ELECTRICAL CONTRACTOR SHALL FIELD
VERIFY ACTUAL CONDITIONS AND MAKE ADJUSTMENTS TO SUIT
ACTUAL CONDITIONS AND TO MEET THE INTENT OF THE CONTRACT
DOCUMENTS.
13
30391.013
G:\P
ro
jects\15Jo
bs\15139.00 B
ig
B
asin
R
ed
wo
oks S.P
. W
ater Tan
k\D
wg
s01\15139E4.d
wg
, 9/21/2015 11:40:00 A
M, fern
an
do