900 series split case fire pump systems - motralec · 900 series split case fire pump systems ......

58
dwzwy :: 2010/2011 1 STAG 3073 Environmental Geology Dr. Wan Zuhairi Wan Yaacob Program Geologi ukm Konsep Asas Geologi Sekitaran

Upload: vanbao

Post on 15-May-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

900 SeriesSplit Case Fire Pump Systems

Pentair Water

BULLETIN 900/REV. E

F M®UL

Approved Listed

MODEL 481

MODEL 483

motralec 4 rue Lavoisier . ZA Lavoisier . 95223 HERBLAY CEDEX Tel. : 01.39.97.65.10 / Fax. : 01.39.97.68.48Demande de prix / e-mail : [email protected]

www.motralec.com

Page 2: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

page 2

Types of Pumps

HORIZONTAL split case pumps are the mostcommon type of Fire Pump. These pumps arespecially tested for fire-service applicationswhere reliability of performance is of vitalimportance. They are characterized by easyaccess to all working parts, ruggedconstruction, liberal water passages, andefficient operation. They are specified when thesource of water is located above the surface ofthe ground and will provide a positive suctionpressure to the pump at any performance point.There are several capacity ratings of Auroraapproved Fire Pumps available ranging from aminimum of 250 GPM. Single stage or multi-stage pumps are available dependent upondischarge pressure requirements.AURORA COMPLIES WITHPERFORMANCE REQUIREMENTS FORFIRE PUMP SERVICE WITH ITSSTANDARD PRODUCTION PUMPS.

Therefore, to the Fire Pump user this featuremeans:1. Lower initial cost.2. Quicker delivery from stock.3. Parts interchangeability with Aurora pumpsspecified elsewhere in your building reducesspare parts inventory and simplifiesmaintenance.The fact that Aurora pumps meet the rigidrequirements of Underwriters Laboratories andFactory Mutual Research is testimonial to thehigh quality of Aurora Pump products. AuroraPump offers the only true line of VERTICALSPLIT CASE Double Suction type pumpsapproved and listed for fire service. Vertical FirePumps provide distinct advantages overhorizontal pump constructions.1. Less floor space required.2. Inline piping arrangement allows piping inany direction in most cases.3. Elevated motor protects against potentialflooding if the pump station is in a low area.4. Components are register fitted to preventmisalignment.

VERTICAL MODELS 483

HORIZONTALMODEL

481

Page 3: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

page 3

Vertical Split Case Pump Features1 COMPUTER-MACHINED majorcomponents with 360 degree registered fits toassure concentricity of parts.2 INTEGRAL BEARING ARMS eliminatebearing misalignment and simplify maintenance.

3 VACUUM CAST ENCLOSED impellerdesign provides high efficiency and performanceon most sizes.4 DYNAMICALLY BALANCED IMPELLERis keyed to the shaft and secured by adjustableshaft sleeves.

5 DOUBLE SUCTIONIMPELLER balances hydraulicthrust loads.6 CAST IRON DRIP RIMBASE directs condensation andany stuffing box leakage to drain.7 SHORT BEARING SPANholds shaft deflection to .002” atface of stuffing box at maximumload.8 INTERNAL WATER SEALPASSAGES between volute andstuffing box cannot be damaged.9 INTERWOVEN,GRAPHITE IMPREGNATEDT.F.E. diagonally cut packingrings seal the pump shaft.10 STUFFING BOXES areextra deep for proper sealing.Split packing glands simplifypacking maintenance.11 DOUBLE ROW THRUSTBALL BEARING.12 GREASE SEALS and non-sparking Neoprene rotatingslingers protect both bearingsduring pump operation andwashdown.13 BEARINGS selected for50,000 hour minimum life atmaximum load. Average bearinglife 5 x minimum.14 SPLIT CASE DESIGNsimplifies disassembly. Thesuction and discharge piping andshaft alignment is not disturbed.15 O-RING SEALED SHAFTSLEEVES prevent corrosion ofthe shaft. This eliminates theneed for stainless steel shafts.16 CASE WEARING RINGSand throttle bushings protect thecasing from wear and are easilyand inexpensively replaced.17 BRONZE SHAFT SLEEVEprevents shaft wear, is slip fit overthe shaft, keylocked, and extendsthe entire length of the seal box.18 CERTIFIEDPERFORMANCE TEST withPOSITIVE SUCTIONPRESSURE is provided for eachFire Pump for customerapproval. Pumps are alsohydrostatically tested perN.F.P.A. 20 at no less than 250P.S.I.

MODEL 483Illustrated

Page 4: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

page 4

Horizontal Split Case Pump Features

MODEL 481 ILLUSTRATED

Page 5: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

page 5

Fire Pump Feature Selector

STANDARDBronze fitted pump constructionBronze shaft sleevesBronze case wearing ringsDynamically balanced impellersStainless steel impeller keyCarbon steel shaftCorrosion-resistant lantern rings*Bronze stuffing box bushingsBronze glandsInterwoven graphite-impregnated T.F.E.

packing ringsCast integral bearing armsRegreasible ball bearingsDouble row thrust bearing (outboard side)Upper casing lifting lugsWater slingers and grease sealsHydrostatic and Certified Performance test**Coupling guard on 481 & 485 modelsSuction and discharge gauges with shut-off

cocksAutomatic air release valveCasing relief valve (electric driven units only)

OPTIONALDuctile iron casings (available in selected 481

& 485 sizes)Right or left hand rotationImpeller wearing ringsDouble row ball bearings on inboard sideExternal by-pass line from casing to stuffing

boxesFormed steel drip-lip base (horizontal electric

driven units only)15’ Suction lift test to verify performance at

150% of rated flowN.P.S.H. test

* Furnished when suction pressure is below40 PSI

** Test is performed with POSITIVE SUCTION PRESSURE

Fire Pump Accessories

Various accessories are required for any firepump installation. Specific needs vary depend-ing upon the requirements of local insuranceauthorities as well as the individual installation.The current edition of the National FireProtection Association (NFPA) pamphlet No.20 specifies many of the accessories required.

Aurora Pump can provide approved FirePumps and a complete line of approved FirePump accessories.Available accessories include: hose valves, hosevalve header, main relief valve, waste cone, con-centric tapered discharge increaser, eccentrictapered suction reducer and splash shields.

Page 6: 900 Series Split Case Fire Pump Systems - Motralec · 900 Series Split Case Fire Pump Systems ... valve header, main relief valve, waste cone, ... Aurora Pump reserves the right to

Jockey Pump Introduction

Occasionally in a Fire Pumpsystem, water leakage will occur atflanged or threaded pipeconnections, valve stems, stuffingboxes, etc. This normal loss ofwater will lower the systempressure gradually until the mainFire Pump is required to start. Tominimize wear on the Fire Pumpresulting from unnecessaryoperation, a Jockey Pump isrecommended for the system. In aJockey Pump system a small pump,motor, and controller/pressureswitch unit is installed in thepiping system. The Jockey Pumppressure switch is set forapproximately five P.S.I.G. greaterthan the pressure switch for themain Fire Pump Controller. When

the water pressure drops below thepre-set level, the pressure switchenergizes a starter which activatesthe Jockey Pump. Correct waterpressure is therefore maintained atall times. An optional minimumrun timer will prevent the JockeyPump from being started toofrequently. This timer will insureoperation for a minimum of 3minutes. If a fire should start, thepressure will continue to drop andthe main Fire Pump will start.Automatic controllers also includea “Hand-Off Automatic” selectorswitch for manual operation.Fusible 3-pole disconnect switch,magnetic motor contactor andthermal overload relays withexternal reset are standard.

NOTE: Aurora Pump reserves the right to make revisions to its products and their specifications, and to this bulletin and related information without notice.

AP-

900/

Rev.

E 6

.98

Pentair Water

ISO90

01REG

ISTERED QUALITY SYSTEM

motralec 4 rue Lavoisier . ZA Lavoisier . 95223 HERBLAY CEDEX Tel. : 01.39.97.65.10 / Fax. : 01.39.97.68.48Demande de prix / e-mail : [email protected]