9. transmission & distribution sys.pdf

Upload: -milan-subedi

Post on 02-Jun-2018

244 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    1/20

    11 March 2011

    1

    Power Transmission / Distribution- Electric power can be transmitted from one place to other with the help of conductorcable, but in doing so some of the electrical power is lost when it is transmitted to

    long distance- Transmission and distribution is designed for minimum loss (less than 10%)

    - At the same time it is also important to keep the costs low.

    All the conductors have some resistance to the flow of electric current. This itself

    show the voltage drop across the length of the conductor.

    Vdrop= Ix R

    "V" drop is depends on:

    1. Type of cable material

    2. Cross-sectional area of the cable

    3. Length of the cable

    Most commonly used conducting materials are:

    - Copper

    - Aluminum

    ACSR (Aluminum Conductor Steel Reinforce)

    ACSR Cable (Typical specification)

    ConductorCurrent rating

    (amp)

    Resistance

    ()/km)

    Weight

    (kg/km)

    Squirrel 76 1.374 85

    Gopher 85 1.089 106

    Weasel 95 0.9047 127.7

    Rabbit 135 0.5404 213.6

    Dog 205 0.2722 394

    Aluminum Cable

    Conductor

    Current

    rating

    (amp)

    Resistance

    (/km)

    4mm2 23 7.15

    6mm2 30 4.76

    10mm2 40 2.86

    16mm2 51 1.78

    25mm2 70 1.14

    )2

    (

    )/(*4.18

    mm

    km

    A

    KR

    K=1 for copper

    k= 1.6 for aluminum

    k=10 for steel 1

    Ex.: A village is 1.5 km away from the powerhouse. Rabbit cable is used to

    transmit 5kW power to the village in single phase. Assuming purelyresistive load, pf. =1.Find the followings:

    1. Voltage drop in the cable.2. Voltage in village, if voltage at Powerhouse is 230 volt

    3. What is the % of voltage drop ?

    The current necessary to transmit 5kW of power, I = P/V = 5000/230 = 21.74 Amp

    From the table, Rabbit conductor has a resistance of 0.5404 / km

    Resistance of the whole cable = 2 * 1.5 (km) * 0.5404 (/km) = 1.62

    i. Voltage drop, Vdrop= I * R = 21.74 (Amp) * 1.62 () = 35.22 Volts

    ii. Voltage in the village = Voltage in PH - Vdrop= 230 - 35.22 = 194.78 Volts

    iii. % of voltage drop = (35.22/230)*100 = 15.3 %

    Since, Vdropis too high more than 10%, means chosen Rabbit cable is too thin. Take

    bigger size cable say Dog and repeat the above calculation:

    From the table, Dog conductor has a resistance of 0.2722 / km

    Resistance of the whole cable = 2 * 1.5 (km) * 0.2722 (/km) = 0.82

    i. Voltage drop, Vdrop = I * R = 21.74 (Amp) * 0.82 () = 17.83 Voltsii. Voltage in the village = Voltage in PH - Vdrop = 23017.83 = 212.17 Voltsiii. % of voltage drop = (17.83/230)*100 = 7.75 % 2

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    2/20

    11 March 2011

    2

    Three-Phase

    V

    V

    V

    V

    R Y B

    Single-Phase

    Three identical winding are putting out 3 voltage waveform at 1200apart.

    Single winding single voltage waveform

    V = Phasevoltage

    I = Phase Current

    Power = V.I. Cos

    VP= Phase voltage

    VL= Line voltage

    VL= 3 . VP

    IP= Phase Current

    IL= Line Current

    IL= 3 . IP

    Power = 3. VP. IP.pf = 3.VL.IL.pf

    Power = P(R)+ P(Y)+ P(B)

    If three phase are balanced

    If three phase are unbalanced 3

    3 Phase Load (Motor)

    ~

    ~ ~

    R (Red)

    N (Neutral)

    Y (Yellow)

    B (Blue)

    VR-N

    VY-NVB-N

    3 Phase Generator

    Single Phase Loads

    Ex. On a 3 phase panel board, following reading are taken:

    VR= 218 V IR= 15 A

    VY= 215 V IY= 16 A

    VB= 220 V IB= 15 A

    Find the total power output of a generator assuming loads of

    unity power factor (p.f.=1)

    Power of the individual phase

    PR= VR.IR. Cos= 218*15*1= 3270 W

    PY = VY.IY. Cos= 215*16*1= 3440 WPB= VB.IB. Cos= 220*15*1= 3300 W

    Total power = PR+PY+PB = 3270+3440+3300=10010 W

    Three phase supply system/ Load system :

    4

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    3/20

    11 March 2011

    3

    Z

    IP

    IP

    IP

    IB

    IY

    IRR

    Y

    B

    Delta Connected balanced load

    VP =VL

    Line voltage = VL

    Phase voltage, VP=

    Phase Current, IP= Line Current, IL

    Power drawn, P = 3.VL.IL.Cos

    VL

    3

    Line Voltage = VL

    Phase Voltage, VP= Line Voltage, VL

    Phase Current, IP=

    Power drawn, P = 3.VL.IL.Cos

    IL

    3

    Three phase star (Y) connected and Delta () connected Loads.

    For balanced Loads: IN= 0

    VR-N = VY-N= VB-N= VPVR-Y= VY-B= V B-R= VL

    IL= IP

    Star Connected balanced load

    Z

    IR

    IB

    IY

    IPIP

    IP

    R

    N

    Y

    B

    VPIN

    For balanced Loads:

    IR = IY= IB= ILIR-Y= IY-B= IB-R= IPVL= VP

    5

    VL

    1 2 3 4 5 6 7 8 9 10 11 12 13 144

    6

    8

    10

    12

    14

    16

    kW-km

    % Vdrop

    Single Phase(220 Volts)

    (Unity power factor)

    ACSR Cable Selection Chart

    6

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    4/20

    11 March 2011

    4

    4 8 12 16 20 24 28 32 36 40 44 48 52 564

    6

    8

    10

    12

    14

    16

    kW-km

    % Vdrop

    Three Phase

    (380/220 Volts)(Unity power factor)

    ACSR Cable Selection Chart

    7

    30 50 70 90 110 130 150 1704

    6

    8

    10

    12

    14

    16

    kW-km

    % Vdrop

    Three Phase(1 KV)

    (Unity power factor)

    ACSR Cable Selection Chart

    8

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    5/20

    11 March 2011

    5

    Ex.: 5 kW of power (at pf=1) has to be transmitted from the power house to a village

    1.8 km away from the PH. The maximum allowable Voltage drop is 10%.

    1. Using single phase transmission, what size cable will be required to transmit

    this power ? How much conductor will be needed ?2. What size cable will be required to transmit this power in three phase (4-wire

    system configuration) ? How much conductor will be needed ?

    km-kW9km1.8*kW5productdistanceandPower dropV10%givewillconductorDogphase)single(forgraphtheFrom A

    kg1418.4(kg/km)394*(km)3.6cable(Dog)theofWeight

    tabletheFrom

    km-kW9km1.8*kW5productdistanceandPower

    dropV9.5%givewillconductorSquirrelphase)(threegraphtheFrom A

    km3.62*.81conductoroflengthTotal

    km7.24*.81conductoroflengthTotal

    kg126(kg/km)85*(km)7.2cable(Squirrel)theofWeight

    tabletheFrom

    1. Single Phase

    2. Three Phase

    9

    Example:If 30 kW, 3-phase of power is to be transmitted 2 km away from PH. What

    size conductor would be required to keep the voltage drop within 10% if the

    transmission is done at 1000 V line voltage ?

    %5.6100*3.577

    7.37V%

    V37.72.178*17.3R*IVphase,perdropVoltage

    2.178/km)(1.089*(km)2R,Resistance

    used,isconductorGopherIf

    Amp.3.173.577*3

    1000*30

    Iphase,perCurrent

    3.5773

    1000Vvoltage,line1000VatphaseperVoltage

    drop

    drop

    ph

    ph

    V

    Check for the Result using the graph for 3 phase; 1 kV

    Transmission system.10

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    6/20

    11 March 2011

    6

    Resistance and Reactance of a Conductor

    11

    dropVdrop,Voltageof(%)allowableDecide:1Step

    condition)for worse5.0pf(TakepfforEstimate:2 Step

    3321

    **:3 sssSspacing,ConductorEffectiveFindStep

    7/4.9)(saytablethefromsize,conductortheuess:4 GStep

    )L*/km(ResistancetheFind:5 kmtable)(FromStep

    )f.L.2.(XXReactance,InductiveFind:6 (H)LL Step

    phase)per(H10*log*465(* 8)10(lengthtrans.effective)(

    r

    sLLH

    )(ZImpedence,Find:7 2)2 LXRZStep

    )*(dropVoltageFind:8 drop ZIVStep

    dropvoltageof%allowableforheck:9

    pro cess)repeat theandcablesizebiggerthechosemore,isdropV%(I f

    CStep

    For conductor spacing 0.3m

    s1=0.3m

    s2=0.3m

    s3=0.6m

    7 strand cable

    Calculation of Voltage drop using Equations Conductor Size & ResistanceNominal

    Area

    (mm2)

    Size

    notation

    Resistance

    (/km)

    22 7/2.06 1.227

    30 7/2.44 0.875

    35 7/2.59 0.777

    40 7/2.79 0.669

    60 7/3.40 0.450

    70 7/3.66 0.389

    75 7/3.79 0.365

    90 7/4.18 0.300

    100 7/4.29 0.270

    125 7/4.90 0.217

    12

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    7/20

    11 March 2011

    7

    A factory requiring 50KW, 3-phase, 380V, 50Hz, power to be supplied by a MHPplant. The PH is 550 m away from the factory. The worse pf is estimated to be of

    pf=0.6. The maximum voltage that can a generator produce is 420 V.

    Find the size of the conductor mm2, If aluminum conductor is to be used andcorresponding Power loss in the conductor.

    9.5%~V40380420 dropVAllowable

    6.0pf

    m0.3spacingConductorAssuming

    cable)](7/4.9tablethe[from125mmConductorofsizethessuming 2A

    119.055.0*217.0*/ LengthkmR

    4810

    810

    10*6.410*00735.0

    378.0log*465(*550

    10*log*465(*

    r

    sLengthLH

    378.06.0*3.0*3.0** 33 321 ssss

    mstrandr 00735.035.73*2

    4.93*radius

    s3s1

    s2

    13

    /phase144.010*6.4*50**2***2 4 LfXL

    phaseper0.1860.1190.144 2222 RXZ L

    V35.2178.114*186.0*phase)( IZperVdrop

    V98.363*35.213*)()( phaseVlineV dropdrop

    wattRIPloss 1568119.0*78.114*phaseper22

    VVVV drop 38398.36420supplysiteat

    Amp78.114

    6.0*)3/420(*3

    50000

    **3

    ,

    pfV

    PICurrent

    wattsPTotal loss 47041568*3 14

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    8/20

    11 March 2011

    8

    Resistance and Reactance of a Conductor

    15

    Transmission & Distribution SystemLine ConfigurationSingle Phase 2-wire systemPower consume by single phase load

    cos**IVP

    Voltage drop

    IxrLVdrop

    *)sin*cos*(**2

    Voltage drop on each phase

    IxrLVdrop

    *)sin*cos*(*

    Power consume by each phase load

    cos**3

    IVP

    P phph

    Three Phase 4-wire system

    Voltage drop on each phase

    IxrLVdrop

    *)sin*cos*(**3

    Power consume by each phase load

    cos**3

    phph IVP

    P

    Three Phase 3-wire system

    16

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    9/20

    11 March 2011

    9

    17

    Example:A 21 mm2 ACSR line with a spacing of 0.30 m is used to bring power 500 m fromthe power house to a load of 3 kW with a power factor of 0.95, resistance (r) = 1.41

    ohm/km and reactance (x) = 0.32 ohm/km. What is the percent voltage drop withfollowing transmission line systems;

    a. Single phase 2-wire systemb. Three phase 4 wire system (per phase)

    p.f. = 0.95 = Cos 180 Sin 180=0.31

    VIxrLVdrop

    75.1973.13*)31.0*32.095.0*41.1(*5.0*2*)sin*cos*(**2

    AmppfV

    PI 73.13

    95.0*230

    1000*3

    *

    %58.8100*230

    75.19100*%

    V

    VV

    drop

    drop

    a. Single ph ase 2-wire system

    b. Three phase 4- wire system (per phase)

    VIxrLVdrop

    29.358.4*)31.0*32.095.0*41.1(*5.0*)sin*cos*(*

    AmppfV

    PI 58.4

    95.0*230*3

    1000*3

    *

    %43.1100*230

    29.3100*%

    V

    VV drop

    drop

    A 10 kW power at a pf=0.8 is being transmitted over a transmission line whoseresistance is given as (Z=0.3 +J*0.1). Find the voltage drop. What would be the

    voltage drop if pf is unity

    AV

    PowerTrueTCCurrentTrue 45.45

    220

    10000)(

    Apf

    TCACCurrentApparent 81.56

    8.0

    45.45)(

    AACRCCurrentactive 346.0*81.56sin*)(Re )34*45.45( jI

    17.96V

    )1.03.0(*)3445.45(

    )1.0*3.0mod(*)34*45.45mod(

    ).mod(*)mod(

    2222

    jj

    ZIVdrop

    14.36V

    )1.03.0(*)45.45(

    )1.0*3.0mod(*)45.45mod(

    ).mod(*)mod(

    222

    j

    ZIVdrop

    Vdropwhen pf=0.8

    Vdropwhen pf=1

    18

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    10/20

    11 March 2011

    10

    Volts = 230 VConductor spacing = 0.3 m

    Frequency = 50 Hz

    Decide the % VdropFind the kW-m, as per system and load configuration shown in above tableWith known value of kW-m draw vertical line to meet the line of % dropDraw horizontal line to fine area of conductor (left for aluminum and right copper)

    19

    Volts = 230 VConductor spacing = 0.3 m

    Frequency = 50 Hz

    Decide the % VdropFind the kW-m, as per system and load configuration shown in above tableWith known value of kW-m draw vertical line to meet the line of % drop

    Draw horizontal line to fine area of conductor (left for aluminum and right copper)

    20

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    11/20

    11 March 2011

    11

    Volts = 230 V

    Conductor spacing = 0.3 mFrequency = 50 Hz

    Decide the % VdropFind the kW-m, as per system and load configuration shown in above tableWith known value of kW-m draw vertical line to meet the line of % dropDraw horizontal line to fine area of conductor (left for aluminum and right copper)

    21

    Typical Load distribution system for MHP

    Uniformly distributed Load

    End Concentration Load

    Unevenly distributed Load

    22

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    12/20

    11 March 2011

    12

    Single Phase 2 wire configuration

    3)()( 10*cos*

    1000*V

    PV

    PI kWkVA 3)()( 10*cos*

    *)sin*cos*(**2

    VPxrLV kWLdrop

    Generalized Equation

    5

    2

    )(10*

    cos*

    **)sin*cos*(*2

    V

    PLxrY

    kW

    L

    3

    2

    )(10*

    cos****2

    V

    PLrZ kW

    Line

    `Configuration

    Balance Load of P

    concentrated at the

    end of the line

    Balance Load of P

    uniformly distributed

    along the line

    Voltage drop factor

    for a 50% unbalanced

    load that totals P

    % Vdrop PLoss(kW) % Vdrop PLoss(kW)Single-Phase

    (2-wire)Y Z Y/2 Z/3 1

    Three-Phase

    (3-wire, delta)Y/2 Z/2 Y/4 Z/6 1.1

    Three-Phase

    (4-wire, wye)Y/6 Z/6 Y/12 Z/18 1.5

    Comparison table, % voltage drop and power loss for different load configuration

    Comparison of different line configuration and load condition

    23

    System

    configuration

    Load condition/

    configuration

    Modification of (kW-m) value (k' )

    For Single

    Phase

    If the load concentratedat the end

    If the load is evenlydistribute

    If the load is unevenly

    distribute

    For ThreePhase, delta

    system

    For perfectly balance

    load system

    First obtain the k'

    (kW-m) value as

    assuming single

    phase for

    corresponding type

    of load d is t r ibu t ion

    system as above

    and modify it for

    three phase

    corresponding to

    load balance

    For 50% balance load

    system

    For ThreePhase, wye

    system

    For perfectly balanceload system

    For 50% balance load

    system

    (km)(kW) L*Pk'km)-(kW k

    2

    L*Pk'km)-(kW

    (km)

    (kW)k

    (km)x(kW)x L*Pk'km)-(kWk

    2

    'km)-(kW

    kk

    8.1

    'km)-(kW

    kk

    6

    'km)-(kW

    kk

    4

    '

    km)-(kW

    k

    k

    To find the equivalent kW-km value using single phase configuration

    24

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    13/20

    11 March 2011

    13

    20 kW, 3-phase, 50 Hz power with pf=0.6 is to be transmitted at a distance of

    360m. Find size of conductor so that voltage drop should be less than 6%.

    m)-(kW2.736.0*20L*Pk'km)-(kW (km)(kW) kFind (kW-m) assuming single phasesystem (concentrated load at end)

    km)-(kW2.16

    2.7

    6

    k'km)-(kW kmodification of k' (kW-m) value For 3-phase, 4-

    wire, wye configuration perfectly balance loadsystem

    - Aluminum conductor of ~ 40mm2to be used to keep Vdropless than 6%

    - Copper conductor of ~25mm2to be used to keep Vdropless than 6%25

    Generator TypesThere are two types of AC Generator (Alternator)

    1. Synchronous Generator

    - Single Phase / Three Phase- Brush / Brushless type

    2. Induction (Asynchronous) Generator

    - Single Phase / Three Phase

    Induction Generator are

    simpler and more reliable

    machine

    It can withstand 200%

    overspeed

    less maintenance required.

    (No brushes that need

    maintenance) It is cheap and easily

    available.

    Both, Synchronous and Asynchronous

    generators are available in single and

    three phase. Induction generator and

    single phase generator are generally

    used for small scheme. For larger

    scheme 3 phase synchronous generators

    are used.

    26

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    14/20

    11 March 2011

    14

    Generator Parts

    Prime mover: mechanical work which turns the rotor, may be a water turbine, gasturbine, diesel engine...

    Armature windings: the conductor in which the output voltage is induced Field windings: the conductors used to produce the electromagnetic field (needs a

    DC power supply)

    Stator: stationary housing of the generator

    Rotor: rotates inside the stator, moved by a prime mover (water turbine, dieselengine etc)

    Sliding contacts (slip-rings and brushes): used to conduct the field or armaturecurrent to and from the rotor

    Generator

    Rotating rectifierExciter rotor

    Exciter stator

    Fieldwinding

    Phase

    windings

    Rotates

    Stationary

    Idc

    27

    V

    Load (A)

    220 V

    Load curve at fixed RPM

    V

    RPM

    220 V

    1500

    No load curve

    V

    Load (A)

    220 V

    Max (A)

    Load curve at fixed RPM

    (with compounding)

    RPM =120 * f

    P(1+s)

    Where;

    s= slip (010%)

    p = No. of poles (2,4...)

    RPM =120 * f

    PWhere;

    P = No. of poles

    When;

    P = 4, f = 50 ;

    RPM = 1500

    When;

    P = 4, f = 50 ; s = 0-5%

    RPM = 1500 - 1575

    Operating Characteristic of Synchronous Generator

    Operating Characteristic of Induction Generator

    V

    RPM

    220 V

    1500

    No load curve

    I.G.

    S.G.

    28

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    15/20

    11 March 2011

    15

    Synchronous Generator Induction Generator

    DC Exciter required for fieldexcitation

    Magnetizing and excitation power is provided from thepower system towhich it is connected

    Synchronization is required for

    parallel operation with grid

    Synchronization is not required as the machine is

    brought above synchronous speed and the breaker is

    closed

    Complicated construction Simple and rugged construction

    Cost is higher Cost is less than synchronous generator

    Operation cost is higher Operating cost is less than synchronous generator

    Suitable for base load and peak

    load duties

    Suitable for base load operation

    Higher efficiency Slightly lower efficiency than synchronous generator

    Comparison between Synchronous and Induction Generator

    Generally, Induction Generator are cheaper for small scheme. But, they are not

    good for supplying power to motors.

    29

    Selection of Generator typeSize of scheme Up to 10 kW 10 to 25 kW More than 25 kW

    Type of Generator Induction

    or

    Synchronous

    Synchronous

    or

    Induction

    Synchronous

    Phase Single

    or

    Three

    Three Three

    Factors to be considered for selecting the size of the Generator.

    A

    Max. ambient Temp.(0C) 20 30 40 50

    Temp. factor 1.10 1.06 1.00 0.92

    B

    Altitude 1000 2000 3000 4000

    Altitude factor 1.00 0.93 0.86 0.8

    C ELC Correction factor 0.83

    D Power factor

    When load resistive (light bulbs) only 1.00

    When loads are light bulbs + Tube-lights

    etc. (Resistive + Inductive)

    0.80

    Generator KVA =Power output in kW

    A x B x C x D 30

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    16/20

    11 March 2011

    16

    Controlling & protection Panel board (Volt meter, Current meter, Circuit

    breaker, Emergency cut-out) Under & over voltage protection

    Under & over current protection

    MCBs / MCCBs must be rated at less than 110% of

    generator rating.

    Generator neutral and all metal casing should be

    earthed

    One Lightning arrestor must be mounted on eachphase on the first pole outside the PH

    One arrestor on each phase per km of transmission,

    and additional as required so that no consumer is

    more than .5 km away from the arrestor31

    Voltage Control kVAR Control pf Control

    Excitation Control

    Generator Control

    By pass

    Jet deflector

    Speed Control

    Main Discharge

    Niddle

    Guide

    Wicket

    Level Control kW Control

    Flow Control

    ELC IGC

    Load Control

    Turbine Control

    Hydro Plant Control

    32

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    17/20

    11 March 2011

    17

    Load

    Controller

    Generator Consumers

    Load

    Electronic Switch

    Ballast

    Load

    Fuses

    A simple Schematic diagram of Load Controller

    The purpose of the ELC is to maintain constant speed by accurately adjusting the secondary

    load (ballast load).

    The ELC sense the generator frequencyWhen the consumers Load decreases, Generator tends to run fast resulting increase in

    frequency.

    When the frequency increases, the electronic switch move to on position that transfer extra

    load to the ballast load. The reverse happens when consumer load increases.

    The ballast load must be rated 20% higher than the maximum generator output

    ELC is suitable to use with Synchronous Generators

    Since it sense only frequency, an AVR is needed with ELC to keep voltage constant.

    Electronic Load Controller (ELC)

    33

    ELC

    Main Load

    Ballast Load

    Main Load draws

    full power

    No power to

    ballast load

    Alternator

    Supply

    20kW

    240V

    ELC

    Main Load

    Ballast Load

    12 kW used by

    Main Load

    8 kW chopped to

    ballast load

    Alternator

    Supply

    20kW

    240V

    ELC

    Main Load

    Ballast Load

    No current drawn

    to Main Load

    20 kW to ballast

    load

    Alternator

    Supply

    20kW240V

    Load

    Controller

    Generator Consumers

    Load

    Electronic Switch

    Ballast

    Load

    Fuses

    Working of ELC

    34

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    18/20

    11 March 2011

    18

    Induction Generator Controller (IGC)

    The IGC sense the generator voltage

    When the voltage is too high, it divert the extra load to the ballast load.

    When the voltage is too low, it divert the additional load to the consumers load.

    The ballast load of the IGC is same as the maximum output of the plant.

    The main function of a Load controller is to maintain constant voltage by keeping

    constant load to the generator.

    Automatic Voltage Regulator (AVR)

    In a simple Synchronous generator, voltage falls as load current increase and vice versa.

    AVR is an electronic unit which regulates the voltage within the limit.

    AVR regulate the generator voltage by varying the field current.

    35

    Typical Generator Specification for MHP application

    Turbine type: (Ex.: Pelton wheel)

    Turbine power : ............ kW

    Generator power rating : ............ KVA

    Duty : Maximum continuous rated

    Operating Speed : .......... RPM

    Over speed : 180% continuously

    Voltage: 415 V

    Phase : 3

    Frequency : 50 Hz

    Power factor : 0.8

    AVR : Voltage regulation 2.5% with under and over voltage andfrequency protection.

    Ambient temperature: ......... 0CAltitude : .. ....... msl

    Induction Motor as Generator (IMG)

    Induction Motor are most commonly used machine. They are simple cheap and plentiful.

    It can be used as generator by putting suitable size capacitor across phase winding.

    Induction motor are generally used as generator for smaller size machine.

    36

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    19/20

    11 March 2011

    19

    TransformerA transformer is a static electrical

    device, which transforms electricalenergy from one voltage level to

    another voltage level.

    This permits electrical energy to begenerated at relatively low voltages

    and transmitted at high voltages

    and low currents, thus reducing

    voltage drop and line losses.

    Need of Transformer After the power distance product gets to about

    54 kW-km, even the largest size conductor

    (say Dog) cable used becomes insufficient in

    even three phase to give the required 10% of

    the voltage drop or better.

    4 8 12 16 20 24 28 32 36 40 44 48 52 5646

    8

    10

    12

    14

    16

    kW-km

    % Vdrop

  • 8/11/2019 9. Transmission & Distribution sys.pdf

    20/20

    11 March 2011

    Classification of Transformer

    Class -A: Dry type : Core and winding are not contained ininsulating liquid. Heat losses ard dissipated to the ambient air,

    hence require large surface area and low current density.

    Class -O: Oil immersed type: Core and winding are contained in

    mineral oil which is simultaneously work as coolant and insulating.

    Transformer Specification

    (i) Type Phase

    (ii) Installation outdoor

    (iii) Rated capacity kVA

    (iv) Rated H.V. (Secondary)kV

    (v) Rated L.V. (Primary) kV

    (vi) Cooling O/A

    (vii) Rated frequency 50 Hz

    (viii) Primary connection Delta

    (ix) Secondary connection Star

    (xi) Efficiency not less than 98%

    40