9 advanced lf topics

Upload: sayedmh

Post on 03-Apr-2018

242 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 9 Advanced LF Topics

    1/23

    Section 9Advanced LF Topics

    Load Flow Convergence

    Voltage Control

    Mvar Control

  • 7/29/2019 9 Advanced LF Topics

    2/23

    Load Flow Convergence

    Negative Impedance Zero or Very Small Impedance

    Widely Different Branch Impedance Values

    Long Radial System Configurations

    Bad Bus Voltage Initial Values

  • 7/29/2019 9 Advanced LF Topics

    3/23

    Voltage Control

    Under/Over Voltage Conditions must befixed for proper equipment operation andinsulation ratings be met.

    Methods of Improving Voltage Conditions:

    Transformer Replacement

    Capacitor Addition

    Transformer Tap Adjustment

  • 7/29/2019 9 Advanced LF Topics

    4/23

    Under-Voltage Example

    Create Under VoltageCondition

    Change Syn2 Quantity to 6.(Info Page, Quantity Field)

    Run LF

    Bus8 Turns Magenta (UnderVoltage Condition)

    Method 1 - Change Xfmr

    Change T4 from 3 MVA to 8MVA, will notice slight

    improvement on the Bus8 kV

    Too Expensive and timeconsuming

    Method 2 - ShuntCapacitor Add Shunt Capacitor to Bus8

    300 kvar 3 Banks

    Voltage is improved

    Method 3 - Change Tap

    Place LTC on Primary of T6

    Select Bus8 for Control Bus

    Select Update LTC in theStudy Case

    Run LF

    Bus Voltage Comes withinspecified limits

  • 7/29/2019 9 Advanced LF Topics

    5/23

    Mvar Control

    Vars from Utility

    Add Switch to CAP1

    Open Switch

    Run LF

    Method 1 Generator

    Change Generator fromVoltage Control to MvarControl

    Set Mvar Design Setting to 5Mvars

    Method 2 Add Capacitor

    Close Switch

    Run Load Flow

    Var Contribution from the

    Utility reduces

    Method 3 Xfmr MVA

    Change T1 Mva to 40 MVA

    Will notice decrease in thecontribution from the Utility

  • 7/29/2019 9 Advanced LF Topics

    6/23

    Panel Systems

  • 7/29/2019 9 Advanced LF Topics

    7/23

    Panel Boards They are a collection of branch circuits

    feeding system loads

    Panel System is used for representing powerand lighting panels in electrical systems

    Click to drop once on OLV

    Double-Click to drop multiple panels

  • 7/29/2019 9 Advanced LF Topics

    8/23

    A panel branch circuit load can be modeled as

    an internal or external load

    Advantages:

    1. Easier Data Entry

    2. Concise SystemRepresentation

    Representation

  • 7/29/2019 9 Advanced LF Topics

    9/23

    Pin 0 is the top pin of the panel

    ETAP allows up to 24 external load connections

    Pin Assignment

  • 7/29/2019 9 Advanced LF Topics

    10/23

    Assumptions

    Vrated (internal load) = Vrated (Panel Voltage)

    Note that if a 1-Phase load is connected to a 3-Phase panel circuit, the rated voltage of the panel

    circuit is (1/3) times the rated panel voltage

    The voltage of L1 or L2 phase in a 1-Phase 3-Wirepanel is (1/2) times the rated voltage of the panel

    There are no losses in the feeders connecting aload to the panel

    Static loads are calculated based on their ratedvoltage

  • 7/29/2019 9 Advanced LF Topics

    11/23

    Line-Line Connections

    Load Connected Between Two Phases of a

    3-Phase System

    A

    B

    C

    Load

    IBCIC = -IBC

    A

    B

    C

    LoadB

    IB = IBC

    Angle by which load current IBC lags the load voltage =

    Therefore, for load connected between phases B and C:

    SBC = VBC.IBC

    PBC = VBC.IBC.cos

    QBC = VBC.IBC.sin

    For load connected to phase B

    SB = VB.IB

    PB = VB.IB.cos ( - 30)

    QB = VB.IB.sin ( - 30)

    And, for load connected to phase C

    SC = VC.IC

    PC = VC.IC.cos ( + 30)QC = VC.IC.sin ( + 30)

  • 7/29/2019 9 Advanced LF Topics

    12/23

    3-Phase 4-Wire Panel

    3-Phase 3-Wire Panel

    1-Phase 3-Wire Panel

    1-Phase 2-Wire Panel

    NEC Selection

    A, B, C from top to bottom or

    left to right from the front of

    the panel

    Phase B shall be the highestvoltage (LG) on a 3-phase, 4-

    wire delta connected system

    (midpoint grounded)

    Info Page

  • 7/29/2019 9 Advanced LF Topics

    13/23

    Intelligent kV CalculationIf a 1-Phase panel is connected to a 3-Phase bus

    having a nominal voltage equal to 0.48 kV, the

    default rated kV of the panel is set to (0.48/1.732

    =) 0.277 kV

    For IEC, Enclosure Type

    is Ingress Protection(IPxy), where IP00 means

    no protection or shielding

    on the panel

    Select ANSI or IEC

    Breakers or Fuses from

    Main Device Library

    Rating Page

  • 7/29/2019 9 Advanced LF Topics

    14/23

    Schedule Page

    Circuit Numbers with

    Column Layout

    Circuit Numbers with

    Standard Layout

  • 7/29/2019 9 Advanced LF Topics

    15/23

    Description TabFirst 14 load items in the list are based on NEC 1999

    Last 10 load types in the Panel Code Factor Table are user-defined

    Load Type is used to determine the Code Factors used in calculating the totalpanel load

    External loads are classified as motor load or static load according to the

    element type

    For External links the load status is determined from the connected loads

    demand factor status

  • 7/29/2019 9 Advanced LF Topics

    16/23

    Rating Tab

    Enter per phase VA, W, or

    Amperes for this load.

    For example, if total Watts

    for a 3-phase load are

    1200, enter W as 400

    (=1200/3)

  • 7/29/2019 9 Advanced LF Topics

    17/23

    Loading Tab

    For internal loads, enter the % loading for the selected loading category

    For both internal and external loads, Amp values are

    calculated based on terminal bus nominal kV

  • 7/29/2019 9 Advanced LF Topics

    18/23

    Protective Device Tab

    Library Quick Pick -LV Circuit Breaker

    (Molded Case, with

    Thermal Magnetic Trip

    Device) or

    Library Quick Pick Fuse will appeardepending on the

    Type of protective

    device selected.

  • 7/29/2019 9 Advanced LF Topics

    19/23

    Feeder Tab

  • 7/29/2019 9 Advanced LF Topics

    20/23

    Action Buttons

    Copy the content of the selected

    row to clipboard. Circuit number,Phase, Pole, Load Name, Link

    and State are not copied.

    Paste the entire content (of the

    copied row) in the selected row.

    This will work when the Link

    Type is other than space or

    unusable, and only for fields

    which are not blocked.

    Blank out the contents of the entire

    selected row.

  • 7/29/2019 9 Advanced LF Topics

    21/23

    Summary Page

    Continuous Load Per Phase and Total

    Non-Continuous Load Per Phase and Total

    Connected Load Per Phase and Total (Continuous + Non-Continuous Load)

    Code Demand Per Phase and Total

  • 7/29/2019 9 Advanced LF Topics

    22/23

    Output Report

  • 7/29/2019 9 Advanced LF Topics

    23/23

    Panel Code Factors

    Code demand load depends on Panel Code Factors

    The first fourteen have fixed formats per NEC 1999

    Code demand load calculation for internal loads are done

    for each types of load separately and then summed up