9 advanced lf topics
TRANSCRIPT
-
7/29/2019 9 Advanced LF Topics
1/23
Section 9Advanced LF Topics
Load Flow Convergence
Voltage Control
Mvar Control
-
7/29/2019 9 Advanced LF Topics
2/23
Load Flow Convergence
Negative Impedance Zero or Very Small Impedance
Widely Different Branch Impedance Values
Long Radial System Configurations
Bad Bus Voltage Initial Values
-
7/29/2019 9 Advanced LF Topics
3/23
Voltage Control
Under/Over Voltage Conditions must befixed for proper equipment operation andinsulation ratings be met.
Methods of Improving Voltage Conditions:
Transformer Replacement
Capacitor Addition
Transformer Tap Adjustment
-
7/29/2019 9 Advanced LF Topics
4/23
Under-Voltage Example
Create Under VoltageCondition
Change Syn2 Quantity to 6.(Info Page, Quantity Field)
Run LF
Bus8 Turns Magenta (UnderVoltage Condition)
Method 1 - Change Xfmr
Change T4 from 3 MVA to 8MVA, will notice slight
improvement on the Bus8 kV
Too Expensive and timeconsuming
Method 2 - ShuntCapacitor Add Shunt Capacitor to Bus8
300 kvar 3 Banks
Voltage is improved
Method 3 - Change Tap
Place LTC on Primary of T6
Select Bus8 for Control Bus
Select Update LTC in theStudy Case
Run LF
Bus Voltage Comes withinspecified limits
-
7/29/2019 9 Advanced LF Topics
5/23
Mvar Control
Vars from Utility
Add Switch to CAP1
Open Switch
Run LF
Method 1 Generator
Change Generator fromVoltage Control to MvarControl
Set Mvar Design Setting to 5Mvars
Method 2 Add Capacitor
Close Switch
Run Load Flow
Var Contribution from the
Utility reduces
Method 3 Xfmr MVA
Change T1 Mva to 40 MVA
Will notice decrease in thecontribution from the Utility
-
7/29/2019 9 Advanced LF Topics
6/23
Panel Systems
-
7/29/2019 9 Advanced LF Topics
7/23
Panel Boards They are a collection of branch circuits
feeding system loads
Panel System is used for representing powerand lighting panels in electrical systems
Click to drop once on OLV
Double-Click to drop multiple panels
-
7/29/2019 9 Advanced LF Topics
8/23
A panel branch circuit load can be modeled as
an internal or external load
Advantages:
1. Easier Data Entry
2. Concise SystemRepresentation
Representation
-
7/29/2019 9 Advanced LF Topics
9/23
Pin 0 is the top pin of the panel
ETAP allows up to 24 external load connections
Pin Assignment
-
7/29/2019 9 Advanced LF Topics
10/23
Assumptions
Vrated (internal load) = Vrated (Panel Voltage)
Note that if a 1-Phase load is connected to a 3-Phase panel circuit, the rated voltage of the panel
circuit is (1/3) times the rated panel voltage
The voltage of L1 or L2 phase in a 1-Phase 3-Wirepanel is (1/2) times the rated voltage of the panel
There are no losses in the feeders connecting aload to the panel
Static loads are calculated based on their ratedvoltage
-
7/29/2019 9 Advanced LF Topics
11/23
Line-Line Connections
Load Connected Between Two Phases of a
3-Phase System
A
B
C
Load
IBCIC = -IBC
A
B
C
LoadB
IB = IBC
Angle by which load current IBC lags the load voltage =
Therefore, for load connected between phases B and C:
SBC = VBC.IBC
PBC = VBC.IBC.cos
QBC = VBC.IBC.sin
For load connected to phase B
SB = VB.IB
PB = VB.IB.cos ( - 30)
QB = VB.IB.sin ( - 30)
And, for load connected to phase C
SC = VC.IC
PC = VC.IC.cos ( + 30)QC = VC.IC.sin ( + 30)
-
7/29/2019 9 Advanced LF Topics
12/23
3-Phase 4-Wire Panel
3-Phase 3-Wire Panel
1-Phase 3-Wire Panel
1-Phase 2-Wire Panel
NEC Selection
A, B, C from top to bottom or
left to right from the front of
the panel
Phase B shall be the highestvoltage (LG) on a 3-phase, 4-
wire delta connected system
(midpoint grounded)
Info Page
-
7/29/2019 9 Advanced LF Topics
13/23
Intelligent kV CalculationIf a 1-Phase panel is connected to a 3-Phase bus
having a nominal voltage equal to 0.48 kV, the
default rated kV of the panel is set to (0.48/1.732
=) 0.277 kV
For IEC, Enclosure Type
is Ingress Protection(IPxy), where IP00 means
no protection or shielding
on the panel
Select ANSI or IEC
Breakers or Fuses from
Main Device Library
Rating Page
-
7/29/2019 9 Advanced LF Topics
14/23
Schedule Page
Circuit Numbers with
Column Layout
Circuit Numbers with
Standard Layout
-
7/29/2019 9 Advanced LF Topics
15/23
Description TabFirst 14 load items in the list are based on NEC 1999
Last 10 load types in the Panel Code Factor Table are user-defined
Load Type is used to determine the Code Factors used in calculating the totalpanel load
External loads are classified as motor load or static load according to the
element type
For External links the load status is determined from the connected loads
demand factor status
-
7/29/2019 9 Advanced LF Topics
16/23
Rating Tab
Enter per phase VA, W, or
Amperes for this load.
For example, if total Watts
for a 3-phase load are
1200, enter W as 400
(=1200/3)
-
7/29/2019 9 Advanced LF Topics
17/23
Loading Tab
For internal loads, enter the % loading for the selected loading category
For both internal and external loads, Amp values are
calculated based on terminal bus nominal kV
-
7/29/2019 9 Advanced LF Topics
18/23
Protective Device Tab
Library Quick Pick -LV Circuit Breaker
(Molded Case, with
Thermal Magnetic Trip
Device) or
Library Quick Pick Fuse will appeardepending on the
Type of protective
device selected.
-
7/29/2019 9 Advanced LF Topics
19/23
Feeder Tab
-
7/29/2019 9 Advanced LF Topics
20/23
Action Buttons
Copy the content of the selected
row to clipboard. Circuit number,Phase, Pole, Load Name, Link
and State are not copied.
Paste the entire content (of the
copied row) in the selected row.
This will work when the Link
Type is other than space or
unusable, and only for fields
which are not blocked.
Blank out the contents of the entire
selected row.
-
7/29/2019 9 Advanced LF Topics
21/23
Summary Page
Continuous Load Per Phase and Total
Non-Continuous Load Per Phase and Total
Connected Load Per Phase and Total (Continuous + Non-Continuous Load)
Code Demand Per Phase and Total
-
7/29/2019 9 Advanced LF Topics
22/23
Output Report
-
7/29/2019 9 Advanced LF Topics
23/23
Panel Code Factors
Code demand load depends on Panel Code Factors
The first fourteen have fixed formats per NEC 1999
Code demand load calculation for internal loads are done
for each types of load separately and then summed up