AZ-ROC #’s: 072973 CA-ROC #: 931867 NV-ROC #: 0073021 NM-ROC #: 360598 Site Location: Mountain Mahogany Community School Sol Classroom February 1, 2019 Bill To: Mountain Mahogany Community School 5014 4th St NW Albuquerque, NM 87107 Attn: Lori Webster Phone: (505) 341-1424 Re: Furnish and install one new Daikin 2.0 ton ductless heat pump as axillary heating and cooling including new electrical service, breaker, disconnect, condensate pump, and condensate drain. (See unit specifications at back of proposal) Comfort Systems USA SW, respectfully submits the price of $10,943.00 plus applicable tax, to furnish the scope of work as described below. This proposal includes the following: Detail project prior to commencing work. Run new electrical service including conduit, boxes and wiring from existing panel to roof mounted condenser and install new breaker in existing panel as required. Run two new electrical distribution circuits including conduit boxes and wiring to location for wall mounted ductless air handlers and condensate pump. Furnish and install one new Daikin 2.0 ton ductless heat pump condenser on roof as required. Furnish and install one new ductless wall mounted air handler, in classroom. Furnish and install refrigerant line set from wall mounted unit to condenser on roof. Furnish and install condensate pump and run condensate line to nearest approved drain. Run electrical power circuit and controls circuit from roof mounted condensing unit to wall mounted unit. Furnish and install remote controlled thermostatic control for unit. Subcontract licensed roofer to seal roof penetrations as required. Start up and check equipment for proper operation. Clean up work area and haul off debris. Page 1 of proposal #1011901 8920 Adams St., NE, Ste. A | Albuquerque, NM 87113 | p. 505.856.9250 | f. 505.821.6536

Upload: others

Post on 07-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

AZ-ROC #’s: 072973 CA-ROC #: 931867 NV-ROC #: 0073021 NM-ROC #: 360598

Site Location:

Mountain Mahogany Community School Sol Classroom

February 1, 2019

Bill To:

Mountain Mahogany Community School 5014 4th St NWAlbuquerque, NM 87107 Attn: Lori WebsterPhone: (505) 341-1424

Re: Furnish Iand install one new Daikin 2.0 ton ductless heat pump as axillary heating and cooling including new electrical service, breaker, disconnect, condensate pump, and condensate drain. (See unit specifications at back of proposal)

Comfort Systems USA SW, respectfully submits the price of $10,943.00 plus applicable tax,to furnish the scope of work as described below.

This proposal includes the following:

Detail project prior to commencing work. Run new electrical service including conduit, boxes and wiring from existing panel to roof mounted

condenser and install new breaker in existing panel as required. Run two new electrical distribution circuits including conduit boxes and wiring to location for wall

mounted ductless air handlers and condensate pump. Furnish and install one new Daikin 2.0 ton ductless heat pump condenser on roof as required. Furnish and install one new ductless wall mounted air handler, in classroom. Furnish and install refrigerant line set from wall mounted unit to condenser on roof. Furnish and install condensate pump and run condensate line to nearest approved drain. Run electrical power circuit and controls circuit from roof mounted condensing unit to wall

mounted unit. Furnish and install remote controlled thermostatic control for unit. Subcontract licensed roofer to seal roof penetrations as required. Start up and check equipment for proper operation. Clean up work area and haul off debris.

Page 1 of proposal #1011901

8920 Adams St., NE, Ste. A | Albuquerque, NM 87113 | p. 505.856.9250 | f. 505.821.6536

Page 2: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

Clarification of Proposal

Specific exclusions for this project:

General building permits.

Permits or engineering of any kind. DDC Controls work of any kind. Repairs of any equipment not mentioned in scope. Alarms, alarm wiring or conduit, of any kind. Providing or installation of DDC and/or FMS systems (this includes all equipment).

Fire monitoring, fire panels, low voltage wiring and conduit.

Outside disconnects or GFCI Outlets for new or existing units. Domestic water piping, condensate and related equipment, except as stated.

Additional insured status, waiver of subrogation except on builders risk, primary insurance status.

Carpentry chases and cutting openings of any kind.

Cutting and/or patching of roof or structure (by others).

Motorized control dampers.

Concrete, rebar, curbs and coil pads.

Insulation of any ductwork.

Starters, disconnects, relays, controls and transformers of any kind other than those mentioned.

Structural roof curbs.

Burglar and/or security bars.

Fire rated enclosures.

Installation or finishes of architectural access doors.

Architectural louvers.

Fire dampers. Fireproofing and/or fire stopping.

Design or engineering services.

Indemnification, defense or hold harmless obligation for fault of others.

Consequential damages, except liquidated damages caused by this bidder.

Certified Test and Balance

Page 2 of proposal #1011901

8920 Adams St., NE, Ste. A | Albuquerque, NM 87113 | p. 505.856.9250 | f. 505.821.6536

AZ-ROC #’s: 072973 CA-ROC #: 931867 NV-ROC #: 0073021 NM-ROC #: 360598

Page 3: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

AZ-ROC #’s: 072973 CA-ROC #: 931867 NV-ROC #: 0073021 NM-ROC #: 360598

TERMS AND CONDITIONS

SCOPE OF WORK. Unless otherwise specified, all prices are based on normal working hours. Normal working hours are defined as between 7:00 A.M. and 3:30 P.M. Monday through Friday. Any work required outside of the normal working hours is not included, and will be charged to the customer at overtime rates. Comfort Systems USA SW, will only be required to make repairs caused by normal usage. No repairs are included that are a result of vandalism, acts of God, unauthorized personnel working on the equipment, or any other cause beyond the control of Comfort Systems USA SW.

CHANGES. Any changes to this proposal must be in writing and signed by both parties.

WARRANTY. Comfort Systems USA SW, guarantees all workmanship for a period of one year. All materials are guaranteed by the manufacturer and are extended to the customer through Comfort Systems USA SW.

PAYMENT. All invoices are due upon receipt and become delinquent after 30 days. If payment in full of any invoice is not made within 30 days, customer agrees that a charge of one and one-half percent (1 1/2%) per month will be added to all unpaid balances more than 30 days old. Customer also agrees to pay Comfort Systems USA SW, its reasonable attorney's fees incurred to collect any delinquent account of customer.

CUSTOMER OBLIGATION. The customer shall operate all equipment as specified by the original design, promptly notify Comfort Systems USA SW, of any abnormal conditions, and provide proper access to all equipment for servicing.

INSURANCE. Comfort Systems USA SW, maintains standard limits of coverage of Worker's Compensation, Employer's Liability, General Liability and Automobile Liability. A certificate of insurance will be furnished upon request.

LIABILITY. Comfort Systems USA SW, liability for work rendered pursuant to this Proposal is limited to the value of the labor and materials furnished by Comfort Systems USA SW. Customer agrees that Comfort Systems USA SW, shall not be liable for any indirect or consequential damages, including but not limited to, loss of business, loss of use or profits, or damage to either buildings, contents, products or persons.

ENTIRE AGREEMENT. This Proposal represents the entire agreement between the parties, and no warranties, expressed or implied, are intended unless specifically set forth herein. No other verbal understanding or agreement is considered a part of this Proposal.

The Above Proposal is Valid for 90 Days Addenda Acknowledged – N/A

D.O.L. # 0302162014022

Date

Comfort Systems USA SW

February 1, 2019

By Steve Adams

Acceptance of Proposal Number 1011901

Customer Authorization

Date __________________________________________

By ___________________________________________

Title __________________________________________ Title Account Executive

Page 3 of proposal #1011901

8920 Adams St., NE, Ste. A | Albuquerque, NM 87113 | p. 505.856.9250 | f. 505.821.6536

Page 4: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056 (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without

notice and without incurring any obligations) Submittal Revision Date: September 2018 Page 1 of 4

Performance

Cooling (Btu/hr)

Rated (Min/Max) 21,200 (5,500 / 24,000)

Sensible @ AHRI 15,760

Moisture Removal gal/h 1.2

Standard Operating Range 50°F – 115°F

Extended Operating Range* -4°F – 115°F

Rated Cooling Conditions: Indoor: 80°F DB/67°F WB

Outdoor: 95°F DB/75°F WB

*With field settings and wind baffle

Heating (Btu/hr)

1:@ 47° Rated (Min/Max) 24,000 (5,800 / 27,600)

2: @ 17° Rated 14,400

3: @ 5° 10,720

Operating Range 5°F – 65°F

1: Rated Heating Conditions: Indoor: 70°F DB/60°F WB

Outdoor: 47°F DB/43°F WB

2: Rated Heating Conditions: Indoor: 70°F DB/60°F WB

Outdoor: 17°F DB/15°F WB

3: Heating Conditions: Indoor: 70°F DB/60°F WB

Outdoor: 5°F DB/5°F WB

Submittal Data Sheet FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System

EfficiencyCooling Heating

SEER 18 HSPF 9.0

EER 12.5 COP 3.50

Electrical208/60/1 230/60/1

System MCA 18.3 18.3

System MFA 20 20

Compressor RLA 12.0 12.0

Outdoor fan motor FLA .38 .38

Outdoor fan motor W 58 58

Indoor fan motor FLA .30 .30

Indoor fan motor W 46 46

MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)

RLA: Rated load amps (A) W: Fan motor rated output (W)

PipingLiquid (in) 1/4

Gas (in) 5/8

Drain (in) 5/8

Max. Interunit Piping Length (ft) 98.4

Max. Interunit Height Difference (ft) 65.625

Chargeless (ft) 32.8

Additional Charge of Refrigerant (oz/ft) .21

Indoor Specifications

Airflow Rate (cfm)

Cooling Heating

H M H M

713 579 745 604

L SL L SL

512 403 470 420

Sound (dBA)

H / M / L / SL 53 / 45 / 39 / 34 53 / 43 / 37 / 34

Dimensions (H × W × D) (in) 11-5/8 × 39 × 10-3/8

Weight (Lbs) 27

Outdoor Specifications Compressor Hermetically Sealed Swing Type

Refrigerant R-410A

Factory Charge (Lbs) 3.20

Refrigerant Oil PVE (FVC50K)

Airflow Rate (cfm)

Cooling Heating

H 2,101 H 1,893

SL 1,762 SL 1,585

Sound Pressure Level (dBA) 55

Dimensions (H × W × D) (in) 28-5/16 × 34-1/4 × 12-5/8

Weight (Lbs) 108

Job Name:

Tag#

Complete warranty details available from your local dealer or at www.daikincomfort.com. To receive the 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. If product is installed in a commercial application, limited warranty period is 5 years.

Page 5: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056 (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without

notice and without incurring any obligations) Submittal Revision Date: September 2018 Page 2 of 4

FTX24NMVJU Dimensional Data

Page 6: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056 (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without

notice and without incurring any obligations) Submittal Revision Date: September 2018 Page 3 of 4

RX24NMVJU Dimensional Data

Page 7: 8920 Adams St., NE, Ste. A | Albuquerque, NM …...Clarification of Proposal Specific exclusions for this project: General building permits. Permits or engineering of any kind. DDC

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056 (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without

notice and without incurring any obligations) Submittal Revision Date: September 2018 Page 4 of 4

Indoor Unit

Included Part Number Description

BRP072A43 Wireless Interface Adapter (S21 Adapter Included)

BRC944B2-A08 Wired Remote Controller kit (Adaptor Required)

BRCW901A08 Wired Remote Controller Cable – 25ft (Included in above kit)

BRCW901A03 Wired Remote Controller Cable – 10ft

KRP980B2 Adaptor for wired remote controller (18 & 24)

KAF970A45 Titanium apatite photocatalytic air-purifying filter WITH frame

KAF970A46 Titanium apatite photocatalytic air-purifying filter WITHOUT frame

DACA-CP1-1 Inline Condensate Pump (Fits inside all Daikin wall & floor mount units)

DACA-CP4-1 External Condensate Pump

KRP928BB2S + KRP980B2 Interface adaptor for DIII-NET

Outdoor Unit

Included Part Number Description

DACA-WB-1 Powder-Coated Wall-Mounted Bracket

KPW063A4 Air direction adjustment grille (18 & 24)

KEH063A4E Daikin BML Drain Pan Heater Large RX18,24 & RXN18,24

KKG063A42 Back protection wire net (18 & 24)

KKP937A4 Drain Plug for OD Unit

Optional Accessories