Compact System in Level Control ELK 4/ ELK 4F Main Features : Ayvaz Compact System GALAXY ELK 4 / ELK 4F work according conductivity mesurement principle. ELK 4/ELK 4F capable of display- ing 4 levels in conductor liquids ; 4 levels, each with one contact point : - High level alarm - Low level alarm - Pump start, - Pump stop. ELK 4/ELK 4F ensure the control of all functions inside the panel. No external control device is required. Function : Conductivity of liquid is utilized for displaying the level of liquid. some liquids are conductor, that is, such liquids allow electric current to go through themselves. Minimum conductivity of liquid must be measured in order to ensure safe functioning of device. Two situa- tions can be detected tank to such characteristic of liquids : - Electrode rod dipped/exposed, - Switch point accessed / not accessed. Before the assembly, sizes of electrode rods must be addapted according to contact levels. (For example; maximum/minimum alarm, vale of pump control.) Applications Steam boilers Supply tanks Chemical applications ORDER SPECIMEN : L1. Length measures : ELK 4 : 500/1000/1500 L2. Length measures : ELK 4F : 436/936/1436 1. FLANGE : DIN 50, PN 40, DIN 2527 DIN 100, PN 40, DIN 2527 2. Rules n the apporoval of boiler stand pipe with connection flange must be taken into consideration 3. Ventilation hole 4. High water level (HW) 5. Electrode rod, d = 14 mm 6. Protection pipe P DN 100 7. Electrode distance P 14 8. Low water level (LW) 9. Reduction : 114.3 x 3.6 - 48.3 x 2.9 W DIN 2616 Important Note For cable connection use multiconduit flexible cable with minimum conductor size of 1.5 mm 2 BSP 1” BSP 1” 1 2 4 DN20 5 8 DN20 DN20 ME O O O20 O20 5 6 8 9 7 4 3 1 2 DN50 20 20 20 P P P10 RL 2 RL 2 STOP (off) START (on) STOP (off) START (on) a b c d e f g a - Max.Seviye Alarm b - Pompa stop c - Pompa start d - Min.Seviye Alarm e - Max.Seviye Alarm f - Pompa start-stop g - Min.Seviye Alarm

Upload: vantram

Post on 06-May-2018

230 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: 83-84 COMPACT SYS IN LEVEL CONTROL - interflow …interflow-th.com/information_Product(more)/ELK4-ELK4F.pdf · Compact System in Level Control ... DIN 2616 Important Note For cable

Compact System in Level Control

ELK 4/ELK 4F

Main Features :Ayvaz Compact System GALAXY ELK 4 / ELK 4F work accordingconductivity mesurement principle. ELK 4/ELK 4F capable of display-ing 4 levels in conductor liquids ;4 levels, each with one contact point :- High level alarm- Low level alarm- Pump start,- Pump stop.ELK 4/ELK 4F ensure the control of all functions inside the panel. Noexternal control device is required.Function :Conductivity of liquid is utilized for displaying the level of liquid.some liquids are conductor, that is, such liquids allow electriccurrent to go through themselves. Minimum conductivity of liquid mustbe measured in order to ensure safe functioning of device. Two situa-tions can be detected tank to such characteristic of liquids :- Electrode rod dipped/exposed,- Switch point accessed / not accessed.Before the assembly, sizes of electrode rods must be addaptedaccording to contact levels. (For example; maximum/minimum alarm,vale of pump control.)ApplicationsSteam boilersSupply tanksChemical applications

ORDER SPECIMEN :L1. Length measures : ELK 4 : 500/1000/1500L2. Length measures : ELK 4F : 436/936/14361. FLANGE : DIN 50, PN 40, DIN 2527 DIN 100, PN 40, DIN 25272. Rules n the apporoval of boilerstand pipe with connection flangemust be taken into consideration3. Ventilation hole4. High water level (HW)5. Electrode rod, d = 14 mm6. Protection pipe P DN 1007. Electrode distance P 148. Low water level (LW)9. Reduction :114.3 x 3.6 - 48.3 x 2.9 WDIN 2616

Important NoteFor cable connection usemulticonduit flexible cable withminimum conductor size of 1.5 mm2

BSP 1” BSP 1”

12

4

DN20

5

8

DN20

DN20

ME

OOOO O20O20

5

6

8

9

7

43

12

DN50

20

20

20

PPPP P 10

RL 2 RL 2

STOP (off)

START (on)

STOP (off)

START (on)

a

b

c

d

e

f

g

a - Max.Seviye Alarmb - Pompa stopc - Pompa startd - Min.Seviye Alarme - Max.Seviye Alarmf - Pompa start-stopg - Min.Seviye Alarm

∅∅∅∅∅

∅∅∅∅ ∅

Page 2: 83-84 COMPACT SYS IN LEVEL CONTROL - interflow …interflow-th.com/information_Product(more)/ELK4-ELK4F.pdf · Compact System in Level Control ... DIN 2616 Important Note For cable

Intermediate Disc : PTFEStandard Sizes :

ELK-4 (L mm) ELK-4F (L mm) L1 L2 500 436 1000 936 1500 1436

Main Supply :230 V EEEEE% 10, 50 - 60 Hz115 V EEEEE% 10, 50 - 60 Hz(Opsiyonel)24 V EEEEE% 10, 50 - 60 Hz(Opsiyonel)

Power Consumption : 5 VAFuse : Thermal Fuse Tmax = 115 oC

Precision :Degree 1 : 10 µS/cmDegree 2 : 0.5 µS/cm

Electrode Voltage : 10 Vss

Output :3 Volt-free relay contact (dry contact)12 A at 125 V AC - 50/60 Hz7 A at 250 V AC - 50/60 Hz7 A at 30 V DC

Current Supply / Current Cut-OutDelay :0 to 7 sec.Dip switch adjusted (defult adjustment 3sec)Indicators and Adjusters :4 leds to indicate“electrode dipped”“current supplied to out output / outputrelay”1 quadripole DIP switch for change inprecision sudject to conductivity.1 Dip switch for change in contact delay.

Cable Inlet :1 x PG 91 x PG 13.5Integral cable, clamp cable.Protection :IP 65, DIN 40050Material Structure :Case : Aluminium Injection 3.2161(G AISI8Cu3)Body :Stainless steel 1.4571 (CrNIMoTi 17122)Flange :Forged Steel 1.0460 (C22.8)Measuring Electrodes :Stainless Steel 1.4571Electrode Insulation : PTFE

FIG. A FIG. B

OPERATING CONDITIONSMax.Operating Temperature TMD. (oC) 238Max.Operating Pressure PMO (bar) 32Max.Allowable Ambient Temperature TMD. (oC) 70Approx Weight (kg) 2.3

CONNECTIONSELK 4 Screwed 1” BSP (DIN ISO 228) (fig. A)ELK 4F Flanged DN 50, PN 40, DIN 2635 For marine aplications (fig. B)

Typical connention types