8 - channel scanner isotherm€¦ · 8 - channel scanner isotherm •upto 8 inputs / 4 relays / 2...
TRANSCRIPT
8 - CHANNEL SCANNER ISOTHERM
·Upto 8 inputs / 4 relays / 2 isolated 4~20 mA outputs
·Universal input : 8 thermocouples, Pt100, mV or mA input front panel selection without DIP reconfiguring for each channel
·
·3 key, 5 level programming
·Tactile membrane keypad
·
·
RS485 with MODBUS RTU
85~265 V AC SMPS
Powerful, flexible SCADA software available
CA
T#
27
5R
6/P
1/4
/30
09
12
/A
8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485
www.radix.co.in/scanners.htm
BASIC
Note : Setpoint 1 corresponds to channel 1, etc.
Example
• No. of inputs : 8
• No. of setpoints : 4
• No. of relays : 4
• No. of current output : 2
SP1
RLY1
CH1
SP2
RLY2
CH2
SP3
RLY3
CH3
SP4
RLY4
CH4
Channels
Relays
Setpoints
Current output
8
4
4
2
Maximum No.
Fig 2
INDICATOR
Note : No alarms / relays
Example
• No. of inputs : 8
• No. of setpoints : None
• No. of relays : None
• No. of current output : 2
CH1
CH2
CH8
Channels
Relays
Setpoints
Current output
8
0
0
2
Maximum No.
Fig 1
TABLE 1 : SOFTWARE VERSIONS
VERSION NO. VERSION NAME DESCRIPTION
Indicator
Basic
No alarms/relays
Setpoint 1 corresponds to channel 1, setpoint 2 to channel 2, etc.
30.XX
30.XX
REFERENCE
Fig2
Fig1
TABLE 2
SENSOR / INPUTLOW SCALE HIGH SCALE
Pt - 6% Rh / Pt - 30% RH (B)
Chromel / Constantan (E)
Iron / Constantan (J)
Chromel / Alumel (K)
Nicrosil / Nisil (N)
Pt / Pt - 13% Rh (R)
Pt / Pt - 10% Rh (S)
Copper / Constantan (T)
Pt100, 3-wire
Linear (0~50 mV, 0~20 mA, 4~20 mA)
400
-270
-210
-270
-270
0
0
-270
-200
-19999
1820
1000
760
1372
1300
1760
1760
400
850
19999
RANGE LIMIT(°C / EU)
LOW SCALE HIGH SCALE
400
-270
-210
-270
-270
0
0
-270
-200
-19999
1820
1000
760
1372
1300
1760
1760
400
850
19999
RANGE IN WHICHACCURACY IS SPECIFIED
TYPICAL ACCURACYAT 30 °C(°C / EU)
± 3
± 1
± 1
± 1
± 1
± 2
± 2
± 1
± 0.5
± 10 EU
WORST CASEACCURACY
(°C / EU)
± 5
± 3
± 3
± 3
± 3
± 5
± 5
± 3
± 1.0
± 50 EU
8 - CHANNEL SCANNER ISOTHERM
CA
T#
27
5R
6/P
2/4
/30
09
12
/A
8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485
Fig 3
ON OFF
HEAT COOL
SP HYST
SP HYST
SP HYST
SP HYST
HIGH ALARM LOW ALARM
SPX*
HYST
SPX*
HYST
SP1
SPX*
HYST
SPX* HYST
SP1
* SPX = SP2/SP3/SP4
INBAND OUTBANDDEV HI
SP = SP1 + SPX *DEV LO
SP = SP1 - SPX *
SP HYSTSP
HYST
CONTROL FUNCTIONS
CONTROL Control functions (Fig 3) ONOFF control Heat or Cool or Cool with
compressor time delay Alarm functions High alarm
Low alarm Deviation high alarm Deviation low alarmInband alarm Outband alarm
Control action Direct / reverse
Hysteresis 0.1 - 99.9 °C / °F / EU
Compressor ON time delay 1 - 200 secAlarm type Autoreset, Latch, Hold, Latch+Hold Latch (Ltch) Once relay gets ON, it remains
'ON' until alarm is acknowledgedby key�
Hold Alarm is disabled at power ONAfter process variable reachesnormal (non alarm) value, thealarm is enabled
Ltch.Hold Combination of Latch & Hold logic Alarm Activation delay 0.0 ~ 99.9 sec
Port RS485, isolatedBaud rate User programmable,
4800 bps, 9600 bps, 19200 bps,38400 bps
Protocol Modbus RTUSlave ID User programmable, 1~255Date type Swapped float
Integer x10Minimum polling interval 250 millisecondsParameters
Process variables Read onlySetpoints Read & write from the host
computer Alarm status Read only Relay status Read only
COMMUNICATION
SOFTWARE VERSIONS
INPUTS
INDICATION
OUTPUTS
ISOLATION
See Table 1
No. of inputs 8Input types
Thermocouple B, E, J, K, N, R, S, T RTD Pt100, 3-wire Linear input 0~50 mV, 0~20 mA, 4~20 mA
(each input independentlyscaleable)
Lead-wire resistance error (Pt100, thermocouple) <0.2 °C for 10 ohms / lead
Range limits See Table 2Accuracy See Table 2 Cold junction compensation Automatic Sensor break protection User programmable
Display type 0.56” (14.2 mm), 7 - segment LED Process variable Upper, 4 ½ digit : redSetpoint Middle, 4 ½ digit : greenChannel no. Lower, 1 digit : redStatus indication 8 red LEDs for alarm,
4 green LEDs for relay status2 red LEDs for communication
No. of relays Indicator : NoneOther : 4 electromagnetic relays
Relay contact type NO-C-NC Relay contact rating 5A / 230V AC, resistive Current output 4~20 mA / 0~20 mA,
isolated from input and supply ORVoltage output 0-1 V / 0-10 V / user specifiedMaximum load for current 500 ohms output
Mutual isolation between 1KV AC RMS/1 minute,input/supply/curent output(s)/ 250 V AC RMS continuous
RS485 port
Channel scan rate < 0.8 seconds for 8 channelsChannel-to-channel isolation Suitable for low (leakage)
voltages less than 3V ACInput protection Thermocouple, mV, RTD inputs ± 10 V DC max Current inputs Current limit < 30 mA, 28 V DC max
Maximum no. of outputs (Y) 4 Output type a) Electromagnetic relay
b) SSR drive
SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise
www.radix.co.in/scanners.htm
CALIBRATIONZero & span Through front panel keys & display
Power consumption 5 wattsDimensions (in mm) 96 (H) x 96 (W) x 220 (D) Mounting In panel cutout of 90x90 mm Operating ambient temperature 0 - 50 °CRelative humidity Below 90%, non condensing
User calibration Sensor span and sensor zeroCJC calibration Room temperature
Keypad Membrane, tactile, 3 keysMemory for programmed Non-volatile, indefinite duration parametersField Connections Screw type connections in plug-in
terminalsPlug-in Terminal Type a) Standard (Brass nickel plated)
b) Gold platedSupply voltage 85~265 V AC, 50/60 hz
OTHER
PROGRAMMABLE PARAMETERS
OTHER MAJOR PARAMETERS
Setpoint Full range adjustableAlarm Full range adjustableUnit User programmable
programmable
Setpoint lockLevel lockDisplay scan rate 1~99 seconds/channelSKIP channel Enable / disableInput bias -99.9 ~ 99.9Power ON output activation 0.0 ~ 99.9 sec delay
Resolution User 0.0001,0.001,0.01, 0.1or 1 for linear input, 0.1 or 1 for temperature
SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise
8 - CHANNEL SCANNER ISOTHERM
8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485
CA
T#
27
5R
6/P
3/4
/30
09
12
/A
ORDERING INFORMATION
Product url : www.radix.co.in/scanners.htm
OTHER PRODUCTS
MULTI-CHANNEL SCANNER · FLP ISOSCAN MULTI-CHANNEL SCANNER · ISOSCAN-H
MULTI-CHANNEL SCANNER · ISOSCAN-V
www.radix.co.in/scanners.htm
Option
1 x Analog output1.
2.
3.
2 x Analog output
1 x Analog output + RS485
Details
1 x 4~20 mA
2 x 4~20 mA
1 x 4~20 mA + RS485
Configuration
01
02
03
00
Software version No. of channels (X) No. of relays (Y) RS485
Indicator 8 0 1
Basic
Basic
8
8
4
4
0
1
Indicator 8 0 0
A
A2206
ORDER CODE
Ordering Options The following ordering options are available on request.Minimum order quantity and/or minimum order value may apply.
8 - CHANNEL SCANNER ISOTHERM
8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485
CA
T#
27
5R
6/P
4/4
/30
09
12
/A
· Flexible trend facility - current and historical
· Alarm function
· Allows read (acquire data) & write
(program setpoint, etc) operations
· Supports thousands of tags
· Supports upto 32 or more instruments
· Capable of storing data upto 10 years
· Compatible with a variety of Radix instruments such as Scanner,
PID & ONOFF controllers, Isolators
· Default screen selection
· 21CFR compliant version also available
ELIPSE SCADA With Ethernet
Ethernet Bus
RS485 Bus
RS232 Bus
rSCADA
rSCADA server
rSCADA
rSCADA
rSCADA clients
INSTRUMENTS
ISOTHERM ISOTHERM ISOTHERM
ISOTHERM ISOTHERM ISOTHERM
ISOTHERM ISOTHERM ISOTHERM
ISOTHERM ISOTHERM ISOTHERM
rSCADA
rSCADA
ISOTHERM ISOTHERM ISOTHERM
C:\Histori cal data fil es\Demo.dat
Radix Electrosystems Pvt Ltd
USER: Administrator
PAGE1
DATA HISTORY REPORT
Date Time PV1 PV2 PV3 PV4 PV5 PV6 PV7 PV8
24-Nov-09 14:10:00 50.5 314.4 320.2 321.1 26.7 48.6 333.2 311.5
24-Nov-09 14:25:00 50.4 314.3 320.1 321.1 26.7 48.6 333.1 311.3
24-Nov-09 14:40:00 50.5 314.3 320.2 321.1 26.5 48.5 333.1 311.4
24-Nov-09 14:55:00 50.5 314.4 320.2 321.1 26.6 48.6 333.2 311.5
24-Nov-09 15:10:00 50.5 314.4 320.1 321.1 26.5 48.6 333.1 311.4
24-Nov-09 15:25:00 50.5 314.3 320.2 321.1 26.6 48.6 333.2 311.5
START DATE & TIME: 24-Nov-09-14:10:00 STOP DATE & TIME: 24-Nov-09-15:25:33 SAMPLE INTERVAL: 900
ISO1:_GRP1
REMARK:
CHECKED BY:
MIN: 50.4 314.3 320.1 321.1 26.5 48.5 333.1 311.3
MAX: 50.5 314.4 320.2 321.1 26.7 48.6 333.2 311.5
SUMMARY: ---------- ---- ---------- ---- ---------- ---- ---------- ---- ---------- ---- ---------- ---- ---------- ---- ---------- ----
www.radix.co.inRadix Electrosystems Pvt Ltd, B-14, 2nd Floor, Ghanshyam Indl Estate, Veera Desai Road, Andheri (West), Mumbai - 400 053, IndiaTel : + 91 22 42537777 · Fax : + 91 22 42537700 · Email : [email protected] · www.radix.co.in
AN ISO 9001:2008 COMPANY
INSTRUMENTS T : + 91 22 42537777 x 701 F : + 91 22 42537700 E : [email protected]
SENSORS T : + 91 22 42537777 x 732 F : + 91 22 42537700 E : [email protected]
GAUGES T : + 91 22 42537777 x 733 F : + 91 22 42537700 E : [email protected]
AUTOMATION C : 0-9322405471 C : E : [email protected]