    7SG13DeltaProtection and Control Relays

    Reyrolle

    Protection

    Devices

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    2/16

    Siemens Protection Devices Limited 2

    7SG13DeltaProtection and Control Relays

    The Delta range of feeder manager relays providesintegrated protection, control, monitoring and measuring

    functions.

    The Delta range provides three operational areas:

    1. Comprehensive protection of the power system usinga wide range of functions, all of which can beoperated simultaneously.

    2. Plant control, indication and analogue values can beindicated on front facia displays, LEDs are used foralarm and trip indication.

    3. Display and recording of measurements, togetherwith sequence of event and disturbance recording offaults.

    Our proven experience in feeder protection and the

    simplicity of operation that is the trademark of Reyrolle

    protection relays now benefits from the addition of

    integrated control facilities.

    The Delta provides integrated control and protection that

    will fit directly into circuit breaker panels, eliminating

    complicated circuit breaker wiring.

    This adds cost-effectiveness to the comprehensive range

    of facilities provided by the Delta.

    Communication using the IEC 60870 or Modbus

    standards allows remote updating of settings and

    integrated access by the control system for time-tagged

    events, measurands and fault disturbance.

    Comprehensive protection, control, monitoring and

    measuring functions.

    Integrated trip circuit supervision.

    Circuit breaker failure protection.Optional number of inputs and outputs.

    Continuous self monitoring.

    20 character x 2 line backlit LCD

    Menu navigation keys

    1 fixed LED.16 or 32 programmable LEDs.

    Analogue values can be displayed on the LCD screen. In

    addition most values can be obtained via the data

    communications channel(s).

    Primary and secondary currents

    Primary and secondary voltages*Direction*

    Frequency*

    Real power (Watts)*

    Reactive power (VAr)*

    Apparent power (VA)*

    Power factor*

    Maximum, minimum & average Demand

    Energy (Watt-hours)*

    Status inputs

    Output contacts

    ARC sequence

    Trip counters

    I2

    t counter

    * Applicable to relays with VT inputs

    Phase fault 50/51

    IDMTL/DTL and DTL elements provide overcurrent

    protection, each with independent current settings and

    delays. Both IEC and ANSI curves are supported. The IDMT

    stage has a programmable reset with either a definite

    time or decaying reset to improve grading with

    electromechanical protection.

    Earth fault 50N/51N 50G/51G

    Two earth fault measurement functions are available:

    One method directly measures the earth current from an

    independent CT or the residual connection of the 3 line

    CTs.

    The second method internally calculates the earth current

    from the 3 phase CTs.

    Both methods provide IDMTL/DTL and Overcurrent

    functions, each with independent current settings and

    Description of Functionality

    Monitoring Functions

    User Interface

    Description

    Function Overview

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    3/16

    Siemens Protection Devices Limited 3

    delays. IEC and ANSI curves are supported along with a

    programmable reset delay.

    Thermal Overload 49

    The thermal algorithm calculates the thermal state from

    the measured currents and can be applied to cables and

    transformers. A hot/cold ratio setting enables the system

    to operate reliably near the thermal capacity and alarms

    are available for thermal overload and thermal capacity.

    Negative Sequence Overcurrent 46IT + DT

    Independent settings with IDMTL or DTL delays are

    provided for the negative sequence overcurrent. These

    can be used to detect unbalances on the system or

    remote earth faults with a Delta-star transformer in

    circuit.

    Phase Unbalance/Broken Conductor 46

    With the circuit breaker closed, if any one or two of the

    line currents falls below setting it may be due to a broken

    conductor. This condition may be alarmed or used to trip

    the circuit breaker.

    Circuit Breaker Fail 50BF

    The circuit breaker fail function may be triggered from a

    trip signal from the Delta or from an external device. It

    operates by monitoring the current following a trip signal

    and issues an output if the current does not stop within a

    specified time interval. This alarm can be used to operate

    an output contact to retrip the circuit breaker. A further

    time delay enables the back-tripping of an upstream

    circuit breaker.

    Trip circuit supervision 74TC

    The trip circuit is monitored by a status input. This is

    linked to an alarm and may be configured to operate an

    output relay.

    CT supervision 74CT

    The CT supervision considers an absence of current in

    one phase together with the presence of current in the

    other two phases for a settable time as a CT failure. This

    is linked to an alarm and may be configured to operate an

    output relay.

    Circuit breaker maintenance

    Two circuit breaker operations counters are provided. One

    is used for the overall number of operations and the other

    for the number of operations since the last reset.

    A summation of I2t provides a measure of the contact

    erosion, indicating the energy broken by the circuit

    breaker. Configurable values for contact separation time

    and definite clearance time enable an accurate record for

    different types of circuit breaker.

    Operations count and I2t alarm levels can be set which,

    when reached, can be used as an input to a condition-based maintenance regime.

    Measurement and Trending

    Analogue values can be displayed in primary or secondary

    quantities on the fascia LCD screen. In addition the values

    can be obtained via the IEC60870-5-103

    communications.

    Plant control

    The circuit breaker control function uses the standard

    facia push buttons or via the remote communications. 16

    or 32 programmable LEDs are available for circuit breaker

    status indication.

    The Out-of-service position prevents tripping and control

    operations from taking place, but allows changes to

    settings and front of panel indication for test purposes.

    Double point indications can be used for plant status

    indication, which results in open, close, transitional and

    DBI (Dont Believe It) states.

    Directional control 67/67N

    Phase fault and earth fault elements can be made

    directional.

    Each stage can be separately selected as forward, reverse

    or non-directional.

    The directional polarisation for the phase fault elements

    is derived from the quadrature voltage.

    For the calculated earth fault element, the user can select

    whether the directional polarisation is provided by the

    calculated residual voltage or the negative phase

    sequence voltage.

    Under and Over voltage 27/59

    Four stages of under/over voltage protection are provided

    with independent DTL delays. Each stage can be

    independently selected as an over or under voltage

    element.

    Negative Sequence Overvoltage 47

    Two independent settings with DTL delays are providedfor the negative sequence overvoltage, which may be

    used in protection schemes for isolated networks.

    Under and Over frequency 81

    Four stages of under/over frequency detection are

    provided with independent DTL delays. Each stage can be

    independently selected as an over or under frequency

    element.

    Neutral Over voltage 59NIT + NDT

    Calculated from the 3 line VTs the neutral overvoltage

    can be used to detect earth faults in high impedance

    earthed or isolated systems.

    Optional Functionality

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    4/16

    Siemens Protection Devices Limited 4

    VT supervision 74VT

    The VT supervision uses a combination of negative

    sequence voltage and negative sequence current to

    detect a VT fuse failure. This condition may be alarmed or

    used to inhibit voltage dependent functions.

    Auto-reclose 79

    The Delta incorporates a 5 trip/4 close auto-reclose

    sequence with 3 pole tripping which can be initiated by

    an internal or external signal. Each trip is programmable

    as either delayed or instantaneous. Programmable dead

    times and reclaim time with a wide setting range.

    Sequence of event records

    Up to 500 events are stored and time tagged to 1ms

    resolution. These are available via the communications.

    Fault records

    The last 10 fault records are available from the fascia with

    time and date of trip, measured quantities and type of

    fault.

    Disturbance recorder

    The waveform recorder may be triggered from a

    protection function or external input and has a

    configurable pre-fault trigger. Up to 5 seconds of fault

    waveforms may be stored with associated analogue and

    digital values. This is user configurable as f ive 1-second

    records, two 2-second records or one 5-second record.

    In addition the demand history for the last 24 hours can

    be obtained.

    Communications

    Two fibre-optic communications ports are provided on the

    rear of the relay. They are optimised for 62.5/125m

    glass-fibre, with BFOC/2.5 (ST) bayonet style connectors.

    In addition users may interrogate the relay locally with a

    laptop PC and the RS232 port on the front of the relay.

    The relay can be user selectable to either IEC 60870-5-

    103 or Modbus RTU as its communications standard.

    Reydisp Evolution

    Fig 2. Typical ReyDisp Evolution screenshot

    This support software is common to the entire range of

    Reyrolle numeric products. It provides the means for theuser to apply settings to the Delta as well as to retrieve

    settings, instruments, events, waveforms and 24 hour

    data.

    Data Storage and Communication

    Additional Functionality

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    5/16

    Siemens Protection Devices Limited 5

    For full technical data refer to the PerformanceSpecification of the Technical Manual.

    Characteristic energising quantity

    AC Current 1, 5 A

    AC Voltage 63.5 V line-neutral,

    110 V line-line

    Thermal Withstand

    AC Current Inputs

    continuous 3.0 xIn10 minutes 3.5 xIn

    5 minutes 4.0 xIn

    2 minutes 6.0 xIn

    1 second 250 A

    1 cycle 625 A peak

    AC Voltage Inputs

    continuous 300 V

    Burden

    AC Current Inputs

    5A Phase/Earth 0.3 VA

    1A Phase Earth 0.1 VA

    AC Voltage Inputs

    0.01 VA

    DC Auxiliary Supply

    Nominal Voltage Operating Range V dc

    30V 24 to 37.5 V

    48/110V 37.5 to 137.5 V

    220 V 178.0 to 280.0 V

    110/220V 88 to 275 V

    Operate State Burden

    Quiescent (Typical) 11 W

    Maximum 14 W

    Burdens are measured at nominal rating.

    Allowable superimposed ac

    component

    12% of dc voltage

    Allowable breaks/dips in

    supply (collapse to zero

    from nominal voltage)

    20 ms

    Status inputs

    Nominal Voltage Operating Range V dc

    30V 24 to 37.5V

    48V 37.5 to 60V

    110 V 87.5 to 137.5V220V 175 to 280V

    The binary input voltage need not be the same as the

    main energising voltage.

    The 30V and 48V inputs meet the requirements of ESI48-

    4 ESI 1. However, the 110V and 220V inputs will operate

    with a DC current of less than 10mA. Where 110V or

    220V inputs compliant with ESI48-4 ESI 1 are required, a

    relay with 48V binary inputs can be supplied with

    external series resistors as follows:

    Nominal Voltage Resistor Value Wattage110V 2k7 5% 2.5 W

    220 V 8k2 5% 6.0 W

    Parameter Value

    Minimum DC current for

    operation

    (30V and 48V inputs only)

    10 mA

    Reset/Operate Voltage Ratio 90 %

    Typical response time < 5 ms

    Typical response time when

    used to energise an output

    relay contact

    < 15 ms

    Minimum pulse duration 40 ms

    Each binary input has an associated timer that can be

    programmed to give time delayed pick-up and time

    delayed drop-off. When set to a minimum of 20ms the

    binary inputs will provide immunity to an AC input signal

    and will not respond to the following:

    250V RMS 50/60 Hz applied for two seconds through a

    0.1F capacitor.

    500 V RMS 50/60 Hz applied between each terminal and

    earth. Discharge of a 10F capacitor charged to

    maximum DC auxiliary supply voltage.

    Output Relays

    Carry continuously 5A ac or dc

    Make and carry(L/R 40 ms and V 300V)

    20A ac or dc for 0.5s30A ac or dc for 0.2s

    Breaking Capacity( 5 A and 300 V):AC ResistiveAC InductiveDC Resistive

    DC Inductive

    1250 VA250 VA at p.f. 0.475 W

    30 W at L/R 40ms50 W at L/R 10ms

    Inputs and Outputs

    Technical Information

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    6/16

    Siemens Protection Devices Limited 6

    Minimum number ofoperations

    1000 at maximum load

    Minimum recommendedload

    0.5 W limits 10mA or 5V

    Vibration(Sinusoidal)IEC 60255-21-1 Class 1

    0.5 gn, Vibration response

    1.0 gn, Vibration endurance 5% variation

    Shock and Bump IEC 60255-21-2 Class 1

    5 gn, Shock response, 11ms

    15 gn, Shock withstand, 11ms

    10 gn, Bump test, 16ms5% variation

    Seismic IEC 60255-21-3 Class 1

    1 gn, Seismic Response 5% variation

    Mechanical Classification

    Durability In excess of 106

    operations

    Recommended load

    Minimum recommended load 0.5 W, limits 10 mA or

    5 V

    Insulation IEC 60255-5

    RMS levels for 1 minute

    Between all terminals and earth 2.0 kV

    Between independent circuits 2.0 kVAcross normally open contacts 1.0 kV

    Transient Overvoltage

    IEC 60255-5

    Between all terminals and earth

    or between any two

    independent circuits without

    damage or flashover

    5 kV

    1.2/50 s

    0.5 J

    High Frequency Disturbance

    IEC 60255-22-1 Class III

    2.5kV, Longitudinal mode

    1.0kV, Transverse mode

    3% variation

    Electrostatic DischargeIEC 60255-22-2 Class III

    8kV, Contact discharge 5% variation

    Fast Transient

    IEC 60255-22-4 Class IV

    4kV, 5/50ns, 2.5 kHz, repetitive 3% variation

    Radio Frequency Interference

    IEC 60255-22-3

    10 V/m, 80 to 1000 MHz 5% variation

    Conducted RFI

    IEC 60255-22-6

    10 V, 0.15 to 80 MHz 5% variation

    Conduct limits

    IEC 60255-25

    Limits dB(V)Frequency Range

    Quasi-peak Average

    0.15 to 0.5 MHz 79 66

    0.5 to 30 MHz 73 60

    Radiated limits

    IEC 60255-25

    Frequency Range Limits at 10 m

    Quasi-peak, dB(V/m)

    30 to 230 MHz 40

    230 to 10000 MHz 47

    Temperature IEC 68-2-1/2

    Operating -10 C to +55 C

    Storage -25 C to +70 C

    Humidity IEC 68-2-3

    Operational test 56 days at 40 C and

    95% RH

    Environmental

    Electrical Tests

    Mechanical

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    7/16

    Siemens Protection Devices Limited 7

    General Accuracy

    Reference ConditionsParameter Reference or Value

    General IEC 60255-3

    Current Settings 100% of In

    Time Multiplier 1.0

    Current input (IDMTL) 2x to 20x Is

    Current input (DTL) 5x Is

    Auxiliary supply Nominal

    Frequency 50 Hz

    Ambient temperature 20 C

    General Settings

    Parameter Value

    Transient Overreach of

    Highset/Lowset (X/R = 100)

    5%

    Disengaging Time(1) < 42 ms

    Overshoot Time < 40 ms

    Output contacts have a minimum dwell time of 100ms,

    after which the disengage time is as above.

    Accuracy influencing factors

    Temperature

    10 C to +55 C 5% variation

    Frequency

    Setting: 5% variation47 Hz to 52 Hz

    Operate time: 5% variation

    Phase Overcurrent protection

    Characteristic

    IDMTL (IEC) Normal Inverse (NI),Very Inverse (VI),

    Extremely Inverse (EI),Long Time Inverse (LTI)

    IDMTL (ANSI) Moderately Inverse (MI),Very Inverse (VI),Extremely Inverse (EI)

    DTL

    Level

    IsSettings 0.05 to 2.50 step 0.05 In

    Operate : 105% of setting 5% or 10mA

    Accuracy

    Reset: 95% of operate current

    Repeatability 1%

    IDMTL Delay

    T.M. Setting 0.025x to 1.600x

    Operate time see curves below

    Accuracy 5% or 30 ms

    Repeatability 1%

    DTL Delay

    Operate: 0.00 to 20.00 secSettings

    Reset: 0.0 to 60.0 secAccuracy 1% or 10 ms

    Repeatability 1%

    Characteristic DTL

    Level

    Settings 0.05 to 25.00 In

    Operate: 100% of setting 5% or 10mA

    Accuracy

    Reset: 95% of operate current

    Repeatability 1%

    Delay

    Settings 0.00 to 864000.00 sec

    Accuracy 5 ms

    Repeatability 1%

    Earth-fault protection (50N/51N) (50G/51G)

    As phase Overcurrent protection

    Thermal protection (49)

    Characteristic Using IEC 60255-8 curves

    Level

    Settings 0.1 to 3.0 In

    Operate: 100% of setting 5%Accuracy

    Reset: 95% of operate current

    Repeatability 1%

    DelayTime constant 1.0 to 1000.0 mins

    Accuracy 5% or 100 ms

    Repeatability 100 ms

    Negative phase sequence (NPS) Overcurrent

    protection (46IT / 46DT)

    Characteristic Normal Inverse (NI),

    Very Inverse (VI),

    Extremely Inverse (EI),

    Long Time Inverse (LTI)

    Moderately Inverse (MI),

    Very Inverse (VI),

    Extremely Inverse (EI)

    Level

    Setting 0.05 to 2.50 In

    Accuracy Operate: 105% of setting

    5% or 10mA

    Reset: 95% of operate current

    Repeatability 1%

    IDMTL Delay

    T.M. Setting 0.025x to 1.600x

    Accuracy 5% or 30 ms

    Repeatability 5%

    Characteristic DTLLevel

    Setting 0.05 to 2.50 In

    Protection Elements

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    8/16

    Siemens Protection Devices Limited 8

    Operate: 105% of setting

    5% or 10mA

    Accuracy

    Reset: 95% of operate current

    Repeatability 1%

    Delay

    Settings 0.00 to 864000.00 sec

    Accuracy 5% or 30 ms

    Repeatability 5%

    Broken Conductor protection (46)

    Level

    Setting 20 to 100%

    Operate: 100% of setting 5%Accuracy

    Reset: 95% of operate current

    Repeatability 1%

    Delay

    Settings 0.02 to 1000.00 sec

    Accuracy 5 msRepeatability 1%

    NPS Overvoltage (47)

    Characteristic DTL

    Level

    Setting 0.01 to 2.00 Vn

    Hysteresis 0 to 80 %

    Operate: 100% of setting

    + 1% or + 0.25V

    Accuracy

    Reset:: 95% of operate voltage

    Repeatability + 1%

    DelaySettings 0.1 to 864000.0 sec

    Accuracy + 1% or + 10ms

    Repeatability + 1%

    Under/Over voltage (27/59)

    Characteristic DTL

    Level

    Settings 0.01 to 2.50 Vn

    Hysteresis 0 to 80 %

    Operate: 100% of setting

    + 1% or + 0.25V

    Accuracy

    Reset:: 95% of operate voltage

    Repeatability + 1%

    Delay

    Settings 0.0 to 864000.0 sec

    Accuracy + 1% or + 10ms

    Repeatability + 1%

    Under/Over frequency (81)

    Characteristic DTL

    Level

    Setting 40 to 70 Hz

    Operate: 100% of setting + 10mHzAccuracy Reset:: + 20mHz of operate frequency

    Repeatability + 1%

    Delay

    Settings 0.1 to 864000.0 sec

    Accuracy + 1% or + 10ms

    Repeatability + 1%

    Neutral Voltage Displacement (59NIT / 59NDT)

    Characteristic IDMTL

    Level

    Setting 0.01 to 2.00 Vn

    Operate: 100% of setting+ 2% or + 0.25V

    Accuracy

    Reset:: 95% of operate voltage

    Repeatability + 1%

    IDMTL Delay

    T.M. Setting 0.025x to 1.600x

    Accuracy + 1% or + 10ms

    Repeatability + 1%

    Characteristic DTL

    Level

    Setting 0.01 to 2.00 Vn

    Operate: 100% of setting

    + 2% or + 0.25V

    Accuracy

    Reset:: 95% of operate voltage

    Repeatability + 1%

    Delay

    Settings 0.1 to 864000.0 sec

    Accuracy + 1% or + 10ms

    Repeatability + 1%

    CT Supervision

    Characteristic DTL

    LevelInps 0.05 to 1.00 In

    Vnps 0.01 to 1.00 VnOperate: 95% of setting 5%Accuracy

    Reset: 105% of operate current

    Repeatability 1%

    Delay

    Settings 0.02 to 1000.00 sec

    Accuracy 5 ms

    Repeatability 1%

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    9/16

    Siemens Protection Devices Limited 9

    VT Supervision

    Characteristic DTL

    LevelInps 0.05 to 1.00 In

    Ipps 0.05 to 20.00 In

    Operate: 95% of setting 5%Accuracy

    Reset: 105% of operate current

    Repeatability 1%

    Delay

    Settings 0.03 to 1000.00 sec

    Accuracy 5 ms

    Repeatability 1%

    Circuit Breaker Failure (50BF)

    Characteristic DTL

    Level

    Setting 0.05 to 2.00 InOperate: 100% of setting

    + 5% or 10mA

    Reset: 95% of operate current

    Repeatability

    Delay

    Re-trip 0 to 60000 msecSettings

    Back-trip 0 to 60000 msec

    Accuracy 5 ms

    Repeatability 1%

    Auto-reclose (79)

    No. of shots 0 to 4Delay

    Deadtime 0.0 to 900.0 sec

    Close Pulse 0.0 to 20.0 sec

    Reclaim 0.0 to 600.0 sec

    Reclose Block 0.0 to 600.0 sec

    Setting

    Lockout 0.0 to 600.0 sec

    Accuracy 1 % or 10 ms

    Repeatability 1%

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    10/16

    Siemens Protection Devices Limited 10

    Fig 3. Overall Dimensions and panel drilling for Epsilon E8 case

    Fig 4. Overall Dimensions and panel drilling for Epsilon E12 case

    Case Dimensions

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    11/16

    Siemens Protection Devices Limited 11

    NORL1NC

    Earth

    S1

    +ve

    -ve

    +ve

    -ve

    13

    14

    15

    21

    23

    S2

    +ve

    -ve

    25

    27

    S3

    +ve

    -ve

    26

    28

    RL4

    RL5P.S.U.

    6

    4

    19

    17

    20

    18

    5

    NCRL2NO

    9

    7

    8

    12

    10

    11

    Case Earth

    NORL1NC

    S4

    +

    -

    1

    3

    S5

    +

    -

    5

    7RL6

    RL7

    RL8

    S817

    S9

    +19

    S1023

    S1125

    27

    RL9

    RL10

    RL11

    I/O 1

    20

    22

    18

    4

    2

    8

    6

    12

    10

    16

    14

    S6

    +

    -

    9

    11

    S7

    +13

    15

    -21

    RL1226

    28

    24

    RL13

    -

    +

    +

    +

    -

    TX

    RX

    TX

    RX

    23

    24

    AN2

    VT

    25

    26

    27

    28

    1A

    5A

    17

    18

    19

    20

    1A

    5A

    21

    22

    23

    24

    1A

    5A

    AN1

    A

    UX

    A

    13

    14

    15

    16

    5A

    B

    C

    2

    20

    3

    4

    5

    6

    7

    ISO Rx

    ISO Tx

    ISORTS

    ISODTR

    ISODTR

    ISOGND

    ISODTR

    25

    26 V

    T

    27

    28 V

    T

    21

    22 V

    T

    A B C

    Va

    Vb

    Vc

    See note 2

    S2

    S1

    See note 1

    P2

    P1

    Directionofpowerflow

    Intheforw

    arddirection

    V1 V1V2 V2

    S12

    +

    -

    1

    3

    S13

    +

    -5

    7RL14

    RL15

    RL16

    S1617

    S17

    +19

    S1823

    S1925

    27

    RL17

    RL18

    RL19

    I/O 2

    20

    22

    18

    4

    2

    8

    6

    12

    10

    16

    14

    S14

    +

    -

    9

    11

    S15

    +13

    15

    -21

    RL2026

    28

    24

    RL21

    -

    +

    +

    +

    -

    S20

    +

    -

    1

    3

    S21

    +

    -

    5

    7

    S2417

    S25

    +19

    S2623

    S2725

    27

    I/O 2

    S22

    +

    -

    9

    11

    S23

    +13

    15

    -21

    -

    +

    +

    +

    -

    S12

    +

    -

    2

    4

    S13

    +

    -

    6

    8

    S1618

    S17

    +20

    S1824

    S1926

    28

    S14

    +

    -

    10

    12

    S15

    +14

    16

    -22

    -

    +

    +

    +

    -

    1A

    5A E/F

    13

    14

    15

    16

    C

    B

    1A

    5A

    25

    26

    27

    28

    1A

    5A

    21

    22

    23

    24

    A

    1A

    5A

    17

    18

    19

    20

    A B C

    A B CVa

    Vb

    Vc

    Dn

    Da

    S2

    S1

    P2

    P1

    Directionofpowerflow

    Intheforwarddirec

    tion

    Phase-phase connection

    - see note 5

    See note 4

    23

    24

    AN2

    V

    T

    25

    26 V

    T

    27

    28 V

    T

    21

    22 V

    T

    Notes

    1. A ring-core CT is recommended for use on sensitive earth-

    fault applications.

    2. Diagram shows star-connected VT. If measurement of

    zero-sequence voltage is required this should be of 5-limb

    type.

    3. The fourth VT input is required for synchronising or direct

    residual voltage measurement. Any phase-relationship may

    be used for synchronising.

    4. Diagram shows Holmgreen connection, typically used on

    measured earth-fault applications.

    5. Alternative connection for voltages, using 5-limb VT with

    separate open-delta winding.

    AN1

    Fig 5. Typical Connection Diagrams

    Typical Connection Diagrams

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    12/16

    Siemens Protection Devices Limited 12

    Product description Variants Order No.

    FM0-00X 7 S G 1 3 - 0 - 0

    Feeder manager relay providing a | | | | | | | | |range of protective functions. | | | | | | | | |

    Relay type | | | | | | | | |FM0-0XX - Standard functionality

    Feeder manager relay providing integrated protection,

    monitoring and measuring functions with standard 20

    character x 2 line LCD and LED indication.

    Measurements and instrumentation

    - Current

    Basic protection functionality - included in all models

    - Phase fault overcurrent (50/51)- Earth-fault overcurrent (residual calculation) (50N/51N)

    - Earth-fault overcurrent (measured) (50G/51G)

    - Thermal overload (49)

    - NPS overcurrent DTL + IDMTL/INST (46IT + DT)

    - Phase unbalance / broken conductor (46)

    - Circuit breaker fail (50BF)

    Supervision functions

    - Trip circuit supervision (74TC)

    0 |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    |||||||

    |||||||||

    | | | | | | | |Protection options | | | | | | | |Option 05 Standard functionality 1 | | | | | | |

    | | | | | | |Auxiliary supply /binary input voltage | | | | | | |30 V DC auxiliary, 30 V DC binary input A | | | | | |30 V DC auxiliary, 48 V DC binary input B | | | | | |48/110 V DC auxiliary, 30 V DC binary input C | | | | | |48/110 V DC auxiliary, 48 V DC binary input 1) D | | | | | |48/110 V DC auxiliary, 110 V DC low burden binary input E | | | | | |220 V DC auxiliary, 110 V DC low burden binary input F | | | | | |220 V DC auxiliary, 220 V DC low burden binary input G | | | | | |

    | | | | | |I/O range | | | | | |3 Binary Inputs / 5 Binary Outputs (incl. 3 changeover) A | | | E |11 Binary Inputs / 13 Binary Outputs (incl. 3 changeover) B | | | E |19 Binary Inputs / 21 Binary Outputs (incl. 3 changeover) C | | | G |27 Binary Inputs / 29 Binary Outputs (incl. 3 changeover) D | | | G |27 Binary Inputs / 13 Binary Outputs (incl. 3 changeover) H | | | G |

    | | | | |Frequency | | | | |50Hz 1 | | | || | | |Nominal current | | | |1/ 5 A 0 | | |

    | | |Voltage inputs | | |Not available 0 | |

    | |Housing size | |Case size E8 (4U high) E |Case size E12 (4U high) G |

    |Communication interface |Fibre optic (ST-connector) / IEC 60870-5-103 or Modbus RTU B

    Ordering Information 7SG13 Delta

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    13/16

    Siemens Protection Devices Limited 13

    Product description Variants Order No.

    FM0-01X 7 S G 1 3 - 0 - 0

    Feeder manager relay providing a | | | | | | | | |range of protective functions. | | | | | | | | |

    Relay type | | | | | | | | |FM0-0XX - Standard functionality

    Feeder manager relay providing integrated protection,

    monitoring and measuring functions with standard 20

    character x 2 line LCD and LED indication.

    Measurements and instrumentation

    - Current

    Basic protection functionality - included in all models

    - Phase fault overcurrent (50/51)

    - Earth-fault overcurrent (residual calculation) (50N/51N)

    - Earth-fault overcurrent (measured) (50G/51G)

    - Thermal overload (49)- NPS overcurrent DTL + IDMTL/INST (46IT + DT)

    - Phase unbalance / broken conductor (46)

    - Circuit breaker fail (50BF)

    Supervision functions

    - Trip circuit supervision (74TC)

    - CT supervision (74CT)

    0 ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    ||||||||||

    |||||||

    | | | | | | | |Protection options | | | | | | | |Option 11 - Standard functionality plus

    Measurements and instrumentation

    - Voltage

    - Power

    - Energy

    Protection functionality

    - Directional detection for phase-fault (67)- Directional detection for earth-fault (67N)

    - 3 phase under/overvoltage (27/59)

    - Under/Over frequency (81)

    - Neutral voltage displacement (59N)

    - NPS overvoltage (47)

    - Neutral overvoltage DTL + IDTML/INST (59NIT + NDT)

    Supervision functions

    - VT supervision (74VT)

    3

    |||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    ||||||||||||||||

    Option 12 - Standard functionality plus

    Measurements and instrumentation

    - Voltage

    - Power

    - Energy

    Protection functionality

    - Directional detection for phase-fault (67)

    - Directional detection for earth-fault (67N)

    - 3 phase under/overvoltage (27/59)

    - Under/Over frequency (81)

    - Neutral voltage displacement (59N)

    - NPS overvoltage (47)

    - Neutral overvoltage DTL + IDTML/INST (59NIT + NDT)

    Control functions

    - Autoreclose (79)

    Supervision functions

    - VT supervision (74VT)

    4 |||||||||||||||||

    |||||||||||||||||

    |||||||||||||||||

    |||||||||||||||||

    |||||||||||||||||

    |||||||||||||||||

    |||||||||||||||||

    continued on following page

    Ordering Information 7SG13 Delta

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    14/16

    Siemens Protection Devices Limited 14

    Product description Variants Order No.

    FM0-01X 7 S G 1 3 - 0 - 0

    (continued from previous page) | | | | | | || | | | | | |

    Auxiliary supply /binary input voltage | | | | | | |30 V DC auxiliary, 30 V DC binary input A | | | | | |30 V DC auxiliary, 48 V DC binary input B | | | | | |48/110 V DC auxiliary, 30 V DC binary input C | | | | | |48/110 V DC auxiliary, 48 V DC binary input 1) D | | | | | |48/110 V DC auxiliary, 110 V DC low burden binary input E | | | | | |220 V DC auxiliary, 110 V DC low burden binary input F | | | | | |220 V DC auxiliary, 220 V DC low burden binary input G | | | | | |

    | | | | | |I/O range | | | | | |11 Binary Inputs / 13 Binary Outputs (incl. 3 changeover) B | | | G |19 Binary Inputs / 21 Binary Outputs (incl. 3 changeover) C | | | G |27 Binary Inputs / 29 Binary outputs (incl. 3 changeover) D | | | J |27 Binary Inputs / 13 Binary Outputs (incl. 3 changeover) H | | | G |

    | | | | |Frequency | | | | |50Hz 1 | | | |

    | | | |Nominal current | | | |1/ 5 A 0 | | |

    | | |Voltage inputs | | |63.5/110 V AC 1 | |

    | |Housing size | |Case size E8 (4U high) E |Case size E12 (4U high) G |

    |Communication interface |

    Fibre optic (ST-connector) / IEC 60870-5-103 or Modbus RTU B

    1) High burden 110V & 220V binary inputs compliant with ESI48-4 ESI 1 available via external dropper resistors with 48V binary input version

    110/125 V application, order combination of the following resistor boxes to suit number of binary inputs

    VCE:2512H10064 (9 inputs, 110V)

    VCE:2512H10065 (5 inputs, 110V)

    VCE:2512H10066 (1 inputs, 110V)

    220/250 V application, order resistor box VCE:2512H10066 in addition

    VCE:2512H10067 (5 inputs, 220V)

    VCE:2512H10068 (1 inputs, 220V)

    Refer to website for application note about ESI48-4 compliance

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    15/16

    Siemens Protection Devices Limited 15

  • 8/13/2019 7SG13 Delta Catalogue Sheet

    16/16

    Published by and copyright 2010:

    Siemens AG

    Energy Sector

    Freyeslebenstrasse 1

    91058 Erlangen, Germany

    Siemens Protection Devices Limited

    P.O. Box 8

    North Farm Road

    Hebburn

    Tyne & Wear

    NE31 1TZ

    United Kingdom

    Phone: +44 (0)191 401 7901

    Fax: +44 (0)191 401 5575

    www.siemens.com/energy

    For more information, please contact our

    Customer Support Center.

    Phone: +49 180/524 70 00

    Fax: +49 180/524 24 71(Charges depending on provider)

    E-mail: [email protected]

    Power Distribution Division Order No. E53000-K7076-C8-1

    Printed in Frth

    Printed on elementary chlorine-free bleached paper.

    All rights reserved.

    Trademarks mentioned in this document are the property of Siemens AG, its affili-

    ates, or their respective owners.

    Subject to change without prior notice.

    The information in this document contains general

    descriptions of the technical options available, which

    may not apply in all cases. The required technical

    options should therefore be specified in the contract.