    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    ISOLUX INGENIERA, S.A.MINISTRY OF ELECTRICITY

    AND WATER

    6M.7 FIRE FIGHTING AND DETECTION SYSTEMItem No. Description Particulars

    1. Fire protection water

    distribution (ring main)

    system1.1 Design Code NFPA

    1.2 Total water flow to feed

    largest risk area

    l/min 5000

    1.3 Design Pressure Bar 12.5

    1.4 Design Temperature C

    1.5 Operating Pressure Range Bar

    1.6 Normal pressure in ring

    main

    Bar

    1.7 Pressure at which pressure

    maintaining device starts

    Bar

    1 8 Pressure at which first pump Bar

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    2/17

    1 8 Pressure at which first pump Bar

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    ISOLUX INGENIERA, S.A.MINISTRY OF ELECTRICITY

    AND WATER

    Item No. Description Particulars

    2. Fire Hydrant System

    2.1 Outdoor hydrants:

    2.2 Type/Model Number

    2.3 Manufacturer

    2.4 Design Codes/Class NFPA 24

    2.5 Quantity

    2.6 Max spacing of fire hydrants m 60

    2.7 Size mm 150

    2.8 Discharge per hydrant outlet

    valve (2 Nos.

    65 mm each)

    l/min

    2.9 Design Pressure bar

    2.10 Design Temperature C

    2.11 Operating pressure (in/out) bar

    2.12 Minimum operating pressure bar

    2.13 End style

    O

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    3/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    ISOLUX INGENIERA, S.A.MINISTRY OF ELECTRICITY

    AND WATER

    Item No. Description Particulars

    2.19 Fire hydrant post indicator

    valves:

    2.19.1 Type/Model Number Butterfly

    2.19.2 Manufacturer

    2.19.3 Design Code

    2.19.4 Quantity

    2.19.5 Size

    2.19.6 Body material

    2.19.7 Internal materials

    2.19.8 Building/plant areas:2.19.9 Breeching inlet (No., size

    and threads)

    No/mm

    3. Standpipes and hose

    cabinet

    3.1 Type/Model Number

    f

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    4/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    ISOLUX INGENIERA, S.A.MINISTRY OF ELECTRICITY

    AND WATER

    Item No. Description Particulars

    3.14 Fire hose: Rack Type

    3.14.1 Type/Model Number

    3.14.2 Manufacturer

    3.14.3 Design Codes/Class

    3.14.4 Quantity

    3.14.5 Length

    3.14.6 Material

    3.15 Hose couplings:

    3.15.1 Type/Model Number

    3.15.2 Manufacturer3.15.3 Pressure rating

    3.15.4 Material

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    5/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    Item No. Description GOPH/ Gas

    ConditioningBuilding

    Gas

    Turbinearea

    Diesel

    generatorunits

    Others

    4. Automatic foam/water

    spray systems

    4.1 General

    4.1.1 Foam concentrate type

    4.1.2 Manufacturer

    4.1.3 Design Code

    4.1.4 Mixture rate %

    4.1.5 Specific gravity

    4.1.6 Maximum useable

    temperature

    oC

    4.1.7 Quantity provided litres

    4.1.8 Guaranteed life years

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    6/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    Item No. Description Gas Turbine area Diesel generatorunits

    Others

    4.2 Diaphragm Pressure

    Proportioner

    4.2.1 Ratio controller

    4.2.2 Quantity

    4.2.3 Type/model No.

    4.2.4 Manufacturer

    4.2.5 Size mm

    4.2.6Flow rate l/sec

    4.2.7 Diaphragm tank:

    4.2.7.1 Quantity

    4.2.7.2 Type/model No.

    4.2.7.3 Manufacturer

    4.2.7.4 Capacity litres

    4.2.8 Valves:

    4.2.8.1 Valve type

    4.2.8.2 Materials:

    4.2.8.3 Body

    4.2.8.4 Internals

    4.2.8.5 Seal

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    7/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    Item No. Description Gas Turbine area Diesel generatorunits

    Others

    4.2.9 Hydraulic/electric ball

    valves:

    4.2.9.1 Valve type

    4.2.9.2 Materials:

    4.2.9.3 Body

    4.2.9.4 Internals

    4.2.9.5 SealTenderer to indicate

    other areas providedwith DiaphragmPressure ProportionerSystem

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    8/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIERA, S.A.

    Item

    No

    Description Particulars

    4.3 Balanced

    proportioning

    equipment

    4.3.1 Ratio controller:

    4.3.2 Quantity

    4.3.3 Type/model No.

    4.3.4 Manufacturer

    4.3.5 Size mm

    4.3.6 Flow rate l/sec

    4.3.7 Proportioning control

    valve:

    4.3.7.1 Quantity

    4.3.7.2 Type/model No.

    4.3.7.3 Manufacturer

    4 3 7 4 Size

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    9/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIERA, S.A.

    Item

    No

    Description Particulars

    4.3.9.3 Manufacturer

    4.3.9.4 Rated Capacity l/s

    4.3.9.5 Net positive suction

    head at rated capacity

    m

    4.3.9.6 Maximum power

    absorbed by pump

    kW

    4.3.9.7 Discharge pressure at

    rated capacity

    bar

    4.3.9.8 Discharge pressure

    against closed valve

    bar

    4.3.9.9 Speed rpm

    4.3.9.10 Pump inlet connection

    diameter

    mm

    4.3.9.11 Pump discharge

    connection diameter

    mm

    4.3.9.12 Weight kg

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    10/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIERA, S.A.

    Item

    No

    Description Particulars

    5.3 Number of carbon

    dioxide type provided

    5.4 Capacity of carbon

    dioxide extinguishers

    kg

    5.5 Number of water

    extinguishers

    5.6 Capacity of water

    extinguishers

    L

    5.7 Number of foam type

    provided

    5.8 Capacity of foam

    extinguishers

    L

    6. Gas extinguishing

    system

    6 1Gas turbine noise

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    11/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIERA, S.A.

    Item

    No

    Description Particulars

    7.5 Volume required tomaintainconcentration for

    required period

    8. Panel injection

    8.1 Type of gas used

    8.2 Volume of gas per

    discharge

    8.3 Number of cylinders (2 100%)

    8.4 Duration of discharge

    8.5 Volume required tomaintainconcentration for

    required period

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    12/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    ItemNo.

    Description No. ofUnitsandlocation

    Approx.oilcontentof eachunit(litres)

    Oilconditions(press./temp. &flash point(bar/oC)

    Envelopedimensions& areataken(m & m2)

    Type ofdetectorsystem

    NumberofDetectorsper unit

    Numberandtype ofnozzlesper unit

    Minimumpressureat eachnozzle(bar)

    Nozzledischargerate atmin.pressure(l/s)

    TheoreticalWaterquantityper unit(l/s)

    Installedwaterquantityper unit(l/s)

    9. Automaticwater spraydelugeprotection

    9.1 Generator

    transformers9.2 Unittransformers

    9.3 Othertransformers

    9.4 11 kV/415Vauxiliarytransformers

    9.5 Cable floors(list allareas)

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    13/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    Item

    No.

    Description No. of

    Units andlocation

    Envelope

    dimensions& area taken(m & m2)

    Type of

    detectorsystem

    Number of

    Detectorsper unit

    Number

    and typeof nozzlesper unit

    Minimum

    pressure ateachnozzle(bar)

    Nozzle

    dischargerate atmin.pressure(l/s)

    Theoretical

    Waterquantityper unit(l/s)

    Installed

    waterquantityper unit(l/s)

    10. Automatic wetpipe sprinklersystems

    10.1 Store buildings

    10.2 Others, if any:

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    14/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    ItemNo.

    Description No. ofUnits/Zones

    Approx.oilcontentof eachunit(litres)

    Oilconditions(press./temp. &flash point(bar/oC)

    Envelopedimensions& area taken(m & m2)

    Type ofdetectorsystem

    Number ofDetectorsper unit

    Numberand typeofnozzlesper unit

    Minimumpressureat eachnozzle(bar)

    Dischargerate ofprojectorat min.pressure(l/s)

    TheoreticalWaterquantity perunit(l/s)

    Installedwaterquantityper unit(l/s)

    11. Automaticfoam/watersprayprotectionsystems

    11.1 Balancedpressure

    proportioningsystems:

    11.1.1 Gas oil pumphouse

    11.1.2 Others (list):

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    15/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    ItemNo.

    Description No. ofzones/unitsandlocation

    Approx.oilcontentof eachunit(litres)

    Oilconditions(press./temp. &flash point(bar/oC)

    Envelopedimensions& area taken(m & m2)

    Type ofdetectorsystem

    Number ofDetectorsper unit

    Numberand typeofnozzlesper unit

    Minimumpressureat eachnozzle(bar)

    Dischargerate ofprojectorat min.pressure(l/s)

    TheoreticalWaterquantity perunit(l/s)

    Installedwaterquantityper unit(l/s)

    20. Automaticfoam/watersprayprotectionsystems(cont)

    11.2 Diaphragm

    pressureproportioningsystems:

    11.2.1 Emergencydieselgeneratorsand daytanks

    11.2.2 GT arealub.oil tanks

    & pipes

    11.2.3 GT Lub. oilsystem

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    16/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    ItemNo.

    Description No. ofzones/unitsandlocation

    Approx.oilcontentof eachunit(litres)

    Oilconditions(press./temp. &flash point(bar/oC)

    Envelopedimensions& area taken(m & m2)

    Type ofdetectorsystem

    Number ofDetectorsper unit

    Numberand typeofnozzlesper unit

    Minimumpressureat eachnozzle(bar)

    Dischargerate ofprojectorat min.pressure(l/s)

    TheoreticalWaterquantity perunit(l/s)

    Installedwaterquantityper unit(l/s)

    11.2.4 GeneratorHydrogenseal oilsystem

    11.2.5 GasConditioningBuilding

    Others(List):

  • 7/30/2019 6M.7 FIRE FIGHTING AND DETECTION SYSTEM.docx

    17/17

    6M. MECHANICAL TECHNICAL DATA SHEET

    6M.7FIRE FIGHTING AND DETECTION SYSTEM

    This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without

    the written permission of ISOLUX INGENIERIA S.A

    MINISTRY OF ELECTRICITY

    AND WATER

    ISOLUX INGENIER A, S.A.

    Itemno.

    Description Room/areadimensions

    LxWxH

    metres

    Storagerack

    dimensions

    metres

    Envelopedvolume

    m3

    Size & No. ofCylinderslitres/No.

    Gasstorage

    capacity anddischargeduration

    litres/secs

    Gas designConcentration

    %

    Quantity typeand

    manufacturerof

    nozzles

    Nozzledischarge rate

    at min.pressure

    ltr/sec

    Typeand

    numberof

    detectorsystems

    12. Gas extinguishingsystems

    Areas protected tobe listed by

    Contractor :

    12.1 Areas with totalroom flooding(unmanned areas)

    12.2 Areas with panelinjection (mannedareas)