5.1. psicrometrici

Upload: farzad-rezaei

Post on 29-Oct-2015

300 views

Category:

Documents


37 download

DESCRIPTION

hvac

TRANSCRIPT

  • Relative humidity = 15 percentWet-bulb temperature = 51.5F

    Dew point = 25.2F

    The enthalpy of the inlet air is obtained from Fig. 12-2 as h1 = h1 + D1 =10.1 + 0.06 = 10.16 Btu/lb dry air; at the exit, h2 = h2 +D2 = 21.1 0.1 = 21 Btu/lbdry air. The heat added equals the enthalpy difference, or

    qa = h = h2 h1 = 21 10.16 = 10.84 Btu/lb dry airIf the enthalpy deviation is ignored, the heat added qa is h = 21.1 10.1 = 11Btu/lb dry air, or the result is 1.5 percent high. Figure 12-7 shows the heatingpath on the psychrometric chart.

    Example 4: Evaporative Cooling Air at 95F dry-bulb temperatureand 70F wet-bulb temperature contacts a water spray, where its relativehumidity is increased to 90 percent. The spray water is recirculated; makeupwater enters at 70F. Determine exit dry-bulb temperature, wet-bulb tempera-ture, change in enthalpy of the air, and quantity of moisture added per pound ofdry air.

    Solution. Figure 12-8 shows the path on a psychrometric chart. The leavingdry-bulb temperature is obtained directly from Fig. 12-2 as 72.2F. Since thespray water enters at the wet-bulb temperature of 70F and there is no heatadded to or removed from it, this is by definition an adiabatic process and therewill be no change in wet-bulb temperature. The only change in enthalpy is thatfrom the heat content of the makeup water. This can be demonstrated as fol-lows:

    Inlet moisture H1 = 70 gr/lb dry airExit moisture H2 = 107 gr/lb dry air

    H = 37 gr/lb dry airInlet enthalpy h1 = h1 + D1 = 34.1 0.22

    = 33.88 Btu/lb dry airExit enthalpy h2 = h2 + D2 = 34.1 0.02

    = 34.08 Btu/lb dry air

    Enthalpy of added water hw = 0.2 Btu/lb dry air (from small diagram,37 gr at 70F)

    Then qa = h2 h1 + hw= 34.08 33.88 + 0.2 = 0

    Example 5: Cooling and Dehumidification Find the cooling loadper pound of dry air resulting from infiltration of room air at 80F dry-bulb tem-perature and 67F wet-bulb temperature into a cooler maintained at 30F dry-bulb and 28F wet-bulb temperature, where moisture freezes on the coil, whichis maintained at 20F.

    Solution. The path followed on a psychrometric chart is shown in Fig. 12-9.

    Inlet enthalpy h1 = h1 + D1 = 31.62 0.1= 31.52 Btu/lb dry air

    Exit enthalpy h2 = h2 + D2 = 10.1 + 0.06= 10.16 Btu/lb dry air

    Inlet moisture H1 = 78 gr/lb dry airExit moisture H2 = 19 gr/lb dry air

    Moisture rejected H = 59 gr/lb dry airEnthalpy of rejected moisture = 1.26 Btu/lb dry air (from small

    diagram of Fig. 12-2)Cooling load qr = 31.52 10.16 + 1.26

    = 22.62 Btu/lb dry air

    Note that if the enthalpy deviations were ignored, the calculated cooling loadwould be about 5 percent low.

    Example 6: Cooling Tower Determine water consumption andamount of heat dissipated per 1000 ft3/min of entering air at 90F dry-bulb tem-perature and 70F wet-bulb temperature when the air leaves saturated at 110Fand the makeup water is at 75F.

    Solution. The path followed is shown in Fig. 12-10.

    PSYCHROMETRY 12-5

    FIG. 12-2 Psychrometric chartmedium temperatures. Barometric pressure, 29.92 inHg. To convert British thermal units per pounddry air-degree Fahrenheit to joules per kilogram-kelvin, multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilo-gram, multiply by 0.0624.

  • 12-6 PSYCHROMETRY, EVAPORATIVE COOLING, AND SOLIDS DRYING

    FIG. 12-3 Psychrometric charthigh temperatures. Barometric pressure, 29.92 inHg. To convert British thermal units per pound tojoules per kilogram, multiply by 2326; to convert British thermal units per pound dry air-degree Fahrenheit to joules per kilogram-kelvin, multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilogram, multiply by 0.0624.

  • PSYCHROMETRY 12-7

    FIG. 12-4 Humidity chart for air-water vapor mixtures. To convert British thermal units per pound to joules per kilo-gram, multiply by 2326; to convert British thermal units per pound dry air-degree Fahrenheit to joules per kilogram-kelvin, multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilogram, multiply by 0.0624.

    FIG. 12-5 Revised form of high-temperature psychrometric chart for air and combustion products, based on pound-moles of water vapor and dry gases. [Hatta, Chem. Metall. Eng., 37, 64 (1930).]

  • 12-28 PSYCHROMETRY, EVAPORATIVE COOLING, AND SOLIDS DRYING

    FIG. 12-36 Psychrometric chart: properties of air and water-vapor mixtures from 20 to 120C. (Carrier Corp.)

  • where hc = heat-transfer coefficient by convection, J/(m2sK) [Btu/(hft2F)]; t = air temperature, K; tw = wet-bulb temperature of air, K;kg = mass-transfer coefficient, kg/(sm2) (kg/kg) [lb/(hft2)(lb/lb)]; =latent heat of evaporation at tw, J/kg (Btu/lb); Hw = saturated humidityat tw = kg/kg of dry air; and Ha = humidity of the surrounding air, kg/kgof dry air.

    For airwater-vapor mixtures, it so happens that hc /kg = Cs approx-imately, although there is no theoretical reason for this. Hence, sincethe ratio (Hw Ha)/(tw t) equals hc /kg /, which represents the slopeof the wet-bulb-temperature lines, it is also equal to Cs /, the slope ofthe adiabatic-saturation lines as shown previously.

    A given humidity chart is precise only at the pressure for which it is evaluated. Most airwater-vapor charts are based on a pressure of 1 atm. Humidities read from these charts for given values of wet- anddry-bulb temperature apply only at an atmospheric pressure of 760mmHg. If the total pressure is different from 760 mmHg, the humid-ity at a given wet-bulb and dry-bulb temperature must be correctedaccording to the following relationship.

    Ha = Ho + 0.622pw (12-23)where Ha = humidity of air at pressure P, kg/kg of dry air; Ho = humid-ity of air as read from a humidity chart based on 760-mm pressure atthe observed wet- and dry-bulb temperatures, kg/kg dry air, pw =vapor pressure of water at the observed wet-bulb temperature,mmHg; and P = the pressure at which the wet- and dry-bulb readingswere taken. Similar corrections can be derived to correct specific vol-ume, the saturation-humidity curve, and the relative-humidity curves.

    HUMIDITY CHARTS FOR SOLVENT VAPORS

    Humidity charts for other solvent vapors may be prepared in an anal-ogous manner. There is one important difference involved, however,in that the wet-bulb temperature differs considerably from the adia-batic-saturation temperatures for vapors other than water.

    1760 pw

    1P pw

    Figures 12-37 to 12-39 show humidity charts for carbon tetrachlo-ride, benzene, and toluene. The lines on these charts have been cal-culated in the manner outlined for airwater vapor except for thewet-bulb-temperature lines. The determination of these linesdepends on data for the psychrometric ratio hc /kg, as indicated by Eq.(12-22). For the charts shown, the wet-bulb-temperature lines arebased on the following equation:

    Hw H = (hc /w kg)(t tw) (12-24)where = radiation correction factor, a value of 1.06 having been usedfor these charts. Values of hc /kg, obtained from values of hc /kgCs aspresented by Walker, Lewis, McAdams, and Gilliland (Principles ofChemical Engineering, 3d ed., McGraw-Hill, New York, 1937), whereCs = humid heat of air with respect to the vapor involved, are as fol-lows:

    CarbonMaterial tetrachloride Benzene Toluene

    hc /kgCs 0.51 0.54 0.47

    A discussion of the theory of the relationship between hc and kg maybe found in the psychrometry part of this section. Because both theo-retical and experimental values of hc /kg apply only to dilute gas mix-tures, the wet-bulb lines at high concentrations have been omitted.For a discussion of the precautions to be taken in making psychro-metric determinations of solvent vapors at low solvent wet-bulb tem-peratures in the presence of water vapor, see the paper by Sherwoodand Comings [Trans. Am. Inst. Chem. Eng., 28, 88 (1932)].

    GENERAL CONDITIONS FOR DRYING

    Solids drying encompasses two fundamental and simultaneousprocesses: (1) heat is transferred to evaporate liquid, and (2) mass is

    SOLIDS-DRYING FUNDAMENTALS 12-29

    FIG. 12-37 Humidity chart for air-carbon tetrachloride vapor mixture. To convert British thermal units per pound tojoules per kilogram, multiply by 2326; to convert British thermal units per pound dry air-degree Fahrenheit to joules perkilogram-kelvin, multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilogram, multiply by 0.0624.

  • FIG. 12-38 Humidity chart for air-benzene-vapor mixture. To convert British thermal units per pound to joules per kilo-gram, multiply by 2326; to convert British thermal units per pound dry air-degree Fahrenheit to joules per kilogram-kelvin,multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilogram, multiply by 0.0624.

    FIG. 12-39 Humidity chart for air-toluene-vapor mixture. To convert British thermal units per pound to joules per kilo-gram, multiply by 2326; to convert British thermal units per pound dry air-degree Fahrenheit to joules per kilogram-kelvin, multiply by 4186.8; and to convert cubic feet per pound to cubic meters per kilogram, multiply by 0.0624.

    12-30

  • McGraw-Hill New York

    San FranciscoWashington, D.C.

    AucklandBogot

    CaracasLisbon

    LondonMadrid

    Mexico CityMilan

    MontrealNew DelhiSan Juan

    SingaporeSydney

    TokyoToronto

    Prepared by a staff of specialists under the editorial direction of

    Late EditorRobert H. Perry

    EditorDon W. Green

    Deane E. Ackers Professor of Chemicaland Petroleum Engineering,

    University of Kansas

    Associate EditorJames O. Maloney

    Professor Emeritus of Chemical Engineering,University of Kansas

    PERRYSCHEMICAL

    ENGINEERSHANDBOOK

    SEVENTH EDITION

  • Library of Congress Cataloging-in-Publication Data

    Perrys chemical engineers handbook. 7th ed. / prepared by a staffof specialists under the editorial direction of late editor Robert H. Perry : editor, Don W. Green : associate editor, James OHara Maloney.

    p. cm.Includes index.ISBN 0-07-049841-5 (alk. paper)1. Chemical engineeringHandbooks, manuals, etc. I. Perry,

    Robert H., date. II. Green, Don W. III. Maloney, James O.TP151.P45 1997660dc21 96-51648

    CIP

    Copyright 1997, 1984, 1973, 1963, 1950, 1941, 1934 by The McGraw-Hill Companies, Inc. Copyright renewed 1962, 1969 by Robert H. Perry.All rights reserved.

    Printed in the United States of America. Except as permitted under theUnited States Copyright Act of 1976, no part of this publication may bereproduced or distributed in any form or by any means, or stored in a database or retrieval system, without the prior written permission of the pub-lisher.

    1 2 3 4 5 6 7 8 9 0 DOW/DOW 9 0 2 1 0 9 8 7

    ISBN 0-07-049841-5

    INTERNATIONAL EDITION

    Copyright 1997. Exclusive rights by The McGraw-Hill Companies, Inc.,for manufacture and export. This book cannot be re-exported from thecountry to which it is consigned by McGraw-Hill. The International Edi-tion is not available in North America.

    When ordering this title, use ISBN 0-07-115448-5.

    The sponsoring editors for this book were Zoe Foundotos and RobertEsposito, the editing supervisor was Marc Campbell, and the productionsupervisor was Pamela A. Pelton. It was set in Caledonia by North MarketStreet Graphics.

    Printed and bound by R. R. Donnelley & Sons Company.

    This book was printed on acid-free paper.

    Information contained in this work has been obtained by The McGraw-Hill Companies, Inc. (McGraw-Hill) from sources believed to be reli-able. However, neither McGraw-Hill nor its authors guarantee theaccuracy or completeness of any information published herein, andneither McGraw-Hill nor its authors shall be responsible for any errors,omissions, or damages arising out of use of this information. This workis published with the understanding that McGraw-Hill and its authorsare supplying information but are not attempting to render engineeringor other professional services. If such services are required, the assis-tance of an appropriate professional should be sought.

    Figure 12-4: Figure 12-4Figure 12-5: Figure 12-5Figure 12-37: Figure 12-37Figure 12-38: Figure 12-38Figure 12-39: Figure 12-39