4WT NO: 3333 JOB NO: 2656 CLIENT REF: Marty McAlenan REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County Down Northern Ireland BT34 1BY Report Prepared by: Lesley J Komatsu

Upload: others

Post on 05-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

4WT NO: 3333JOB NO: 2656CLIENT REF: Marty McAlenanREPORT NO: 1859

REPORTON THE TESTING

OF

CT1 POWER GRAB ‘n’ BOND

Supplied by:

C-Tec N.I LtdUnit 6

Ashtree Enterprise ParkNewry

County DownNorthern Ireland

BT34 1BY

Report Prepared by:

Lesley J Komatsu

Page 2: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 2 of 12

R1859/3333/2656/MartyMcAlenan

Report on the testing of

CT1 Power Grab ‘n’ Bond

4ward Testing Ltd were contacted by C-Tec N.I. Ltd of Unit 6, Ashtree Enterprise Park,Newry, County Down, Northern Ireland, BT34 1BY and asked to carry out a series of testson CT1 Power Grab ‘n’ Bond

Identification

Material: Construction AdhesiveCustomer Identification: CT1 Power Grab ‘n’ BondBatch No: 5790499Customer Reference: Marty McAlenan4ward Sample No: 3333Job No: 2656Date Received: 01/07/2015

Test Data

The Construction Adhesive was tested as received from the customer with samples beingprepared by the Laboratory.

The following tests were carried out using CT1 Power Grab ‘n’ Bond

Vertical butt pull-off test

The Construction Adhesive was used to adhere a steel dollie to a concrete substrate.Following cure time the dollie was removed from the concrete substrate which was held ina vertical position.

No of dollies: 3Diameter of dollie: 50mmCure time: 7 days @ 23±2°C, 50±5%RHTest machine: Instron 4204, UKAS calibration certificate:E105060515100830Speed of test: 5mm/min

Page 3: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 3 of 12

R1859/3333/2656/MartyMcAlenan

Photo to show Vertical butt pull-off sample

Test set-up for Vertical butt pull-off test

Page 4: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 4 of 12

R1859/3333/2656/MartyMcAlenan

Shear test based on BS EN 12003

The Construction Adhesive was used to prepare Shear test samples according to BS EN12003

Ceramic Tile type: V2 (fully vitrified)No of Shear assemblies: 3Cure time: 7 days @ 23±2°C, 50±5%RHTest machine: Instron 4204, UKAS calibration certificate: E105060515100830Speed of test: 5mm/min

Photo to show typical sample assembly

Page 5: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 5 of 12

R1859/3333/2656/MartyMcAlenan

Photo to sample in shear test rig

Page 6: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 6 of 12

R1859/3333/2656/MartyMcAlenan

Determination of Slip resistance based on BS EN 1308

The Construction Adhesive was used to prepare Shear test samples according to BS EN1308

Size of concrete base:Ceramic tile type: V2 (fully vitrified)No of samples: 3Load applied: 50±0.1NTime allowed for slip: 20mins

Photos to show test set up

Page 7: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 7 of 12

R1859/3333/2656/MartyMcAlenan

Date of testing: 14/07 – 28/07/2015

Page 8: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 8 of 12

R1859/3333/2656/MartyMcAlenan

Test results

Vertical butt pull off strength

Photo to show typical failure mode

SAMPLE MAXIMUM LOAD (N)VERTICAL BUTT PULL

OFF STRENGTH(N/mm²)

FAILURE MODE

1 740.4 0.38

2 634.5 0.32

3 1364.4 0.69

Mean 913.1 0.46

SOME SMALL PATCHYCOHESIVE FAILURE OF

CONCRETE TOADHESIVE BUT MAILNLYADHESIVE FAILURE TOCONCRETE ( COHESIVE

FAILURE TO METAL)

Page 9: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 9 of 12

R1859/3333/2656/MartyMcAlenan

0.00

200.00

400.00

600.00

800.00

1000.00

1200.00

1400.00

1600.00

0 20 40 60 80 100 120

Load (N)

Scans

Typical Vertical butt pull-off

Page 10: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 10 of 12

R1859/3333/2656/MartyMcAlenan

Shear Adhesion of CT1 Power Grab ‘n’ Bond

Point of failure is determined by drop in load, the only visible sign is possibly the ceramictile cracking or breaking.

SAMPLE MAXIMUM LOAD (N)SHEAR ADHESIVE

STRENGTH (N/mm²)

1 2465.3 1.49

2 2458.2 1.48

3 2698.2 1.63

Mean 2540.6 1.53

0.00

500.00

1000.00

1500.00

2000.00

2500.00

3000.00

0 10 20 30 40 50 60 70 80 90

Load (N)

Scans

Typical Shear Strength graph

Page 11: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 11 of 12

R1859/3333/2656/MartyMcAlenan

Resistance to Slip of CT1 Power Grab ‘n’ Bond

Photo to show typical lack of any slip after 20mins

These results relate only to the material tested

SAMPLE SLIP (mm) AFTER 20 MINS

1 0

2 0

3 0

Mean 0

Page 12: 4ward Testing Ltd Report - SpecifiedBy...REPORT NO: 1859 REPORT ON THE TESTING OF CT1 POWER GRAB ‘n’ BOND Supplied by: C-Tec N.I Ltd Unit 6 Ashtree Enterprise Park Newry County

www.4wardtesting.co.uk

Issue 01 29 July 2015 Page 12 of 12

R1859/3333/2656/MartyMcAlenan

Work carried out and recorded by the following personnel:

L J Komatsu ACQITechnical Manager

Anthony HansonQuality Engineer

Work approved by the following personnel:

L J Komatsu ACQITechnical Manager

This Report shall not be reproduced except in full,without the prior approval of 4ward Testing Ltd in writing.

……………………… END ………………………