2
Publication No: EN-NP24-12R-01 • January 2005 Dimensions Specifications NOMINAL VOLTAGE: 12V NOMINAL CAPACITY: 20 hr. rate of 1.25A to 10.5V 25.0Ah 10 hr. rate of 2.25A to 10.5V 22.5Ah 5 hr. rate of 4.0A to 10.2V 20.0Ah 1 hr. rate of 15.0A to 9.60V 15.0Ah WEIGHT (approx.): 19 pounds (8.8 Kg) ENERGY DENSITY (20 hr. rate): 1.35 WH/cubic inch (79 WH/liter) SPECIFIC ENERGY (20 hr. rate): 15.8 WH/pound (35 WH/Kg) INTERNAL RESISTANCE OF CHARGED BATTERY: 10 milliohms (approx.) MAXIMUM DISCHARGE CURRENT WITH STANDARD TERMINALS: 150 amperes MAXIMUM SHORT-DURATION DISCHARGE CURRENT: 500 amperes OPERATING TEMPERATURE RANGE: CHARGE 5 0 F to 122 0 F (-15 0 C to 50 0 C) DISCHARGE -4 0 F to 140 0 F (-20 0 C to 60 0 C) CHARGE RETENTION (shelf life) at 68˚F (20˚C): 1 month 97% 3 months 91% 6 months 85% LIFE EXPECTANCY: STANDBY USE 3 to 5 years CYCLE USE (approx.): 100% depth of discharge 250 cycles 50% depth of discharge 550 cycles 30% depth of discharge 1200 cycles SEALED CONSTRUCTION: Can be operated in any position without leakage. STANDARD TERMINAL: Receptacle M5 HOUSING MATERIAL: ABS Resin OPTIONAL: Container and cover made from Flame Retardant ABS (UL94-V0/L.O.I.>28%) HARDWARE: 2-M5-.8 x 12mm Bolt w/ lock washer & flat washer NP NP24-12R NP24-12RFR Sealed Rechargeable Lead-Acid Battery 12V, 24Ah DIMENSIONS: MM (INCHES) Terminal DIMENSIONS: MM (INCHES) Φ12.0(0.47) M5 UL listing pending - File No MH16464

Upload: others

Post on 30-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 45996 EN-NP24-12R-01 (Page 1) · Publication No: EN-NP24-12R-01 • January 2005 Dimensions Specifications • NOMINAL VOLTAGE: 12V • NOMINAL CAPACITY: 20 hr. rate of 1.25A to 10.5V

Publication No: EN-NP24-12R-01 • January 2005

Dimensions

Spec i f icat ions

• NOMINAL VOLTAGE: 12V

• NOMINAL CAPACITY:20 hr. rate of 1.25A to 10.5V 25.0Ah10 hr. rate of 2.25A to 10.5V 22.5Ah

5 hr. rate of 4.0A to 10.2V 20.0Ah1 hr. rate of 15.0A to 9.60V 15.0Ah

• WEIGHT (approx.): 19 pounds (8.8 Kg)

• ENERGY DENSITY (20 hr. rate):1.35 WH/cubic inch (79 WH/liter)

• SPECIFIC ENERGY (20 hr. rate):15.8 WH/pound (35 WH/Kg)

• INTERNAL RESISTANCE OF CHARGED BATTERY: 10 milliohms (approx.)

• MAXIMUM DISCHARGE CURRENT WITH STANDARD TERMINALS: 150 amperes

• MAXIMUM SHORT-DURATIONDISCHARGE CURRENT:500 amperes

• OPERATING TEMPERATURE RANGE: CHARGE 50F to 1220F

(-150C to 500C)DISCHARGE -40F to 1400F

(-200C to 600C)

• CHARGE RETENTION (shelf life) at 68˚F (20˚C):1 month 97%3 months 91%6 months 85%

• LIFE EXPECTANCY:STANDBY USE 3 to 5 yearsCYCLE USE (approx.):100% depth of discharge 250 cycles 50% depth of discharge 550 cycles30% depth of discharge 1200 cycles

• SEALED CONSTRUCTION: Can be operated in any position without leakage.

• STANDARD TERMINAL:Receptacle M5

• HOUSING MATERIAL: ABS Resin

• OPTIONAL:Container and cover made from Flame Retardant ABS (UL94-V0/L.O.I.>28%)

• HARDWARE:2-M5-.8 x 12mm Bolt w/lock washer & flat washer

NPNP24-12R

NP24-12RFRSealed Rechargeable

Lead-Acid Battery

12V, 24Ah

DIMENSIONS: MM (INCHES)

Terminal

DIMENSIONS: MM (INCHES)

Φ12.0(0.47)

M5

UL listing pending - File No MH16464

Page 2: 45996 EN-NP24-12R-01 (Page 1) · Publication No: EN-NP24-12R-01 • January 2005 Dimensions Specifications • NOMINAL VOLTAGE: 12V • NOMINAL CAPACITY: 20 hr. rate of 1.25A to 10.5V

Represented by:

CHARGING METHODS (At 20ºC) Cycle use: Maximum charging current 0.25CCharging voltage 14.4 to 15.0V

Standby use: Float charging voltage 13.50 to 13.80VCAUTION •Avoid short circuit

•Do not charge in a sealed container.

When the battery will be used by current in excess of 3C, consult with EnerSys prior to use.

SELF DISCHARGE CHARACTERISTICS OPEN CIRCUIT VOLTAGEVS REMAINING CAPACITY

CYCLE SERVICE LIFE IN RELATIONTO DEPTH OF DISCHARGE

FLOAT SERVICE LIFE

REM

AINI

NG C

APAC

ITY

(%)100

75

50

25

0

(AH%)

120

100

80

60

40

20

0

(V)14.0

13.0

12.0

11.0

10.0

STORAGE TIME (MONTHS)

PERC

ENTA

GE O

F CA

PACI

TY A

VAIL

ABLE

PERC

ENTA

GE O

F CA

PACI

TY A

VAIL

ABLE

NUMBER OF CYCLES

TESTING CONDITIONS: DISCHARGE CURRENT: 0.17C AMP. (F.V. 1.7V/CELL)CHARGING CURRENT: 0.09C AMP.CHARGING VOLUME: 125% OF DISCHARGED CAPACITYAMBIENT TEMPERATURE: 200C TO 250C (680F TO 770F)

TESTING CONDITIONS: FLOATING VOLTAGE 2.25 TO 2.30V/CELLAMBIENT TEMPERATURE: 200C TO 220C (640F TO 720F)

OPEN

CIR

CUIT

VOL

TAGE

REMAINING CAPACITY (%)

3 6 9 12 15 18 0 20 40 60 80 100

(AH%)120

100

80

60

40

20

0

LIFE (YEARS)

1 2 3 4 5 5.5

200 400 600 800 1000 1200 1400

200C (680F)

AT 250C (770F)

300C (860F)400C (1040F)

30% DEPTH OF DISCHARGE50% D.O.D.100% D.O.D.

PERC

ENTA

GE O

F CA

PACI

TY A

VAIL

ABLE

TEMPERATURE EFFECTS IN RELATIONTO BATTERY CAPACITY

DISCHARGE CHARACTERISTIC CURVES AT 250C (770F)

TERM

INAL

VOL

TAGE

Publ

icat

ion

No:

EN

-NP2

4-12

R-01

• Ja

nuar

y 20

05Su

bjec

t to

rev

isio

ns w

ithou

t pr

ior

notic

e. E

.&O

.E.

www.enersys.com

EnerSys EMEA

Brussels, BelgiumTel:+32 (0)2 247 94 47

EnerSys Asia

Guangdong, ChinaTel:+86-755-2689 3639

EnerSys Limited

Rake Lake,Clifton Junction,Swinton, ManchesterM27 8LR, UKTel:+44 (0) 161 794 4611Fax:+44 (0) 161 727 3809

Global Headquarters

P.O. Box 14145Reading, PA 19612-4145USATel: +1-610-208-1991

+1-800-538-3627Fax:+1-610-372-8613