4188-989 issue 1_06/10_SENTRI4_Install
Installation instructions
SenTRI 4 control panel basedFire detection and alarm system
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Contents
Contents - - - - - - - - - - - - - - - - - - - 2Preface - - - - - - - - - - - - - - - - - - - - - - - 3
Abbreviations - - - - - - - - - - - - - - - - - - - - 3
Notes on system installation - - - - - - - - - - 4Installation requirements - - - - - - - - - - - - - - - 4
Second fix installation - - - - - - - - - - - - - - - - 4
Fixture and fittings - - - - - - - - - - - - - - - - - 4
As fitted drawings - - - - - - - - - - - - - - - - - - 4
Cable type and routing - - - - - - - - - - - - - - - - 4
Fire sensor covers - - - - - - - - - - - - - - - - - - 4
Earth continuity - - - - - - - - - - - - - - - - - - - 4
Mains supply - - - - - - - - - - - - - - - - - - - - 4
Local Manual Call Point - - - - - - - - - - - - - - - 4
EN54 information - - - - - - - - - - - - - - - 5Optional functions with requirements of thisEuropean standard - - - - - - - - - - - - - - - - - - 5
System wiring- - - - - - - - - - - - - - - - - 5Requirements of cables - - - - - - - - - - - - - - - 6
Loop cable - - - - - - - - - - - - - - - - - - - - - 6
Mains Supply cable - - - - - - - - - - - - - - - - - 6
Typical SENTRI4 system - - - - - - - - - - - - - - 7
Devices per Device loop - - - - - - - - - - - - - - - 8
SenTRI 4 panel - - - - - - - - - - - - - - - - 10Technical data- - - - - - - - - - - - - - - - - - - - 10
Installation checks - - - - - - - - - - - - - - - - - - 12
Back box installation - - - - - - - - - - - - - - - - 13
Semi-Flush fixing the control panel- - - - - - - - - - 14
Cable termination and markings - - - - - - - - - - - 14
Mains supply - - - - - - - - - - - - - - - - - - - - 15
Mains and battery supply connections - - - - - - - - 15
Terminals for external circuits - - - - - - - - - - - - 16
Loop circuits - - - - - - - - - - - - - - - - - - - - 17
Master alarm circuits - - - - - - - - - - - - - - - - 18
Auxiliary relay circuits - - - - - - - - - - - - - - - 18
Clean contacts- - - - - - - - - - - - - - - - - - - - 18
RS232 / RS485 Communication - - - - - - - - - - - 19
Connecting a Remote printer - - - - - - - - - - - - - 19
On completion of wiring installation - - - - - - - - - 19
Zonal Mimic panel - - - - - - - - - - - - - - 20Technical Data - - - - - - - - - - - - - - - - - - - 20
Typical Mimic illuminations - - - - - - - - - - - - - 20
Compatibility - - - - - - - - - - - - - - - - - - - - 21
Installation - - - - - - - - - - - - - - - - - - - - - 21
Mounting the backbox - - - - - - - - - - - - - - - - 21
External wiring - - - - - - - - - - - - - - - - - - - 22
How to fit the inner door assembly - - - - - - - - - - 22
Where to connect the internal cables - - - - - - - - - 23
How to fit the outer cover - - - - - - - - - - - - - - 23
Repeat Panel (loop connectable) - - - - - - - - 24Compatibility - - - - - - - - - - - - - - - - - - - - 24
Technical Data - - - - - - - - - - - - - - - - - - - 24
Installation - - - - - - - - - - - - - - - - - - - - - 25
Back box mounting - - - - - - - - - - - - - - - - - 25
Doors, Cables and Power up - - - - - - - - - - - - - 25
Repeat Indicator panel - - - - - - - - - - - - - 27Technical data- - - - - - - - - - - - - - - - - - - - 27
Installation - - - - - - - - - - - - - - - - - - - - - 27
SenTRI Sensors - - - - - - - - - - - - - - - - 28General specification - - - - - - - - - - - - - - - - 28
Base - - - - - - - - - - - - - - - - - - - - - - - - 28
Base Gasket- - - - - - - - - - - - - - - - - - - - - 28
Base labels - - - - - - - - - - - - - - - - - - - - - 28
Indicators - - - - - - - - - - - - - - - - - - - - - - 28
Dust Cover - - - - - - - - - - - - - - - - - - - - - 28
Do's and Don't - - - - - - - - - - - - - - - - - - - 28
Siting - - - - - - - - - - - - - - - - - - - - - - - - 28
Metal back box - - - - - - - - - - - - - - - - - - - 29
In - Out wiring to SenTRI bases - - - - - - - - - - - 29
Programmable input/output - - - - - - - - - - - - - 29
Tools for SenTRI devices - - - - - - - - - - - - - - 30
To remove a SenTRI device - - - - - - - - - - - - - 30
To fit a SenTRI device- - - - - - - - - - - - - - - - 30
To fit a dust cover - - - - - - - - - - - - - - - - - - 30
To remove a dust cover - - - - - - - - - - - - - - - 30
SenTRI device Semi-flush fixing kit(SEN-FLUSH) - - - - - - - - - - - - - - - - 31
Technical data- - - - - - - - - - - - - - - - - - - - 31
Beam Sensor - - - - - - - - - - - - - - - - - 32Technical Data - - - - - - - - - - - - - - - - - - - 32
Do's and Dont's - - - - - - - - - - - - - - - - - - - 33
Test Keyswitch - - - - - - - - - - - - - - - - - - - 34
How to install an Angle bracket and fit a Beam sensor - 34
How to pre-assemble the parallel bracket - - - - - - - 35
How to install a Parallel Bracket and fit a Beam sensor 35
Duct kit - - - - - - - - - - - - - - - - - - - - 36Technical date- - - - - - - - - - - - - - - - - - - - 36
SenTRI Sounder Strobe - - - - - - - - - - - - 37Technical data- - - - - - - - - - - - - - - - - - - - 37
Installation - - - - - - - - - - - - - - - - - - - - - 38
Manual Call Points - - - - - - - - - - - - - - 39Technical data- - - - - - - - - - - - - - - - - - - - 39
Installation - - - - - - - - - - - - - - - - - - - - - 39
Keyswitch Interface / MCP - - - - - - - - - - 41Keyswitch assembly - - - - - - - - - - - - - - - - - 41
Technical data- - - - - - - - - - - - - - - - - - - - 41
Installation - - - - - - - - - - - - - - - - - - - - - 42
Operation - - - - - - - - - - - - - - - - - - - - - - 42
Label - - - - - - - - - - - - - - - - - - - - - - - - 42
Features- - - - - - - - - - - - - - - - - - - - - - - 43
Cables - - - - - - - - - - - - - - - - - - - - - - - 43
Installation - - - - - - - - - - - - - - - - - - - - - 43
Interface Modules for SenTRI -Low voltage (LV) Input/Output - - - - - - - - 43
Wiring diagrams - - - - - - - - - - - - - - - - - - 44
Technical data- - - - - - - - - - - - - - - - - - - - 45
Interface Module for SenTRI -Medium Voltage (MV) Output - - - - - - - - - 46
Features- - - - - - - - - - - - - - - - - - - - - - - 46
Cables - - - - - - - - - - - - - - - - - - - - - - - 46
Installation - - - - - - - - - - - - - - - - - - - - - 46
Wiring - - - - - - - - - - - - - - - - - - - - - - - 46
2
Installation instructions
Technical data- - - - - - - - - - - - - - - - - - - - 47
Mains Powered Interface (from Qtr 3 2010)- - - 48Technical Data - - - - - - - - - - - - - - - - - - - 48
Features- - - - - - - - - - - - - - - - - - - - - - - 49
Installation - - - - - - - - - - - - - - - - - - - - - 49
Mains supply - - - - - - - - - - - - - - - - - - - - 50
External wiring - - - - - - - - - - - - - - - - - - - 51
Options - - - - - - - - - - - - - - - - - - - - - - - 51
Network of systems - - - - - - - - - - - - - - 52Copper network connections - - - - - - - - - - - - - 52
Fibre network connections - - - - - - - - - - - - - - 52
Network wiring - - - - - - - - - - - - - - - - - - - 53
Network cable screen continuity - - - - - - - - - - - 53
How to minimise cross talk - - - - - - - - - - - - - 53
Network cables - - - - - - - - - - - - - - - - 54
Domain Bridge across Networks - - - - - - - - 55
SenTRI 4 system parts - - - - - - - - - - - - - 58Control Panel - - - - - - - - - - - - - - - - - - - - 58
Printer - - - - - - - - - - - - - - - - - - - - - - - 58
Repeat panels - - - - - - - - - - - - - - - - - - - - 58
Zonal Mimic panel - - - - - - - - - - - - - - - - - 58
T-Breaker and Remote LED - - - - - - - - - - - - - 58
Manual call points - - - - - - - - - - - - - - - - - - 59
SenTRI Analogue Sensor, Sounder & Strobe - - - - - 59
Duct Sensor - - - - - - - - - - - - - - - - - - - - - 59
Beam sensor - - - - - - - - - - - - - - - - - - - - 59
Sounder and Strobe - - - - - - - - - - - - - - - - - 59
SenTRI Interfaces - - - - - - - - - - - - - - - - - - 60
Mains powered interfaces - - - - - - - - - - - - - - 60
Surge protection- - - - - - - - - - - - - - - - - - - 61
Manuals - - - - - - - - - - - - - - - - - - - - - - 61
Supported products - - - - - - - - - - - - - - - - - 61
3
SENTRI4 -EN54 System
Preface
This is the first issue of the Installation instructions for the SenTRI 4panel based system. These instructions must be read in conjunction withthe recommendations in BS5839:Part 1 code of practice for Firedetection and alarm system for buildings.
Associated DocumentsOperating instructions
Log book
Conventions
� This is a note to highlight important text that isnormally hidden in the main text.
� This is either a caution to prevent damage to theequipment or a warning to inform of dangerous conditionsthat may result in injury or death.
Abbreviations
ac - Alternating current
AS - Anti surge
C - Common
CH -Channel
dc - Direct current
DKC - Display keyboard card
EMC - Electromagnetic Compatibility
EOL - End of line
ESD - Electrostatic discharge
GND - Ground
I/F - Interface
IO or I/O - Input output
IOC - Input output card (Card15)
IP - Ingress protection
LCD - Liquid crystal display
LED - Light emitting diode
LPC - Loop processor card
LPCB - Loss prevention council certification board
LVD - Low voltage directive
MCC - Main controller card (CARD 0)
MCP - Manual call point
MICC - Mineral insulated copper cable
NC - Normally closed
N/O - Normally open
NVM - Non Volatile Memory (NVM on backplane CARD 14)
OC - Open circuit
OS - Outstation (Loop device)
PCB - Printed circuit board
PSU - Power supply unit
QB - Quick blow
Rx - Receiver
SC - Short circuit
S3 - Speech sounder strobe
S4 - Speech sounder strobe sensor
T - Anti-surge (fuse)
TBA - To be advised
Notes on systeminstallation
The power-up of the control panel andcommissioning of the system is done by the
Servicing organisation.
Installation requirements
It is recommended that the installer follow the general requirements ofBS5839:Part 1, which is the code of practice relating to fire detection andalarm systems for buildings. The installer must follow the relevant partsof BS7671 : 1992 Requirements for Electrical installations, IEE wiring
regulations 16th edition if installation is in the United Kingdom, UK.
Second fix installation
To prevent the possibility of damage or dirt degrading the performance orappearance of the products, the installed products must be suitablyprotected until all major building work in the area is complete.
� The installation of all outstanding parts is usuallycarried out during commissioning of the system.
Fixture and fittings
It is the installer's responsibility to provide adequate fixtures and fittingsfor the type of construction surface onto which a product is to beinstalled, whilst utilising the fixing points on the respective product. As anaid to this decision, the weight and overall size of each full assemblytogether with implications on cable entries and routing should be takeninto consideration.
� All these procedures assume that the cable, gland,steel box (BESA box) and other related accessories are providedby the installer.
As fitted drawings
The installer should acquire site specific information from the interestedparties, for details on the location of products for installation. Theacquired information together with this guide and the relevant standardsshould be used to assist the work.
Each product assembly can be identified from its package label. Thecontents of all packages should be checked for any discrepancies.
Cable type and routing
Appropriate attention must be given to ensure correct cable type isinstalled in accordance with as fitted drawings, site specific informationand recommendations of BS5839 Part 1 : 2002. The cables must beinstalled using cable manufacturers recommended fixings andaccessories.
Fire sensor covers
Each fire sensor may be supplied with a plastic dust cover and can beordered separately. If supplied, the cover must be fitted to prevent dustand dirt from the building work contaminating the fire sensor.
Earth continuity
All earth connection points should be clean to provide a goodelectrical conductivity path. To maintain the earth continuity allearth leads and fittings provided should be installed. The loop cablescreen must be continued through each system device on the loopcircuit, whether the earth is connected to the device or not.
�Do not rely on any part of building structure for earthing.
Some of the system products having metal enclosures have a zinccoating around the cable termination points, the coating provide a goodelectrical conductivity path for cable earth termination.
The zinc coating on the metal enclosures should not be damaged. Anydamage will expose bare metal, which can corrode and make a poorearth connection.
Mains supply
Mains supply to any fire alarm control and indicating equipment must bevia an unswitched 5A fused spur unit. A 'disconnect device' must beprovided to disconnect both poles and must have a minimum gap of3mm. The 'disconnect device' should be available as part of the buildinginstallation and must be easily accessible after installation is complete.
�All mains powered equipment must be earthed.
Local Manual Call Point
To comply with the requirements of EN54 : Part 2 : 1997 a conventionalmanual call point must be installed near the main control panel. The callpoint must be wired to an input line of an interface unit on the loop circuit.During commissioning call point input must be set up to evacuate allsectors without delay.
� Failure to install and configure a local manual callpoint in the manner described above when delays are set up onthe system will result in the panel not complying toEN54 : Part 2 : 1997.
4
Installation instructions
EN54 informationOptional functions with requirements of this European standard
The Control panel complies with the requirements of EN54 : Part 2 : 1997. In addition to the basic requirements of the standard the panel conformsto the following optional clauses:
Clause Description
7.8 Output to fire alarm devices
7.11 Delays to action outputs
8.3 Fault signals from point
9.5 Disablement of each addressable point
10 Test condition
System wiring
�If instructed by the project, the installer may need to terminate as well as connect the cables to the appropriate terminal blocks.
Cable separationWhere the outgoing and return cables of a loop which covers more than the equivalent of one zone they must not run together, for example, eitherclose to the Control Panel or in a service duct. There should be as much physical separation as possible between the cables and the mechanicalprotection of the cable should be to a particularly high standard. This is to minimise the risk of accidental damage to both cables. There should beseparation from the mains supply cable.
Lightning protectionWhere a loop cable or network cable is to be mounted to an external wall or between two buildings then consideration should be given to the use oflightning protection devices.
5
SENTRI4 - EN54 system
ControlPanel
1
1
2 2
Zone circuit
Sounder circuit
3230V ac
Other loop devices
ControlPanel
1
1
2 2
Zone circuit
Sounder circuit
3230V ac 3
230V ac
Other loop devices
4
SecureNetwork
3
1
2
4
4
Loop voltagesurge protection
Mains 230Vacvoltage surgeprotection
Input Output linevoltage surgeprotection
Networkvoltage surgeprotection
There must be a good earthconnection to the voltage surgeprotection device.
Looppoweredinterface
Mainspoweredinterface
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Requirements of cables
The British Standard BS5839 Part 1 : 2002 Code of practice for systemdesign, installation, commissioning and maintenance states therequirements for standard and fire-resisting cables in Clause 26.2 sectiond and e.
d) Standard fire-resisting cables should meet PH 30 classificationwhen tested in accordance with EN50200 and maintain circuit integrity ifexposed to the following test:
- a sample of the cable is simultaneously exposed to flame at atemperature of 830ºC - 0+40ºC and mechanical shock for 15min,followed by simultaneous exposure to water spray and mechanical shockfor a further 15min.
e) Enhanced fire-resisting cables should meet the PH120 classificationwhen tested in accordance with EN 50200 and maintain circuit integrity ifexposed to the following test:
- a single sample of the cable is simultaneously exposed to flame at atemperature of 930ºC - 0+40ºC and mechanical shock for a period of60min, followed by simultaneous exposure to water spray andmechanical shock for a further 60min."
� The cables listed in this manual are those that havebeen tested for EMC compliance with the system products.
Loop Cable usage
� There is a maximum limit of 1Km loop cable usageallowed per loop circuit. This maximum limit is the sum of thecable used to wire the main loop circuit, the spurs off main loopcircuit, plus cables that run to all input / output lines off the looppowered interface units installed on the same loop.
There is a further maximum limit of 100m cable run allowed perinput / output line off loop powered interface unit.
Loop cable
The loop cable carries both data and power supply, therefore itsselection is important. Note the following:
� In countries where the European EMC directive is inforce, only EMC Compliant cables are to be used.
� The loop cable usage must not exceed 1Km. Thisincludes the cable usage on main loop, spur circuitsand interface lines.
� Single pair cable must be used. It is NOT permissible torun mixed loops or outgoing and return pairs in a multicore cable, due to inadequate separation and possibleelectrical interference problems.
� Each core of the loop cable must be 1.5mm2 crosssection area.
� the cable screens must be capable of being earthed ateach system device (outstation).
� Red is the preferred cover sheath for fire applications.
� The specified loop circuit cables are also suitable forwiring master alarm, auxiliary relay, input/output linesand mains supply.
Enhanced cables
� Mineral insulated cable (MICC) to BS6207:Part 1
� Approved Enhanced cable:Draka Firetuf Plus Enhanced FTPLUS2EH1.5RD
� Prysmian (formally Pirelli) FP PLUS *
Standard cables
Approved EMC cables for loop wiring
� Draka Firetuf EMC Standard 1.5mm2
FTEMC2EH1.5RDR
� Draka Firetuf FTZ2E1.5 FIRETUF OHLS *fire resistant data cable
� Raydex CDT FG950 *
� Cavicel SpA FIRECEL SR 114H *distributed by Cables Britain
� AEI Cables FIRETEC *
� BICC Pyrotenax FLAMESIL FRC *
� Datwyler LIFELINE *
� Alcatel cable PYROLON E * distributed by Winstonlead
� Huber & Suhner RADOX FR *
� Prysmian (formally Pirelli) FP200 FLEX *
� Prysmian (formally Pirelli) FP200 GOLD *
� The cables marked * utilise laminated aluminium tapewith a tinned drain wire for electrostatic screening. Under certainenvironmental conditions galvanic action may take placebetween the aluminium and the drain wire. This will severelydegrade EMC performance as the foil to drain wire impedancewill increase.Armoured variants of the cables marked * can also be used onloop circuit.
Mains Supply cable
The mains supply cable must be a standard fire-resisting type and shouldmeet PH30 classification, like the standard and enhanced cables listedabove.
6
Installation instructions
Typical SENTRI4 system
The loops allow wiring of addressable devices like fire sensors, alarm sounders, call points, interface units, zonal mimic and repeat panels. Acombined maximum of up to 200 devices is allowed per loop circuit, a further limit on a loop circuit is determined by the load factor.
7
SENTRI4 - EN54 system
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Repeat Panel
Conventional 2-wiresystem equipment
Conventional 2-wiresystem equipment
230V ac
Magnetic doorrelease
230V ac
230V ac Single control as per4-channel interface
Spur
Optional Loop circuits up to 4
SenTRI 4Control Panel
Input output signalsmay be used to controland monitor:Plant equipmentBuilding management system
ConventionalSounders
(Two masteralarm circuits)
250mA per circuit
Two auxiliary relayscontacts rated 1A @ 24Vdc
Clean contacts rated1A @ 24Vdc
T
Tx Rx
System Devices (Outstations)
- Call Point
- End of Line Unit
- Magnetic door release
Conventional System Products
- Alarms
- Conventional Fire Detectors
- Manual Call Point
Loop circuit 1
T S
S
S
- Beam sensorTransmitter and receiver
Tx
Rx
S- Sounder & Strobe Unit
Repeatindicatorpanel
RS232
Monitored Input
Port 0
Port 1 / 2
230V ac Zonal Mimic Panel
Secure Network loop circuit
RS485
- T BreakerT
S - Sensor, Sounder & Strobe
S
S
EN54 Parts 2 & 4: 1997
- 4-Input/OutputMains powered interface unit
- 1-Inputloop powered interface
1i
- 1-Output + Confirmationinput loop powered interface
1o/i
- Mains outputloop powered interface
1o
- 4-Input/Outputloop powered interface
4i/o
4 i/oMP
1o/i
1i
4 i/oMP
230V ac
S
S
S
S
Devices per Device loop
� It is important that redundancy is built into the system to accommodate future expansions.
The number of devices on one loop circuit can be limited by the total number of addresses available, the electrical load on the circuit, the maximumcable length and other geographical considerations.
� A loop circuit must not cover more than 10,000m2 of floor area of a protected site.
� In total a maximum of 200 devices are allowed per loop circuit..
� As a general rule allow 1000 load factor per loop circuit.
� A maximum of 512 loop devices is allowed per panel.
The following table can be used as a rough guide only to determine the loop load.
� For a precise battery standby value use the Battery Standby Calculator. The Battery Standby Calculator tool should be usedduring system design stage to determine the loop loading. The tool can be downloaded from the SMS forum (www.smstoolbox.co.uk),which is accessible to registered users.
Device code number DescriptionLoad factorper device
Maximumdevices perloop
SENTRI-RPT Repeat panel (loop powered) 3 4
SENTRI-ZONE A3 Zonal Mimic Panel 3 4
SENADV-IP-ST-XX Strobe (red) 9 100
SENADV-SN-XSENADV-IP-SN-X
78400-03NM
Sounder (standard tone) 5 200
SENADV-SN-ST-XR Sounder (standard tone) + red Strobe 13 80
SEN-INT-INPUT
SEN-INT-4IO
SEN-INT-OUTPUT
1 - LV Input interface (IZ - EZ)
4 - LV Input/Output interface (IZ - EZ)
1 - LV Output Interface
IZ = Value Including ZoneEZ = Value Excluding Zone
1 - 4 switch inputs
1 - 4 relay output (8 individually sectored)
Zone Input
Every LED Output
1 - 24
5 - 28
1
1
2
26
+ 5
24 - 32
28 - 32
170
170
170
32
100
SEN-INT-ACDINor SEN-INT-AC
1 - MV Output Interface module 5 200
78302-02NM / 78302-12NM New Mains powered interface 4 8
78301-01NM Mains powered interface
SEN-715 Optical Sensor 0.5 200
SEN-720 Heat Sensor 0.5 200
SEN-780 Heat Sensor & Sounder 7 140
SEN-770-ST Heat Sensor, Sounder & Strobe 17 60
SEN-710 Optical Heat Sensor 0.5 200
SEN-770 Optical Heat Sensor & Sounder 6 150
SEN-DUCT Venturi-Air Duct Kit 0.5 200
SENTRI-BEAM Beam sensor pair 3 per pair 16 (ie 8 pair)
SEN-8XX rangeSEN-INT-KEY
SenTRI Manual call pointSenTRI Keyswitch Interface
44
200170
8
Installation instructions
Device code number DescriptionLoad factorper device
Maximumdevices perloop
78299-01NM Tee breaker 0.4 127
Supported products
78215-01NM78210-01NM78220-01NM
Optical sensorOptical Heat sensorHeat sensor
0.5 200
78280-01NM Optical sensor Sounder 8 125
78270-01NM Optical Heat Sounder 8 125
The load factors and maximum devices stated in the table above are revised due to changes in product specification.~ - A maximum of up to 100 input channels are allowed per loop.
* - These values are applicable when sounder is operating in turbo mode.LV - Low voltageMV - Medium voltage
9
SENTRI4 - EN54 system
SenTRI 4 panelThe SenTRI 4 panel is a four loop analogue addressable fire alarm paneldesigned to meet the requirements of EN54 Parts 2 and 4. The panelcan accommodate up to 4 loop circuits for the connection of SenTRIrange of analogue and addressable devices. The panel has an integralmains derived power supply. It has space to accommodate batteries tosupply standby power in the event of mains power failure. A lockablefront door prevents unauthorised access to fire alarm controls but allowsall of the indicators to be seen. The panel has integral zonal indicators toprovide zone fire indications. Two push button controls are located on thefront door below the display that enable fire messages to be scrolled inthe event of multiple fires. The panel is designed for surface orsemi-flush mounting with rear and top cable entry points.
Features
� Analogue addressable fire alarm control panel
� Supports up to four loop circuits per panel
� Up to 200 addressable devices can be connected to aloop circuit. Devices like sensors, MCPs and interfaceunits etc.
� Two master alarm circuits
� Optional RS485 to connect to a Repeat Indicator panel
� Optional RS232 to connect to another control panel(domain bridge) or external printer
� USB port for commissioning tool connection
� Two sets of auxiliary relay change over contactsconfigurable to operate with fire, fault or disablement
� One set of clean voltage-free change over contacts thatoperates with fire events
� Standby supply to power the system during mains failure
� LCD alphanumeric display with back light to show eventinformation
� Integral 32 zone LED indicators (with First fire steady /flashing or disable integral zone indication's options)
� LED lights for event indication
� Local buzzer gives audible sound to announce events
� Push button for essential controls and menu options
� Four programmable control buttons (U1 to U4)
Technical data
Control panel
Standard Designed to EN54 Part 2:1997 +AMD 1:2006 (and include optionalclauses 7.8, 7.10, 7.11, 8.3, 9.5and 10)
Approval LPCB approved
Panel dimensions inmm with outer door
height 543 x width 406 x depth 172
Panel weight 10.2Kg approximately + 2 batteries12V 21Ah battery - 6Kg each
Storage temperature -10 to 55ºC
Operatingtemperature
-5 to 40ºC
Relative Humidity(Non condensing)Temperature-5 to 40°C
up to 90%
Emission BS EN61000-6-3:2001 Residential,Commercial & Light IndustryClass B limits.
Immunity BS EN50130-4: 1996: Part 4Alarm systems: Electromagneticcompatibility. Product familystandard: Immunity requirementsfor components of fire, intruder andsocial alarm systems.
Ingress Protection IP30
Colour Door: Dusty Grey (RAL 7040)Back box: Graphite Grey(RAL 7024)
Loops The panel is supplied with a loopcard for 1 loop circuit. It cansupport up to 4 Loop circuits, usingoptional loop cards.
Network Two types of network cards areavailable for secure networkconnection:Fibre Optics - 2Km maximumCopper (RS485) - 1.2Km maximum
RS232 and RS485connections
The panel will require an optionalstandard IO Card to facilitateRS232 for connections for domainbridging, remote printer. Themaximum cable length allowed forRS232 is 15m.
The panel has an RS485 port toaccept a Repeat Indicator panel.
The Commissioning tool can beconnected to the panel via theUSB port on the Master ControlCard.
Devices per loop A maximum of 200 addressabledevices per loop circuit.
10
Installation instructions
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
042bc
Device label Each device can be given a32 character label for identification.Each MCP is restricted to28 character label.
Plug in Card slots
MCC / LCC -P1IOC / N/W -P2
Loop 1 - P3Loop 2 - P4Loop 3 - P5Loop 4 - P6
IOC or N/W-P7IOC or N/W -P8
Master Control card - suppliedInput Output card / Network cardLoop card - suppliedLoop card optionLoop card optionLoop card optionInput Output card or Network cardInput Output card or Network card
Clean contacts 1 set of voltage free change overcontacts rated 1A @ 24Vdc, activewith a fire event.
Master alarm circuits 2 - (24 volts nominal)400 mA max per circuitMA1 - fuse 1A FS1MA2 - fuse 1A FS2
(20 x 5mm) on Terminal card.
Auxiliary relays
Aux relay 1
Aux relay 2
Voltage-free contacts rated1A @ 24Vdc2 sets of change over contactsconfigured to operate immediatelywith Fire event. The relay isnormally de-energised.
2 sets of change over contactsconfigured to operate immediatelywith Fault event. The relay isnormally energised.
The relays can be re-configured tooperate with Fire, Fault orDisablement event, with amaximum delay of up to10 minutes and can operate in anormally energised or de-energisedstate.
Internal sounder To announce Fire and Faultevents, plus give a key pressconfirmation beep.
Display Alpha-numeric display - 8 lines by40 characters per line, back-lit,(Black characters on greenbackground, liquid crystal display)
Menus [Control], [Setup], [Information] and[Test Engineering] menusaccessed via Menu On/Off, F1, F2,F3 and F4 buttons.
Controls(with door closed)Access level 1
Next and Previous buttonsoperable during Fire condition only.
Controls(with door open)
Access level 2a
User having door key
Sound Alarms, Silence Alarms,Reset, Cancel Buzzer, Verify,F1-F4 keys, Menu On/Off key,QWERTY key board, U1-U4 keysavailable if configured to performsite specific actions by triggering ofcommand builds 251, 252, 253 and254.
Access level 2b
User having an outerdoor key andcustomer password
Access as level 2a plus access tocomplete level 2 menu commands.
Access level 3
Engineer having anouter door key andengineer password
Access as level 2b plus access toall level-3 menu commands.
Indicators Fire (red)
32 - Zones (red) hidden until litPower (green)Power Fault (amber)Delay (amber)Test (amber)Verify (amber)CB253 CB254 (amber)Fault (amber)Disablement (amber)System fault (amber)Sounder (amber)
Logs Active Logs: Fire, Fault andDisablement
Historic log: All events
Event logs: Fault, Disablement,Warning, Supervisory, Exceptionsand Historic fires.
Printer The integral printer if fittedoperates when the outer door isopen. The 'printer menu' include:ON, OFF, Line feed and Test printcontrols.
An optional remote printer can beconnected to the panel.
BatteriesThe batteries provide 24 hour standby supply plus power to alarm loadfor 30 minutes. The Battery Loop Loading calculator can be used todetermine the load on the loop to achieve the standby power in the eventof mains failure.
Battery Batteries installed in the panel2 x Powersonic 12V 21Ahr - (notsupplied)Model number PG12V21 B
Temperaturemonitoring
Inside the enclosure for automaticadjustment of battery charge voltagewith change in temperature.
� Always use the recommended replacementbattery, as there is a risk of an explosion if incorrectbattery is used.
11
SENTRI4 -EN54 System
Power supply
Standard Designed to EN54 Part 4:1997 +AMD 1:2002 and AMD 2:2006
Mains operatingvoltage
230V 50Hz +10% -6% isprotected by a 3.15A (T) 250VCeramic (20 x 5mm) on PSU.Input current - 1.4A
Nominal supply voltagefor master alarmcircuits
24V +1V, -4V
Battery circuit(s) Terminals to connect to internallyhoused batteries. Batteries reachfully charged state in 72Hr
Battery current withmains disconnected
4.5A max.
Light indications To show the status of PSU
PSU Fuses Mains
44V supply
Battery charge circuit
FS6 T3.15A Ceramic
FS2 F3.15A Glass
FS7 F5A Ceramic
All fuses are 20mm x 5mm size
Storage temperature -10 to +55ºC
Operating temperature -5 to 40ºC
Relative Humidity(Non condensing)
up to 90%Temperature -5 to 40°C
Maximum current frombattery without mainsconnected
5.8A
EN54 Part 4 data I min -> 780uA
I max a -> 108mA @ 43.5V
I max b -> 1.6A @ 43.5V and2 x 0.5V @ 24V
Ri max -> 1.25RUVLO -> 20.7V ± 0.4V
� Hazardous voltages may still be present even ifthis indication is extinguished.
Installation checks
The control panel includes the following parts:
� Back box assembly with PSU to power the control panel
� Inner door for control panel
� Moulded outer door
� Loop Card (1- loop card supplied), can accommodateup to 4 maximum in panel
� Main Controller Card
� 2x12V 21Ah batteries (required but not supplied)
Parts supplied in spares packs
Part Qty
Cable tie 3
Ferrite core
1
22K 0.5W Resistor 2
Battery lead
1
Spade tag 2
Link lead 1
Battery lead fused
Instructions1
20 x 5mm Fuse 5A QB Ceramic 1
20 x 5mm Fuse 3.15A AS Ceramic 1
20x 5mm Fuse 3.15A QB glass 1
20x 5mm Fuse 10A QB Ceramic
Terminal block
Adhesive backed foam pad1
Each battery pair of 2 x 12V 21Ah is supplied with:
12
Installation instructions
i
4 x bolts 4 x spring washers4 x washers
Back box installation
These instructions cover installation of the panel. The cards and batteries are installed during the commissioning of the system by the servicingorganisation. The control panel can be surface or flush mounted.
a. Identify the package SENTRI4 and check that it contains all the parts.
b. Remove the temporary cover from the Back box.
c. Knock out/in the required cable entry points from the Control panel back box .
d. Use the fixing points provided and mount the Back box to the wall using suitable fixings.
� The fixings must support a fully assembled Control panel with batteries weighing 22.2Kg .
e. Stick the adhesive backed foam pad supplied to cover gaps around the centre key-hole fixing point in the back box.This is done to seal any gaps to prevent ingress.
f. Terminate each cable at the entry point leaving 400mm tail wire length and mark each core to identify its finalconnecting point.
� If the mains cable is not connected to the respective terminals then ensure the tail ends are insulated to guardagainst accidental switching ON of the mains supply.
13
SENTRI4 - EN54 system
50
2m
m
390mm
Cable entry points
18 - Back
18 - Top
2 - Bottom side
(on the right)Mains supply
cable
Knock outs
9-off Earth points
(1-0ff bottom side
on the right hand)
Back box
5-off Backbox
fixing points
(includes
1 keyhole)
1.7
m
Floor level
Dust
cover
over
backplane
Earth to
Inner door
Backplane
0V
to printer
PSU
Adhesive backed foam pad
to seal up gap to prevent
ingress
Semi-Flush fixing the control panel
The control panel may be semi-flush mounted using a semi-flush surround.
a. Check the contents of the semi-flush surround package.
b. Cut out an aperture in the wall to allow the semi-flush surround to be fitted, see the diagram below for dimensions ofthe aperture in the wall.
c. Using the fixing holes on the semi-flush surround secure it into the aperture side walls.
d. Knock out the appropriate top or rear cable points on the control panel back box.
e. Route the cables through the cable entry points into the back box and at the same time insert the back box into thesemi-flush surround.
f. Fit the back box to the semi-flush surround using the 5 - 5mm fixing-screws supplied in the spares pack.
Cable termination and markings
�Unused knockouts that have been removed must NOT be left open.
The wires between the termination point and terminals should be asshort and straight as possible.
Where a cable has an earth drain wire, the wire must be fitted to theearth point nearest to the cable entry point. Ensure the drain wire lengthdoes not exceeding 50mm.
Terminate each cable at the dedicated entry point on the enclosure,using the cable manufacturer recommended techniques.
Where the cable is not required to be connected, leave 400mm tailwire length (unless otherwise instructed) and mark each coreidentifying its final point of connection.
Where the cable is required to be connected, ensure it is secured to therespective terminal.
Wiring tests
� Don't undertake high voltage insulation tests WITH THE CABLES CONNECTED to the panel and system deviceterminals. Such a test may damage the electronics circuitry in loop devices and at the panel.
14
Installation instructions
Control Panel
Cross section of
the wall to which
the panel is to be
semi-flush mounted
Flush
Surround
5mm diameter
fixing holes
Aperture Height:
- Control panel510mm
Aperture Width:
- Control panel390mm
Aperture depth
- 132mm
Control panel
semi-flush surround
MICC CABLE
GLAND
BRASS
LOCKNUT
ZINC PLATED
LOCK WASHER GLAND
BOARD
TERMINALS
MICCCABLE TERMINATION
MICC CABLE
GLAND
BRASS
LOCKNUT
ZINC PLATED
LOCK WASHER
Softskin Cable
GLAND
BOARD
TERMINALS
EARTHDRAINWIREShould notbe more than50mm longand must besleeved
CABLE TERMINATION
PANEL
enclosure
Softskin (Fire Tuf)
Mains supply
� Ensure that the mains supply cable enters thepanel through a dedicated cable entry point.
� These fire alarm system products are NOT designedto be powered from IT Power systems.
All mains powered equipment must be earthed.
Mains supply to any fire alarm control and indicating equipment must bevia an unswitched 5A fused spur unit. A disconnect device must beprovided to disconnect both poles and must have a minimum gap of3mm. The Disconnect device should be available as part of the buildinginstallation and must be easily accessible after installation is complete.
The fused spur isolator cover should be marked:FIRE ALARM - DO NOT SWITCH OFF
The fire alarm equipment’s fused spur unit must be fed from adedicated switch or protective device at the local mains supplydistribution board.
Mains and battery supply connections
The mains and battery supply cables must be installed to the stage tofacilitate the power up for commissioning, which is carried out by theServicing organisation.
� Where mains cable is to remain disconnected, itstail ends must be insulated to prevent dangerousconditions arising in the event of accidental switching Onof the mains supply.
15
SENTRI4 -EN54 System
Dedicated mains supplyfrom consumer unit
5A Unswitchedfused spur unit
P2L N
mains cable
27
0m
m
50
mm
5mm
mainscable
The mains cable must be strippedback to the length shown to allowlive and neutral wires to be woundtwice through the ferrite core.
ferritecore
(supplied)
35
mm
Panel
45
mm
must be sleeved
Use cable ties(supplied)
Gland
PSU PCB
Terminals for external circuits
The Terminal card holds all the terminals for the connection of external circuits. The exceptions are:
� terminals for CARDS in slots P7 and P8, these are located on the Backplane
� terminals for mains supply are located on the PSU
� terminals for batteries are located on the PSU.
16
Installation instructions
CARD 4LOOP 4
L1 0V L2 0V
CARD 3LOOP 3
L1 0V L2 0V
CARD 2LOOP 2
L1 0V L2 0V
CARD 1LOOP 1
L1 0V L2 0V
RS485A 5V B 0V
RS232Tx CTS Rx RTS (WITH IO CARD IN SLOT P2 OF BACKPLANE)
P4
MA1+ MA1- MA2+ MA2-
Master alarm
P5
Clean CNC C NO
P6
Auxiliary Relay 1NC C NO NC C NO
P7
Auxiliary Relay 2NC C NO NC C NO
P8
RS232 0V0V 0V 0V 0V
P12
PB1
PB2
BackplaneTerminal card
Quick release terminals
P2 P3
0V1 +VE1 -VE1 0V2 N/C N/C +VE2 -VE2 (WITH NETWORK CARD IN SLOT P2 OF BACKPLANE)
NETWORK CARD IN SLOT P80V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/C
IO CARD IN SLOT P8A 5V B 0V CTS Rx RTS TX
IO (RS232) CARD IN SLOT P7N/C 0V CTS RX RTS TX
P2L N
PSU board (located behind the cardboard cover)
Loop circuits
The loop circuits can each accept the connection of addressable devices, a maximum of 200 devices is allowed per loop. To maintain earthcontinuity on a loop it is important for the loop cable screen to be continued through each system device, whether the earth is connected to adevice or not.
� As every loop device has an isolator fitted, it is not necessary to apply special attention where there are more than32 devices. However no more than a maximum of 512 devices shall be installed on one control panel.
�A loop circuit must not cover more than 10,000m2 of floor area of a protected site.
A spur circuit must always be taken from the line common terminals of a 3-way loop device.
A spur should not cover more than the equivalent of one zone as defined in BS5839 : Part 1.
17
SENTRI4 - EN54 system
L2
02
Sounder & Strobe device(2-way)
01
L1
L1
01
L2
02
02
L2
01
L1
++
+
+L1
L2
0 V
L1
0V
Manual call point
L2
0V
PANEL
2 - way device
Earth tometal box
Terminal Card
LOOP CIRCUIT 1
Note: The 0V terminalsin the terminal plateare electricallyconnected together.
L1 0V L2 0V
LOOP n
IN4OUT5
C3
SenTRIdevice
IN4OUT5
C3
SenTRIdevice
Sounder & Strobe device(2-way)
Master alarm circuits
The control panel operates the master alarm circuits in the event of a firein the system. The two master alarm circuits accept the connection ofconventional alarm sounders including the conventional Sounder-Strobeproducts.
Auxiliary relay circuits
The control panel operates the auxiliary contacts when the configuredevent is received from the system. The auxiliary relays 1 and 2 contactscan be used to control external equipment, such as an automatic diallerthat makes the call for fire fighting action. The relays can be individuallyre-configured to operate with either fire, fault or disablement event in thesystem. The relay operation can also be delayed by up to 10 minutesand can be set up to operate in a normally energised or de-energisedstate. The contacts should be powered from an independent powersupply.
Clean contacts
The control panel will operate the clean contacts when a fire event isreceived from the system. The clean contacts can be used to switchplant equipment, such as lift control system. The relay operates in theevent of a fire. The contacts should be powered from an independentpower supply.
18
Installation instructions
P5
MA2 - FS1 1A
MA1 - FS2 1A
MA1+ MA1- MA2+ MA2-
Terminal card
PANEL
22K Ohms - End-of-line resistorfitted in the last alarm sounder
Conventionalalarm sounders
MASTER ALARMS
PANEL
Factory default:Aux relay 1 is normally de-energised and operates with afire event without delay.Aux relay 2 is normally energised and de-energises with afault event without delay.
Note: Aux relay 2 has been shown in the above diagram inits de-energised state, which is the state when there isno power to the panel.
NC C NO NC C NO
P7
AUXILIARYRELAY 1
Change over contacts rated 1A @ 24Vdc,to control external equipment
NC C NO NC C NO
P8
Terminal CardAUXILIARYRELAY 2
PANEL
The clean contact relay isnormally de-energisedand operates with a fireevent without delay.
NC NOC
Terminal Card
P6
CLEANCONTACTS
Change over contactsrated 1A @ 24Vdc, tocontrol external equipment
RS232 / RS485 Communication
The control panel offers RS232 and RS485 communication via the IOcard.
A standard IO card (not supplied) must be inserted in slot P2 of thebackplane of the panel, which facilate RS232 and RS485 communicationvia terminal block P4 onTerminal card. Note the RS232 is PORT 0 andRS485 is PORT 1. The domain address and communication baud rateare configured by setting the DIL switch located on the left edge of theDisplay Keyboard card.
Connecting a Remote printer
When a remote printer is connected to a standalone control panel, it willprint local system events.
� An IO card (not supplied) must be inserted in slot 2 ofthe backplane of the panel, which will facilate remote printerfunctionality.
On completion of wiring installation
On completion of all wiring refit the temporary cover ontothe back box. All outstanding work is done by the servicingorganisation during commissioning.
19
SENTRI4 -EN54 System
PANEL
Terminals for IO cardin slot P2 of the backplane
NETWORK CARD IN SLOT P80V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/C
IO CARD IN SLOT P8A 5V B 0V CTS Rx RTS TX
Terminal card
PANEL
Backplane
MCC / LCC - P1
LOOP or RS232 - P3
I/O or N/W - P2
LOOP or RS232 - P4
LOOP or RS232 - P5
LOOP or RS232 - P6
LOOP or RS232 - P7
- P8LOOP, N/W or I/O
IO card
IO or Network option
PB1 PB2
IO (RS232) CARD IN SLOT P7N/C 0V CTS RX RTS TX
IO card option
RS485A 5V B 0V
RS232Tx CTS Rx RTS
P4
PORT 1 PORT 0
25-way D-type connector
GN
DG
ND
TxTx
Rx
Rx
PANEL / NODE
TxCTS RxRTS
Terminals for
in slot P2 of the backplane
If the
is installed in a spare sloton the backplane then use
the corresponding terminals
IO card configured forRemote printer
IO card to which aremote printer is connected
RS232
Terminal card
P4
A 5V B 0V
RS485
Remote Printer(Serial printer)
Zonal Mimic panel
A A3 Zonal Mimic panel must be connected to a loop circuit of the firedetection and alarm system. It is used to provide indication of fire eventsin the system. However it can also be used to provide indication of faultand supervisory events in the system. The panel can be mounted inlandscape or portrait orientation.
The Zonal Mimic provides a traditional zone by zone indication of a fire.Each zone is given a location label to identify the area within a building.
The panel has its own mains derived power supply with battery forstandby power in the event of mains supply failure.
Technical Data
Panel dimensions height 403mm, width 338mm,depth 101mm
Weight 7.9Kg without batteries10.5Kg with batteries
Storagetemperature
-10 to 55ºC
Operatingtemperature
0 to 45ºC
Relative humidity(Non condensing)
Up to 90% temperature5 - 45°C
Battery 2 x 6V 7Ah sealed lead acid
(weight 1.3Kg each)The integral battery provides power for72 hours in standby condition and afurther 30 minutes in alarm.
Mains operatingvoltage
230V 50Hz +10% -6%
Emission BS EN61000-6-3 : 2001
Immunity BS EN50130-4 : 1996 : Part 4
LVD BS EN 60950-2006
Ingressprotection
IP30 (estimated)
Colour Door - Pantone 422Back box - Graphite Grey
(RAL 7024)
Control Cancel fault buzzer / lamp test button
Indicators 1536 high intensity RED LEDs.
Loop connection 3-way connection to a loop circuit
Typical Mimic illuminations
20
Installation instructions
Flashing in phaseor anti phase
Customised Mimic Zonal Mimic
ZONE n
Zone in fire- steady indication
Latest zone in fire- flashing indication
Compatibility
As a Zonal Mimic panel the system control panel must have thefollowing card software:
Control panel CARDEN54 Control Panel
software
LPC
Shorter Card ONLY
� V4.19
� means equal to or greater than
Installation
Fuses on Master Repeat Card
Fuses Rating
FS4 3.15A AB Ceramic 20mm x 5mm
FS2 3.15A AB Ceramic 20mm x 5mm
FS3 2A QB 20mm x 5mm
The Mimic Panel set consists of:
Component Quantity
� Backbox assembly
1
� Inner door assembly
1
� Outer cover assembly
1
� Key for Outer cover1
� 3.15A 20mm x 5mm AB Ceramic2
� 2A 20mm x 5mm Quick Blow Fuse1
� Battery lead
1
Link lead1
6V 7Ah Battery
2
� Overlay pack for A3 Mimicpanel
1 x pre-printed Zonal sheet
2 x blank A3 sheets for printinga Mimic or Zonal overlay
1 x LED spacing sheet
The overlays in the pack are highquality UV protected A3 paper.
A magnetic strip used to hold an overlayin place is fitted to the top side of theinner door.
1 Set
Mounting the backbox
The standard A3 Zonal mimic panel must only be mounted landscapewhen using the overlay supplied.a. Locate the package Back box assembly�.
Portrait orientation
b. Knock out the required cable entry points from the backbox.
c. Mark out the 4-back box fixing positions on the wall towhich the panel is to be mounted and secure it withsuitable fixings.
� Ensure the mains power is isolated to from thepanel.
d. Terminate the loop and mains cables at the entrypoints and if required connect the cables to theappropriate terminals.
e. All the other parts are installed during commissioning.
21
SENTRI4 -EN54 System
Back box
Top cable entry points5-off Back5-off Top
Earth points4-off
380mm
24
0m
m
SENTRI FIRE SYSTEM
NOT YET IN SERVICE
AWAITING COMMISSIONING
SENTRI FIRE SYSTEM
NOT YET IN SERVICE
AWAITING COMMISSIONING
External wiring
The external cables are routed into the back box using the cable entry points on the back box. The left 4 entry points are for the loop cables thatconnects to terminal block P16. The right cable entry point is for the mains cable which is connects to the terminal block P9.
� All the other parts supplied with the A3 zonal mimic panel are fitted during the commissioning stage, however theprocedures are described here for completeness.
How to fit the inner door assembly
The following procedures describe how to fit the inner door assembly to the backbox.
Align the inner door assembly� to the two hinge pin positions� on the back box� and slide the door down until it is seated correctly. Insert the
top (removable) hinge pin and secure it by rotating the pin into the back box. Close the inner door assembly� and lock it using the fastners at
position�. For minor adjustment of the inner door, open the fixing screw� and adjust the hinge plate� to a required position and then secure
the plate to the backbox by tightening the screw�.
22
Installation instructions
Inner door assembly
Hinge pin
Back boxassembly
Magnetic strip
Adjustable Hinge Plates
P9
L N
FS4
3.15A(T)mains fuse
01 L1 02 L20C LC
P16
Loop IN
Loop OUTFrom
Mains fused spur
Loop COM
Master Repeat Card01 L1 02 L20C LC P9L NN
P17
DANGERWRITE PROTECT
L N
FS4P16
P4
RESET
Where to connect the internal cables
Remove the protective cardboard cover from the Master Repeat Card. Connect the earth lead� from the back box to the inner door assembly.
Connect the flat flexible cable to socket P13 on the Master Repeat Card , see details on fitting and remove of flat flexible cable.
How to fit the outer cover
Hook� the Outer Cover� over the top edge of the Back Box�. Close� the bottom of the Outer Cover onto the Back box and secure the
Outer Cover by the two captive screws on the cover using the key supplied.
Ensure the zonal mimic plan is located centrally within the anti glare window of the outer cover.
For full information see the leaflet supplied with the product.
23
SENTRI4 - EN54 system
A
A
Outer Cover
Back box
Inner door
Back box
Fit earth leadfrom back boxto inner door
Connect the flatflexible cable frominner door to MRC
Master Repeat Card (MRC)
Repeat Panel(loop connectable)
The repeat panel duplicates all of the control panel indications and theessential controls.
The repeat panel has its own mains derived power supply with battery forstandby power in the event of mains supply failure. A lockable front doorprevents unauthorised access to fire alarm controls but allows all of theindicators to be seen. The panel is designed for semi-flush or surfacemounting and facilitates both rear and top cable entry points.
This repeat panel can be installed on a loop circuit of the SenTRI 4 firedetection and alarm system. It can be sited near an entry or exit point ofa building and fit in with the loop cable routing.
Compatibility
The repeat panel is compatible with system control panel having cardand software listed below:
Control panelCARD
Control Panel Software
EN54
LPCShorter Card
ONLY
� V4.19
� means equal to or greater than
Technical Data
Panel dimensions height 403mm, width 338mm,depth 101mm
Weight 9Kg with batteries (approximate)
Storagetemperature
-10 to 55ºC
Operatingtemperature
0 to 45ºC
Relative humidity(Non condensing)
Up to 90% temperature5 to 45°C
Battery 12V 7Ah sealed lead acid
Mains operatingvoltage
230V +10% -6% 50Hz
Emission BS EN61000-6-3 : 2001
Immunity BS EN50130-4 : 1996 : Part 4
LVD BS EN 60950-2006
Ingress protection IP31 (estimated)
Colour Door - Pantone 422Back box - Graphite Grey(RAL 7024)
Controls(with door closed)
Access level 1
Next and Previous buttonsoperable during fire conditiononly.
Control buttons(with door open)
Access level 2
Sound Alarms, Silence Alarms,Reset Fire, Cancel Fault Buzzer,Verify, F1-F4, Menu On/Off andU1-U4.
Indicators Fire, Verify, Power, Fault, PowerFault, System Fault, Delay andCB253/254.EN panel only: Sounder, Delay,Disablement Test and 32-FireZone LEDs.Display: 8 lines 40 charactersper line, back-lit LCD.
Loop connection 3-way connection to loop circuit
EN54-17 dataFire detection andfire alarm systemshort circuit isolators
Vmax 42V Vnom 40V
Vmin 24V VSO max 16V
VSO min 8V IC max 0.4A
IS max 1A IL max 20�A
ZC max 0.1�
24
Installation instructions
SenTRI Fire System
Panel healthy15:45
EN54 Parts 2 & 4: 1997
Installation
The Repeat Panel Set consists of:
Parts Quantity
� Backbox assembly 1
� Outer door assembly 1
� Inner door assembly 1
� 20 Way ribbon cable 1
� 40 Way ribbon cable 1
� Spares pack (includes battery leads) 1
Battery 12V 7Ahr 1
Fuses on the Master Repeat Card
Fuse Rating
FS4 3.15A AS 20mm x 5mm
FS2 3.15A AS 20mm x 5mm
FS3 2A QB 20mm x 5mm
Back box mounting
a. Find the Repeat panel Back box � package andremove the temporary cover.
b. Secure the back box to the wall with suitable fixings. Ifthe backbox is to be semi-flushed then use the optionalsemi-flush surround.
c. Terminate the cable at the entry point leaving 400mmtail wire length.
� If mains supply cable ends are not required to beconnected then ensure the ends are insulated for safety.
d. Refit the temporary cover to protect the panel until allbuilding work is complete.
Doors, Cables and Power up
The doors and cables can be installed after the building work hasfinished.a. Remove the protective cover from the backbox.
b. Fit the inner door� to the panel enclosureremembering to connect the earth lead from thebackbox to the inner door. Fit the outer moulded door
� to the backbox.
c. Wiring the panel:
� Ensure the mains supply is completely powereddown before wiring the mains cable ends.
• connect the mains cable to terminal block P9 on theMaster Repeat Card.
• fit battery lead� supplied in the spares to connector P5on Master Repeat Card.
• connect the loop cables to terminal block P16 on theMaster Repeat Card.
• connect the 40 way ribbon cable� to the Master RepeatCard connector P2 and the other end to Display Key Cardon the top right edge connector - P1.
• connect the 20 way ribbon cable� to the Master RepeatCard connector P1 and the other end to Display Key Cardon the top right edge connector - P6.
d. Power-up is done during commissioning by the serviceorganisation and it involves switching ON the mainssupply and connection of battery leads. Power upindications are:
• all the LEDs on the panel are lit for a short duration and apower up message displayed.
• the local buzzer sounds
• the display reads: Main panel is off Line
• the Fault and System Fault LEDs are lit.
25
SENTRI4 -EN54 System
cL
310mm
115mm115mm
37
0m
m
28
5m
m
45
mm
Floor level
1.6
5m
Cable entry points
4-off - Back and 4-off - Top3-off
Earth points
BackboxFixing centres
4-off
01 L1 02 L20C LC P9L N
P17
DANGER
BT
+B
T-
+RS485
0V 24V-
WRITE PROTECT
BUZZERDISABLE
P8
DANGERDO NOTREMOVE
L N
P5
FS2
FS4P16
P4
P2
P1
SW3
PB2
WD1P14P7USB
FS32A(QB)
RESET
DANGER
WARNINGRemoval of
cover exposeslive parts.
Repeat Panel
Cross section ofthe wall to whichthe panel is to besemi-flush mounted
5mm diameterfixing holes
ApertureHeight:380mm
Aperture Width: 320mm
Aperture depth should not be less than: 59mmRepeat panelsemi-flush surround
26
Installation instructions
40-wayribbonto DKC
12V 7Ah battery
Earth toInner door
3.15A(T)mains fuse
01 L1 02 L20C LC
P16 P9
L N
20-wayribbonto DKC
Red
Black
Inner and outerdoors not shown
Loop IN Loop OUT From Mains fused spur
FS4
3.15A(T)mains fuse
FS2
3.15A(T)Ceramic
(Anti Surge)
Battery Fuse
Loop COM
Master Repeat Card01 L1 02 L20C LC P9L NN
P17
DANGER
BT
+B
T-
+RS485
0V 24V-
WRITE PROTECT
BUZZERDISABLE
P8
DANGERDO NOTREMOVE
L N
P5
FS2
FS4P16
P4
P2
P1
SW3
PB2
WD1P14P7USB
FS32A(QB)
RESET
DANGER
WARNINGRemoval of
cover exposeslive parts.
mains electricalsupply
Loop OUT
Previous Next
Spur Connection
SenTRI Fire Alarm SystemDesigned to EN54 Pt 2 & 4
Panel healthy 15:45
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1617 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
Fault
System Fault
Delay
Test
Fire
Power
Power Fault Verify
Disablement
Sounder
Loop IN
Repeat panel
CB1
CB2
Repeat Indicator panelThe repeat indicator panel provides messages and indications of systemevents and it connects directly to the SenTRI 4 fire panel.
Technical data
Dimensions in mm height 177 x width 206 xdepth 48.5
Full assembly weight 750g
Storage temperature 0 to 60ºC
Operatingtemperature
0 to 45ºC
Relative humidity(Non condensing)
up to 90%Temperature 5 to 45°C
Ingress protection IP30 estimated
Colour White
Indicators Fire, Fault, Disablement,Power On, System fault,Sounder2 line 20 character per line,back-lit, display.
Controls(with flap closed)
Test and Cancel buzzer
Controls(with flap open)
Fire, Fault, Disablement,Warning, Display Mode andNumeric keypad.
� If only one repeat indicator panel is to be connectedto the control panel then make use of the 24V supply at thepanel, there is no need to use an external power supply
� Belden No. 9842 EIA RS485 Applications, O/A Beldfoil®Braid 1Km maximum cable distance from the control
panel to the last repeat indicator panel must have followingcharacteristics:
• Two twisted pairs
• 24AWG (7 strands x 32 AWG) conductors
Installation
a. Open the outer cover.
b. Insert the external cable into the backbox assembly atthe required entry point.
c. Mark the fixing points and secure the backbox to thewall.
d. Connect the cable to terminals.
e. Refit the front cover and flap.
27
SENTRI4 -EN54 System
1 2 3
4 5 6
7 8 9
0
+
RE
L
-
24
V
ab
RS
48
5
ON
1 2 3 4 5 6 7 8
J6 J5 J7
Back cable entry pointThinned sectionson sides of enclosure forcable entry 4 enclosure fixing points
PANEL
TERMINAL CARD
Terminals P4 is PORT 1
REPEAT INDICATOR PANEL 1
a
bRS485
earth
REPEAT INDICATOR PANEL 4
-
+24V
a
bRS485
earth
UP TO 4 REPEAT INDICATORPANELS MAXIMUM
POWERSUPPLY UNIT
+ -
-
+24V
24V
P4RS485
A 5V B 0V
SenTRI Sensors
This following is information on the SenTRIproduct range. The SenTRI product integratesdual angle smoke, heat and carbon monoxidegas detection with electronic sounder, speechand LED flasher (Strobe) in one assembly.
General specification
Operating voltage 35V - 41V
Weight 110g
with base - 170g
Dimensions 117mm diameter by 49.6mmheight
With base the heightincreases to 63.8mm
IP rating IP30IP20 when mounted on ametal back box
Enclosure ABS
Colour RAL 9010
Approval LPCB approved
Storage Temperature -20�C to 70�C
Ambient operatingtemperature
-10�C to 50�C
Relative Humidity 95% non condensing(5°C to 45°C)
Heat (H) Standard EN54 : Part 5
Optical (O) Standard EN54 : Part 7
Sounder (S) Standard EN54 : Part 3
Multi sensor standard CEA 4021
Information on minimum sound output levels to include polar dispersionis covered in a technical note TECH7018.033, available on request frommanufacturer.
Base
The base has terminals for external cables to allow it to be electricallyconnected to the panel loop circuit and to the monitored input or outputcircuit. Any SenTRI device can be plugged into an SenTRI base.
Base Gasket
The optional foam rubber base gasket S4-BASE-GASKET can be fittedto the base to prevent water damage from dripping water from theceiling.
Base labels
An optional label SEN-BASE-LABEL can be fitted to the base. The labelcan be marked up with device location information.
Indicators
The SenTRI has a red LED that gives an indication in the event of a fire.The LED can be configured to flash periodically, as an 'in operation'confirmation, this indication is given system-wide at all SenTRI device.
Dust Cover
A dust cover is supplied with the SenTRI, to prevent dust from buildingwork contaminating the sensor. The cover is removed prior to thecommissioning of the fire alarm system.
Do's and Don't
�DO NOT locate smoke detectors where products ofcombustion may be present such as kitchens, garages,furnace rooms, welding shops etc.
DO NOT locate heat detectors above boilers or heaters orwhere the temperature is normally very high or liable tosudden fluctuations.
DO NOT locate smoke or heat detectors: -• In dusty or dirty environment.• Near heating or air-conditioning grilles.• Outdoors in stables, sheds etc.• In excessively damp areas.• In dead air spaces at the junctions of
ceilings and walls.• At ceiling locations where a ‘thermal
barrier' may exist.Follow recommendations detailed in section 22of BS5839 : Part 1 : 2002.
Siting
A SenTRI device plugs into a dedicated Base that is installed in theprotected premises. The Bases should be sited in locations as defined bythe project plans and by BS5839 : Part 1 : 2002.
28
Installation instructions
Metal back box
A metal back box must be used for base or semi-flush mounting. Theearth continuity must be maintained throughout the whole loop. The earthmust be securely connected to the back box.
In - Out wiring to SenTRI bases
Programmable input/output
All SenTRI devices can be configured as either monitored input orunmonitored output. The factory setting of the programmable input /output is unmonitored output, to drive an external repeat LED without aseries resistor. There is a maximum cable length limit of 15 metres fromthe SenTRI base to the external I/O Unit.
The input can accept signals such as fire, non fire or fault, these areconfigured during commissioning. As a fire input it is possible to connecta conventional Manual Call Point (non UK application only) with a seriesresistor of value 470 Ohms coupled with an end-of-line 10Kohmsresistor. In this case the fire input is fully monitored for open or shortcircuit faults.
The input can be setup as a non-fire or fault input using a similararrangement with series and parallel resistors as shown. It is possible forsuch an input to trigger a command that is configured to action an outputelsewhere in the system to control plant equipment such as theventilation system.
29
SENTRI4 -EN54 System
EM2OUT5
IN4C3
L10V
L2
+
-
+ -
Unmonitored LED output
+ -
Remote LED unitSEN-LED
+-+-
+-+-
EM2OUT5
IN4C3
L10V
L2
47
0�
10
K�
InputBeam Transmitter base
FIRE
keyswitch
O
I
Active
O
I
Normal
O
I
EM2OUT5
IN4C3
EM2OUT5
IN4C3
L10V
L2
L1
0V
L2
LOOP CABLE
STANDARD 60mm METAL BACK BOX
CABLE GLAND
LOOP CABLE
BASECEILING TILE
2 SCREWS TO SECUREBASE TO METAL BACK BOX
CROSS SECTIONOF CEILING TILE
Tools for SenTRI devices
An extractor tool allows removal and fitting of the SenTRI device headinto the base. By fitting a screw-on adaptor, the tool can be used toremove the sensor dust cover.
To remove a SenTRI device
Fit the tool onto the SenTRI device. Turn SenTRI device anticlockwiseuntil it stops and remove the SenTRI device from the base.
To fit a SenTRI device
Fit the SenTRI device on to the tool. Offer SenTRI device to base androtate clockwise until it moves upwards on to the base and rotate it againuntil it clicks and goes no further, the lines on the base and SenTRIdevice will align.
To fit a dust cover
Place the dust cover onto the tool inside the cradle. Offer the cover to theSenTRI device, locate and push to fit it onto the assembly. Withdraw thetool when the dust cover is in place.
To remove a dust cover
A dust cover remover tool must be fitted to the main tool to extract thedust cover. Press the pad of the dust cover remover tool onto the dustcover, this creates an air tight grip, to allow the cover to be pulled offfrom the SenTRI device.
30
Installation instructions
Base
SenTRI device
Tool
Tool
Dust cover
Tool
Dust coverremover tool
Dust cover
SenTRI device
Tool
SenTRI device Semi-flushfixing kit (SEN-FLUSH)An SenTRI device can be semi-flush mounted to a ceiling tile to a depthof the approximate 20mm, which is slightly deeper than the baseassembly. To semi-flush mount a special housing must be used, whichconsists of a main assembly and a trim ring.
� There is an enhanced volume output of sound from asemi flush mounted SenTRI device.
Technical data
Weight 164g with trim ring
Dimensions 174mm diameter by 50mm depth
Enclosure ABS
Colour RAL 9010
StorageTemperature
-20�C to 70�C
Ambienttemperature
-10�C to 50�C
Relative Humidity 95% non condensing(5 to 45°C)
31
SENTRI4 -EN54 System
SenTRI device
Trim ring
Cross sectionof Ceiling Tile
Semi-Flush shroud
SenTRI Base
Do not over tighten the clampingscrews as this will cause theclamps to cut into the ceiling tile.
Metal back box
Cut a 140mmdiameter hole in theceiling tile.(
)
If required use a Bi-Metal Holesaw140mm or 146mm, fromwww.shop4tools.co.uk
Insert the semi-flush shroudassembly into the holein the ceiling tile.
Hold the semi-flush shroudto the ceiling tile and tightenthe three screws to splay theclamps to secure the shroud to the tile.
Locate the SenTRI Base intothe semi-flush shroud, such that thetwo locating pillars on theshroud feeds through the twoelongated holes on the Base.Push the Base into the shrouduntil the Base click locks intothe shroud.
Offer the trim ring to the shroudand slowly rotate ring clockwise until itclicks and goes no further. This willlock the ring in position.
Fit the metal box onto the backof the semi-flush shroud using theappropriate fixing screws to securethe box to the flush shroud.
Offer the SenTRI device to the Baseand rotate the SenTRI deviceclockwise until it moves upwards intoBase, and then rotate the SenTRIdevice again until it clicks and goes no further.
Make the cable connections.
Clamp
Beam Sensor
Transmitter (red retainer) Receiver (black retainer)
� Beam sensor pair(Transmitter & Receiver)
� Beam Transmitter only
� Beam Receiver only
� Angle bracket with base
� Parallel bracket with base
� Light Shield (5 per pack) Test Cards
The Beam Sensor pair allows the detection of smoke over distances from2 m to 100 m, using a 'beam transmitter' and a 'beam receiver', eachmounted on a base fixed to either bracket.
Technical Data
Standards -designed to meet
EN54 : Part 12 : 2002EN54 : Part 17 : 2005
Approval LPCB Approval pendingSTATES 0, 1, 2 and 3
Overallassembleddimensions in mm
Transmitter or receiver:
� 117 x d 54Angle bracket with base:h 145 x w 106 x d 130Parallel bracket with base:
� 152 x d 27
Light shield: � 50 x 75
Assembled weight(approximate)
Transmitter or receiver:105gAngle bracket + base: 620gParallel bracket + base: 600gLight shield: 14g
Enclosure ABS
Colour (Sensor) RAL9010
Storagetemperature
-20 to 70ºC
Ambient operatingtemperature
-10 to 50°C
Relative Humidity(Non condensing)
up to 95%
Temperature 5 - 45°C
Emission BS EN61000-6-3: 2007 EMC forresidential, commercial & lightIndustry.
Immunity BS EN50130-4: 1996 + A1:1998 +A22003for alarm systems
Ingress Protection(estimated)
IP30IP20 mounted on bracket
Operating voltage 35-41V
Indicators Two Red and Seven Green LEDsvisible at 500LUX ambient light levels5m
EN54-17 : 2005(section 4.8)data:
Vmax 42V IC max 0.4A
Vnom 40V IS max 1A
Vmin 24V IL max 20�A
VSO max 16V VSO min 8V
ZC max 0.130�
Compatible PANEL: Main Controller � V4.41
LPC � V4.39
32
Installation instructions
Base
Sleeve
Do's and Dont's
A general guidance on Do's and Dont's is illustrated here, however for full information on siting beam sensor pair refer to BS5839 Part 1.
33
SENTRI4 - EN54 system
IR Beam(invisible)
Solid Wall
Floor level
IR Beam projection
Solid Walls
Plan view (flat ceiling)
Receiver
Receiver
Transmitter
Transmitter
Transmitter Receiver
Shelves and Storage boxes
Solid Wall
Floor level
Ceiling
Building structure support
Solid Wall
Floor level
Ceiling Ventilation duct
0.3m - 0.6m
15m
> 0.15m
Metal Ceiling
Unistrut
25m maximum
15m
2m to 100m maximum
1m minimum7m maximum
Solid Walls
Plan view (flat ceiling)
Receiver
Receiver Transmitter
Transmitter
15m
3m max.
> 0.5m
ReceiverTransmitter
ReceiverTransmitter
ReceiverTransmitter
Metal beam
Solid Wall
2.5 m
17.5 m width
17.5 m width covered by one beam sensor pair within 600mmvertical of the apex, using the extra coverage of 25% givenby the roof angle of 25
o
25o
1.25 m
10
mm
ou
ntin
gh
eig
ht
20
m
600mm
Calculated from12.5% of 10mmounting height
Seven beam sensorpair requiredat this height
2.5 m calculated fromtwice 12.5% of 10mmounting height
ATRIUM
Side view (flat ceiling)
Obstructions
Cladding panels / Plaster board
Transmitter
Transmitter
Receiver
Glass Atrium
Heat Source
Receiver
Horizon
Sunlight or Strong light source
Horizon
Sunlight or Strong light source
Test Keyswitch
A test keyswitch unit can be connected to the 'beam transmitter' to facilitate simulation of a test fire condition. The keyswitch unit is required to have
a series resistor of value 470� coupled with an end-of-line 10K� resistor wired as illustrated below.
There is a maximum cable length limit of 15 metres fromthe 'beam transmitter' base to the external KeyswitchUnit.
A keyswitch input at the 'beam transmitter' must beenabled during commissioning.
The wiring is monitored for open and short circuit failure.
On operating the keyswitch it will cause a ramp downsignal to generate a test fire condition.
How to install an Angle bracket and fit a Beam sensor
The installation of the angle bracket and beam sensor are illustrated by steps� to �. Note steps� and� require setting of adjusters forsensor to face the opposite sensor assembly, which is normally done during commissioning.
34
Installation instructions
EM2OUT5
IN4C3
L10V
L2
47
0�
10
K�
InputBeam Transmitter base
FIRE
keyswitch
O
I
Active
O
I
Normal
O
I
L1
0V L2 0V
L1
(1)
0V
(4)
0V
(2)
L2
(3)
EA
RT
H(5
)
The numbers in bracketsrefer to alternative cablesleeve markings which maybe used to denote wires.
Metal box
Earth
Cable from the sensor base
Loop - In cable Loop - Out cable
Angle bracket with base
Metal boxmounted ona solid wall
Beam Sensor
Keyswitch wiring if used
The Test Keyswitchconnects to terminalsEM2 and C3 in thebase.
How to pre-assemble the parallel bracket
The parallel bracket may be pre-assembled as illustrated by steps� to�.
How to install a Parallel Bracket and fit a Beam sensor
The installation of the parallel bracket and beam sensor are illustrated by steps� to�.
For full instructions see the leaflet supplied with the panel.
35
SENTRI4 - EN54 system
THIS WAY UP
Pre-assembledParallel bracket
Metalbox
Beam SensorBase
EM2OUT5
IN4C3
L10V
L2
LOOP IN
LOOP OUT
Loop CableIn - Out
Test Keyswitch wiring if used
The Test Keyswitchconnects to EM2 andC3.
SleeveEnsure the base is mounted to the bracket suchthat the Beam sensor LEDs can be seen from floor level.
ARROW
Fixed plate
Adjustable plate
Adjuster
Bush
Lock nut
Bush
Spring
8m
m
8m
m
Ensure the adjusters are set to provide an 8mmgap all around between the adjustable and fixed plates.
Duct kit
The air duct kit is used in combination with different Venturi tubes andspecial fire sensor for the surveillance of air ducts in buildings.
The kit is fastened to the outside of the air duct. The Venturi tube is leadinto the duct through a hole drilled for this purpose. The air streamingthrough the air duct is picked up by the Venturi tube and led via thedeflecting unit inside the housing directly to the detector for subsequentevaluation.
The inserted fire detector is directly connected to the analog loop of theFire Alarm System. The operation and indication of alarm and faultmessages is given at the connected fire alarm panel.
Venturi tubeThe Venturi tubes are available in various lengths.
Length (mm) 600 1500 2800
Weight 0.2Kg 0.6Kg 1.2Kg
Technical date
Fire Sensor and base
Operating voltage 35V - 41V
Weight Sensor only: 88g(with base - 148g)
Dimensions 117mm diameter by 49.6mm height(With base the height increases to63.8mm)
Enclosure ABS
Colour RAL 9010
StorageTemperature
-20�C to 70�C
Ambient operatingtemperature
-10�C to 50�C
Relative Humidity 95% non condensing(5°C to 45°C)
Optical Sensor (O)Standard
EN54 : Part 7 : 2000
EN54-18 : 2005
EN54-17 : 2005(section 4.8)data:
Vmax 42V IC max 0.4AVnom 40V IS max 1A
Vmin 24V IL max 20�A
VSO max 16V ZC max 0.1�VSO min 8V
Housing
Dimensions(W x H x D) in mm
180 x 235 x 183
Terminals 1.5 mm² max.
Air velocity 1 m/s to 20 m/s
Full Assemblyweight
Approx. 800g(without sensor & base)
Storagetemperature
-15 °C to +65 °C
Operatingtemperature
-10 °C to +60 °C
Housing ABS plastic
Colour grey (with transparent cover)
Immunity BS EN50130-4: 1996: Part 4Alarm systems
Ingress Protection IP54
Colour White
For full instructions see the leaflet supplied with the product.
36
Installation instructions
SenTRI Sounder StrobeThe low power addressable Sounder and Strobe products provideaudible and visual alarm signals, and are designed for use in SMSanalogue and addressable fire alarm systems.
The SenTRI devices are supplied with standard sounder and strobeoption. The devices are configured during commissioning to operate tosite specific requirements. The devices are supplied with either a deepbase (40mm) or a shallow base (25mm), offering IP55C and IP31Cratings respectively, with the exception of the system range (seediagram below) which is available with deep base only.
These SenTRI product range incorporates innovative design features
protected by Patents GB2388994, GB2388995 and GB2388916. The product
design has also been registered.
� If you have a sounder only product then ignore thestrobe information given.
� The addressable SenTRI products are fullysynchronised on the same fire panel.
Technical data
Sound output for standardtone (levels given aretypical values with
measurement taken at 90�anechoic - fast response)
Low profile - 100dBA +/-3dBA
System - 103dBA+/-3dBA
Standard (sounder only) EN54 : Part 3
Messages, Tones andStrobe flash rate
see instructions supplied withthe product
Strobe light output withred lens
equivalent to 3W Xenonflasher
Operating voltage range 35V to 41V
Terminal size 2.5mm2
maximum
IP rating with deep base
with shallow base
IP55C
IP31C
Enclosure colour White and Red (with redtranslucent lens cover fitted tounit with Strobe).
Enclosure material Flame retardant ABS (Strobecover is polycarbonate) Theplastic enclosures meet theflammability requirements ofISO 1210:1992 Class FH-2.
Weight 0.3Kg (approximate).
Operating temperature -10�C to 50�C
Storage temperature -20�C to 70�C
Relative humidity(non condensing)
up to 90%
IR operating distance(to select volume level)
3m
37
SENTRI4 -EN54 System
Low profile devices System devices
Available in deep or shallow base Available in deepbase only
40
112
90
60
25
75
75
112
with shallow base
35
with deep base
with deep base
120 DIA
Installation
a. Drill or knockout the required cable entry points on thebase.
b. If using the deep base option and IP55C protection isrequired, then stick the circular wall gasket on to thecentre back of the base.
c. Secure the base to the wall whilst ensuring Top of thebase is in correct orientation.
d. Terminate the cable at the entry point leaving no morethan 10cm (4") tail wire length for connection.
e. Ensure the transparent cover is in place over thePCB. Connect the wires to the terminal block.
f. Close the main assembly to the base.
Retrofitting a System SenTRI deviceA system SenTRI Mark I device can be retrofitted to an alarm sounderbase. The existing base having a terminal block to which loop cables areconnected.
38
Installation instructions
LC
0C
L1
01
L2
02
LC
0C
L1
01
main assembly
L2
02
base
Sounder Strobe device (3-way)
red
black
red
black
red
black
Loop INLoop OUT
COMMON LINEto Spur
Ensure the terminal blockis placed inside the back of the base
112
50
60
35
25mm depth
40mm depth
Shallow base
Deep base
Top
Top
Cable entry1- Back
112
BaseGasket
Thinned sectionfor IR receiver
Thinned sectionfor IR receiver
EarthcontinuityStrap
Cable entry2 - Top1 - Bottom1 - Back
WallGasket
DO NOT FLUSHMOUNT THE BASE.
TOP
Infraredreceiver
Main assembly
# Locating pegsfor the transparent cover
#
#
PCB
Label
Transparentcover
Adhesive spot usedto secure the transparent cover
02
L2
0C
LC
01
L1
P16
P6
D4
Connector used to program the device(Programmable base required)
Adhesive spot usedto secure the transparent cover
02
L2
01
L1
Manual Call Points
Options
� Manual Call Point (Glass)
� Manual Call Point (Resettable element)
Glass or Resettable element options
Optional Back box
The optional back box has recessed centres 'D', 3 at the top and 1 at thebottom, a maximum of 2 are usable.
Technical data
Standard EN54: Part 11: 2001
Dimensions height 88 mm x width 88 mmdepth 21 mm or 57 mm whensurface mounted
Full assembly weight 110g - approximate
Storage temperature -30 to 70ºC
Operatingtemperature
-25 to 70°C
Relative Humidity(Non condensing)
up to 95%Temperature 25 to 55°C
Emission BS EN61000-6-3:2001 Residential,Commercial & Light Industry ClassB limits
Immunity BS EN50130-4: Part 4 :1996
Ingress Protection IP43 estimated standard type
IP55 estimated with protective coverand back box
Colour Red (similar to RAL3020)
Case ABS engineering plastic
Indicators
Normal
Active
Green LED for status and finddevice application
Red LED and Yellow tab for activeor Fire indication
Testing The operation of the MCP is testedby using a test key
Terminals 2.5mm2maximum
Approval LPCB ApprovedSEN-800 and SEN-805
Operating voltage 35V to 41V
Installation
a. Check the contents of the package:
Component Quantity
Call point assembly 1
Earth Strap 1
Test Key 1
Long Screw 2
b. The call point assembly may be mounted on astandard electrical box or on the optional red back boxSEN-895.
c. Feed the fire rated cables through the entry holes andmount an electrical box or the red optional back box toan even wall surface using suitable fixing.
� When semi flush fixing the call point assembly astandard electrical box must first be flushed into the wall beforethe call point assembly is fitted.
39
SENTRI4 -EN54 System
87
87
C
15
21RemovableTerminal block
A
Glass
Top
B
Resettable element
Top
36
THIS WAY UP
50
88
43,5
18,5
D
D
88
d. Terminate each cable entry at the back box. Use the earth strap or the earth point in the back box to maintain loopcable earth continuity. Connect the loop cable to the terminals.
e. Disengage front cover from the call point assembly using the end of the test key 'E' and lift out the cover from thebottom edge.
f. Secure the call point assembly to the back box using the 2 long screws supplied.
g. To re-assemble the glass or resettable element, using the test key turn the tab to position 'F' and insert the glass 'A'or optional resettable element 'B'.
h. Hook the front cover onto the top edge of the call point assembly and then push the bottom edge down until it clickshut. Check both hooks on the top of the front cover are locked onto the call point assembly.
i. Turn the test key anticlockwise to position 'G' (not visible) such that the glass or optional resettable element is heldunder the yellow arm.
40
Installation instructions
E
F G
1IN
2O
UT
4C
Manual Call Point
LoopIn
LoopIn
1IN
2O
UT
34C
Keyswitch
LoopOut
LoopOut
3
Keyswitch Interface / MCP
The keyswitch units covered in this leaflet are suitable for installation inSenTRI analogue addressable fire alarm system. The product rangecovered here include:
� Keyswitch MCP (Red)
� Keyswitch Interface (Blue)
� Spare Keys (Pack of 2)
� Surface Back Box for InterfaceRed Plastic (Pack of 10)
Keyswitch assembly
Back box
The back box has recessed centres 'D', 3 at the top and 1- at the bottom,a maximum of 2 are usable.
Technical data
Standard EN54: Part 17
EN54: Part 18
Dimensions height 88 mm x width 88 mmdepth 32mm or 66mm when surfacemounted
Full assembly weight 128g - without backbox192g - with backbox
Storage temperature -30 to 70ºC
Operatingtemperature
-25 to 70°C
Relative Humidity(Non condensing)Temperature25 - 55°C
up to 95%
Emission BS EN61000-6-3:2001 Residential,Commercial & Light IndustryClass B limits
Immunity BS EN50130-4: Part 4 :1996
Ingress Protection IP43 estimated standard type
Colour Red (similar to RAL3020)Blue (similar to RAL5015)
Case ABS engineering plastic
Indicators Normal
Active
Green LED for status and finddevice application
Red LED for active or Fire indication
Terminals 2.5mm2maximum
Operating voltage 35V to 41V
EN54-17 data Vmax 42V
Vnom 40V
Vmin 24V
VSO max16V
VSO min 8V
IC max 0.4A
IS max 1A
IL max 20�A
ZC max 0.1�
41
SENTRI4 -EN54 System
Red enclosurefor Fire applications(supplied with backbox)
Blue enclosurefor Plant interface applications(supplied with backbox)
I I
8815
32
RemovableTerminal block
O
I88
36
THIS WAY UP
50
88
43,5
18,5
D
D
88
Installation
a) Check the contents of the package:
Component Quantity
Keyswitch Interfaceassembly (red / blue)
1
Earth Strap 1
Operating Key 2
Opening Key 1
Long Screw 2
Instruction leaflet 1
Blue Back boxsupplied with Bluekeyswitch interfaceassembly
1
b) The keyswitch assembly may be mounted on astandard electrical box or on the backbox.
c) Feed the fire rated cables through the entry holes andmount an electrical box or the red/blue back box to aneven wall surface using suitable fixing.
� When semi flush fixing the keyswitch assembly astandard electrical box must first be flushed into the wall beforethe keyswitch assembly is fitted.
d) Terminate each cable entry at the back box. Use theearth strap or the earth point in the back box tomaintain loop cable earth continuity. Connect the loopcable to the terminals.
e) Disengage front cover from the keyswitch assemblyusing the end of the opening key 'E' and lift out thecover from the bottom edge.
f) Secure the keyswitch assembly to the back box usingthe 2 long screws supplied.
g) Hook the front cover onto the top edge of the keyswitchunit and then push the bottom edge down until it clickshut. Check both hooks on the top of the front coverare locked onto the keyswitch assembly.
Operation
To operate the keyswitch insert the operating key into the keyhole 'J' andturn clockwise to the stop position, the red LED 'K' is flashing. The greenLED 'I' gives an operating indication.
Apply the reverse procedure to return the keyswitch to a normaloperating position.
Label
When using the blue keyswitch interface to control plant ensure the unitis labelled to describe what is being controlled by the keyswitch.
It is suggested that an A4 sheet white paper label32 x 12mm is used, such as the one from RS, part number RS495 385.The required text can be printed onto the label. The label is stuckcentrally inside the aperture behind the transparent cover. Ensure LEDsremain visible and are not covered by the label.
42
Installation instructions
E
i
THIS WAY UP
1IN
2O
UT
4C
Manual Call Point
LoopIn
LoopIn
1IN
2O
UT
34C
Keyswitch
LoopOut
LoopOut
3
I JK
Normal
Active
O
I
O
I
O
I
DisableZone n
32 x 12mmstick on label
Transparent cover
These instructions cover the above interface modules and accessories.The SenTRI interface modules are designed for use with any SenTRI 4fire alarm control panel. Each module includes a loop isolator for deviceisolation. Each module use one of 200 available device addresses on aloop and responds to regular polls from the control panel reporting thetype of device and the status (open/normal/short) of its supervised inputcircuit(s).
Features
� Analogue addressable communications
� Built-in type identification automatically identifies thesedevices to the control panel
� Reliable communication technique with high noiseimmunity
� Soft or SAFE addressing
� Common mounting options including surface mount,panel mount and DIN rail mount
� Dual-colour LEDs
� Plug-in terminal connections for ease of wiring
� EN54-17:2005 and EN54-18:2005
Cables
The cables recommended for wiring the input / output lines are the sameas those used for loop wiring, see instructions supplied with the firecontrol panel.
Installation
The SenTRI interface modules can be mounted in other equipmenthousings using the DIN rail mount brackets. A module can also be fittedinto a plastic box or metal box. The boxes have cable termination pointson the enclosure.
43
SENTRI4 -EN54 System
SEN-INT-INPUT1-Input InterfaceModule(low voltage)
SEN-INT-OUTPUT1-Output &1-Input InterfaceModule (low voltage)
SEN-INT-4IO# 4-Input / OutputInterface Module(low voltage)
L1
L2
0V
0VC
ha
nn
el1
Ch
an
ne
l2
Ch
an
ne
l3
Ch
an
ne
l4
L1
L2
0V
0V
NCIn
pu
t
L1
L2
0V
0VIn
pu
t
CO
M
NO
Output
SEN-490Plastic box
1- End-of-lineCapacitor unit
2- 10K Resistors
2- 10K Resistors 1- End-of-lineCapacitor unit
8- 10K Resistors SEN-491DIN rail mountbracket# Now supplied fully assembled
1- Allen key 2 - M4 Screws
SEN-492Metal box
2 - M4 Posi Pan Screws7 - Hole plugs
FIRE ALARMINTERFACE
EQUIPMENT INTERFACED
Interface Modules for SenTRI - Low voltage (LV)Input/Output
Module
DIN rail mount bracket
Slide &lock
Hook and pushto lock
DIN rail
Connect to loopcable screen
Allenkey
Box
Module
M4 Screws
Door
64
10
6
62.5 62.5
3 - box fixing points(Includes 1-keyhole)
7 - top cableentry points
Module
M4 Screws
Lid
80
140
Metalbackbox
7 usable cable entry points
Wiring diagrams
� The loop cable screen must be continued through each interface module. The loop, switch input, zone input andLED output cable screens where used must connect to an earth terminal.
44
Installation instructions
1-Output & 1-input moduleconnection details
Note 2 - Only channel 1 (terminals 5 & 6) can beconfigured as an zone input.
Note 3 - Contact rating 1A 30V ac/dc Resistive load.
Note 4 - Output is 1.5mA @ 24V dc.
Note 1 - When the input is configured as a Zone inputit is possible to attach conventional detectorsand MCPs (with 470 Ohms or 3V9 zenerdiode in series with normally open contacts),maximum load is 2mA @ 24V nominal(18V minimum) with End-of-line capacitor.
# Can be configured as LED output
The cable screens must be connected to anon the chassis or in the metal box.
If a module is mounted on a then theDIN rail must electrically connected tothe
*earth terminal
DIN rail
loop cable screen via the earth terminal.
EO
L1
0K
10
K
121110 9 8 7 6 5 4 3 2 1
ConfirmationInput(Optional)
NC
CO
MN
O
Output - Relaycontact rating1A 30V ac/dcResistive load
Lo
op
L1
+L
oo
p0
VL
oo
pL
2+
Lo
op
0V
#
*
*
4-Input/Output moduleconnection details
121110 9 8 7 6 5 4 3 2 1
NC
/N
O
CO
MR
ela
yO
utp
uts
se
eN
ote
3
EO
L1
0K
10
K
SwitchInput
Zone Inputsee Note 2
LE
DO
utp
ut
se
eN
ote
4
Ch
an
ne
l1
Ch
an
ne
l2
Ch
an
ne
l3
Ch
an
ne
l4
EOL
Lo
op
L1
+L
oo
p0
VL
oo
pL
2+
Lo
op
0V
* *
*
*
1-Input moduleconnection details
121110 9 8 7 6 5 4 3 2 1
10K
10KEOL
Zone InputModeSee Note 1
EOLCapacitor unit
SwitchInputMode
Lo
op
L1
+L
oo
p0
VL
oo
pL
2+
Lo
op
0V
#
*
**
Chassis
Z+ Z-
Z+
Z-
8 7 6 5 4 3 2 1
Technical data
1- Input 4-Input /Output 1-Output & 1-Input
Approval EN54-17:2005 and EN54-18:2005 (Approved)
Weight-dimen. modulemodule in plastic boxmodule in metal box
92g �1047g 782g�
100g �1055g 790g �
100g �1055g 790g �
Storage temperature -30ºC to 70ºC
Operating temperature -10ºC to 60ºC
Relative Humidity Up to 95% - Temperature 5ºC to 45°C (Non condensing)
Emission BS EN 61000-6-3:2001 Residential, Commercial & Light Industry Class B limits
Immunity BS EN50130-4: 1996: Part 4
LVD BS EN 60950-2002
Ingress Protection IP31 for plastic box & IP40 estimated for metal box
Colour Module-white / Plastic box-dark grey (Lid-light grey) / Metal box-dark grey
Input mode Input channel-1 only can be configured as a zoneinput to accept conventional devices, with a load of2mA quiescent and 9mA alarm maximum at 24Vnominal (18V minimum). With configurable 2s to 5sreset period and 5s to 40s alarm validation delay.
Switch input can workwith or without a delay.
Input channel can be configured as a switch input of Fire*, Fault*, Supervisory* (non fire) orConfirmation# signal. * with input acceptance delay of up to10 seconds for a Fire input and up to 300s for Fault or Supervisory input. # A fault isgenerated if confirmation input is not seen within predefined period of the output action(Confirmation function is not a feature of the single input module).
Output mode - A relay output of either NOor NC set of contacts rated1A - 30Vac/dc resistiveload.
A relay output of change overcontacts NC, COM and NO rated 1A -30Vac/dc resistive load.
LED output 1.5mA at 24Vdc (Normally On or Normally Off)
EN54-17 data Vmax Vnom Vmin VSO max VSO min IC max IS max IL max ZC max
42V 40V 24V 16V 8V 0.4A 1A 20µA 0.1O�
Panel compatibility Fully compatible with LPC � V4.35 & MCB � V4.37.
� means equal to or greater thanFor further information on upgrade requirements contact SMS.
45
SENTRI4 - EN54 system
90mm
93
mm
23mm
22
7m
m
245mm
Depth 77mm
HealthyFaultFault
System faultgreen
amber
202mm
12
5m
m
Depth 50mm
Metal Box
Plastic Box
Interface Module forSenTRI Medium Voltage(MV) OutputThese instructions cover the above interface options and accessories.
These SenTRI Single Output Interfaces are designed for use with anySenTRI fire alarm control panel. Each module includes loop isolators fordevice isolation.
The SenTRI Single Output Interfaces are suitable for mains switching,they provide normally closed and normally open contacts rated at 13A250Vac (nominal 230Vac) resistive load.
The SenTRI interfaces use one of 200 available device addresses on aloop and respond to regular polls from the control panel reporting thetype of device.
Features
� Analogue addressable communications
� Built-in type identification automatically identifies thesedevices to the control panel
� Reliable communication technique with high noiseimmunity
� Soft or SAFE addressing
� Common mounting options including surface mount andDIN rail mount
� EN54-17:2005 and EN54-18:2005
Cables
Any suitably rated cable may be used for wiring the output lines to drivethe required load. For information on cables recommended for wiring theloop circuits see instructions supplied with the fire control panel.
Installation
The SenTRI Single Output Interface module can be mounted in otherequipment housing using a DIN rail (491).
The SenTRI Single Output Interface is available in a metal box(SEN-415). The box provides cable termination points on the enclosure.
Wiring
The loop cable screen must be continued through each interface module.If a module is mounted on a DIN rail, then the DIN rail must beelectrically connected to the loop cable screen.
� The output contacts are rated at 13A 230V ac resistiveload. In order to meet the requirements of European SafetyStandards, ensure that all cables carrying voltages in excess of48V (Live and Neutral) are suitably fused.
46
Installation instructions
EarthLoop 0V
Loop L2+Earth
Loop 0VLoop L1+
NC
COM
NO
OUTPUT
Hook and Pushto lock onto DINRail
DIN Rail
Connect to loopcable screen
Single Output Interface ModuleDIN rail mountable(Medium Voltage)
Single Output Interface PCB with cover(Medium Voltage) in a metal box
Technical data
Approval EN54-17:2005 & EN54-18:2005(Approved)
Dimensions inmm
See illustrations
Weight DIN mountable:138gPCB with cover in metal box:800g
Storagetemperature
-30ºC to 70ºC
Operatingtemperature
-10ºC to 60ºC
RelativeHumidity
Up to 95% - Temperature5ºC to 45°C(Non condensing)
Emission BS EN 61000-6-3:2001Residential, Commercial & LightIndustry Class B limits
Immunity BS EN50130-4: 1996: Part 4
LVD BS EN 60950-2002
IngressProtection
Metal box - IP40 estimated
Colour -Metal Box
Dark Grey
Output Single pole change over contactsrated at 13A 230V ac Resistiveload.
Contact ratings
Type
Cycle
1hp @ 240V ac, 1/2hp @120V ac (UL508)
6x103
Terminals 2.5mm2
EN54-17 data Vmax 42V
Vnom 40V
Vmin 24V
VSO max 16V
VSO min 8V
IC max 0.4A
IS max 1A
IL max 20�A
ZC max 0.1�
Compatibile Compatible with panel having:
Main Controller � V4.31
LPC � V4.33
.
47
SENTRI4 -EN54 System
125mm
75
mm
Depth 48mm
PCB on DIN railmountable module
202mm
12
5m
m
Depth 50mm
PCB in metal box
Mains Powered Interface(from Qtr 3 2010)
The Mains powered interface units (78302-02NM and 78302-12NM) areEN54-4 compliant battery backed power supplies that can be directlyconnected to the loop and also have highly flexible interfacing capability.
The 4 channels can be individually configured to provide Output andInput interface in various configuration modes, to control externalequipment and receive input to allow the fire system to make decisionsand take actions. It is now possible to have combined inputs and outputsgiving a total of 8 external circuits connected (e.g. 4 sector outputs and 4confirmation inputs). The units have room to accommodate optionalmodules on to DIN rails. It has a configurable auxiliary power output thatis derived from its self contained mains power supply unit, which isbattery backed to continue to deliver power in the event of mains supplyfailure.
Technical Data
Standards -designed to meet
EN54:part 4:1998
EN54:part 17:2005
EN54:part 18:2005
Overalldimensions
478mm x 322mm x 128mm
Assembled weight(approximate)
7Kg (excluding batteries and optionalcomponents fitted)
Enclosure Steel
Colour RAL7024 Graphite Grey(fine textured)
Storagetemperature
-20 to 70ºC
Ambient operatingtemperature
-10 to 45°C
Relative Humidity(Non condensing)
up to 95%
Temperature 5 - 45°C
Ingress Protection IP31(estimated)
Operating voltage 230V 50Hz +10% -6%
Rated current 0.7A
Input modes Input can be fault monitored, voltagefree, contacts OR conventionaldetection zone circuit. Refer to thecommissioning information for moredetails.
Zone
Nominal voltage
Quiescent current16V or 22.5V (default) �15%
20mA per zone (default)
Zone short circuit current limitedto < 30mAEN54 compliance limitation:32 devices OR Maximum of 20diode bases per zone
Output modes Outputs are monitored 24V (nominal)0.5A OR LED drive. Refer to thecommissioning information for moredetails
Confirmationmodes
It is possible to configure all Inputsand Outputs as confirmation channels
Sector andAuxiliary Outputs
Sector and Auxiliary Outputs
0.5A max each @ 24V +/-3V,
electronically current limited to
approximately 1A at 25oC
Maximum total output current:
78302-02NM = 1.5A
78302-12NM = 2.5A
Auxiliary power output:12V / 24V ±0.5V (78302-12NM) or
24V ±3V (78302-02NM)
Batteries Two types:2 x 12V 2.1Ahr (1Kg each)
for 78302-02NM
2 x 12V 12Ahr (4.31Kg each)
for 78302-12NM
Compatible Panel# :Main Controller � V4.41
:LPC � V4.39
EN54-17 : 2005(section 4.8)data:
Vmax 42V IC max 0.4A
Vnom 40V IS max 1A
Vmin 24V IL max 20�A
VSO max 16V ZC max 0.1�
VSO min 8V
Emission BS EN61000-6-3: 2007 EMC forresidential, commercial & lightIndustry.
Immunity BS EN50130-4: 1996 + A1:1998 +A22003 for alarm systems
Terminals 3-way device (terminals provided forspur or sub-loop)
� Repetitive switching of capacitive loads greaterthan 1500uF is not possible and will result in the thermalprotection circuit automatically reducing the outputvoltage.
48
Installation instructions
Features
� Fail-safe operation
A fail-safe operation is available on all sectored outputs, if loopcommunications are lost for a defined duration then the sector outputswill be turned ON. Sector outputs will turn OFF immediately whencommunication is restored.
� Synchronisation
Adjustable synchronisation pulses can be selected for all sector outputsto synchronise the operation of devices such as xenon strobes or speechsounders.
� Auxiliary Output
The Auxiliary output can be programmed to automatically turn OFF whena mains failure occurs to preserve battery capacity. The output can alsobe programmed to provide a reset pulse when a fire reset occurs.
Installation
The batteries are supplied in a separate pack.
Spare Parts packages Qty
Fuse 3.15A AS Ceramic (20mm x 5mm) 1
Fuse 3.15A QB Glass (20mm x 5mm) 1
Resistor 5.6K 0.6W 4
Resistor 470R 0.6W 8
Resistor 10K 0.5W 4
Battery Link 1
Battery Lead 1
Capacitor 22uF 35V 4
Instructions 1
keys are supplied in a plastic bag fitted to the enclosure.
49
SENTRI4 -EN54 System
PB2
S+ Z+ Z-S-
SECTOR / ZONE1
PB3
S+ Z+ Z-S-
SECTOR / ZONE2
PB4
S+ Z+ Z-S-
SECTOR / ZONE3
PB5
S+ Z+ Z-S-
SECTOR / ZONE4
PB1
0C LC 01 L1 02 L2LOOP
L N
PB6
+ + --
AUX O/P
P3
FS6T3.16ACERAMICANTI-SURGE
SW1 - POWER UP
P7
Mains PoweredInterface Unit Mk 3
P1
DANGERDO NOTREMOVE
4 Backbox mounting points
Top and rearcable entry points
Mains interface PCB(Not all components shown)
Door lock
Terminals for Auxiliary outputand Zone/Sector circuits
Terminals for mains cable+ mains fuse
Earth points for DIN rail modules
Backbox to door earth lead
DIN rail for optional modules
Quick reference label
Earth points for wiring
Loop terminals
Battery connector
Relay
SurgeProtection
IS GalvanicIsolator
Metalscreen
FS8 F3.16AQUICKBLOW Battery fuse
Battery ‘Power up’push button
Batteries are fitted hereduring commissioning
Mains supply
The mains supply cable must be a standard fire resisting type and should meet PH30 classification, such as any of the standard and enhanced loopcable. Requires a minimum conductor cross sectional area of 0.75mm2.
� Ensure that the mains supply cable enters the enclosure through a dedicated cable entry, located adjacent to themains terminal block and that is also segregated from loop wiring.
�These fire alarm system products are not designed to be powered from IT Power systems.
All mains powered equipment must be earthed. Mains supply to any fire alarm control and indicating equipment must be via an unswitched 5A fusedspur unit. A disconnect device must be provided to disconnect both poles and must have a minimum gap of 3mm. The disconnect device should beavailable as part of the building installation and must be easily accessible after installation is complete.
Wiring test
� DO NOT undertake high voltage insulation tests WITH THE CABLES CONNECTED to the Mains Interface unit andexternal equipment. Such a test may damage the electronics circuitry in external equipment and in the Mains Interface unit.
50
Installation instructions
Dedicated mains supplyfrom consumer unit
5A UnswitchedFused spur unit
Ensure the mains supply remainsisolated until system commissioningstage when the unit is powered up.
Mains Interface Backbox
NLPE
FS33.15A(T)mains fuse
Disconnect Device
Minimum gap 3mm
External wiring
Options
These optional products should be mounted on the DIN rail.
� The relays and intrinsically safe products listed below should be mounted apart, a metal screen is providedinside the enclosure.
� Low voltage power relay
� Intrinsically safe galvanic isolator for IS detectors and call points
� Intrinsically safe galvanic isolator for IS sounders
For full information see the leaflet supplied with the product.
51
SENTRI4 - EN54 system
PB1
0C LC 01 L1 02 L2
LOOP
LOOP OUTLOOP IN
LOOPCOMMON
PB6
+ + --
AUX O/P
ExternalEquipment
PB2, PB3,PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
LED Output
PB2, PB3,PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K EOL�
IS Sector Output
IS Galvanicisolator (02518-10)
PB2, PB3,PB4 or PB5
Z+ Z-
ZONE 1, 2, 3 or 4
22uF EOL
Zone Input
PB2, PB3,PB4 or PB5
Z+ Z-
ZONE 1, 2, 3 or 4
5K6 EOL
IS Zone Input
PB2, PB3,PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K EOL�
Sector Outputwith Sounders
PB2, PB3,PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K EOL�
Flybackdiode
Sector Outputwith Inductiveload (eg Relay)
PB2, PB3,PB4 or PB5
Z+ Z-
ZONE 1, 2, 3 or 4
470R EOL
Switch Input
470RIS Galvanicisolator (17740-20)
Auxiliary Output:12V# or 24V @ 0.5A# - for S43440-12 only
11+ 12-
1+ 2-
12 11
2 1
Connected tometal enclosure
End-of-line units
Capacitor 22uF
Resistor 470�
yellow, violet, brown
Resistor 5K6K�
green, blue, red
Resistor 10K�
Brown, black, orange
It is possible toconnect a number ofLEDs in series(current is 1.5mA.
To avoid damage to equipment alwaysconfigure the interface inputs andoutputs before connecting the externalcircuits.
Intrinsicallysafe devices
Normally closed contactsshould be used forfail-safe applications.
Intrinsicallysafe devices
ca
ble
len
gth
ma
x.
50
m ca
ble
len
gth
ma
x.
15
0m
ca
ble
len
gth
ma
x.
15
0m
ca
ble
len
gth
ma
x.
15
0m
ca
ble
len
gth
ma
x.
50
m
ca
ble
len
gth
ma
x.
15
0m
ca
ble
len
gth
ma
x.
15
0m
Network of systemsIt is possible to network together up to 31 standalone SENTRI4 EN54 fire alarm systems. Each standalone system has an EN54 SENTRI4 controlpanel fitted with a network card, which permits RS485 communication between other control panels. The cable distance between panels can be upto 1.2Km maximum.
Copper network connections
Fibre network connections
52
Installation instructions
Control panel
Control panel
Control panel Control panel Control panel
#
#
# - 1.2Km Copper network cable distance2Km Fibre network cable distance
#
##
#
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Control panel
Cable screen
N/C
0V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/CPB1
Connections forNetwork card inSocket P8 (Card 6)
Control Panel
PB1
Connections forNetwork card inSocket P8 (Card 6)
BACKPLANE
Control Panel
0V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/C
BACKPLANE
Fromprevious
panel
Noconnection
To Nextpanel
C8
76
54
32
1
BACKPLANE
Control Panel
Side 1(End 1)
P7Rx
P4Tx
P6Rx
P5Tx
P3P2
Links P2 and P3 are booster links.Normally the links are not fitted, however fordistance exceeding 750m the links must be fitted.
RxTx
C8
76
54
32
1
BACKPLANE
Control Panel
P7Rx
P4Tx
P6Rx
P5Tx
P3P2
RxTx
Side 2(End 2)
Side 1(End 1)
Side 2(End 2)
Network wiring
� In countries where the European EMC directive is in force use only those cables that are EMC Compliant, see list under theheading Network cables.
The recommended cables used to interconnect control panels are listed in this section.
Network cable screen continuity
Ensure a good screen continuity joint exists where there is a split cable.
� DO NOT mix cables of different types on the same leg of a network, as this will create impedance imbalance anddisruption to data communication.
How to minimise cross talk
� When using standard MICC cable in a network the different legs of the cable must not be closely placed together,as this will cause signal crosstalk which results in communication failure.
There are three practical ways of overcoming the crosstalk problem:
� used a twisted-core MICC cable
� put a ferrous screen between the cables (ie in the two runs of steel conduit)
� maintain a distance between the network cables of at least 50mm
53
SENTRI4 - EN54 system
These split cables
MUST BE of the same type.
Panel 1 Panel 2
Panel Earth Screen continuity
connection at the joint
NOTE:
the joint Panel 2.
The cable screens are notconnected to earth
at or at
THE JOINT
Network cablesFor an overview definition of what is a standard and enhanced fire alarmcable see page 6. For information on cable separation see page 5.
Enhanced Network cables
� Mineral insulated copper cable (EMC Compliant)800m maximum Panel to Panel or Panel to networknode cable distance.
• BS6207: Part 1
• 3 parallel cores
• having continuous metal sheath encapsulating
• each core having 1.5mm2 cross section area
• a red cover sheath (preferred for alarm applications)
� Fireshield Enhanced FSN G20001.2Km maximum Panel to Panel or Panel to Networknode cable distance
• 3 Core (1 pair + 1 and earth
• each core having 1mm2 cross section area
Standard Network cables
� Delta Crompton Firetuf FDZ1000*1200m maximum Panel to Panel or Panel to Networknode cable distance
• Three core
� Huber & Schner Radox series FR communicationcable*1200m maximum Panel to Panel or Panel to Networknode cable distance
• Three core twisted triad screened
• 1.5mm2 (7/0.42 stranded) conductors
• Nominal impedance 200 ohms (1KHz)
• Capacitance between conductors 110pF/m (1KHz)
• Capacitance between screen to core 210pF/m (1KHz)
• Fire resistance tested to BS6387 category CWZ andIEC 331.
� Belden No 9729 (UL Style 2493) (EMC Compliant)1200m maximum Panel to Panel or Panel to Networknode cable distance
• Two twisted pairs
• Each pair individually screened24AWG (7 strands x 32 AWG)
• Low capacitance between conductors - 39.4pF/m at 1kHz
• Low capacitance conductor to screen - 72.2pF/m at 1kHz
• Temperature range -30oC to +60oC .
� Teflon jacketed Belden TR No. 897291200m maximum Panel to Panel or Panel to Networknode cable distance
• Two twisted pairs
• Each pair individually screened24AWG (7 strands x 32 AWG)
• Low capacitance between conductors - 39.4pF/m at 1kHz
• Low capacitance conductor to screen - 72.2pF/m at 1kHz
• Temperature range up to 200oC
� Belden Armoured equivalent (EMC Compliant)This cable being a two-pair cable to BS5308:Part 1 (type2) 0.5mm2 (16/0.2mm).600m maximum Panel to Panel or Panel to Networknode cable distance.
Belden No. 9842 EIA RS485 Applications, O/ABeldfoil® Braid1200m maximum Panel to Panel or Panel to Networknode cable distance
• Must have following characteristics:
• Two twisted pairs
• 24AWG (7 strands x 32 AWG) conductors
• Low characteristic impedance - 120 ohms
• Low capacitance between conductors - 42pF/m at 1kHz
• Low capacitance conductor to screen - 75.5pF/m at 1kHz
� Prysmian (formally Pirelli) FP200 Flex*(EMC Compliant)800m maximum Panel to Panel or Panel to Networknode cable distance
• 3 Core
• each core having 1.5mm2 cross section area
� Prysmian (formally Pirelli) FP200 Gold*(EMC Compliant)1.2Km maximum Panel to Panel or Panel to Networknode cable distance
• 3 Core
• each core having 1.5mm2 cross section area
� Prysmian (formally Pirelli) FP Plus*(EMC Compliant)1.2Km maximum Panel to Panel or Panel to Networknode cable distance
• 3 Core
• each core having 1.5mm2 cross section area
� Draka FT Plus (EMC Compliant)1.2Km maximum Panel to Panel or Panel to Networknode cable distance
• 3 Core
• each core having 1.5mm2 cross section area
� Doncaster Cables Firesure Plus
• 1.2Km maximum Panel to Panel or Panel to Networknode cable distance
• 4 Core (2- pair plus earth)
• each core having 1.5mm2 cross section area
� The cables marked * utilise laminated aluminium tapewith a tinned drain wire for electrostatic screening. Under certainenvironmental conditions galvanic action may take placebetween the aluminium and the drain wire. This will severelydegrade EMC performance as the foil to drain wire impedancewill increase.
54
Installation instructions
Domain Bridge across NetworksIt is possible to connect two or more SENTRI4 networks together by means of domain bridge. To domain bridge two or more networks a Domainbridge IO card must be installed in the bridging panel.
There are various methods of domain bridging depending on the distances between panels. Domain bridge can be made directly using RS232 portsof the IO card, via modem, RS422 converter unit, Fibre optics or via dedicated network using NPORT units.
Methods of domain bridging
� A domain bridge IO card is required to be installed in the bridging panel/node.
Star connection
55
SENTRI4 - EN54 system
RS23215m max
Modem
Fibre Optic2Km
Domain bridge IOC
ControlPanel
DOMAINBRIDGE
IOC IOC
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
ControlPanel
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Domain Bridge Domain Bridge
DomainBridge
Domain1
Control panel- 4 IOC Cards- 1 Network Card
If remote sites are residentialthen it is not permissible torely on domain bridge link tocall the fire brigade.
Domain3
IOC
Domain4
IOCDomain
2
IOC
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
Fibre Optic Domain bridge using FO Network DOM card
56
Installation instructions
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
DOMAINBRIDGE
Domain 1
MINIMUM OF 4 CORE FIBRE CABLETO ALLOW 100% REDUNDANCY
Fibre opticpatch panel
Fibre patch cable
Fibre opticpatch panel PanelPanel
Tx Tx
RxRx
FO Net DOMFO Net DOM
Domain 2Fibre OpticsFO Net
DOM
FO Net
DOM
RS232 Domain bridge using Domain IO card
Modem Domain bridge
57
SENTRI4 - EN54 system
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
DOMAINBRIDGE
Control panel
IOCIOCDomain 1 Domain 2RS232 15m Cable length
Backplane Backplane
Control panel
PB2
N/C 0V CTS RX RTS TX
DOM IO CARD IN SLOT P7PB2
N/C 0V CTS RX RTS TX
DOM IO CARD IN SLOT P7
DOMAINBRIDGE
Domain 1 Domain 2
Panel
BT Leased line
Panel
Backplane
3
2
7
Modem
25-wayD-type plug
IOCIOCPanel Modem Modem
BT Leased line
Mainssocket
PB2
N/C 0V CTS RX RTS TX
IO CARD IN SLOT P7
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 Fire System
Designed to EN54 Pt 2 & 4
Healthy
15:45Fault
System Fault
Test
Fire
Power
Power Fault
CB254
Disablement
Sounder
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32
Zones
PreviousNext
Delay
Verify
CB253
EN54 Parts 2 & 4f o u r 0XXXX
SenTRI 4 system partsThis section lists parts that can be used in the SenTRI system. For further details on the availability of the parts, contact your supplier.
Control Panel
SENTRI4 EN54 Control panel (24 hour standby) c/w 1 loop card (Not supplied are 2 x 12V 21Ahr batteries)
Spares
SENTRI4-BATT Spare battery 2 x 12V 21Ahr for Control panel
VS-PROLL Spare thermal paper for the integral printer
SEN-KEY Outer door key
Cards
SENTRI4-LPC Loop Card (EN54)
SENTRI4-MCC-24 Main Controller Card (EN54) spare for SENTRI4 panel
SENTRI4-NC Copper Network Card (EN54)
VIG-NC-FO Fibre Optics Network Card (EN54)
VIG-IOC-DOM Domain Bridge Input/Output Card (EN54)
AccessoriesSENTRI4-FLUSH Flush mounting kit (Control panel)
Printer
PRINTER-HAND Handheld serial thermal printer RS232
PRINTER-H-PAPER Thermal paper for handheld printer
Repeat panels
SENADV-IND Repeat indicator panel (connects directly to the control panel)
SENTRI-RPT Repeat panel (EN54)
SENTRI-RPT-BATT Battery pack for Repeat panel (for SENTRI-RPT)
SENTRI-RPT-FLUSH Repeat panel flush surround
Zonal Mimic panel
SENTRI-ZONE A3 Zonal mimic panel (EN54) supplied with 12V 7Ah Battery
T-Breaker and Remote LED
78299-01NM T-Breaker (to create a spur circuit off the main loop)
SEN-LED Remote LED module
ZF18 Square remote LED indicator
58
Installation instructions
Manual call points
SEN-800 Manual Call Point with break glass IP43
SEN-805 Manual Call Point with Resettable element
SEN-890 Resettable Element for MCP (Pack of 10)
SEN-891 Replacement Glass for MCP (Pack of 10)
SEN-892 Protective cover for MCP (Pack of 5)
SEN-895 Surface Back Box for MCP red plastic - (Pack of 10)
71167-91NM Test Key (Pack of 10)
Keyswitch interfaceSEN-807 Keyswitch call point (Red)
SenTRI Analogue Sensor, Sounder & Strobe
SEN-715 SenTRI Optical Sensor
SEN-710 SenTRI Optical Heat Sensor
SEN-770 SenTRI Optical Heat Sensor Sounder
SEN-770-ST SenTRI Optical Heat Sensor Sounder Strobe
SEN-720 SenTRI Heat Sensor
SEN-780 SenTRI Heat Sensor Sounder
SEN-780-ST SenTRI Heat Sensor Sounder Strobe
SEN-DUCT SenTRI Venturi-Air Duct Kit
Associated products
SEN-700 SenTRI Base
SEN-FLUSH SenTRI Semi-Flush fixing kit
SEN-DUST-COVER SenTRI Sensor dust cover (pack of 50)
SEN-EXTRACTOR SenTRI Removal tool
SEN-COVER-REMOVER SenTRI Dust cover remover tool(spare adaptor)
SEN-BASE-LABEL SenTRI Label plate (pack of 50)
Duct Sensor
SEN-DUCT SenTRI Duct kit
SEN-PROBE-06 Venturi tube 600 mm
SEN-PROBE-15 Venturi tube 1500 mm
SEN-PROBE-28 Venturi tube 2800 mm
EN-DUCT-BRACKET Mounting kit for circular andinsulated air ducts
SEN-715 SenTRI Optical Sensor
Beam sensor
SENTRI-BEAM SenTRI Beam sensor pair
SEN-741-01 Angle bracket with base
SEN-741-03 Parallel bracket with base
S4-34741-99 Light shield (5 per pack)
S4-34741-50 Test Cards
Sounder and Strobe
Sounder
SENADV-IP-SN-W Sounder (system type) white bodyIP55
SENADV-IP-SN-R Sounder (system type) red bodyIP55
SENADV-SN-W Sounder (low profile) white bodyIP31
SENADV-SN-R Sounder (low profile) red bodyIP31
Strobe
SENADV-IP-ST-RR Strobe (low profile) red bodyIP65 red lens
Sounder Strobe
SENADV-IP-SN-ST-RR Sounder Strobe (low profile)red body and red lens IP65
59
SENTRI4 -EN54 System
SenTRI Interfaces
KeyswitchSEN-INT-KEY Keyswitch interface (Blue)
Low voltage rangeSEN-INT-INPUT SenTRI 1-Input Interface module (low voltage)
SEN-INT-OUTPUT SenTRI 1-Output & 1-Input Interface module (low voltage)
SEN-INT-4IO SenTRI 4-Input / Output Interface module (low voltage)
OptionsThe above interface modules can be mounted in any of the following optional enclosure and on a DIN rail mount bracket.
SEN-490 SenTRI Plastic box
SEN-492 SenTRI Metal box
SEN-491 SenTRI DIN rail mount bracket (pack of 5)
Medium voltage rangeSEN-INT-ACDIN SenTRI Single Output Interface Module with DIN rail mounting (Medium Voltage)
SEN-INT-AC SenTRI Single Output Interface PCB with cover in a metal box (Medium Voltage)
Mains powered interfaces
New 4- Channel mains powered interface (Qtr 3 2010)78302-02NM Mains powered fire alarm interface 24V only
78302-12NM Mains powered fire alarm interface 12V / 24V
19104-52 Low voltage power relay
17740-20 Intrinsically safe galvanic isolator for IS detectors and call points
02518-10 Intrinsically safe galvanic isolator for IS sounders
Old 4- Channel mains powered interface (Supported)78301-01NM Mains powered fire alarm interface (require batteries)
19104-52 Power relay (for mains powered interface)(up to 4 maximum can be fitted inside the interface -supplied with base and diode unit)
Domain Bridge productsVIG-DOM-MODEM Modem pair
60
Installation instructions
Surge protection
5530440 1 x Mains, 1 x Loop & 1 x Zone/Sector suppression (enclosure has space for 1 extra loop (2 x 2817958)
5530452 1 x Mains, 1 x Network, 1 x Loop & Zone / Sector suppression (enclosure has space for 1 extra loop (2 x 2817958)
5530465 1 x Mains, 1 x Network suppression
5530478 1 x Mains suppressor
2817958 1 x Additional Loop suppressor (module only)
Replacement Plug ins2798844 Mains suppressor
2838762 Network suppressor
2839648 Loop suppressor
2838351 Zone / Sector suppressor
Manuals
4188-989 SenTRI 4 system Installation instructions
4188-990 SenTRI 4 system Operating instructions
4188-749 Log book
Surge protection5530440 1 x Mains, 1 x Loop & 1 x Zone/Sector suppression (enclosure has space for 1 extra loop (2 x 2817958)
5530452 1 x Mains, 1 x Network, 1 x Loop & Zone / Sector suppression (enclosure has space for 1 extra loop(2 x 2817958)
5530465 1 x Mains, 1 x Network suppression
5530478 1 x Mains suppressor
2817958 1 x Additional Loop suppressor (module only)
Replacement Plug ins
2798844 Mains suppressor
2838762 Network suppressor
2839648 Loop suppressor
2838351 Zone / Sector suppressor
Manuals4188-990 SENTRI4 System Operating instructions
4188-749 Log book
61
SENTRI4 - EN54 system
Supported products
Sensors78215-01NM Optical sensor
78280-01NM Optical sensor sounder
78210-01NM Optical heat sensor
78270-01NM Optical heat sounder
78220-01NM Heat sensor
78285-01NM Heat sensor sounder
Terminal Plate78200-01NM 2-way terminal plate
Tools78290-01NM Sensor chamber extraction tool - removes
chambers
78290-05NM Sensor electronic module extraction tool
62
Installation instructions
Notes:
63
SENTRI4 - EN54 system
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notifyany person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN Website: www.smsfire.co.uk
Telephone: +44 (0)116 246 2100 Fax (UK): +44 (0)116 246 2016
Technical Support: www.smstoolbox.co.uk
64 4188-989 issue 1_06/10_SENTRI4_Install
Installation instructions
Do not dispose of with your normal household waste.Do not burn.
WEEE Directive:At the end of their useful life, the packaging,product and batteries should bedisposed of via a suitable recycling centre.
At the end of their useful life, the packaging,product and batteries should be disposed ofvia a suitable recycling centre and inaccordance with national or local legislation.
0832
Gent by HoneywellHamilton Industrial Park, 140 Waterside Road, Leicester LE5 1TN, UK
0832-CPD-1454 1-4 LOOP PANEL
Control and Indicating equipment for fire detection and fire alarm systemsin buildings.
SENTRI4
EN54-2: 1997, A1:2006
7.8 Output to fire alarm devices7.11 Delays to action outputs8.3 Fault signals from point9.5 Disablement of each addressable point10 Test condition
Power supply equipment for fire detection and fire alarm systems inbuildings.
Other technical data: see documents in project file 7023, held by themanufacturer.
EN54-4: 1997, A1:2002, A2:2006