LT0432Issue 2.2
Australian Wiring Diagrams4100ESi
tsoever, without the written consent of Tyco. ight to change the content without prior notice.
yco International Services AG or its affiliates in the
r nts of Australian fire alarm systems. Some aspects of
uration will be customized by the User to define in ent this installation from meeting statutory
n any particular configured system.
ely revised for 4100ESi
sheets 608 and 708.8, 309, 427, 603, 604, and 705.
ithdrew sheet 212.
evised sheet 207.
Copyright and trademarksCopyright (c) 2017 Tyco. All rights reserved. Information contained in this document is subject to copyright and shall not be reproduced in any form whaInformation contained in this document is believed to be accurate and reliable. However, Tyco reserves the r
Tyco, Simplex, the Simplex logo, MAPNET II, IDNet, TrueAlarm, MINIPLEX, TrueAlert, MX are trademarks of TU.S. and/or other countries. VESDA is a trademark of Xtralis.
End user liability disclaimeThe wiring details described in this document are intended to allow compliance with the statutory requiremecompliance require corresponding settings in the configuration of the fire alarm system. Because this configdetail the operation of particular 4100ES or 4100ESi systems, changes may be made by the User that prevrequirements.
Therefore, Tyco cannot accept any responsibility as to the suitability of the functions generated by the User i
Revision history2.0 12-07-2016 Extensiv
2.1 17-11-2016Added
Revised sheets 30W
2.2 23-01-2017 R
e 4100ES (AS4428.1) or 4100ESi (AS7240.2)
divided into ranges, reflecting the type of device or
About this guideThese diagrams show the wiring for particular modules or cards or detector bases which can be used with thSimplex Fire Alarm systems.
OrganizationEach diagram has a 3 digit reference number from the drawing series 1976 - 181. This sheet numbering is module, as follows:
Sheet Number Type of Devices Covered
100-199 Detectors & bases
200-299 Zone modules & cards providing detection circuits
300-399 Input devices
400-499 Output devices or mixed input/output devices
500-599 Fault isolators
600-699 Communications – networks, printers, etc.
700-799 Power Supply details
essable device communication.
vice communication.
ctors.
d Slave transponders.
s and visual warning devices, usually with
munication protocol on an addressable loop.
Abbreviations
Abbreviation Description
MAPNET Multi-Application Peripheral Network – early version of addr
IDNet Individual Device Network – later version of addressable de
IAM Individually Addressable Module.
ZAM Zone Addressable Module – interfaces to conventional dete
RUI Remote Unit Interface – connects 4100ES Master panel an
RTU Remote Transponder Unit – slave unit.
NAC Notification Appliance Circuit – drives DC-powered soundersupervision.
MX Refers to detectors and devices using the MX DIGITAL comNot compatible with MAPNET/IDNet devices.
NC Normally Closed Relay Contact.
NO Normally Open Relay Contact.
D111111111
Z22222222222
In333333
Table of contentsetectors and bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500: 2W Detector Bases - QuickConnect Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 601: 2W Detector Bases - Conventional Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702: TrueAlarm Addressable Detector Bases. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 803: Flame Detector with Analog ZAM (4190-9050). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 904: 4B/5B MX Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1005: 4BI/5BI MX Isolator Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106: 4B-C MX Continuity Base. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1207: 802SB/901SB MX Sounder Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1308: LPSB3000/LPAV3000 MX Addressable Sounder/Beacon Bases . . . . . . . . . . . . . 14
one module and detection cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1500: 8 Zone Module Motherboard (4100-5004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1601: Mapnet Monitor ZAM (2190-9156) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1702: IDNet Zone Addressable Module (ZAM) (4090-9101) . . . . . . . . . . . . . . . . . . . . . . . . . 1803: IDNet Module (4100-3101) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1904: VESDA High Level Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2005: IDNet ZAM (2190-9156) Ex Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2106: IDNet+ Loop Card (4100-3107) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2207: IDNet2/IDNet2+2 Loop Card (4100-3109/4100-3110) . . . . . . . . . . . . . . . . . . . . . . 2308: Dual Loop Card (MX) (4100-6077) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2410: DIM800 MX Monitor ZAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2511: DDM800 MX Monitor ZAM Loop Powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
put devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2700: MapNet/IDNet Addressable MCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2801: IDNet Supervised IAM (4090-9001, 4090-9051) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2902: IDNet 4-20mA Analog Monitor AMZ (4190-9050) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3003: Alarm Acknowledgment - IDNet AAM2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3104: Alarm Acknowledgment - IDNet AAM4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3205: MIM800 MX Mini IAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
306: CIM800 MX Dual Input IAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
307: CP820/CP830 MX MCP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35308: VIO800 Multi I/O with Laser Scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36309: AAM2 with MX Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Output devices and mixed I/O devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39400: IDNet 6 Point I/O Module (4090-9120) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40401: MapNet2 Relay Module with Supervised Input (2190-9173) . . . . . . . . . . . . . . . . . . 41402: IDNet Relay IAMs with Inputs (4090-9118, 4090-9119) . . . . . . . . . . . . . . . . . . . . . 42403: MapNet2 Signal ZAM (2190-9162) and Control ZAM (2190-9164) . . . . . . . . . . 43404: IDNet Relay IAM (4090-9002) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44405: 8 Point Auxiliary Relay Card (4100-3003) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45406: 6 Point Signal Card (4100-4321). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46407: SPS NAC Outputs (4100-9848AU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47408: SPS NAC Connection to T-GEN50 Tone Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48409: SPS NAC Connection to Multi-Gen Tone Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . 49410: SPS NAC Connection to Strobe Driver: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50411: SPS to Centaur/WA ASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51412: Fan Controls with Relay IAMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52413: 24 Point I/O Card (002-124+4100-0302) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53414: 4100-3204/3206 PDI Relay Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54415: Signal ZAM (4090-9007) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55416: MapNet/IDNet Relay IAM (4090-9008) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56417: Fan Interface - IDNet Loop Powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57418: Fan Interface - IDNet 24V Powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58419: 6 Signal Card Connection to Mini-Gen Tone Generator . . . . . . . . . . . . . . . . . . . . . . . . 59420: 6 Signal Card Connection to Strobe Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60421: MIO800 MX Multi I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61422: SNM800 MX Signal IAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62423: RIM800 MX Relay Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63424: APS/LPS NAC Connection to T-GEN50 Tone Generator . . . . . . . . . . . . . . . . . . . . . . 64425: APS/LPS NAC Connection to Mini-Gen Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65426: APS/LPS NAC Connection to Strobe Driver: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66427: Fan Interface - MX Loop Powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67428: LPSx800x MX Loop Powered Sounders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Is555
C6666666666666
P7777777
olators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6900: IDNet addressable Loop Isolator (4090-9116) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7001: IDNet Addressable Power Isolator (4090-9117AU) . . . . . . . . . . . . . . . . . . . . . . . . . . . 7102: LIM800 Loop Isolator Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
ommunication devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7300: Transponder Interface Card (4100-0620) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7401: Network Interface Card (Wired Media) (4100-6078) . . . . . . . . . . . . . . . . . . . . . . . . . . 7502: Network Interface Card (Fiber-optic) (4100-6078) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7603: Fiber-optic Modem (4100-6072/6073) - Style 7 (Ring). . . . . . . . . . . . . . . . . . . . . . . . 7704: Fiber-optic Modem (4100-6072/6073) - Style 4 (Spur) . . . . . . . . . . . . . . . . . . . . . . . 7805: Dual RS232 Card (4100-0113K legacy) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7906: LCD Annunciator (4604-9201) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8007: 4100MB Modbus Interface (4100-0113K legacy) . . . . . . . . . . . . . . . . . . . . . . . . . . . 8108: Dual RS232 PDI Card (4100-6046). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8209: Remote Fire Brigade Panel (4100-FP1048) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8310: NT Brigade Door (FP1093) wiring to APS/LPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8411: Centaur/WA/Cube ASE to APS/LSP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8512: 4100MB Modbus Interface (4100-6046 PDI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ower supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8700: SPS Power Outputs (4100-9848AU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8801: 1948 2A PSU Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8902: 4100U 5A PSU Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9005: Vigilant PSUs in 4100U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9106: 5A PSU (ME0470) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9207: ME0504 APS/ME0508 LPS AS7240.4 PSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9308: APS/LPS/SPS battery sharing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Detectors and bases
| 6 |
1976-181B
100 N
4100ES
WIRING DIAGRAM
3
LT0432 Issue 2.2
100: 2W Detector Bases - QuickConnect Detectors
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 7 |
R
L2
L
L1
1976-181B
101 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2101: 2W Detector Bases - Conventional Detectors
R
L2
L
L1
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 8 |
1976-181C
102 N
4100ES
WIRING DIAGRAM
LT0432 Issue 2.2
102: TrueAlarm Addressable Detector Bases
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A3
| 9 |
1976-181B
103 N
4100ES
WIRING DIAGRAM
3
LT0432 Issue 2.2
103: Flame Detector with Analog ZAM (4190-9050)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 10 |
1976-181A
104 1
4100ESi4B / 5B MX BASEWIRING DIAGRAM
3
LT0432 Issue 2.2
104: 4B/5B MX Base
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 11 |
1976-181A
105 N
4100ESi4BI / 5BI MX ISOLATOR BASE
WIRING DIAGRAM
LT0432 Issue 2.2
105: 4BI/5BI MX Isolator Base
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A3
| 12 |
1976-181A
106 N
4100ESi4B-C MX CONTINUITY BASE
WIRING DIAGRAM
LT0432 Issue 2.2
106: 4B-C MX Continuity Base
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A3
| 13 |
1976-181A
107 N
4100ESi2SB / 901SB MX SOUNDER BASE
WIRING DIAGRAM
3
LT0432 Issue 2.2
107: 802SB/901SB MX Sounder Base
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
80
A
| 14 |
LT0432 Issue 2.2108: LPSB3000/LPAV3000 MX Addressable Sounder/Beacon Bases
s
Zone module and detection card| 16 |
4100ESi
WIRING DIAGRAM
A3200 N1976-181
C
LT0432 Issue 2.2
200: 8 Zone Module Motherboard (4100-5004)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 17 |
1976-181B
201 1
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
201: Mapnet Monitor ZAM (2190-9156)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 18 |
1976-181B
202 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
202: IDNet Zone Addressable Module (ZAM) (4090-9101)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 19 |
1976-181D
203 N
4100ESIDNET LOOP CARD WIRING
WIRING DIAGRAM
A3
LT0432 Issue 2.2
203: IDNet Module (4100-3101)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 20 |
1976-181A
204 N
4100ESiVESDA HIGH LEVEL I/F
WIRING DIAGRAM
A3
LT0432 Issue 2.2
204: VESDA High Level Interface
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 21 |
1976-181C
205 N
4100ES4090-9101 ZAM & "Ex" DETECTORS
WIRING DIAGRAM
A3
LT0432 Issue 2.2
205: IDNet ZAM (2190-9156) Ex Detectors
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 22 |
1976-181B
206 N
4100ESIDNET+ LOOP CARD
WIRING DIAGRAM
A3
LT0432 Issue 2.2
206: IDNet+ Loop Card (4100-3107)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 23 |
LT0432 Issue 2.2207: IDNet2/IDNet2+2 Loop Card (4100-3109/4100-3110)
| 24 |
LT0432 Issue 2.2208: Dual Loop Card (MX) (4100-6077)
| 25 |
LT0432 Issue 2.2210: DIM800 MX Monitor ZAM
| 26 |
LT0432 Issue 2.2211: DDM800 MX Monitor ZAM Loop Powered
Input devices
| 28 |
1976-181B
300 N
4100ESPNET / IDNET ADDRESSABLE MCP
WIRING DIAGRAM
LT0432 Issue 2.2
300: MapNet/IDNet Addressable MCP
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
MA
A3
| 29 |
4100ES
WIRING DIAGRAM
3301 N1976-181
B
LT0432 Issue 2.2
301: IDNet Supervised IAM (4090-9001, 4090-9051)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 30 |
1976-181B
302 N
4100ES
WIRING DIAGRAM
3
LT0432 Issue 2.2
302: IDNet 4-20mA Analog Monitor AMZ (4190-9050)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 31 |
1976-181B
303 N
4100ES
WIRING DIAGRAM
3
LT0432 Issue 2.2
303: Alarm Acknowledgment - IDNet AAM2 Wiring
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 32 |
1976-181B
304 N
4100ESLARM ACKNOWLEDGEMENT - AAM4
WIRING DIAGRAM
3
LT0432 Issue 2.2
304: Alarm Acknowledgement - IDNet AAM4 Wiring
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
A
| 33 |
LT0432 Issue 2.2305: MIM800 MX Mini IAM
| 34 |
LT0432 Issue 2.2306: CIM800 MX Dual Input IAM
| 35 |
LT0432 Issue 2.2307: CP820/CP830 MX MCP
| 36 |
LT0432 Issue 2.2308: VIO800 Multi I/O with Laser Scanner
309: AAM2 with MX Devices
vices
Output devices and mixed I/O de| 40 |
1976-181B
400 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
400: IDNet 6 Point I/O Module (4090-9120)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 41 |
1976-181B
401 N
4100ES
(2190-9173) WIRING DIAGRAM
A3
LT0432 Issue 2.2
401: MapNet2 Relay Module with Supervised Input (2190-9173)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 42 |
1976-181C
402 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
402: IDNet Relay IAMs with Inputs (4090-9118, 4090-9119)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 43 |
1976-181C
403 N
4100ES
3
LT0432 Issue 2.2
403: MapNet2 Signal ZAM (2190-9162) and Control ZAM (2190-9164)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 44 |
1976-181B
404 N
4100ESIDNET RELAY IAM (4090-9002)
WIRING DIAGRAM
A3
LT0432 Issue 2.2404: IDNet Relay IAM (4090-9002)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 45 |
1976-181B
405 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
405: 8 Point Auxiliary Relay Card (4100-3003)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 46 |
1976-181B
406 N
4100ESi POINT SIGNAL CARD (4100-4321)
WIRING DIAGRAM
A3
LT0432 Issue 2.2
406: 6 Point Signal Card (4100-4321)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
6
| 47 |
1976-181C
407 N
4100ESSPS NAC LOADSWIRING DIAGRAM
A3
LT0432 Issue 2.2
407: SPS NAC Outputs (4100-9848AU)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 48 |
1976-181B
408 N
4100ESPS NAC CONNECTION TO T-GEN50
WIRING DIAGRAM
A3
LT0432 Issue 2.2
408: SPS NAC Connection to T-GEN50 Tone Generator
EVAC
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
S
| 49 |
1976-181C
409 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
409: SPS NAC Connection to Multi-Gen Tone Generator
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 50 |
1976-181C
410 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
410: SPS NAC Connection to Strobe Driver:
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 51 |
1976-181D
411 N
4100ESSPS TO CENTAUR / WA ASE
WIRING DIAGRAM
A3
LT0432 Issue 2.2
411: SPS to Centaur/WA ASE
²
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 52 |
1976-181C
412 N
4100ESFAN CONTROLS WITH RELAY IAMS
WIRING DIAGRAM
A3
LT0432 Issue 2.2412: Fan Controls with Relay IAMs
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 53 |
1976-181D
413 N
4100ESi24 POINT I/O CARD (002-124)
WIRING DIAGRAM
A3
LT0432 Issue 2.2
413: 24 Point I/O Card (002-124+4100-0302)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 54 |
1976-181B
414 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
414: 4100-3204/3206 PDI Relay Modules
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 55 |
1976-181B
415 N
4100ESSIGNAL ZAM (4090-9007) WIRING
WIRING DIAGRAM
A3
LT0432 Issue 2.2
415: Signal ZAM (4090-9007)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 56 |
1976-181B
416 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
416: MapNet/IDNet Relay IAM (4090-9008)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 57 |
1976-181B
417 N
4100ESFAN INTERFACE - LOOP POWERED
WIRING DIAGRAM
A3
LT0432 Issue 2.2
417: Fan Interface - IDNet Loop Powered
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 58 |
1976-181B
418 N
4100ESFAN INTERFACE - 24V POWERED
WIRING DIAGRAM
A3
LT0432 Issue 2.2
418: Fan Interface - IDNet 24V Powered
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 59 |
1976-181B
419 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
419: 6 Signal Card Connection to Mini-Gen Tone Generator
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 60 |
1976-181B
420 N
4100ESi
WIRING DIAGRAM
3
LT0432 Issue 2.2
420: 6 Signal Card Connection to Strobe Driver
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 61 |
LT0432 Issue 2.2421: MIO800 MX Multi I/O Module
| 62 |
LT0432 Issue 2.2422: SNM800 MX Signal IAM
| 63 |
LT0432 Issue 2.2423: RIM800 MX Relay Interface Module
| 64 |
1976-181A
424 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
424: APS/LPS NAC Connection to T-GEN50 Tone Generator
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 65 |
1976-181A
425 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
425: APS/LPS NAC Connection to Mini-Gen Generator
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 66 |
1976-181A
426 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
426: APS/LPS NAC Connection to Strobe Driver:
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 67 |
LT0432 Issue 2.2427: Fan Interface - MX Loop Powered
| 68 |
LT0432 Issue 2.2428: LPSx800x MX Loop Powered Sounders
Isolators
| 70 |
1976-181C
500 N
4100ES
WIRING DIAGRAM
3
LT0432 Issue 2.2
500: IDNet addressable Loop Isolator (4090-9116)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
A
| 71 |
1976-181B
501 N
4100ES
WIRING DIAGRAM
A3
LT0432 Issue 2.2
501: IDNet Addressable Power Isolator (4090-9117AU)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 72 |
LT0432 Issue 2.2502: LIM800 Loop Isolator Module
Communication devices
| 74 |
1976-181C
600 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
600: Transponder Interface Card (4100-0620)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 75 |
1976-181C
601 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
601: Network Interface Card (Wired Media) (4100-6078)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 76 |
1976-181B
602 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2602: Network Interface Card (Fiber-optic) (4100-6078)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 77 |
LT0432 Issue 2.2603: Fiber-optic Modem (4100-6072/6073) - Style 7 (Ring)
| 78 |
LT0432 Issue 2.2604: Fiber-optic Modem (4100-6072/6073) - Style 4 (Spur)
| 79 |
1976-181B
605 N
4100ESDUAL RS232 CARD (4100-0113K)
WIRING DIAGRAM
A3
LT0432 Issue 2.2
605: Dual RS232 Card (4100-0113K legacy)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 80 |
1976-181B
606 N
4100ESiLCD ANNUNCIATOR (4604-9201)
WIRING DIAGRAM
A3
LT0432 Issue 2.2606: LCD Annunciator (4604-9201)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 81 |
LT0432 Issue 2.2607: 4100MB Modbus Interface (4100-0113K legacy)
| 82 |
LT0432 Issue 2.2608: Dual RS232 PDI Card (4100-6046)
| 83 |
1976-181A
609 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
609: Remote Fire Brigade Panel (4100-FP1048)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 84 |
OTECTION PRODUCTS
,+64 3 3895938+64 3 3895096PH:
ER DRIVE
FAX:
tection Products
FP1093
4100ESiNT BRIGADE DOOR TO APS
WIRING DETAILS
A2610 N1976-181
A
LT0432 Issue 2.2
610: NT Brigade Door (FP1093) wiring to APS/LPS
TYCO FIRE PR
CHRISTCHURCH
17 MARY MULLP.O. BOX 19545
NEW ZEALAND.
Fire Protyco
| 85 |
1976-181A
611 N
4100ESi
WIRING DIAGRAM
A3
LT0432 Issue 2.2
611: Centaur/WA/Cube ASE to APS/LSP
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 86 |
1976-181A
612 N
4100ESi4100MB MODBUS INTERFACE (PDI)
WIRING DIAGRAM
A3
LT0432 Issue 2.2
612: 4100MB Modbus Interface (4100-6046 PDI)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
Power supplies
| 88 |
1976-181D
700 N
4100ESSPS POWER OUTPUTS
WIRING DIAGRAM
A3
LT0432 Issue 2.2
700: SPS Power Outputs (4100-9848AU)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 89 |
1976-181B
701 N
4100ES1948 2A PSU POWER OUTPUTS
WIRING DIAGRAM
A3
LT0432 Issue 2.2701: 1948 2A PSU Outputs
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 90 |
1976-181D
702 N
4100ESiME0470 24V 5A PSU
WIRING DIAGRAM
A3
LT0432 Issue 2.2
702: 4100U 5A PSU Outputs
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 91 |
LT0432 Issue 2.2705: Vigilant PSUs in 4100U
| 92 |
1976-181B
706 N
4100ESiME0470 CONNECTION
WIRING DETAILS
A3
LT0432 Issue 2.2
706: 5A PSU (ME0470)
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 93 |
4100ESiAPS / LPS OUTPUTSWIRING DIAGRAM
A3707 N1976-181
A
LT0432 Issue 2.2
707: ME0504 APS/ME0508 LPS AS7240.4 PSU
TYCO FIRE PROTECTION PRODUCTS
NEW ZEALAND. +64 3 3895938+64 3 3895096PH:
17 MARY MULLER DRIVEP.O. BOX 19545
FAX:CHRISTCHURCH,
Fire Protection Productstyco
| 94 |
LT0432 Issue 2.2708: APS/LPS/SPS battery sharing
LT0432Issue 2.2