400VDC in Data & Telecom Centers 2013-09-05 Data Center Conference, Moscow Marek Szpek Business Development EMEA
© Emerson Network Power AB 2012. All rights reserved throughout the world. The information in this document is the property of Emerson Network Power AB. Except as authorized by Emerson Network Power AB in a written document, those receiving this document shall keep all the information contained herein confidential, and shall protect the same from disclosure and dissemination to third parties. While every precaution has been taken to ensure accuracy and completeness in this document, Emerson Network Power AB assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. This information in this document is subject to change without notice.
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Agenda
Data Center Trends and Emerging Technologies
Gains with 400V DC in Data Center and Telecom Center
400VDC pilot installations
400VDC Eco-system availability
400VDC power portfolio availability
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Data Center Landscape Changing
3
Different compute models available (enterprise, cloud, hyper-scale, co-location)
Demands for data and connectivity increase daily
Segmentation of computing applications
Green data center operations objectives
Customers have choices like never before
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Convergence Creating Choices
VOICE DC POWER Traditional AC
Traditional DC
High-Voltage AC
DATA AC POWER
High-Voltage DC
Eco-Mode
Renewables
Convergence creates several power choices
© 2013 Emerson Network Power Intellectual Property. All rights reserved
AC Power in Data Centers
30+ years of history
Established ecosystem
Highly reliable and efficient platform
Will be a choice of many customers for years to come
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400V DC – widely discussed and considered in several applications
Data Centers High availability, high efficiency and lower total costs thanks to a simple architecture
Telecom sites Copper savings for telecom central offices lowers investment and installation costs
Commercial buildings / Micro grids Easy integration of renewable energy sources with a common 400V DC bus
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400VDC drivers in Data Centers
Source: NTT-Facilities
Higher availability vs. AC UPS > 6x, due to more simple architecture
Increased overall efficiency, 8-12% (less conversion stages)
Lower footprint, ≈ 30%
More simple architecture - Data center loads are DC loads - Unnecessary conversions
AC/DC, DC/AC are eliminated
Easier integration with Renewable
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400VDC drivers in Telecom (48V)
Key driver - Copper cable saving, 10x
Long distance power feeding (50 x lower distribution losses)
Similar architecture to 48V
2-4% higher overall efficiency
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400VDC drivers in Commercial Buildings and Micro Grids
Energy sourcing becomes decentralized
- Local “green” production is typically DC
Connecting local sources to AC grid cost energy and money
- Part of the “green” energy is lost in conversions before it reaches any “real” load
- DC is converted to AC and back to DC
Sharing DC bus by different sources is much simpler than AC grid
- No phase/voltage balancing
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Duke Energy 380V DC
Univ. California 380V DC
Other Japan Demos 300V/350V DC
NTT Group (several sites)
380V/400V DC
UPN AB. 350V/380V DC
Intel 380V DC
China Telecom 240V/380V DC
SAP 380V DC
Nextek 380V DC
Syracuse University 380V DC
China Mobile 380V DC
Vendor participants include: HP, IBM, EMC, Fujitsu, Hitachi,
NEC
Netpower Labs AB (several sites)
350V/380V DC Green.Ch 380V DC
France Telecom 380V DC
Telecom Data Center Buildings / Microgrids Emerson power equipment
France Telecom 380V DC
European Telecom 380V DC
North American Telecom 380V DC IBM Singapore
380V DC
Clustered Systems 380V DC
Selection of 400VDC field trials
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400V Eco-system Availability
11
DC Power System DC Breaker ICT Load Rack PDU Connector Server Power
Supply
Emerson ABB Netpower Delta* Eltek*
ABB Carling Schneider Nader Siemens GE Eaton
ServerTech* API Technologies Delta* Fujitsu*
Anderson Hubbel Rong Feng / Delta Fujitsu*
Emerson* Delta* LiteOn*
NEI – catalog products available HP – 2013 release of common slot power supply IBM* – some X and Z series available today, new power available 2014 Juniper* – products in evaluation Supermicro* – 2 servers models available for trial
*Pre-production products available
Components Are Available for the 400V DC Ecosystem, but Supply Chain Is Still Maturing
© 2013 Emerson Network Power Intellectual Property. All rights reserved
HP 1200W 380VDC/12VDC common slot power supply
Source :HP
- Common slot 1200W (100-240VAC, 48VDC, 380VDC) power unit for HP’s ”pizza” portfolio/switches, servers etc. - Highest efficiency, 94% with 380VDC interface - Commercially available
© 2013 Emerson Network Power Intellectual Property. All rights reserved
IBM 380VDC server
Source: IBM
- New 400VDC power supplies for IBM blade servers planned for release 2014
© 2013 Emerson Network Power Intellectual Property. All rights reserved
NEI 380VDC servers
Source: NEI
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Greenfield - Bulk: 400V DC Loads Redundancy Implementation Options
Distribution B Side
Bus or cable Cable or bus cont’d
(N+1)
(2N)
Bus or cable Cable or bus cont’d Cable or bus cont’d
Bus or cable
A B A B
Battery Power strips 400V Equipment Racks
Distribution A Side (Alt. 2)
400V DC UPS N+m Rectifiers Internal
Battery A Side
Battery B Side
Distribution A Side
Distribution B Side
A B
Equipment Rack
400V DC UPS N+m Rectifiers Internal
400V DC UPS N+m Rectifiers
Internal
400V DC
400V DC 400V DC
Output DC Distribution
(Alt. 1)
Distribution B Side
(Opt, Alt. 2)
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Cable saving at transision from 48V to 400V & 400V/48V, 100kW load 48V Battery
100kW/48V Telecom Eq.
1-3 x PDU 200 x 6-63A c.b.
120kW/48V Power System
400V Battery
120kW/400V Power System
1-3 x PDU 200 x 6-63A
400V
48V
100kW/48V Telecom Eq.
10m 30m 5m
Tot cable material saving ≈ 25 kEUR Distribution losses saving ≈ 1kW =1%
21kW-400V/48V
35 mm² market price 4.1 EUR/m, 150 mm²market price 19.2 EUR/m
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Available today: NetSure™ 4015 30kW 400V Integrated System Standard system offering (1) output distribution sub-rack
(1) power and controls sub-rack
(2) battery trays (back-up 20kW-7min)
Integrated into 24U 19” IT rack
HWD: 1200mm x 600mm x 1000mm
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Under Development: Integrated 120kW cabinet module
Controller
Individual input c.b. to rectifiers
Rectifiers
Output Distribution (400VDC) single section
Insulation Failure Detector
AC Input Breakers
2x250A/400VAC (A+B)
360kW power system = 3x120kW
© 2013 Emerson Network Power Intellectual Property. All rights reserved
400V information on Emerson WEB site http://www.EmersonNetworkPower.eu/400vdc
© 2013 Emerson Network Power Intellectual Property. All rights reserved
Remaining Hurdles for 400VDC
20 20
Limited components across IT ecosystem
Standards under development
Lack of familiarity with the technology
Installed base of knowledge & information
These obstacles will be overcome with additional deployments