400VDC in Data & Telecom Centers 2013-09-05 Data Center Conference, Moscow Marek Szpek Business Development EMEA © Emerson Network Power AB 2012. All rights reserved throughout the world. The information in this document is the property of Emerson Network Power AB. Except as authorized by Emerson Network Power AB in a written document, those receiving this document shall keep all the information contained herein confidential, and shall protect the same from disclosure and dissemination to third parties. While every precaution has been taken to ensure accuracy and completeness in this document, Emerson Network Power AB assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. This information in this document is subject to change without notice. © 2013 Emerson Network Power Intellectual Property. All rights reserved

Upload: tranduong

Post on 15-Jun-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

400VDC in Data & Telecom Centers 2013-09-05 Data Center Conference, Moscow Marek Szpek Business Development EMEA

© Emerson Network Power AB 2012. All rights reserved throughout the world. The information in this document is the property of Emerson Network Power AB. Except as authorized by Emerson Network Power AB in a written document, those receiving this document shall keep all the information contained herein confidential, and shall protect the same from disclosure and dissemination to third parties. While every precaution has been taken to ensure accuracy and completeness in this document, Emerson Network Power AB assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. This information in this document is subject to change without notice.

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Agenda

Data Center Trends and Emerging Technologies

Gains with 400V DC in Data Center and Telecom Center

400VDC pilot installations

400VDC Eco-system availability

400VDC power portfolio availability

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Data Center Landscape Changing

3

Different compute models available (enterprise, cloud, hyper-scale, co-location)

Demands for data and connectivity increase daily

Segmentation of computing applications

Green data center operations objectives

Customers have choices like never before

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Convergence Creating Choices

VOICE DC POWER Traditional AC

Traditional DC

High-Voltage AC

DATA AC POWER

High-Voltage DC

Eco-Mode

Renewables

Convergence creates several power choices

© 2013 Emerson Network Power Intellectual Property. All rights reserved

AC Power in Data Centers

30+ years of history

Established ecosystem

Highly reliable and efficient platform

Will be a choice of many customers for years to come

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400V DC – widely discussed and considered in several applications

Data Centers High availability, high efficiency and lower total costs thanks to a simple architecture

Telecom sites Copper savings for telecom central offices lowers investment and installation costs

Commercial buildings / Micro grids Easy integration of renewable energy sources with a common 400V DC bus

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400VDC drivers in Data Centers

Source: NTT-Facilities

Higher availability vs. AC UPS > 6x, due to more simple architecture

Increased overall efficiency, 8-12% (less conversion stages)

Lower footprint, ≈ 30%

More simple architecture - Data center loads are DC loads - Unnecessary conversions

AC/DC, DC/AC are eliminated

Easier integration with Renewable

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400VDC drivers in Telecom (48V)

Key driver - Copper cable saving, 10x

Long distance power feeding (50 x lower distribution losses)

Similar architecture to 48V

2-4% higher overall efficiency

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400VDC drivers in Commercial Buildings and Micro Grids

Energy sourcing becomes decentralized

- Local “green” production is typically DC

Connecting local sources to AC grid cost energy and money

- Part of the “green” energy is lost in conversions before it reaches any “real” load

- DC is converted to AC and back to DC

Sharing DC bus by different sources is much simpler than AC grid

- No phase/voltage balancing

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Duke Energy 380V DC

Univ. California 380V DC

Other Japan Demos 300V/350V DC

NTT Group (several sites)

380V/400V DC

UPN AB. 350V/380V DC

Intel 380V DC

China Telecom 240V/380V DC

SAP 380V DC

Nextek 380V DC

Syracuse University 380V DC

China Mobile 380V DC

Vendor participants include: HP, IBM, EMC, Fujitsu, Hitachi,

NEC

Netpower Labs AB (several sites)

350V/380V DC Green.Ch 380V DC

France Telecom 380V DC

Telecom Data Center Buildings / Microgrids Emerson power equipment

France Telecom 380V DC

European Telecom 380V DC

North American Telecom 380V DC IBM Singapore

380V DC

Clustered Systems 380V DC

Selection of 400VDC field trials

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400V Eco-system Availability

11

DC Power System DC Breaker ICT Load Rack PDU Connector Server Power

Supply

Emerson ABB Netpower Delta* Eltek*

ABB Carling Schneider Nader Siemens GE Eaton

ServerTech* API Technologies Delta* Fujitsu*

Anderson Hubbel Rong Feng / Delta Fujitsu*

Emerson* Delta* LiteOn*

NEI – catalog products available HP – 2013 release of common slot power supply IBM* – some X and Z series available today, new power available 2014 Juniper* – products in evaluation Supermicro* – 2 servers models available for trial

*Pre-production products available

Components Are Available for the 400V DC Ecosystem, but Supply Chain Is Still Maturing

© 2013 Emerson Network Power Intellectual Property. All rights reserved

HP 1200W 380VDC/12VDC common slot power supply

Source :HP

- Common slot 1200W (100-240VAC, 48VDC, 380VDC) power unit for HP’s ”pizza” portfolio/switches, servers etc. - Highest efficiency, 94% with 380VDC interface - Commercially available

© 2013 Emerson Network Power Intellectual Property. All rights reserved

IBM 380VDC server

Source: IBM

- New 400VDC power supplies for IBM blade servers planned for release 2014

© 2013 Emerson Network Power Intellectual Property. All rights reserved

NEI 380VDC servers

Source: NEI

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Greenfield - Bulk: 400V DC Loads Redundancy Implementation Options

Distribution B Side

Bus or cable Cable or bus cont’d

(N+1)

(2N)

Bus or cable Cable or bus cont’d Cable or bus cont’d

Bus or cable

A B A B

Battery Power strips 400V Equipment Racks

Distribution A Side (Alt. 2)

400V DC UPS N+m Rectifiers Internal

Battery A Side

Battery B Side

Distribution A Side

Distribution B Side

A B

Equipment Rack

400V DC UPS N+m Rectifiers Internal

400V DC UPS N+m Rectifiers

Internal

400V DC

400V DC 400V DC

Output DC Distribution

(Alt. 1)

Distribution B Side

(Opt, Alt. 2)

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Cable saving at transision from 48V to 400V & 400V/48V, 100kW load 48V Battery

100kW/48V Telecom Eq.

1-3 x PDU 200 x 6-63A c.b.

120kW/48V Power System

400V Battery

120kW/400V Power System

1-3 x PDU 200 x 6-63A

400V

48V

100kW/48V Telecom Eq.

10m 30m 5m

Tot cable material saving ≈ 25 kEUR Distribution losses saving ≈ 1kW =1%

21kW-400V/48V

35 mm² market price 4.1 EUR/m, 150 mm²market price 19.2 EUR/m

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Available today: NetSure™ 4015 30kW 400V Integrated System Standard system offering (1) output distribution sub-rack

(1) power and controls sub-rack

(2) battery trays (back-up 20kW-7min)

Integrated into 24U 19” IT rack

HWD: 1200mm x 600mm x 1000mm

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Under Development: Integrated 120kW cabinet module

Controller

Individual input c.b. to rectifiers

Rectifiers

Output Distribution (400VDC) single section

Insulation Failure Detector

AC Input Breakers

2x250A/400VAC (A+B)

360kW power system = 3x120kW

© 2013 Emerson Network Power Intellectual Property. All rights reserved

400V information on Emerson WEB site http://www.EmersonNetworkPower.eu/400vdc

© 2013 Emerson Network Power Intellectual Property. All rights reserved

Remaining Hurdles for 400VDC

20 20

Limited components across IT ecosystem

Standards under development

Lack of familiarity with the technology

Installed base of knowledge & information

These obstacles will be overcome with additional deployments

© 2013 Emerson Network Power Intellectual Property. All rights reserved