300 MVAR Static VAR Compensator at Jacksonville, NC

Testing and Commissioning Experiences

Paper # 14TD0242 By: John O’Connor Gregory F. Reed

Dan Sullivan Nobuki Shimokaji

Joseph Birsa

1

Page 2: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

+300/-100 SVC CONFIGURATION

2

Page 3: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

3

SVC CONTROL BLOCK DIAGRAM

Page 4: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

General Testing Consideration

• Location on weak part of system

• High Delta-V/Delta Q

• Testing during light system load conditions

• System Operator (and Plant Operator) “comfort level”

• Both the manufacturer and utility would like to test as much of the range of the SVC as is possible

4

Page 5: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

PERFORMANCE TESTING GOALS

• Initial Energization

• Component Integrity Checks

– Control logic

– Cooling system

– Thyristor switching and blocking

– Full load testing for individual components

– Thermography

5

Page 6: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

PERFORMANCE TESTING GOALS

• Testing individual components

– Thyristor Controlled Reactor

– Harmonic Filter Capacitors

– Thyristor Switched Capacitors

6

Page 7: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

+300/-100 SVC at -100 MVARS 7

Page 8: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

+300/-100 SVC at +100 MVARS 8

Page 9: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

PERFORMANCE TESTING GOALS

• Response rate testing of overall SVC

• PSSE (or PSLF) simulations to determine expected grid and plant response

– Static power flow simulations sufficient to predict testing results (dynamic simulations not necessary)

• Knowing the Thevenin Equivalent Impedance (available short circuit current) is helpful

9

Page 10: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

TRANSMISSION SYSTEM

• Equipment over voltage considerations

– SVC side: step up transformer over-voltage rating is much higher than a typical T/D transformer

– Grid side: stay below 1.05 per unit and most transmission equipment voltage limits are not an issue

• Transmission circuit breaker interrupting capability voltage ratings

10

Page 11: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

DISTRIBUTION SYSTEM

• Distribution voltage limits

– Utility limit of 126 volts (on a 120 volt basis)

• Distribution voltage regulator margin

• Distribution capacitor bank status/operation

11

Page 12: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

GENERATING PLANTS

• Generator voltage limits

• Generator minimum MVAR limits

• Generator MVAR changes during testing

• Plant Operator understanding

12

Page 13: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

SYSTEM OPERATORS

• System Operator understanding

• System Operator in control of testing

– Include time for Operators to “play” with the SVC

• Contingency plans for testing problems or unforeseen occurrences

13

Page 14: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

COORDINATION OF TESTING

• Utility Transmission System Operator

• Utility Maintenance Technicians

• Utility Field Support Engineer

• Utility Transmission Planning Engineer

• Supplier Field Test Engineers

• Utility Distribution System Operator

• Utility Generating Plant Operators

14

Page 15: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Thyristor Stack (One Phase)

Page 16: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Thyristor Stack Installed

Page 17: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Thyristor Switched Capacitor (TSC)

Page 18: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Thyristor Switched Capacitor (TSC)

Page 19: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Thyristor Controlled Reactor (TCR)

Page 20: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Filter Capacitor

Page 21: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

Transformers (3 single phase + spare)

Page 22: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

SVC Control Panels in Bldg

Page 23: 300 MVAR Static VAR Compensator at Jacksonville, NC ... · PDF file300 MVAR Static VAR Compensator at Jacksonville, NC Testing and Commissioning Experiences ... •PSSE (or PSLF

QUESTIONS ?