3 4-3 transmission hodder kasztenny & fischer backupconsiderations

Upload: kleber

Post on 01-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    1/43

    Copyrigh t © Hydro One Netwo rks, Inc. and SEL 2012

    Backup Considerations for LineCurrent Differential Protection

    Steven HodderHydro One Networks, Inc.

    Bogdan Kasztenny and Normann FischerSchweitzer Engineering Laboratories, Inc.

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    2/43

    Outline

    • Line protection redundancy• Loss of 87L protection

    • 87L backup schemes♦ POTT or DCB

    ♦ Zone 1 extension

    ♦ Stepped distance♦ Overcurrent

    • Backup protection strategies

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    3/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    4/43

    Line Protection Considerations

    • Critical fault clearing time – protection type• Forced outages avoided – protection

    availability

    • HV / EHV applications♦ Breaker failure protection

    ♦ Communications-assisted schemes♦ Parallel redundancy of protection

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    5/43

    Hydro One Example

    • Operates Ontario transmission system(500, 230, and 115 kV)

    • Follows NPCC guidelines

    • Categorizes BES lines♦ Impactive

    ♦ Nonimpactive

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    6/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    7/43

    Instantaneous Tripping Lost

    • BES-impactive circuit♦ Independent electricity system operator

    (IESO) must be notified within 5 minutes ofsecond failure

    ♦ Forced line outage is immediate

    • Non-BES-impactive circuit♦ Line typically removed from service

    ♦ If removal has adverse impact on customerload, leave line in service and rely on timed

    backup only

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    8/43

    Line Current Differential Protection

    • Inherently selective• Very sensitive

    • Immune tosystem conditions

    • Easy to set

    • Dependent oncommunications

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    9/43

    Loss of 87L Protection

    • 87L element blocked• Relay out of service

    • Problems with communications♦ Channel loss

    ♦ Channel brownout

    • Inability to align local and remotecurrents – loss of time referencewhen using asymmetrical channels

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    10/43

    Loss of Time Reference

    • IRIG-B connection severed• IRIG-B signal noisy

    • Time source (external clock) malfunction

    • Time source not locked

    • GPS problems

    Using IEEE C37.118-compliant clocksthat report time quality is important

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    11/43

    87L Adaptivity to

    Channel Problems

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    12/43

    Primary Channel

    Hot Standby Channel

    Hot StandbyLogic

    Hot StandbyLogic

    87L 87L

    87L Relay 87L Relay

    Hot Standby Logic

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    13/43

    Primary Channel

    Hot Standby Channel

    Hot StandbyLogic

    Hot StandbyLogic

    87L 87L

    87L Relay 87L Relay

    Hot Standby Logic

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    14/43

    Channel 1

    C h a n n e l 2 C h a n

    n e l 3

    Master Master

    Master

    87L1

    87L2

    87L

    3

    Three-Terminal Applications

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    15/43

    Three-Terminal Applications

    C h a n n e l 2 C h a n

    n e l 3

    Slave Slave

    Master

    87L1

    87L2

    87L

    3

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    16/43

    87L

    87L

    87L

    Stub Bus Zone

    Line ZoneMaster

    Master

    Master

    Channel Loss Under Stub Bus

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    17/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    18/43

    CommunicationsRedundancy

    A87LMain Path

    B87L Alternate Path

    SONETRing #1

    A87L

    Alternate Path

    B87L

    Main Path

    SONET

    Ring #2

    Add / Drop

    MUX

    A87L B87L

    DS1MUX

    DS1MUX

    DS1MUX

    DS1MUX

    Add / DropMUX

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    19/43

    Hydro One ProtectionPhilosophy With SONET

    DS0 Protection Circuits Static (Pinned)

    • Avoid complexity (e.g., testing), especiallyas SONET network grows

    • Support protection scheme designed towork despite single communications failure

    • Ensure channel symmetry, especially forbusiness-class SONET equipment

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    20/43

    SONET Path Routing forThree-Terminal Lines

    1 2

    3

    Line

    Distance

    Line

    Distance

    LineDistance

    Main1-2

    Main2-1

    Alternate1-3

    Alternate

    3-1

    Alternate2-4

    Main

    3-4

    Alternate4-2

    Main

    4-3

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    21/43

    Communications Contingencies

    • Channel redundancy is preferred solutionfor POTT or DCB over SONET

    • Channel redundancy is limited option for

    87L schemes♦ Available for two-terminal schemes only

    when direct point-to-point channels are used

    ♦ SONET path switching may cause problems

    • 87L backup is preferred over 87L channelredundancy

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    22/43

    87L Backup

    • Backup required for rare occasions when87L is unavailable♦ Channel problems

    ♦ Timing problems

    • Backup integrated within multifunction 87Lrelay acceptable and beneficial

    • Selectivity requirements can be relaxed if87L backup engaged only when needed

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    23/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    24/43

    Directional Comparison

    • Not practical in many cases – requireschannel in addition to 87L channel

    • More difficult to set compared with 87L

    • Sensitive if 67Q / 67G used, maycause sequential tripping

    • Less secure compared with 87L

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    25/43

    Zone 1 Extension Logic

    • Substitute for extra channel atexpense of selectivity♦ Trips from overreaching Z1

    ♦ Reduces Z1 reach before reclosing

    • Less sensitive compared with 87L

    • Susceptible to load and power swings• Supplemented with 51Q / 51G and

    67Q / 67G for high-resistance faults

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    26/43

    Stepped Distance

    • Time-delayed for selectivity and coordination• Part of remote backup strategy (if used)

    • More difficult to set (infeed)

    • Less sensitive compared with 87L

    • Susceptible to load and power swings

    • Supplemented with 51Q / 51G and67Q / 67G for high-resistance faults

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    27/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    28/43

    87L Backup Strategies

    • Fully operational backup• Backup engaged only upon loss of 87L

    • Adaptive backup

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    29/43

    Fully Operational Backup

    • Parallel with 87L scheme• Requires no information about 87L state –

    standalone implementation

    • Biases protection toward dependability

    • Must be set conservatively to maintainsecurity – faces settings challenges

    • Not justified if redundant system operational

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    30/43

    Backup Engaged if 87L Lost

    • Does not adversely impact security• Can follow simpler operating principles –

    stepped distance

    • Can be biased toward dependability –Zone 1 extension

    • Faces fewer settings challenges

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    31/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    32/43

    87L

    21

    87L

    21

    87L 21

    Backup Engaged if 87L Lost

    • Master-slave mode uponfirst channel failure

    • Backup remains blocked

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    33/43

    87L

    21

    87L

    21

    87L 21

    Backup Engaged if 87L Lost

    Backup engaged whensecond channel fails

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    34/43

    87L

    21

    87L

    21

    87L 21

    Backup Engaged if 87L Lost

    Or…

    Backup engaged ifany relay is slave

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    35/43

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    36/43

    Adaptive Backup Examples

    87L /21P /21G

    87L /21P /21G

    Z AX

    Terminal A Terminal C

    Zone 2 (Timed)Zone 1 (Instantaneous)

    ZCX

    ZBX

    Terminal B

    87L / 21P / 21G

    X

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    37/43

    87L /21P /21G

    87L /21P /21G

    Z AX

    Terminal A Terminal C

    Zone 2 (Timed)Zone 1 (Instantaneous)

    ZCX

    ZBX

    Terminal B

    87L / 21P / 21G

    X

    Adaptive Backup Examples

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    38/43

    DTT A-C-B

    DTT C-B

    Master-Slave Configuration

    87L21P21G

    87L21P21G

    87L, 21P, 21G

    Terminal A Terminal C

    Terminal B

    DTT A-C

    DTT A-B

    21-1

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    39/43

    Stub Bus

    DTT Rem2 _ Local_Rem1

    DTT Rem1 _ Local_Rem2

    Z2_Pickup (Rem1)Z2_Pickup (Rem2)

    Local_Stub_Bus

    DTT Local_Rem1

    DTT Local_Rem2

    Local_DTT_TX

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    40/43

    Conclusions

    • 87L is selective, sensitive, and secure• Communications paths and equipment

    affect overall 87L availability

    • Communications and timing contingenciescan render 87L unavailable

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    41/43

    Conclusions

    • 87L backup covers failures incommunications and timing, not relays

    • Regulatory requirements and internal

    practices impact selection of backup• Typical backup schemes include 21T,

    Z1EXT, 51, and POTT or DCB

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    42/43

    Conclusions

    • Settings backup schemes are typicallymore involved than 87L

    • 87L backup elements integrated within

    same protective device are prudent• Backup only engages upon loss of 87L

    ♦ Benefits security

    ♦ Simplifies settings selection

  • 8/9/2019 3 4-3 Transmission Hodder Kasztenny & Fischer BackupConsiderations

    43/43

    Questions?