ENERGY CONVERSION ONE (Course 25741)

Chapter TwoTRANSFORMERS

…continued

Page 2: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Output Voltage of Transformer Varies with Load• Due to Voltage Drop on Series Impedance of Transformer

Equivalent Model• Full Load Regulation Parameter, compares output no-load

Voltage with its Full Load Voltage: V.R. = • At no load VS= VP / a thus : V.R.=

• in per unit: V.R. = • For Ideal Transformer V.R.=0

%100..,

..,..,

LFS

LFSLNS

VVV

%100)/(

..

..

LF

LFP

VVaV

%100,,

,,,

puFLS

puFLSpuP

VVV

Page 3: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• The transformer phasor diagram• To determine the voltage regulation of a transformer: The voltage drops should be determined• In below a Transformer equivalent circuit referred to

the secondary side shown:

Page 4: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• since current which flow in magnetizing branch is small can be ignored

• Assuming secondary phasor voltage as reference VS with an angle of 0◦

• Writing the KVL equation:

• From this equation the phasor diagram can be shown:• At lagging power factor:

SeqSeqSP IjXIRVaV

Page 5: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• If power factor is unity, VS is lower than VP so V.R. > 0

• V.R. is smaller for lagging P.F.• With a leading P.F., VS is larger VP V.R.<0• P.F. =1

• P.F. leading

Page 6: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

Table Summarize possible Value for V.R. vs Load P.F.:

• Since transformer usually operate at lagging P.F., a simplified method is introduced

Lagging P.F. VP/ a > VS V.R. > 0 Unity P.F. VP / a > VS V.R. >0 (smaller)Leading P.F. VS > VP/ a V.R. < 0

Page 7: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Simplified Voltage Regulation Calculation• For lagging loads: the vertical components

related to voltage drop on Req & Xeq partially cancel each other angle of VP/a very small

Page 8: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Transformer Efficiency (as applied to motors, generators and motors)

• Losses in Transformer: 1- Copper I²R losses 2- Core Hysteresis losses 3- Core Eddy current losses• Transformer efficiency may be determined as follows:

%100xPP

in

out %100xPP

P

lossout

out

%100cos

cos xIVPP

IV

SScoreCu

SS

Page 9: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Example:• A 15kVA, 2300/230 V transformer tested to determine

1- its excitation branch components, 2- its series impedances, and 3- its voltage regulation

• Following data taken from the primary side of the transformer:

Open Circuit Test Short Circuit TestVOC=2300 V VSC=47 V IOC=0.21A ISC=6 A

POC= 50 W PSC= 160 W

Page 10: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

(a) Find the equivalent circuit referred to H.V. side(b) Find the equivalent circuit referred to L. V. side(c) Calculate the full-load voltage regulation at 0.8 lagging PF,

1.0 PF, and at 0.8 leading PF(d) Find the efficiency at full load with PF 0.8 laggingSOLUTION:Open circuit impedance angle is:

Excitation admittance is:

8421.02300

50coscos 11

OCOC

OCOC IV

P

0000908.00000095.0

841013.984230021.084 5

jVIYOC

OCE

Page 11: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Impedance of excitation branch referred to primary:

• Short Circuit Impedance angle:

• Equivalent series Impedance:

Req=4.45 Ω, Xeq=6.45 Ω

kX

kR

M

C

110000908.01

1050000095.01

4.55647

160coscos 11

SCSC

SCSC IV

P

45.645.4

4.55833.74.55647

jIVZ SCSC

SCSE

Page 12: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• The equivalent circuits shown below:•

Page 13: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• (b) To find eq. cct. Referred to L.V. side, impedances divided by a²=NP/NS=10 RC=1050 Ω , XM=110 Ω Req=0.0445 Ω , Xeq=0.0645 Ω• (c) full load current on secondary side: IS,rated=Srated/ VS,rated=15000/230 =65.2 A To determine V.R., VP/ a is needed VP/a = VS + Req IS + j Xeq IS , and: IS=65.2/_-36.9◦ A , at PF=0.8 lagging

Page 14: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Therefore:VP / a =

V.R.=(234.85-230)/230 x 100 %=2.1 % for 0.8 lagging• At PF=0.8 leading IS=65.2/_36.9◦ A VP / a =

Vj

jj

j

4.085.23462.184.234

36.352.274.132.22301.5321.49.369.20230

9.362.650645.0)9.362.65)(0445.0(0230

Vj

jj

j

27.185.22910.58.229

36.352.274.132.22309.12621.49.369.20230

9.362.650645.0)9.362.65)(0445.0(0230

Page 15: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• V.R. = (229.85-230)/230 x 100%= -0.062% • At PF=1.0 , IS= 65.2 /_0◦ A• VP/a=

• V.R. = (232.94-230)/230 x 100% = 1.28 % for PF=1

Vj

j

j

04.194.23221.49.232

21.49.22309021.409.20230

)02.65)(0645.0()02.65)(0445.0(0230

Page 16: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• Example: Phasor Diagrams …

Page 17: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• (d) to plot V.R. as a function of load is by repeating the calculations of part “c” for many different loads using MATLAB

Page 18: 25471 Energy Conversion 6

Transformer Voltage Regulation and Efficiency

• (e) Efficiency of Transformer: - Copper losses: PCu=(IS)²Req =(65.2)² (0.0445)=189 W - Core losses: PCore= (VP/a)² / RC= (234.85)² / 1050=52.5 W output power: Pout=VSIS cosθ=230x65.2xcos36.9◦=12000 W η= VSIS cosθ / [PCu+PCore+VSIS cosθ] x 100%= 12000/ [189+52.5+12000] = 98.03 %

Page 19: 25471 Energy Conversion 6

Efficiency of Distribution Transformers

Page 20: 25471 Energy Conversion 6

Energy Losses in Electrical Energy Systems

• The total electrical energy use per annum of the world is estimated as 13,934

• TeraWatthours [TWh] (1 TWh = 10^9 kWh) • it is further estimated [2] that the losses in all of the

world’s electrical distribution systems total about 1215 TWh or

• about 8.8% of the total electrical energy consumed. About 30-35% of these losses are generated in the Transformers in the Distribution systems.

• Studies estimate that some 40-80% of these transformer losses are potentially saveable by increasing transformer efficiencies, i.e. 145-290 TWh.

Page 21: 25471 Energy Conversion 6

Electrical Energy Losses in Distribution Networks

Page 22: 25471 Energy Conversion 6

Transformer Taps & Voltage Regulation

• Distribution Transformers have a series taps in windings which permit small changes in turn ratio of transformer after leaving factory

• A typical distribution transformer has four taps in addition to nominal setting, each has a 2.5% of full load voltage with the adjacent tap

• This provides possibility for voltage adjustment below or above nominal setting by 5%

Page 23: 25471 Energy Conversion 6

Transformer Taps & Voltage Regulation

• Example: A 500 kVA, 13200/480 V distribution transformer has 4, 2.5 % taps on primary winding. What are voltage ratios?

• Five possible voltage ratings are:• +5% tap 13860/480 V• +2.5% tap 13530/480 V • Nominal rating 13200/480 V• -2.5% tap 12870/480 V• -5% tap 12540/480 V

Page 24: 25471 Energy Conversion 6

Transformer Taps & Voltage Regulation

• Taps on transformer permit transformer to be adjusted in field to accommodate variations in tap voltages

• While this tap can not be changed when power is applied to transformer

• Some times voltage varies widely with load, i.e. when high line impedance exist between generators & particular load; while normal loads should be supplied by an essentially constant voltage

• One solution is using special transformer called: “tap changing under load transformer”

• A voltage regulator is a tap changing under load transformer with built-in voltage sensing circuitry that automatically changes taps to preserve system voltage constant

Page 25: 25471 Energy Conversion 6

AUTO TRANSFORMER

• some occasions it is desirable to change voltage level only by a small amount

• i.e. may need to increase voltage from 110 to 120 V or from 13.2 to 13.8 kV

• This may be due to small increase in voltage drop that occur in a power system with long lines

• In such cases it is very expensive to hire a two full winding transformer, however a special transformer called: ”auto-transformer” can be used

Page 26: 25471 Energy Conversion 6

AUTO TRANSFORMER

• Diagram of a step-up auto-transformer shown in figure below:

• C: common, SE: series

Page 27: 25471 Energy Conversion 6

AUTO TRANSFORMER

• A step-down auto-transformer :

• IH=ISE

• IL=ISE+IC

Page 28: 25471 Energy Conversion 6

AUTO TRANSFORMER

• In step-up autotransformer:• VC / VSE = NC / NSE (1)• NC IC = NSE ISE (2)• voltages in coils are related to terminal voltages

as follows:• VL=VC (3)• VH=VC+VSE (4)• current in coils are related to terminal currents:• IL=IC+ISE (5) • IH=ISE (6)

Page 29: 25471 Energy Conversion 6

AUTO TRANSFORMER• Voltage & Current Relations in Autotransformer• VH=VC+VSE

• since VC/VSE=NC/NSE VH=VC+ NSE/NC . VC

• Noting that: VL=VC VH=VL+ NSE/NC . VL= (NSE+NC)/NC . VL

• VL / VH = NC / (NSE+NC) (7)• Current relations: • IL=IC+ISE employing Eq.(2) IC=(NSE / NC)ISE • IL= (NSE / NC)ISE + ISE, since ISE=IH IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IH IL / IH = (NSE + NC)/NC (8)

Page 30: 25471 Energy Conversion 6

AUTO TRANSFORMER• Apparent Power Rating Advantage of Autotransformer• Note : not all power transferring from primary to

secondary in autotransformer pass through windings • Therefore if a conventional transformer be

reconnected as an autotransformer, it can handle much more power than its original rating

• The input apparent power to the step-up autotransformer is : Sin=VLIL

• And the output apparent power is: Sout=VH IH

Page 31: 25471 Energy Conversion 6

AUTO TRANSFORMER• And : Sin=Sout=SIO

• Apparent power of transformer windings: SW= VCIC=VSE ISE • This apparent power can be reformulated: SW= VCIC=VL(IL-IH) =VLIL-VLIH• employing Eq.(8) SW= VLIL-VLIL NC/(NSE+NC) =VLIL [(NSE+NC)-NC] /(NSE+NC)=SIO NSE /(NSE+NC) SIO / SW = (NSE+NC) / NSE (9)

Page 32: 25471 Energy Conversion 6

AUTO TRANSFORMER

• Eq.(9); describes apparent power rating advantage of autotransformer over a conventional transformer –

• smaller the series winding the greater the advantage• Example one: A 5000 kVA autotransformer connecting

a 110 kV system to a 138 kV system has an NC/NSE of 110/28

• for this autotransformer actual winding rating is:• SW=SIO NSE/(NSE+NC)=5000 x 28/ (28+110)=1015 kVA• Example Two: A 100 VA 120/12 V transformer is

connected as a step-up autotransformer, and primary voltage of 120 applied to transformer.

Page 33: 25471 Energy Conversion 6

AUTO TRANSFORMER

(a) what is the secondary voltage of transformer(b) what is its maximum voltampere rating in this mode of operation(c) determine the rating advantage of this autotransformer connection over transformer’s rating of conventional 120/12 V operation• Solution: NC/NSE= 120/12 (or 10:1)• (a) using Eq.(7),VH= (12+120)/120 x 120 = 132 V • (b) maximum VA rating 100 VA ISE,max=100/12=8.33 A

Page 34: 25471 Energy Conversion 6

AUTO TRANSFORMER Sout=VSIS=VHIH= 132 x 8.33 = 1100 VA = Sin

(c) rating advantage: SIO/SW=(NSE+NC)/NSE=(12+120)/12=11 or: SIO/SW= 1100/100 = 11• It is not normally possible to reconnect an ordinary transformer

as an autotransformer due to the fact that insulation of L.V. side may not withstand full output voltage of autotransformer connection

• Common practice: to use autotransformer when two voltages fairly close

• Also used as variable transformers, where L.V. tap moves up & down the winding

• Disadvantage: direct physical connection between primary & secondary circuits, and electrical isolation of two sides is lost

Page 35: 25471 Energy Conversion 6

AUTO TRANSFORMER

• Internal Impedance of an Autotransformer• Another disadvantage: effective per unit

impedance of an autotransformer w.r.t. the related conventional transformer is the reciprocal of power advantage

• This is a disadvantage where the series impedance is required to limit current flows during power system faults (S.C.)

Page 36: 25471 Energy Conversion 6

AUTO TRANSFORMER

• Example three:• A transformer rated 1000 kVA, 12/1.2 kV, 60 Hz when used as a two winding conventional

transformer and its series resistance & reactance are 1 and 8 percent per unit

It is used as a 13.2/12 kV autotransformer (a) what is now the transformer’s rating ? (b) what is the transformer’s series impedance

in per unit?

Page 37: 25471 Energy Conversion 6

AUTO TRANSFORMER

• Solution: (a) NC/NSE= 12/1.2 (or 10:1) the voltage ratio of

autotransformer is 13.2/12 kV & VA rating : SIO=(1+10)/1 x 1000 kVA=11000 kVA

(b) transformer’s impedance in per-unit when connected as conventional transformer:

Zeq=0.01 + j 0.08 pu Power advantage of autotransformer is 11, so

its per unit impedance would be: Zeq=(0.01+j0.08)/11=0.00091+j0.00727 pu

Page 38: 25471 Energy Conversion 6

Example of Variable Auto-Transformer