NO 1 2 3 4 5 6 7 8 ITEM CODE 602V003 602V002 600V008 600V034 600V035 600V036 600V038 600V039 QTY 1 1 1 2 3 1 1 1 DESCRIPTION 3,200L Septic Tank 3,200L S.C.A. Tank 950L Pump Well TJ Surround, 125 thick, Ø600 Void TJ Ø700mm Lid, 65mm Thick Pump Well Surround, Ø600 Void 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC A3 D. Egan Turbojet 2000 (Sheet 1 of 3) 0 NO 17/02/2010 DATE Product Redrawn REVISIONS UNCONTROLLED ONCE PRINTED ISO 9001:2008 SIZE REV DWG NO LIFTING TOTAL MASS NOTES TITLE W: www.mcpipes.com.au T: 1300 557 143 Excavation Level Ground Level 200 mm 1660 mm 400 mm 200 mm 50 mm In-Line Configuration Sewer Inlet Pump 1 1400 mm 510*mm 1910 mm 2290 mm 1 2 8 7 710 mm Air Water Jets Pump 2 2075 mm 50 mm 710 mm 1400 mm - Top of Primary Sewage & S.C.A. tanks to be installed level - "In-Line" configuration shown here. - Min of 50mm fall of pipe between tanks. - Top of cover & surround to be 75mm above ground level. - Deeper installations require one or more risers to bring to ground level, additional saddles & risers are available in 200/400mm increments. - Manifold to be located as high as possible in the saddle or the top riser. - Concrete tanks to be manufactured to AS 1546.1 - Patent No. 45342/89 applies. Infringement will result in legal action. Ø100 PVC Inspection Pipe & Cap by Others (TYP) 1610 mm 5 75 mm Alarm Float (Refer to Sheet 3 of 3) 300 mm 550 mm 1100 mm Min 150 - 300 mm Ø100mm U.P.V.C. Droppers 125 mm Contact Tank Capacity: 740L Primary Sewage Tank Capacity: 3,200L Submerged Contact Aeration Tank Capacity: 1,880L Humus Tank Capacity: 1,320L Vortex Sludge Return Line Retention Time Minimum of 1 Hour, Average Capacity 400L D.S.P. Tablet Dispensing Chlorinator (Not Standard, by Request Only) 6 Effluent to Approved Means of Disposal by Statutory Authority Ø19mm Recirculation Pipe (To be installed by others) *Deeper installations require one or more saddles and/or risers to bring to ground level. Please advise the sewer inlet depth determined on site. All saddles and risers to be sealed. For deeper installations raise the manifold to top riser and hang Pump 1 from a stainless steel bracket and chain. Also for deeper installations where a riser is used on the contact tank, position the valve & union in the riser so they can be accessed for servicing. 75 mm 15 mm Irrigation Kit (Sold Separately) 125 mm Top of Access Covers Min 75 mm Above GL 4 Attach Submersible Pump to Tank with Bracket OR Slude return line. Ø19mm recirculation pipe to be sleeved in crush proof conduit (by others). Ø100mm UPVC Dropper Contact Media Blocks Pump 1 Ø920 mm Ø800 mm Ø710 mm - Internal Base Alarm Float Control Panel Electrical supply (by others), seperate circuit from switchboard to control panel NOT covered by RCD unit. NOT Refer to Sheet (3 of 3) 20 AMP, 240V Pump 2 Through wall or saddle. All pipework & electrical conduits to be sealed inside & outside. Contact Media Blocks 870 mm 3 550 mm Barrel Unions Non-Return Valves (Locate as high as possible in tank) Turbojet 2000 Max Hydraulic Load 2000L/day Max BOD 625g/day 17/03/2010 01/19

Upload: others

Post on 26-Mar-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2290 mm Turbojet 2000 Max Hydraulic Load Max BOD 625g/day · 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC D. Egan A3 Turbojet 2000

NO12345678

ITEM CODE602V003602V002600V008600V034600V035600V036600V038600V039

QTY11123111

DESCRIPTION3,200L Septic Tank3,200L S.C.A. Tank

950L Pump WellTJ Surround, 125 thick, Ø600 Void

TJ Ø700mm Lid, 65mm ThickPump Well Surround, Ø600 Void

400mm Turbojet Saddle200mm Turbojet Saddle

SCALEDATE

DRAWN

1:25

R. Hourani CHECKED601V002VIC

A3D. Egan

Turbojet 2000 (Sheet 1 of 3)

0NO

17/02/2010DATE

Product RedrawnREVISIONS

UNCONTROLLED ONCE PRINTED

ISO 9001:2008

SIZE

REVDWG NO

LIFTING

TOTAL MASS

NOTES

TITLEW: www.mcpipes.com.au T: 1300 557 143

Excavation Level

Ground Level200 mm

1660 mm

400 mm 2

00 m

m 50

mm

In-Line Configuration

SewerInlet

Pum

p 1

1400 mm

510*mm

1910 mm

2290 mm

12

8

7

710 mm

Air Water Jets

Pum

p 2

2075 mm

50

mm

710 mm

1400 mm

- Top of Primary Sewage& S.C.A. tanks to beinstalled level- "In-Line" configurationshown here.- Min of 50mm fall of pipebetween tanks.- Top of cover & surroundto be 75mm aboveground level.- Deeper installationsrequire one or morerisers to bring to groundlevel, additional saddles& risers are available in200/400mm increments.- Manifold to be locatedas high as possible in thesaddle or the top riser.- Concrete tanks to bemanufactured toAS 1546.1- Patent No. 45342/89applies. Infringementwill result in legal action.

Ø100 PVCInspection

Pipe & Cap byOthers (TYP)

1610 mm

5

75 mm

Alarm Float(Refer to Sheet 3 of 3)

300 mm

550 mm

1100 mmMin

150 - 300 mm

Ø100mm U.P.V.C.Droppers

125 mm

Contact TankCapacity: 740L

Primary Sewage TankCapacity: 3,200L

Submerged ContactAeration TankCapacity: 1,880L

Humus TankCapacity: 1,320L

Vortex SludgeReturn Line

Retention Time Minimum of1 Hour, Average Capacity 400L

D.S.P. TabletDispensing Chlorinator

(Not Standard, by Request Only) 6 Effluent to ApprovedMeans of Disposal byStatutory Authority

Ø19mm Recirculation Pipe(To be installed by others)

*Deeper installations require one or more saddlesand/or risers to bring to ground level. Please advisethe sewer inlet depth determined on site. All saddlesand risers to be sealed. For deeper installations raisethe manifold to top riser and hang Pump 1 from a stainlesssteel bracket and chain. Also for deeper installationswhere a riser is used on the contact tank, position thevalve & union in the riser so they can be accessed for servicing.

75 mm

15

mm

Irrigation Kit(Sold Separately)

125 mm

Top of AccessCovers Min

75 mm Above GL4

Attach SubmersiblePump to Tank with Bracket

OR

Slude return line. Ø19mm recirculationpipe to be sleeved in crushproof conduit (by others).

Ø100mm UPVC Dropper

Contact MediaBlocks

Pump 1

Ø920 mm

Ø800 mm

Ø710 mm - Internal Base

Alarm Float

Con

trol

Pane

l Electrical supply(by others), seperate

circuit fromswitchboard to

control panel NOTcovered by RCD

unit.

NOT

Refer to Sheet (3 of 3)

20 AMP, 240V

Pump 2

Through wall or saddle.All pipework & electrical

conduits to be sealedinside & outside.

Contact Media Blocks

870 mm

3

550 mm

Barrel Unions

Non-ReturnValves

(Locate as high aspossible in tank)

Turbojet 2000Max Hydraulic Load

2000L/dayMax BOD 625g/day

17/03/2010 01/19

Page 2: 2290 mm Turbojet 2000 Max Hydraulic Load Max BOD 625g/day · 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC D. Egan A3 Turbojet 2000

NO12345678

ITEM CODE602V003602V002600V008600V034600V035600V036600V038600V039

QTY11123111

DESCRIPTION3,200L Septic Tank3,200L S.C.A. Tank

950L Pump WellTJ Surround, 125 thick, Ø600 Void

TJ Ø700mm Lid, 65mm ThickPump Well Surround, Ø600 Void

400mm Turbojet Saddle200mm Turbojet Saddle

SCALEDATE

DRAWN

1:25

R. Hourani CHECKED601V002VIC

A3D. Egan

Turbojet 2000 (Sheet 2 of 3)

0NO

15/03/2010DATE

Product RedrawnREVISIONS

UNCONTROLLED ONCE PRINTED

ISO 9001:2008

SIZE

REVDWG NO

LIFTING

TOTAL MASS

NOTES

TITLEW: www.mcpipes.com.au T: 1300 557 143

Horse Shoe Configuration

- Top of Primary Sewage& S.C.A. tanks to beinstalled level- "In-Line" configurationshown here.- Min of 50mm fall of pipebetween tanks.- Top of cover & surroundto be 75mm aboveground level.- Deeper installationsrequire one or morerisers to bring to groundlevel, additional saddles& risers are available in200/400mm increments.- Manifold to be locatedas high as possible in thesaddle or the top riser.- Concrete tanks to bemanufactured toAS 1546.1- Patent No. 45342/89applies. Infringementwill result in legal action.

1660 mm

Contact TankCapacity: 740L

Primary Sewage TankCapacity: 3,200L

ORAlarm Float

Control

Panel

Electrical supply(by others), seperate

circuit fromswitchboard to

control panel NOTcovered By RCD

unit.

Refer to Sheet (3 of 3)20 AMP, 240V

NOT

Submerged ContactAeration TankCapacity: 1,880L

Humus TankCapacity: 1,320L

2290 mm

Slude return line. Ø19mm recirculationpipe to be sleeved in crush

proof conduit (by others).

House

Inlet

3600 mm900 mm

4200

mm

2900 mm

Pump 2

Excavation Parameter

1610

mm

1200 mm

4200 mm

290 mm

300 mm

290 mm

2110

mm

1910

mm

200

mm

2100 mm 2100 mm

Excavation Level

75 mm75 mm

520 mm

160 mm

OutletInlet

1400

mm

510*mm

125 mm4 5

78

1

2

Ground Level

PLAN VIEW SIDE VIEW A-A

3

Through wall or saddle.All pipework & electrical

conduits to be sealedinside & outside.

Primary Sewage TankCapacity: 3,200L

Submerged ContactAeration TankCapacity: 1,880L

*Deeper installations require one or more saddlesand/or risers to bring to ground level. Please advisethe sewer inlet depth determined on site. All saddlesand risers to be sealed. For deeper installations raisethe manifold to top riser and hang Pump 1 from a stainlesssteel bracket and chain. Also for deeper installationswhere a riser is used on the contact tank, position thevalve & union in the riser so they can be accessed for servicing.

Ø100mm UPVC Dropper

Pump 1

Contact MediaBlocks

Turbojet 2000Max Hydraulic Load

2000L/dayMax BOD 625g/day

17/03/2010 01/19

Page 3: 2290 mm Turbojet 2000 Max Hydraulic Load Max BOD 625g/day · 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC D. Egan A3 Turbojet 2000

NO123

ITEM CODE QTY DESCRIPTIONSCALEDATE

DRAWN

1:2524/03/2010R. Hourani CHECKED

601V002VIC 0A3D. Egan

Turbojet 2000 (Sheet 3 of 3)

0NO

24/03/2010DATE

Product RedrawnREVISIONS

UNCONTROLLED ONCE PRINTED

ISO 9001:2008

SIZE

REVDWG NO

LIFTING

TOTAL MASS

CONCRETE GRADE

NOTES

TITLEW: www.mcpipes.com.au T: 1300 557 143

Please read these instructions carefully. It is critical that the system is wired to Icon-Septech specificationsso that the plant may be commissioned appropriately, and so that warranties are NOT made void.

1. Mount the controller approximately 1.5m to 1.7m from the finished ground level on the external structure that allows good accessfor future servicing.2. All conduits and unused penetrations must be sealed inside and outside against moisture and vermin.3. All work must be carried out by a licenced electrical contractor in accordance with the local authorities and regulations.4. Hard wire the controller from an independent 20 Amp circuit from the switchboard NOT RCD protected.5. Cables extended from the controller to each piece of equipment in the treatment plant must be, independent, continuous,heavy duty submersible flex (Versolex or approved equivalent).6. Cables extended from the controller must ONLY be joined to each piece of equipment in an accessible location within the treatment plant.At least 1.0m spare controller cable must be left, so that the piece of equipment may be brought to the surface and maintained.

Pum

p 1

Pum

p 2

Alarm Float(Refer to Sheet 2 of 2)

300 mm

550 mm

7. Join cables to each piece of equipment using in line crimp lugs in a staggered formation, individually insulated with resin cored heatshrink. Then insulate overall with resin cored heat shrink ensuring an overlap at each end of at least 50mm.

Control Panel Mk 5 Installation & Specs

AE N

A A

RemoteAlarm

A AN NE EPump 1 Pump 2

(Circulation) (Irrigation)6 Amp 6 Amp

Alarm Float(N/Closed Contacts Used)

20mm HDConduit to

SubmergedContactAeration

Tank

25mm HD Conduitto Contact

(Irrigation) Tank

240V Supply, seperate20 Amp circuit fromswitch board. (Notconnected to RCD

unit.)

50 mm, sand paper scratched& cleaned with primer fluid.

12mm resin core heat shrink

9mm resin core heat shrink

1.5mm copper crimp lugs

ControlPanel

1.0m of spare cable, coiled,cable-tied and positionedas high as possiblein the tank or saddle/riser.

25mm HD Conduit

Contact TankSubmerged ContactAeration Tank Humus Tank

20mm HDConduit

3 Core Versolex Cable

2 Core Versolex Cable

8. The float switch circuit is 3 Volts. Use normally closed contacts for high water (alarm float).

15

mm