    STUDY OF SUBSTATION

    EQUIPMENT ANDPROTECTION

  • 7/31/2019 220 Kv Station

    2/32

    ABSTRACT:

    The economics of generation of electrical

    energy and the huge demands of powerin the modern times require creationbigger power plant . These may be hydro, thermal , atomic etc . The transmission

    network is inevitable . large and highvoltage transmission lines are necessaryto transmit huge blocks of power fromthe source of generation to load centers .

    In b/w the power plant and ultimateconsumer a number of transmission andswitching stations have to be created .This is done by SUBSTATION

  • 7/31/2019 220 Kv Station

    3/32

  • 7/31/2019 220 Kv Station

    4/32

    Major equipments of

    Substation

    Power Transformers Bus Bars

    Circuit breakers

    Isolators Relays

    Control Panels

    Instrument Transformers

    DC System

  • 7/31/2019 220 Kv Station

    5/32

    Power Transformers

  • 7/31/2019 220 Kv Station

    6/32

  • 7/31/2019 220 Kv Station

    7/32

  • 7/31/2019 220 Kv Station

    8/32

  • 7/31/2019 220 Kv Station

    9/32

  • 7/31/2019 220 Kv Station

    10/32

  • 7/31/2019 220 Kv Station

    11/32

    BUS BARS

    The choice of the bus bars scheme for

    a substation depends upon the degree

    of reliability and economic justification.The degree of reliability is evaluated

    by determining the continuity of

    service and possible faults.TYPES OF BUS BARS

    ARRANGEMENTS:

  • 7/31/2019 220 Kv Station

    12/32

    ARRANGEMENT

    SSSSSSSSI

    This system is used for 132 KV

    substations. It is cheapestamong all the others bus bars. It

    is totally shut down in case of a

    fault.

  • 7/31/2019 220 Kv Station

    13/32

    DOUBLE BUS BARS: This system is costlier then a single bus bars

    system. One bus can serve as reserve, which is

    used during maintenance or fault. It is used for 220

    KV sub stations.

  • 7/31/2019 220 Kv Station

    14/32

    CIRCUIT BREAKERS

    Circuit breaker is automatic switching device which can

    carrying normal current and switching in & out normalloads

    Interrupt short circuiting currents

    Able to performer auto reclose duty. Classification of Circuit breaker:

    Based on VOLTAGE

    Low-less than 1kv

    Medium-1kv to 52kv

    High/Extra High-66kv to 765kv

    Ultra High-above 765kv

  • 7/31/2019 220 Kv Station

    15/32

    Based on LOCATION Indoor

    Outdoor

    Based on INTERRUPTING MEDIUM

    Air breakAir break Circuit breaker(ACB)

    Air blastAir blast Circuit breaker..(ABCB)

    Bulk oil.. Bulk oil Circuit breaker.(BOCB)

    Minimum oil..Minimum oil Circuit breaker.(MOCB)

    SF6 gas insulated.SF6 Circuit breaker

    Vacuum Vacuum Circuit breaker(VCB)

    Selection of a CB depends on:

    Type of application Rated voltage, current

    Its breaking capacity(fault level of the installation)

    Auto-reclose duty cycle

  • 7/31/2019 220 Kv Station

    16/32

    SF6 CIRCUIT BREAKER

  • 7/31/2019 220 Kv Station

    17/32

    Opening operation: Opening is affected by pulling the insulating rod

    (201), piston rod (111), puffer cylinder (110)moving contact, moving arc contact (107) andthe nozzle (105).After contacts wipe the

    stationary and moving and contact (104), (107)separate, there by generating arc. During downward movement the gas in puffer chamber buildsup and high pressure gas flows through nozzleand quenches the arc.

    Closing Operation: In closing operation, insulating rod (201) is pulled

    up and the parts move in the reverse direction ofopening operation. And also SF6 gas taken in topuffer chamber.

  • 7/31/2019 220 Kv Station

    18/32

    ADVANTAGES OF SF6 CB

    Mostly widely used in EHV application

    Low operating noise

    Simple construction & compact size

    Easy installation, inspection &

    maintenance.

    SF6 is identified as a green house

    gas.

  • 7/31/2019 220 Kv Station

    19/32

    POTENTIAL TRANSFORMER

  • 7/31/2019 220 Kv Station

    20/32

    What are Relays?

    Relays are electrical switches

    that open or close another

    circuit under certain conditions.

  • 7/31/2019 220 Kv Station

    21/32

    Relay Purpose

    Isolate controlling circuit from controlled circuit.

    Control high voltage system with low voltage.

    Control high current system with low current.

    Logic Functions

  • 7/31/2019 220 Kv Station

    22/32

    How a Relay Works

  • 7/31/2019 220 Kv Station

    23/32

    How a Relay Works

  • 7/31/2019 220 Kv Station

    24/32

    INSTRUMENT TRANSFORMERS

    INSTRUMENT TRANSFORMERS: Current transformer

    Potential transformer

    Current transformer: Currenttransformer are used for supplying the

    current circuits of indicatinginstruments (ammeters, watt metersetc) recording meters (energy metersetc) and protective relays.

  • 7/31/2019 220 Kv Station

    25/32

    CT is ideally a short circuitedtransformer where the secondary

    terminal voltage is zero, and the

    magnetizing current is negligible. Ip*Np =Is*Ns

    Ratio error

    Phase angle error Composite error

  • 7/31/2019 220 Kv Station

    26/32

    CURRENT TRANSFORMER

  • 7/31/2019 220 Kv Station

    27/32

  • 7/31/2019 220 Kv Station

    28/32

  • 7/31/2019 220 Kv Station

    29/32

    VOLTAGE TRANSFORMER: These instrument are used for supplying the voltage

    circuit of indicating instruments, meters, and protectiverelay.

    All voltage transformer are designed for a standardsecondary voltage of 110v, 110/1.732 (63.5)

    For voltage transformers at the following is valid:

    Ep/Es=Np/Ns

    Actual voltage ratio =Primary volts/secondary volts

    Voltage transformer errors:

    A) voltage ratio error B) Phase angle error.

    The errors at which the VTs operate depend on itsburden and primary voltage