Page 1: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

© 2020 Colorado Code Consulting, LLC 1

2018 International Residential CodeChapter 3 Building Planning

Page 2: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 1

© 2020 Colorado Code Consulting, LLC 1

2018 International Residential CodeChapter 3 Building Planning 2

Instructor

Gil RossmillerIn the construction industry for over 40 yearsICC – IRC Plumbing & Mechanical Code Development Committee ICC – Commercial Energy Code Development Committee 2003-2016 Building Official Parker, Colorado

© 2020 Colorado Code Consulting, LLC

What are we going to talk about?

Chapter 3 Building Planning Non-structural

provisions Fire-resistant rated

construction Egress Openings Means of Egress Safety glazing Photovoltaic Systems

© 2020 Colorado Code Consulting, LLC 3

International Residential CodeScope Detached One

Family Dwellings Detached Two

Family Dwellings Townhouses

© 2020 Colorado Code Consulting, LLC 4

Page 3: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 2

R301.1 Application

Buildings and structures, and all parts thereof, shall be constructed to safely support all loads, including dead loads, live loads, roof loads, flood loads, snow loads, wind loads and seismic loads as prescribed by this code.

© 2020 Colorado Code Consulting, LLC 5

R301.1 Application The construction of

buildings and structures in accordance with the provisions of this code shall result in a system that provides a complete load path that meets all requirements for the transfer of all loads from their point of origin through the load-resisting elements to the foundation.

© 2020 Colorado Code Consulting, LLC 6

R301.1.1 Alternative provisions As an alternative to the

requirements in Section R301.1 the following standards are permitted subject to the limitations of this code and the limitations therein.

Where engineered design is used in conjunction with these standards, the design shall comply with the International Building Code.

© 2020 Colorado Code Consulting, LLC 7

R301.1.1 Alternative provisions1. AF&PA Wood Frame

Construction Manual (WFCM).

2. AISI Standard for Cold-Formed Steel Framing—Prescriptive Method for One- and Two-Family Dwellings (AISI S230).

3. ICC Standard on the Design and Construction of Log Structures (ICC 400).

© 2020 Colorado Code Consulting, LLC 8

Page 4: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 3

© 2020 Colorado Code Consulting, LLC 9

Construction SystemsR301.1.2

Wood: Platform Frame Balloon Frame

Concrete or Masonry: Balloon Frame

Other systems: Designed per

accepted engineering practices

© 2020 Colorado Code Consulting, LLC 10

Climatic and geographic design criteria - Table R301.2(1)

R301.2.1.1 - Wind limitations and wind design required The wind provisions of this code

shall not apply to the design of buildings where wind design is required in accordance with Figure R301.2(4)B or where the basic wind speed from Figure R301.2(4)A equals or exceeds 110 miles per hour (49 m/s).

Exceptions: 1. For concrete construction, the

wind provisions of this code shall apply in accordance with the limitations of Sections R404 and R611.

2. For structural insulated panels, the wind provisions of this code shall apply in accordance with the limitations of Section R613.

© 2020 Colorado Code Consulting, LLC 11

R301.2.1.1 - Wind limitations and wind design required In regions where wind design is

required in accordance with Figure R301.2(4)B or where the basic wind speed shown on Figure R301.2(4)A equals or exceeds 110 miles per hour, the design of buildings for wind loads shall be in accordance with one or more of the following methods: 1. AF&PA Wood Frame Construction

Manual (WFCM); or 2. ICC Standard for Residential

Construction in High-Wind Regions (ICC 600); or

3. ASCE Minimum Design Loads for Buildings and Other Structures (ASCE 7); or

4. AISI Standard for Cold-Formed Steel Framing—Prescriptive Method For One-and Two-Family Dwellings (AISI S230); or

5. International Building Code.

© 2020 Colorado Code Consulting, LLC 12

Page 5: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 4

R301.2.2 Seismic provisions The seismic provisions

of this code shall apply as follows: 1. Townhouses in

Seismic Design Categories C, D0, D1 and D2.

2. Detached one- and two-family dwellings in Seismic Design Categories, D0, D1 and D2.

© 2020 Colorado Code Consulting, LLC 13

R301.3Story Height (Wind & Seismic)

Wood wall framing 11 feet 7 inches and

Table R602.3(5) Cold-formed steel wall

framing 11 feet 7 inches and

maximum 10 feet unsupported stud height

Masonry 13 feet 7 inches 12 feet bearing wall clear

height

© 2020 Colorado Code Consulting, LLC 14

R301.3Story Height

Insulated concrete form walls 11 feet 7 inches and

maximum unsupported wall height per Tables R608

SIP walls 11 feet 7 inches and

Section R610 tables not to exceed 10 feet

© 2020 Colorado Code Consulting, LLC 15 © 2020 Colorado Code Consulting, LLC 16

Live Load - Table R301.5

Page 6: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 5

R301.7 Deflection The allowable

deflection of any structural member under the live load listed in Sections R301.5 and R301.6 or wind loads determined by Section R301.2.1 shall not exceed the values in Table R301.7.

© 2020 Colorado Code Consulting, LLC 17

R302Fire Resistant Construction

Moves everything fire-resistance related to R302 Exterior Walls Townhouse Separation Two-Family Separation Penetrations Garage to Dwelling Under Stairs Foam Plastics Interior Finishes Fireblocking Draftstopping Insulation

© 2020 Colorado Code Consulting, LLC 18

R302.1Exterior Walls

Construction, projections, openings and penetrations of exterior walls of dwellings and accessory buildings shall comply with Table R302.1(1); or dwellings equipped throughout with an automatic sprinkler system installed in accordance with Section P2904 shall comply with Table R302.1(2).

© 2020 Colorado Code Consulting, LLC 19

Location on Lot - R302

© 2020 Colorado Code Consulting, LLC 20

a. The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.

b. The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake overhang where gable vent openings are not installed.

Page 7: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 6

Table R302.1 (1) footnote: a

© 2020 Colorado Code Consulting, LLC 21

Table R302.1 (1) footnote: b

© 2020 Colorado Code Consulting, LLC 22

Gable vent not allowed

© 2020 Colorado Code Consulting, LLC 23

Location on Lot - R302

2 Feet

a. For residential subdivisions where all dwellings are equipped throughout with an automatic sprinkler system installed in accordance with Section P2904, the fire separation distance for exterior walls not fire-resistance rated and for fire-resistance-rated projections shall be permitted to be reduced to 0 feet, and unlimited unprotected openings and penetrations shall be permitted, where the adjoining lot provides an open setback yard that is 6 feet or more in width on the opposite side of the property line.b. The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.c. The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake overhang where gable vent openings are not installed.

Table R302.1(2)Footnote A For residential subdivisions

where all dwellings are equipped throughout with an automatic sprinkler systems installed in accordance with Section P2904, the fire separation distance for nonrated exterior walls and rated projections shall be permitted to be reduced to 0 feet, and unlimited unprotected openings and penetrations shall be permitted, where the adjoining lot provides an open setback yard that is 6 feet or more in width on the opposite side of the property line.

© 2020 Colorado Code Consulting, LLC 24

6 ft.

Page 8: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 7

302.1 Exterior WallsExceptions1. Walls, projections, openings or penetrations in walls perpendicular to the line used to determine the fire separation distance.2. Walls of dwellings and accessory structures located on the same lot.3. Detached tool sheds and storage sheds, playhouses and similar structures exempted from permits are not required to provide wall protection based on location on the lot. Projections beyond the exterior wall shall not extend over the lot line.4. Detached garages accessory to a dwelling located within 2 feet of a lot line are permitted to have roof eave projections not exceeding 4 inches.5. Foundation vents installed in compliance with this code are permitted.

© 2020 Colorado Code Consulting, LLC 25

Site/Plot Plan An overhead

diagram of the property including property lines the building outline, and other improvements on the property

Dimensions to building

© 2020 Colorado Code Consulting, LLC 26

© 2020 Colorado Code Consulting, LLC 27© 2020 Colorado Code Consulting, LLC

28

Face of wall to Property Line

Prop

erty

Lin

e

Page 9: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 8

R302.2 TownhousesWalls separating townhouse units shall be constructed in accordance with Section R302.2.1 or R302.2.2.

Common walls separating townhouses shall be assigned a fire-resistance rating in accordance with Section R302.2, Item 1 or 2. 1. Sprinklers = 1-hour 2. No Sprinklers = 2 hours

© 2020 Colorado Code Consulting, LLC 29

R302.2 TownhousesWalls separating townhouse units shall be constructed in accordance with Section R302.2.1 or R302.2.2.

R302.2.1 Double wallsEach townhouse shall be separated by two 1-hour fire-resistance-rated wall assemblies tested in accordance with ASTM E119, UL 263 or Section 703.3 of the International Building Code.

© 2020 Colorado Code Consulting, LLC 30

R302.2 Townhouses

The common wall shared by two townhouses shall be constructed without plumbing or mechanical equipment, ducts or vents in the cavity of the common wall.

The wall shall be rated for fire exposure from both sides and shall extend to and be tight against exterior walls and the underside of the roof sheathing

© 2020 Colorado Code Consulting, LLC 31

Townhouse Separation Wall

© 2020 Colorado Code Consulting, LLC 32

Page 10: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 9

ContinuityR302.2.1

The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.

© 2020 Colorado Code Consulting, LLC 33

ParapetR302.2.2

1. Where roof surfaces adjacent to the wall or walls are at the same elevation, the parapet shall extend not less than 30 inches above the roof surfaces.

© 2020 Colorado Code Consulting, LLC 34

ParapetR302.2.2

2. Where roof surfaces adjacent to the wall or walls are at different elevations and the higher roof is not more than 30 inches above the lower roof, the parapet shall extend not less than 30 inches above the lower roof surface.

© 2020 Colorado Code Consulting, LLC 35

ParapetR302.2.2

A parapet is not required in previous two situations Roof is covered with a minimum class C roof covering Roof sheathing is noncombustible materials or approved fire-retardant-treated wood

for a distance of 4 feet on each side of the wall or walls, or one layer of 5 /8 -inch Type X gypsum board is installed directly beneath the roof

sheathing for a distance of 4 feet on each side of the wall or wallsand any openings or penetrations in the roof are not within 4 feet of the common walls..

© 2020 Colorado Code Consulting, LLC 36

Page 11: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 10

ParapetR302.2.2

© 2020 Colorado Code Consulting, LLC 37

A parapet is not required:

• Different elevations and the higher roof is more than 30 inches above the lower roof.

• Common wall construction from the lower roof to the underside of the higher roof deck shall not have less than a 1-hour fire-resistive rating. Dwelling “A” Dwelling “B”

>30”

roof

roof

One-hourwall1 HR

Parapet ConstructionR302.2.3

Same fire resistance of supporting wall

non-combustible faces at uppermost 18”

>2:12 roof slope extend to same

height or roof 3’ away, not less than 30”

© 2020 Colorado Code Consulting, LLC 38

Structural IndependenceR302.2.4

Each townhouse shall be structurally independent

Exceptions: foundations roof & wall sheathing may

fasten to common wall nonstructural wall coverings flashing common wall separation

© 2020 Colorado Code Consulting, LLC 39

Dwelling Unit SeparationR302.3

Two-family dwellings One-hour fire-resistive

wall and/or floor assembly ASTM E119 / UL263 Extend to and against

exterior wall and to underside of roof sheathing

© 2020 Colorado Code Consulting, LLC 40

Page 12: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 11

Dwelling Unit SeparationR302.3 Exception 1 ½ hour separation when buildings are

equipped with NFPA 13 Sprinklers

© 2020 Colorado Code Consulting, LLC 41

Dwelling Unit SeparationR302.3 Exception 2. Wall assemblies need not

extend through attic spaces 5/8-inch Type X ceiling and an attic draft stop provided above and along the wall separating the dwellings.

Framing supporting the ceiling shall also be protected by 1/2-inch gypsum board or equivalent.

© 2020 Colorado Code Consulting, LLC 42

R302.3.1 Supporting construction When floor

assemblies are required to be fire-resistance rated by Section R302.3, the supporting construction of such assemblies shall have an equal or greater fire-resistance rating.

© 2020 Colorado Code Consulting, LLC 43

Rated PenetrationsR302.4

Through penetrations of fire-resistance-rated assemblies approved penetration

fire stop system F rating equal to

separation rating Membrane penetrations

approved penetration fire stop system

© 2020 Colorado Code Consulting, LLC 44

Page 13: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 12

Through Penetration ExceptionsR317.3.1

Penetrating items - steel, ferrous or copper pipes or steel conduits concrete/masonry wall

or floor assembly max. 6” diameter, max 144 sq. in. - concrete, grout or mortar OK

material in annular space prevents passage of flame or hot gases.

© 2020 Colorado Code Consulting, LLC 45

Membrane PenetrationsR302.4

recessed light fixtures to be installed so fire resistance not reduced

Exceptions: steel electrical boxes - total area not to

exceed 100 sq. in. in 100 sq. ft. separated from other boxes

24” horizontally Depth of wall cavity with insulation Listed putty pads Other listed materials & methods

rated nonmetallic boxes with above separations

sprinkler penetration with escutcheon

© 2020 Colorado Code Consulting, LLC 46

Garages & CarportsR302.5

No openings into sleeping room

Other openings solid wood door 1 3/8” honeycomb core steel door 1

3/8” 20-minute fire-rated Self-closing

Ducts 26 gauge or other approved

material

© 2020 Colorado Code Consulting, LLC 47

R302.5.3 Other penetrations Must be protected as

required by Section R302.11, Item 4.

An approved material to resist the free passage of flame and products of combustion.

The material filling this annular space shall not be required to meet the ASTM E 136 requirements.

© 2020 Colorado Code Consulting, LLC 48

Page 14: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 13

Separation RequiredTable R302.6

© 2020 Colorado Code Consulting, LLC 49

Table R302.6 Dwelling/Garage Separation

© 2020 Colorado Code Consulting, LLC 50

Under Stair ProtectionR302.7

Enclosed space under stairs that is accessed by a door or access panel shall have walls, under-stair surface and any soffits protected on the enclosed side with 1/2-inch gypsum board.

© 2020 Colorado Code Consulting, LLC 51

302.9 Interior Finishes

Flame spread = 200 max.

Smoke Developed = 450 max.

Tested per ASTM E84 / UL 723 –Steiner Tunnel

© 2020 Colorado Code Consulting, LLC 52

Page 15: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 14

InsulationR302.10

Flame-spread index not to exceed 25 with an accompanying smoke-developed index not to exceed 450Insulating materials, where tested in accordance with the requirements of this section, shall include facings, where used, such as vapor retarders, vapor permeable membranes and similar coverings.

Except:facings in substantial contact with unexposed surface of ceiling, floor, or wall finishCellulose loose-fill (not spray applied) per Section R302.10.3 SD = 450 onlyFoam Plastic – R316

© 2020 Colorado Code Consulting, LLC 53

Fire BlockingR302.11

In concealed spaces of stud walls and partitions, including furred spaces and parallel rows of studs or staggered studs; as follows: 1.1. Vertically at the ceiling

and floor levels. 1.2. Horizontally at intervals

not exceeding 10 feet

© 2020 Colorado Code Consulting, LLC 54

Fire BlockingR302.11

2. At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings.

© 2020 Colorado Code Consulting, LLC 55

Fire BlockingR302.11

3. In concealed spaces between stair stringers at the top and bottom of the run.

© 2020 Colorado Code Consulting, LLC 56

Page 16: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 15

Fire BlockingR302.11

4. At openings around vents, pipes, and ducts at ceiling and floor level, with an approved material to resist the free passage of flame and products of combustion.

© 2020 Colorado Code Consulting, LLC 57

Fire BlockingR302.11

5. For the fire blocking of chimneys and fireplaces, see Section R1001.16.

© 2020 Colorado Code Consulting, LLC 58

ApprovedNon‐combustiblefire stop

Floor level

Fire BlockingR302.11

6. Fire blocking of cornices of a two-family dwelling is required at the line of dwelling unit separation.

© 2020 Colorado Code Consulting, LLC 59

Fire Block MaterialR302.11.1

2" nominal lumber or two 1" 23/32" structural panel

backed 3/4" particle board backed 1/2” gypsum board 1/4” cement based millboard Batts or blankets of mineral

wool or glass fiber or other approved materials installed in such a manner as to be securely retained in place.

Cellulose insulation installed as tested for the specific application.

© 2020 Colorado Code Consulting, LLC 60

Page 17: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 16

R302.11.1.1 - Batts or blankets of mineral or glass fiber Batts or blankets of

mineral or glass fiber or other approved nonrigid materials shall be permitted for compliance with the 10-foot horizontal fireblocking in walls constructed using parallel rows of studs or staggered studs.

© 2020 Colorado Code Consulting, LLC 61

R302.11.1.2 Unfaced fiberglass Unfaced fiberglass batt

insulation used as fireblocking shall fill the entire cross section of the wall cavity to a minimum height of 16 inches measured vertically.

When piping, conduit or similar obstructions are encountered, the insulation shall be packed tightly around the obstruction.

© 2020 Colorado Code Consulting, LLC 62

R302.11.1.3 Loose-fill insulation material

Loose-fill insulation material shall not be used as a fireblockunless specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and to retard the spread of fire and hot gases.

© 2020 Colorado Code Consulting, LLC 63

Draftstopping RequiredR302.12

Usable space above & below Suspended ceiling, open-web trusses No concealed area exceeds 1,000 s.f., divided equally

© 2020 Colorado Code Consulting, LLC 64

Page 18: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 17

R302.12.1 Draftstopping Materials 1/2-inch gypsum board 3/8-inch wood structural

panels other approved materials

adequately supported Must be installed parallel

to the floor framing members unless otherwise approved by the building official.

The integrity of the draftstops shall be maintained.

© 2020 Colorado Code Consulting, LLC 65

R302.13Fire Protection of Floors

Non FR floorassemblies:

…shall be provided with ½” Gypsum Board 5/8” Wood Structural

Panel Or equivalent…

…on the underside of the floor framing member

66© 2020 Colorado Code Consulting, LLC

R302.13Fire Protection of Floors

Penetrations or openings for ducts, vents, electrical outlets, lighting, devices, luminaires, wires, speakers, drainage, piping and similar openings or penetrations shall be permitted (in ceiling membrane).

© 2020 Colorado Code Consulting, LLC 67

R302.13 – Fire Protection of Floors

Exception 1 Floor assemblies

located directly over a space protected by fire sprinklers P2904 NFPA 13d

68© 2020 Colorado Code Consulting, LLC

Page 19: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 18

R302.13 – Fire Protection of Floors Exception 2

Floor assemblies located directly over a crawl space not intended for storage or for the installation of fuel-fired or electric heating appliances

Intended to recognize conditions where low fuel loading will occur.

69© 2020 Colorado Code Consulting, LLC

R302.13 – Fire Protection of Floors

Exception 3 Permits unprotected

floor assemblies when: 80sf area or less per

story in aggregate Fire blocking is provided

in the cavity between the protected and unprotected portions

Intended to address mechanical areas with piping, ducts or other penetration issues.

70© 2020 Colorado Code Consulting, LLC

R302.13 – Fire Protection of Floors

Exception 4 Wood floor

assemblies using 2x10 or greater dimension solid or composite lumber.

Also permits testing for equivalency to these materials.

71© 2020 Colorado Code Consulting, LLC

R302.14 Combustible insulation clearance Combustible

insulation must be separated a minimum of 3 inches from recessed luminaires, fan motors and other heat-producing devices.

Exception: Where devices are listed for lesser clearances

© 2020 Colorado Code Consulting, LLC 72

Page 20: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 19

© 2020 Colorado Code Consulting, LLC 73

Natural light & ventilationR303.1

Habitable Rooms Aggregate glazing area

of 8 percent of floor area of room

Natural ventilation via openings to the outdoor air shall be 4 percent of the floor area.

Light, Ventilation & HeatingR303.1 Exceptions 1. The glazed areas

need not be openable where an egress opening is not required and a whole-house mechanical ventilation system is installed per Section M1507.

© 2020 Colorado Code Consulting, LLC 74

Light, Ventilation & HeatingR303.1 Exceptions 2. The glazed areas

need not be installed in rooms where Exception 1 above is satisfied and artificial light is provided capable of producing an average illumination of 6 footcandles over the area of the room at a height of 30 inches above the floor level.

© 2020 Colorado Code Consulting, LLC 75

Light, Ventilation & HeatingR303.1 Exceptions

3. Use of sunroom and patio covers shall be permitted for natural ventilation if in excess of 40 percent of the exterior sunroom walls are open, or are enclosed only by insect screening.

© 2020 Colorado Code Consulting, LLC 76

Page 21: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 20

R303.2 Adjoining rooms For the purpose of

determining light and ventilation requirements, any room can be considered as a portion of an adjoining room when at least ½ of the area of the common wall is open and unobstructed and provides an opening of not less than 1/10 of the floor area of the interior room but not less than 25 square feet.

© 2020 Colorado Code Consulting, LLC 77

R303.2, ExceptionAdjoining rooms Openings shall be permitted

to open into a sunroom with thermal isolation or a patio cover, provided that there is an openable area between the adjoining room and the sunroom or patio cover of not less than 1/10 of the floor area of the interior room but not less than 20 square feet.

The minimum openable area to the outdoors shall be based upon the total floor area being ventilated.

© 2020 Colorado Code Consulting, LLC 78

R303.3 Bathrooms

Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet, one-half of which must be openable.

Exception: Not required where artificial light and a local exhaust system in accordance with Section M1507. Exhaust air from the space shall be exhausted directly to the outdoors.

© 2020 Colorado Code Consulting, LLC 79

R303.4 Mechanical Ventilation Required

Where the air infiltration rate of a dwelling unit is less than 5 air changes per hour when tested with a blower door at a pressure of 0.2 inch w.c(50 Pa) in accordance with Section N1102.4.1.2, the dwelling unit shall be provided with whole-house mechanical ventilation in accordance with Section M1507.3.

80© 2020 Colorado Code Consulting, LLC

Page 22: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 21

R303.5.1 Intake openings

Mechanical and gravity outdoor air intake openings shall be located a minimum of 10 feet from any hazardous or noxious contaminant, such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks, except as otherwise specified in this code.

Where a source of contaminant is located within 10 feet of an intake opening, such opening shall be located a minimum of 3 feet below the contaminant source.

For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious.

© 2020 Colorado Code Consulting, LLC 81

R303.5.2 Exhaust openings Exhaust air shall not

be directed onto walkways.

© 2020 Colorado Code Consulting, LLC 82

R303.6 Outside opening protection

Air exhaust and intake openings that terminate outdoors shall be protected with corrosion-resistant screens, louvers or grilles having a minimum opening size of 1/4 inch and a maximum opening size of 1/2 inch, in any dimension.

Openings shall be protected against local weather conditions.

Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code.

© 2020 Colorado Code Consulting, LLC 83

R303.7 Interior stairway illumination Interior stairways shall be

provided with an artificial light source to illuminate the landings and treads. The light source shall be capable of illuminating treads and landings to levels of not less than 1 foot-candle as measured at the center of treads and landings.

There shall be a wall switch at each floor level to control the light source where the stairway has six or more risers.

© 2020 Colorado Code Consulting, LLC 84

Page 23: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 22

R303.8 Exterior stairway illumination

Exterior stairways shall be provided with an artificial light source located at the top landing of the stairway.

Exterior stairways providing access to a basement from the outdoor grade level shall be provided with an artificial light source located at the bottom landing of the stairway.

© 2020 Colorado Code Consulting, LLC 85

R303.9Required Glazed Openings

Open directly on Yard, Court, Street, or Alley Roofed porch 65% open,

7’ minimum ceiling Eaves are NOT

obstructions Under deck, balcony, bay,

or floor cantilever with 36” height

© 2020 Colorado Code Consulting, LLC 86

R303.9.1 Sunroom additions Required glazed openings

shall be permitted to open into sunroom additions or patio covers that abut a street, yard or court if in excess of 40 percent of the exterior sunroom walls are open, or are enclosed only by insect screening, and the ceiling height of the sunroom is not less than 7 feet.

© 2020 Colorado Code Consulting, LLC 87 © 2020 Colorado Code Consulting, LLC 88

Required HeatingR303.10 Where winter design

temperature is below 60° F, dwelling shall be provided with heating facilities to maintain 68°F at a point 3 Ft. above floor and 2 Ft. from exterior wall portable space heaters

not permitted to be used for required heating

Page 24: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 23

© 2020 Colorado Code Consulting, LLC 89

Minimum Room AreasR304

Habitable rooms minimum 70 square feet Except kitchens

Minimum 7 feet horizontal dimension Except kitchens

R304.4 Height effect on room area Portions of a room with

a sloping ceiling measuring less than 5 feet or a furred ceiling measuring less than 7 feet from the finished floor to the finished ceiling shall not be considered as contributing to the minimum required habitable area for that room.

© 2020 Colorado Code Consulting, LLC 90

R305.1 Minimum ceiling height

Habitable space, hallways and portions of basements containing these spaces shall have a ceiling height of not less than 7 feet.

Bathrooms, toilet rooms and laundry rooms shall have a ceiling height of not less than 6 feet 8 inches

© 2020 Colorado Code Consulting, LLC 91

R305.1 Minimum ceiling height

Exception 1. Sloped ceilings - at least

50% of the required floor area must have a ceiling height of at least 7 feet and no portion of the required floor area may have a ceiling height of less than 5 feet

© 2020 Colorado Code Consulting, LLC 92

Page 25: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 24

© 2020 Colorado Code Consulting, LLC 93

R305.1 Minimum ceiling height

Exception 2 The ceiling height above

bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose.

A shower or tub equipped with a showerhead shall have a ceiling height of not less than 6 feet 8 inches above an area of not less than 30 inches by 30 inches at the showerhead.

R305.1 Minimum ceiling height

Exception 3 Beams, girders, ducts or

other obstructions in basements containing habitable space shall be permitted to project to within 6 feet 4 inches of the finished floor.

© 2020 Colorado Code Consulting, LLC 94

R305.1.1 Basements

Portions of basements that do not contain habitable space, hallways, bathrooms, toilet rooms and laundry rooms shall have a ceiling height of not less than 6 feet 8 inches.

Exception: Beams, girders, ducts or other obstructions may project to within 6 feet 4 inches of the finished floor.

© 2020 Colorado Code Consulting, LLC 95 © 2020 Colorado Code Consulting, LLC 96

SanitationR306

Toilet Facilities water closet, tub or

shower,lavatory Kitchen

kitchen sink Connected to sanitary

sewer Water to fixtures

hot & cold water to sinks, lavatories, tubs, showers, bidets, laundry tubs and washing machine boxes

Page 26: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 25

Figure R307.1 Minimum Fixture Clearances Bathtub and shower

floors and walls above bathtubs with installed shower heads and in shower compartments shall be finished with a nonabsorbent surface. 6 feet above the floor.

© 2020 Colorado Code Consulting, LLC 97

R307.2 Bathtub and shower spaces

Bathtub and shower floors and walls above bathtubs with installed shower heads and in shower compartments shall be finished with a nonabsorbent surface.

Such wall surfaces shall extend to a height of not less than 6 feet above the floor.

© 2020 Colorado Code Consulting, LLC 98

R308 Labeling Safety Glazing

Glazing label: CPSC 16

CFR 1201 ANSI Z97.1

Used where CPSC does not preempt

© 2020 Colorado Code Consulting, LLC 99

R308.3.1 ANSI Z97.1 not

permitted for: Stairway Glazing Pool Wall and

Fence Glazing Bathtub, Hot Tub,

Sauna Glazing

© 2020 Colorado Code Consulting, LLC 100

Page 27: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 26

R308.4.1 Glazing in doors

Glazing in all fixed and operable panels of swinging, sliding and bifold doors shall be considered a hazardous location. Exceptions: 1. Glazed openings of a

size through which a 3-inch-diameter sphere is unable to pass.

2. Decorative glazing.

© 2020 Colorado Code Consulting, LLC 101

R308.4.2 Glazing adjacent to doors

Glazing in an individual fixed or operable panel adjacent to a door shall be considered to be a hazardous location where the bottom exposed edge of the glazing is less than 60 inches above the floor or walking surface and it meets either of the following conditions:

© 2020 Colorado Code Consulting, LLC 102

R308.4.2 Glazing adjacent to doors

1. Where the glazing is within 24 inches of either side of the door in the plane of the door in a closed position.

© 2020 Colorado Code Consulting, LLC 103

R308.4.2 Glazing adjacent to doors

2. Where the glazing is on a wall less than 180° from the plane of the door in a closed position and within 24 inches of the hinge side of an in-swinging door.

© 2020 Colorado Code Consulting, LLC 104

Yes

NoNo

No

If less than 180°

Page 28: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 27

R308.4.2 Glazing adjacent to doors

Exceptions 1. Decorative glazing. 2. When there is an

intervening wall or other permanent barrier between the door and the glazing.

3. Where access through the door is to a closet or storage area 3 feet or less in depth. Glazing in this application shall comply with section R308.4.3.

4. Glazing that is adjacent to the fixed panel of patio doors.

© 2020 Colorado Code Consulting, LLC 105 © 2020 Colorado Code Consulting, LLC 106

Glazing in windowsR308.4.3

Fixed or operable panel > 9 square feet < 18 inches above floor top edge > 36 inches above

floor walking surface within 36

inches

Glazing in windowsR308.4.3

Exceptions 1. Decorative glazing. 2. Horizontal rail installed on the

accessible side(s) of the glazing 34 to 38 inches above the walking surface. Capable of withstanding a horizontal load of 50 pounds per linear foot without contacting the glass and be a minimum of 1½ inches in cross sectional height.

3. Outboard panes in multiple glazed panels when the bottom edge of the glass is 25 feet or more above grade, a roof, walking surfaces or other horizontal [within 45 degrees of horizontal] surface adjacent to the glass exterior.

© 2020 Colorado Code Consulting, LLC 107

R308.4.5 – Glazing and Wet Surfaces

Glazing in walls, enclosures, or fences containing OR FACING:BathtubsShowersWhirlpools, saunas, steam rooms, indoor and outdoor poolsShall be safety glazing if less than 60” AFF and 60” or less measured horizontally and in a straight line, from the water’s edge

108© 2020 Colorado Code Consulting, LLC

60”

Page 29: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 28

R308.4.5 – Glazing and Wet Surfaces

Exception:Glazing that is more than 60” measured horizontally and in a straight line from the water’s edge of a bathtub, hot tub, spa, whirlpool, or swimming pool or from the edge of a shower, sauna or steam room.

109© 2020 Colorado Code Consulting, LLC

>60”

R308.4.6 –Glazing Adjacent to Stairs and Ramps

Changes hazardous location of glazing along stairs to 36” from walking surfaces of stairways, landings between flights, and ramps. Exception: Glazing protected

by a guard complying with Section R312 and the plane of the glass is more than 18 inches from the guard.

110© 2020 Colorado Code Consulting, LLC

R308.4.7Glazing Adj. to Bottom Stair Landing

Glazing adjacent to the landing at the bottom of a stairway where the glazing is less than 36 inches above the landing and within 60 inches horizontally of the bottom tread. Exception: Glazing protected

by a guard complying with Section R312 and the plane of the glass is more than 18 inches from the guard.

111© 2020 Colorado Code Consulting, LLC

R308.6.2 Skylight Permitted materials

The following types of glazing may be used: 1. Laminated glass with a minimum

0.015-inch polyvinyl butyral interlayer for glass panes 16 square feet or less in area located such that the highest point of the glass is not more than 12 feet above a walking surface or other accessible area; for higher or larger sizes, the minimum interlayer thickness shall be 0.030 inch.

2. Fully tempered glass. 3. Heat-strengthened glass. 4. Wired glass. 5. Approved rigid plastics.

© 2020 Colorado Code Consulting, LLC 112

Page 30: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 29

R308.6.3 Screens, general For fully tempered or

heat-strengthened glass, a retaining screen meeting the requirements of Section R308.6.7 shall be installed below the glass, except for fully tempered glass that meets either condition listed in Section R308.6.5.

© 2020 Colorado Code Consulting, LLC 113

R308.6.4 Screens with multiple glazing When the inboard pane is

fully tempered, heat-strengthened or wired glass, a retaining screen meeting the requirements of Section R308.6.7 shall be installed below the glass, except for either condition listed in Section R308.6.5.

All other panes in the multiple glazing may be of any type listed in Section R308.6.2.

© 2020 Colorado Code Consulting, LLC 114

R308.6.5 Screens not required

Screens shall not be required when fully tempered glass is used as single glazing or the inboard pane in multiple glazing and either of the following conditions are met: 1.Glass area 16 square feet or less.

Highest point of glass not more than 12 feet above a walking surface or other accessible area, nominal glass thickness not more than 3/16 inch, and (for multiple glazing only) the other pane or panes fully tempered, laminated or wired glass.

2.Glass area greater than 16 square feet. Glass sloped 30 degrees or less from vertical, and highest point of glass not more than 10 feet above a walking surface or other accessible area.

© 2020 Colorado Code Consulting, LLC 115

R308.6.8 Curbs for skylights All unit skylights

installed in a roof with a pitch flatter than three units vertical in 12 units horizontal shall be mounted on a curb extending at least 4 inches above the plane of the roof unless otherwise specified in the manufacturer’s installation instructions.

© 2020 Colorado Code Consulting, LLC 116

Page 31: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 30

R308.6.9 .Testing and labeling Unit skylights and tubular

daylighting devices shall be tested by an approved independent laboratory, and bear a label identifying manufacturer, performance grade rating and approved inspection agency to indicate compliance with the requirements of AAMA/WDMA/CSA 101/I.S.2/A440.

© 2020 Colorado Code Consulting, LLC 117

R309.1 Garage floor surface

Garage floor surfaces shall be of approved noncombustible material.

The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.

© 2020 Colorado Code Consulting, LLC 118

R309.2 Carports

Carports shall be open on at least two sides.

Carport floor surfaces shall be of approved noncombustible material.

Carports not open on at least two sides shall be considered a garage and shall comply with the provisions of this section for garages. Exception: Asphalt surfaces shall be

permitted at ground level in carports. The area of floor used for parking of

automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.

© 2020 Colorado Code Consulting, LLC 119

R309.3 Flood hazard areas

For buildings located in flood hazard areas as established by Table R301.2(1), garage floors shall be:

1. Elevated to or above the design flood elevation; or

2. Located below the design flood elevation provided they are at or above grade on at least one side, are used solely for parking, building access or storage, meet the requirements of Section R322 and are otherwise constructed in accordance with this code.

© 2020 Colorado Code Consulting, LLC 120

Page 32: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 31

R309.4 Automatic garage door openers Automatic garage

door openers, if provided, shall be listed and labeled in accordance with UL 325.

© 2020 Colorado Code Consulting, LLC 121

R309.5 Fire sprinklers Private garages shall be

protected by fire sprinklers where the garage wall has been designed based on Table R302.1(2), Footnote a. (Subdivision 0” lot line)

Connected to an automatic sprinkler system that complies with Section P2904.

Must be residential sprinklers or quick-response sprinklers, designed to provide a density of 0.05 gpm/ft2.

Garage doors not considered obstructions with respect to sprinkler placement.

© 2020 Colorado Code Consulting, LLC 122

R310.1Emergency Escape/Rescue

Basements, habitable attics and every sleeping room shall have at least one operable emergency escape and rescue opening.

Where basements contain one or more sleeping rooms, emergency egress and rescue openings shall be required in each sleeping room. Exception: Storm shelters and

basements used only to house mechanical equipment and not exceeding total floor area of 200 square feet.

© 2020 Colorado Code Consulting, LLC 123

R310.1Emergency Escape/Rescue Emergency escape

and rescue openings shall open directly into a public way, or to a yard or court that opens to a public way.

© 2020 Colorado Code Consulting, LLC 124

Page 33: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 32

R310.1 ExceptionsEmergency Escape/Rescue1. Storm shelters and basements used only to house mechanical equipment not exceeding a total floor area of 200 square feet

© 2020 Colorado Code Consulting, LLC 125

R310.1 ExceptionsEmergency Escape/Rescue

2. Where the dwelling or townhouse is equipped with an automatic sprinkler system installed in accordance with Section P2904, sleeping rooms in basements shall not be required to have emergency escape and rescue openings provided that the basement has one of the following:

2.1. One means of egress complying with Section R311 and one emergency escape and rescue opening.

2.2. Two means of egress complying with Section R311.

© 2020 Colorado Code Consulting, LLC 126

R310.1.1 - Operational constraints and opening control devices

Emergency escape and rescue openings shall be operational from the inside of the room without the use of keys, tools or special knowledge.

Window opening control devices complying with ASTM F 2090 shall be permitted for use on windows serving as a required emergency escape and rescue opening.

© 2020 Colorado Code Consulting, LLC 127 © 2020 Colorado Code Consulting, LLC 128

Minimum opening areaR310.2.1

5.7 square feet net clear opening 5 square feet at grade

floor (w/in 44”) > 24 inches height > 20 inches width Must be obtained by

the normal operation of the emergency escape and rescue opening from the inside.

Page 34: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 33

R310.2.2Window sill height

Where a window is provided as the emergency escape and rescue opening, it shall have a sill height of not more than 44 inches above the floor;

Where the sill height is below grade, it shall be provided with a window well in accordance with Section R310.2.3.

© 2020 Colorado Code Consulting, LLC 129

R310.2.3Window wells

Minimum horizontal area of the window well be 9 square feet

Minimum horizontal projection and width of 36 inches.

Must allow the emergency escape and rescue opening to be fully opened.

Exception: Ladders & steps can encroach 6”.

© 2020 Colorado Code Consulting, LLC 130

R310.2.3.1Ladder and steps

Window wells with a vertical depth greater than 44 inches shall be equipped with a permanently affixed ladder or steps usable with the window in the fully open position. Not required to comply with

Sections R311.7 and R311.8. Ladders or rungs - inside width of

at least 12 inches Must project at least 3 inches

from the wall Must be spaced not more than 18

inches on center vertically for the full height of the window well.

© 2020 Colorado Code Consulting, LLC 131

R310.2.3.2 Drainage

Window wells shall be designed for proper drainage by connecting to the building’s foundation drainage system required by Section R405.1 or by an approved alternative method. Exception: A drainage system for

window wells is not required when the foundation is on well-drained soil or sand-gravel mixture soils according to the United Soil Classification System, Group I Soils, as detailed in Table R405.1.

© 2020 Colorado Code Consulting, LLC 132

Page 35: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 34

© 2020 Colorado Code Consulting, LLC 133

R310.2.4 Emergency escape windows under decks and porches

Escape and rescue window must open fully and the path is not less than 36 inches in height to yard or court.

R310.2.5 Replacement windows

Replacement windows installed in buildings meeting the scope of this code shall be exempt from the maximum sill height requirements of Section R310.2.2 and the requirements of Section R310.2.1, provided that the replacement window meets the following conditions:

© 2020 Colorado Code Consulting, LLC 134

R310.2.5 Replacement windows

1. The replacement window is the manufacturer's largest standard size window that will fit within the existing frame or existing rough opening. The replacement window is of the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window2. The replacement window is not part of a change of occupancy

© 2020 Colorado Code Consulting, LLC 135

R310.3Emergency Escape/Rescue Doors (2018)

Where a door is provided as the required emergency escape and rescue opening, it shall be permitted to be a side-hinged door or a slider.

Where the opening is below the adjacent ground elevation, it shall be provided with an area well

© 2020 Colorado Code Consulting, LLC 136

Page 36: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 35

R310.3.1 Minimum door opening size

The minimum net clear height opening for any door that serves as an emergency and escape rescue opening shall be in accordance with Section R310.2.1. (Egress openings)

© 2020 Colorado Code Consulting, LLC 137

R310.3.2 Area wells (2018)

Area wells shall have a width of not less than 36 inches. The area well shall be sized to allow the emergency escape and rescue door to be fully opened.

© 2020 Colorado Code Consulting, LLC 138

R310.3.2.1 Ladders and stepsRequired if area well greater than 44” deepNeed not comply with R311.7

(Stairways)Ladders or rungs

Inside ≥ 12”Project ≥ 3”Rung spacing ≤ 18”

© 2020 Colorado Code Consulting, LLC 139

R310.4 Bars, grilles, covers and screens Bars, grilles, covers, screens or

similar devices are permitted to be placed over emergency escape and rescue openings, bulkhead enclosures, or window wells that serve such openings, provided: Minimum net clear opening size

complies with Sections R310.1.1 to R310.1.3,

Such devices are releasable or removable from the inside without the use of a key, tool, special knowledge or force greater than that which is required for normal operation of the escape and rescue opening.

© 2020 Colorado Code Consulting, LLC 140

Page 37: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 36

R310.5 Dwelling additions

Where dwelling additions occur that contain sleeping rooms, an emergency escape and rescue opening shall be provided in each new sleeping room.

Where dwelling additions occur that have basements, an emergency escape and rescue opening shall be provided in the new basement.

© 2020 Colorado Code Consulting, LLC 141

R310.5 Dwelling additions

Exceptions: 1. An emergency escape and

rescue opening is not required in a new basement that contains a sleeping room with an emergency escape and rescue opening.

2. An emergency escape and rescue opening is not required in a new basement where there is an emergency escape and rescue opening in an existing basement that is accessible from the new basement.

© 2020 Colorado Code Consulting, LLC 142

R310.6 Alterations or repairs of existing basements

An emergency escape and rescue opening is not required where existing basements undergo alterations or repairs. Exception: New sleeping

rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section R310.1.

© 2020 Colorado Code Consulting, LLC 143

R311.1Means of Egress

All dwellings shall be provided with a means of egress.

Must provide a continuous and unobstructed path of vertical and horizontal egress travel from all portions of the dwelling to the exterior of the dwelling at the required egress door without traveling through a garage.

The required egress door shall open directly into a public way or to a yard or court that opens to a public way.

© 2020 Colorado Code Consulting, LLC 144

Page 38: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 37

© 2020 Colorado Code Consulting, LLC 145

Exit Door RequiredR311.2

Not less than one egress door shall be provided for each dwelling unit.

The egress door shall be side-hinged, and shall provide a clear width of not less than 32 inches where measured between the face of the door and the stop, with the door open 90 degrees

© 2020 Colorado Code Consulting, LLC 146

Door Type and SizeR311.2

The clear height of the door opening shall be not less than 78 inches in height measured from the top of the threshold to the bottom of the stop.

Other doors shall not be required to comply with these minimum dimensions.

Door must be readily openable from inside the dwelling without the use of a key or special knowledge or effort.

Floors and Landings at EXTERIOR Doors - R311.3

There shall be a floor or landing on each side of each exterior door.

© 2020 Colorado Code Consulting, LLC 147 © 2020 Colorado Code Consulting, LLC 148

Floors and Landings at EXTERIOR Doors - R311.3

The width of each landing shall not be less than the door served.

Every landing shall have a minimum dimension of 36 inches measured in the direction of travel.

Maximum slope ¼:12

36” min.

Page 39: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 38

R311.3Small Balcony Exception Exterior balconies

less than 60 square feet and only accessible from a door are permitted to have a landing less than 36 inches measured in the direction of travel.

© 2020 Colorado Code Consulting, LLC 149 © 2020 Colorado Code Consulting, LLC 150

R311.3.1 Floor Elevation at REQUIRED EGRESS Doors

Landings or finished floors at the required egress door shall not be more than 1 ½ inches lower than the top of the threshold.

© 2020 Colorado Code Consulting, LLC 151

R311.3.1 Floor Elevation at REQUIRED EGRESS Doors

Exception: The landing or floor on the exterior side shall not be more than 7 ¾ inches below the top of the threshold provided the door does not swing over the landing or floor.

R311.3.1 Floor Elevation at REQUIRED EGRESS Doors

Where exterior landings or floors serving the required egress door are not at grade, they shall be provided with access to grade by means of a ramp or a stairway.

© 2020 Colorado Code Consulting, LLC 152

Page 40: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 39

© 2020 Colorado Code Consulting, LLC 153

Floor Elevations for OTHER Exterior Doors - R311.3.2

Doors other than the required egress door shall be provided with landings or floors not more than 7 ¾ inches below the top of the threshold.

© 2020 Colorado Code Consulting, LLC 154

Floor Elevations for OTHER Exterior Doors - R311.3.2

Exception: A landing is not required where a stairway of two or fewer risers is located on the exterior side of the door, provided the door does not swing over the stairway.

R311.4Vertical Egress Egress from

habitable levels including habitable attics and basements not provided with an egress door shall be by a ramp or a stairway.

© 2020 Colorado Code Consulting, LLC 155

AttachmentR311.5.1

Exterior landings, decks, balconies, stairs and similar facilities shall be positively anchored to the primary structure to resist both vertical and lateral forces or shall be designed to be self-supporting.

Attachment shall not be accomplished by use of toenails or nails subject to withdrawal.

© 2020 Colorado Code Consulting, LLC 156

Page 41: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 40

© 2020 Colorado Code Consulting, LLC 157

HallwaysR311.6 The minimum width

of a hallway shall be not less than 3 feet.

© 2020 Colorado Code Consulting, LLC 158

Stairway WidthR311.7.1

36 inches minimum width above handrail below headroom height handrails permitted to

project 4 1/2 inches on either side

31.5 inches minimum width below one handrail

27 inches minimum width below two handrails

36”

27” - 31.5”

© 2020 Colorado Code Consulting, LLC 159

Stairway HeadroomR311.7.2

Minimum 6’ 8” headroom measured vertically from the sloped plane adjoining the tread nosing or from the floor surface of the landing or platform

Stairway HeadroomR311.7.2 Exception: Where the

nosings of treads at the side of a flight extend under the edge of a floor opening through which the stair passes, the floor opening shall be allowed to project horizontally into the required headroom a maximum of 4¾ inches.

© 2020 Colorado Code Consulting, LLC 160

Page 42: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 41

© 2020 Colorado Code Consulting, LLC 161

Vertical Rise311.7.3

A flight of stairs shall not have a vertical rise larger than 151 inches between floor levels or landings

R311.7.5 Stair treads and risers For the purposes

of this section all dimensions and dimensioned surfaces shall be exclusive of carpets, rugs or runners.

© 2020 Colorado Code Consulting, LLC 162

R311.7.5.1Risers The riser height shall

be not more than 7¾ inches.

The riser shall be measured vertically between leading edges of the adjacent treads.

The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch

© 2020 Colorado Code Consulting, LLC 163

R311.7.5.1Risers Risers shall be vertical or

sloped from the underside of the nosing of the tread above at an angle not more than 30 degrees from the vertical.

Open risers are permitted provided that the openings located more than 30 inches, as measured vertically, to the floor or grade below do not permit the passage of a 4-inch-diameter sphere.

© 2020 Colorado Code Consulting, LLC 164

Page 43: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 42

R311.7.5.1Risers

Exceptions: 1. The opening

between adjacent treads is not limited on spiral stairways.

2. The riser height of spiral stairways shall be in accordance with Section R311.7.10.1.

© 2020 Colorado Code Consulting, LLC 165

R311.7.5.2Treads Minimum tread 10” leading edges of the

foremost projection of adjacent tread’s leading edge

greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch.

© 2020 Colorado Code Consulting, LLC 166

R311.7.5.2.1 Winder treads Minimum tread depth of 10 inches

measured between the vertical planes of the foremost projection of adjacent treads at the intersections with the walkline (12” from from the side where the winders are narrower).

Minimum tread depth of 6 inches at any point within the clear width of the stair.

Within any flight of stairs, the largest winder tread depth at the walklineshall not exceed the smallest winder tread by more than 3/8 inch.

Consistently shaped winders at the walkline shall be allowed within the same flight of stairs as rectangular treads and do not have to be within 3/8 inch of the rectangular tread depth.

© 2020 Colorado Code Consulting, LLC 167 © 2020 Colorado Code Consulting, LLC 168

NosingsR311.7.5.3

The radius of curvature at the leading edge of the tread shall be no greater than 9/16 inch

A nosing not less than 3/4 inch but not more than 1 ¼ inches shall be provided on stairways with solid risers

Beveling of nosing shall not exceed 1/2 inch Exception where 11” tread provided.

Page 44: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 43

© 2020 Colorado Code Consulting, LLC 169

Landings for StairwaysR311.7.6

Top and bottom of stairs except interior where

door does not swing over

As wide as stair Minimum of 36” in

direction of travel

R311.7.7 Stairway walking surface The walking surface

of treads and landings of stairways shall be sloped no steeper than one unit vertical in 48 inches horizontal.

© 2020 Colorado Code Consulting, LLC 170

© 2020 Colorado Code Consulting, LLC 171

HandrailsR311.7.8

At least one side of each continuous run of treads or flight with four or more risers

34” - 38” above tread Continuous full length of stairs

from top riser to bottom riser in the same flight newel posts permitted

Ends returned or terminate at newel post or safety rail use of volute, turnout or

starting easing allowed at lowest tread

1.5 inch space at wall

R311.7.8.3 Grip-size Type I. Circular cross section shall

have an outside diameter of at least 1¼ inches and not greater than 2 inches.

If not circular, must have a perimeter dimension of at least 4 inches and not greater than 6¼ inches with a maximum cross section of dimension of 2¼ inches.

Edges - minimum radius of 0.01 inch

© 2020 Colorado Code Consulting, LLC 172

Page 45: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 44

R311.7.8.3 Grip-size Type II. Perimeter greater than 6¼ inches

shall have a graspable finger recess area on both sides of the profile.

The finger recess shall begin within a distance of ¾ inch measured vertically from the tallest portion of the profile and achieve a depth of at least 5/16 inch within 7/8 inch below the widest portion of the profile.

This required depth shall continue for at least 3/8 inch to a level that is not less than 1¾ inches below the tallest portion of the profile.

The minimum width of the handrail above the recess shall be 1¼ inches to a maximum of 2¾ inches.

Edges - minimum radius of 0.01 inch.

© 2020 Colorado Code Consulting, LLC 173

R311.7.10.1Spiral stairways

Spiral stairways are permitted, provided that the clear width at and below the handrail is not less than 26 inches and the walklineradius is not greater than 24 ½ inches.

Each tread shall have a depth of not less than 6 ¾ inches at the walkline. All treads shall be identical, and the rise shall be not more than 9 ½ inches. Headroom shall be not less than 6 feet 6 inches.

© 2020 Colorado Code Consulting, LLC 174m

R202Definitions ALTERNATING TREAD

DEVICE. A device that has a

series of steps between 50 and 70 degrees from horizontal, usually attached to a center support rail in an alternating manner so that the user does not have both feet on the same level at the same time.

© 2020 Colorado Code Consulting, LLC 175

R311.7.11 Alternating tread devices Alternating tread devices

shall not be used as an element of a means of egress.

Alternating tread devices shall be permitted provided that the required means of egress stairway or ramp serves the same space at each adjoining level or where a means of egress is not required.

The clear width at and below the handrails shall be not less than 20 inches.

© 2020 Colorado Code Consulting, LLC 176

Page 46: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 45

R311.7.12 Ships ladders Ships ladders shall not be

used as an element of a means of egress.

Ships ladders shall be permitted provided that a required means of egress stairway or ramp serves the same space at each adjoining level or where a means of egress is not required.

The clear width at and below the handrails shall be not less than 20 inches.

© 2020 Colorado Code Consulting, LLC 177

R311.7.12.1 Treads of ships ladders

Treads shall have a depth of not less than 5 inches.

The tread shall be projected such that the total of the tread depth plus the nosing projection is not less than 8½ inches. The riser height shall be not more than 9 ½ inches.

© 2020 Colorado Code Consulting, LLC 178

R311.7.12.2 Handrails of ships ladders Handrails shall be

provided on both sides of ships ladders and shall comply with Sections R311.7.8.2 to R311.7.8.4.

Handrail height shall be uniform, not less than 30 inches and not more than 34 inches.

© 2020 Colorado Code Consulting, LLC 179

R311.8.1 Ramps Maximum slope

Ramps serving the egress door required by Section R311.2 shall have a slope of not more than 1 unit vertical in 12 units horizontal.

All other ramps shall have a maximum slope of 1 unit vertical in 8 units horizontal.

© 2020 Colorado Code Consulting, LLC 180

Page 47: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 46

R311.8.2 Landings required

A minimum 3-foot-by-3-foot landing shall be provided: 1. At the top and bottom

of ramps. 2. Where doors open

onto ramps. 3. Where ramps change

direction.

© 2020 Colorado Code Consulting, LLC 181

R311.8.3 Handrails required Required on at least one side of

all ramps exceeding a slope of one unit vertical in 12 units horizontal.

34’” – 38” above the finished surface of the ramp slope

Must comply with Section R311.7.8.3 (Grip size).

Must be continuous for the full length of the ramp.

Handrail ends must be returned or terminate in newel posts or safety terminals.

1 ½ inches between the wall and the handrails.

© 2020 Colorado Code Consulting, LLC 182

R312Guards

Guards shall be located along open-sided walking surfaces, including stairs, ramps and landings, that are located more than 30 inches measured vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side.

Insect screening shall not be considered as a guard.

© 2020 Colorado Code Consulting, LLC 183

R312.1.2 Height

36 inches high measured vertically above the adjacent walking surface or the line connecting the leading edges of the treads. Exceptions: 34” along the side of

stairs. Serving as a handrail can

be 34-38 inches along stairs.

© 2020 Colorado Code Consulting, LLC 184

34”

Page 48: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 47

© 2020 Colorado Code Consulting, LLC 185

Guard Opening LimitationsR312.2

Intermediate rails or ornamental closures cannot allow passage of a sphere 4 inches in diameter. Exceptions:

6 inch sphere permitted at riser/tread triangle

4 3/8” on sides of stair treads

6”

R312.2.1 Window sills

In dwelling units, where the top of the sill of an operable window opening is located less than 24 inches above the finished floor and greater than 72 inches above the finished grade or other surface below on the exterior of the building, the operable window shall comply with one of the following:

© 2020 Colorado Code Consulting, LLC 186

R312.2.1 Window sills 1. Operable

windows with openings that will not allow a 4-inch-diameter sphere to pass through the opening where the opening is in its largest opened position.

© 2020 Colorado Code Consulting, LLC 187

R312.2.1 Window sills 2. Operable

windows that are provided with window fall prevention devices that comply with ASTM F 2090.

© 2020 Colorado Code Consulting, LLC 188

Page 49: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 48

R312.2.1 Window sills 3. Operable

windows that are provided with window opening control devices that comply with Section R312.2.2.

© 2020 Colorado Code Consulting, LLC 189

R312.2.2 Window opening control devices

Window opening control devices shall comply with ASTM F 2090.

The window opening control device, after operation to release the control device allowing the window to fully open, shall not reduce the net clear opening area of the window unit to less than the area required by Section R310.2.1.

© 2020 Colorado Code Consulting, LLC 190

R313.1Automatic fire sprinklers

Required in all new one- and two-family dwellings and townhouses

Must be designed in accordance with P2904 or NFPA 13D

© 2020 Colorado Code Consulting, LLC 191

P2904Residential Sprinkler Design Prescriptive

Residential Sprinkler Provisions

Intended to be installed by Plumber Homeowner

© 2020 Colorado Code Consulting, LLC 192

Page 50: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 49

© 2020 Colorado Code Consulting, LLC 193

R314.1 Smoke Alarm Listings

Smoke alarms must comply with NFPA 72

Smoke alarms must be listed in accordance with UL 217. Combination smoke and carbon monoxide alarms shall be listed in accordance with UL 217 and UL 2034.

© 2020 Colorado Code Consulting, LLC 194

Alterations, repairs and additionsR314.2.2

When alterations , repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created in existing dwellings , the individual dwelling unit shall be equipped with smoke alarms located as required for new dwellings.

Alterations, repairs and additionsR314.2.2 Exceptions

Work involving the exterior surfaces of dwellings

Plumbing and mechanical exemptions for: Installation Repairs Alterations

© 2020 Colorado Code Consulting, LLC 195 © 2020 Colorado Code Consulting, LLC 196

LocationR314.3

Smoke alarms required: Each sleeping room Outside of each

separate sleeping area Each additional story

including basements & habitable attics but not including crawl spaces and uninhabitable attics

Page 51: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 50

R314.3Smoke alarm location

4. Smoke alarms shall be installed not less than 3 feet horizontally from the door or opening of a bathroom that contains a bathtub or shower unless this would prevent placement of a smoke alarm required by Section R314.3.

© 2020 Colorado Code Consulting, LLC 197

R314.3.1 Installation near cooking appliances

1. Ionization not less than 20 feet.

2. Ionization with an alarm-silencing switch shall not be installed less than 10 feet.

3. Photoelectric not be installed less than 6 feet.

© 2020 Colorado Code Consulting, LLC 198

© 2020 Colorado Code Consulting, LLC 199

Contains small amount of americium-241 Creates a small electrical current which is interrupted when smoke enters the chamber Will detect a small amount of smoke produced by fast flaming firesLike cooking, or fires fueled by paper or flammable liquids

Contain a light source in a light-sensitive electric sensor, which are positioned at 90-degree angles to one another. Normally, light from the light source shoots straight across and misses the sensor. When smoke enters the chamber, it scatters the light, which then hits the sensor and triggers the alarm. Typically respond faster to a fire in its early, smoldering stage

© 2020 Colorado Code Consulting, LLC 200

Page 52: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 51

R314.4 Interconnection (2018)Removed the exception:Interconnection of smoke alarms in existing areas shall not be required where alterations or repairs do not result in removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection without the removal of interior finishes

© 2020 Colorado Code Consulting, LLC 201

R314.5 Combination alarms Combination smoke

and carbon monoxide alarms shall be permitted to be used in lieu of smoke alarms.

© 2020 Colorado Code Consulting, LLC 202

© 2020 Colorado Code Consulting, LLC 203

Power SourceR314.6

New Construction building wiring battery backup battery operated when

commercial power not provided

Alterations, repairs, additions not required to be hard wired & buildings w/o commercial power battery operated

permitted

R314.7 Fire alarm systems

Must comply with IRC and the household fire warning equipment provisions of NFPA 72.

Detectors listed in accordance with UL 268.

Detectors installed in the locations specified in Section R314.3.

Must be a permanent fixture of the occupancy, owned by the homeowner.

Combination smoke and carbon monoxide detectors shall be permitted if listed in accordance with UL 268 and UL 2075.

© 2020 Colorado Code Consulting, LLC 204

Page 53: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 52

R315Carbon monoxide alarms R315.2 Where

required. Carbon monoxide alarms shall be provided in accordance with Sections R315.2.1 and R315.2.2.

© 2020 Colorado Code Consulting, LLC 205

R315.2.1 New construction For new construction,

carbon monoxide alarms shall be provided in dwelling units where either or both of the following conditions exist. 1. The dwelling unit

contains a fuel-fired appliance.

2. The dwelling unit has an attached garage with an opening that communicates with the dwelling unit.

© 2020 Colorado Code Consulting, LLC 206

R315.2.2 Alterations, repairs and additions Where alterations,

repairs or additions requiring a permit occur, or where one or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be equipped with carbon monoxide alarms located as required for new dwellings.

© 2020 Colorado Code Consulting, LLC 207

R315.2.2 Alterations, repairs and additions Exceptions:

1. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, is exempt from the requirements of this section.

2. Installation, alteration or repairs of plumbing or mechanical systems are exempt from the requirements of this section.

© 2020 Colorado Code Consulting, LLC 208

Page 54: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 53

R315.3 Location Carbon monoxide alarms

in dwelling units shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms.

Where a fuel-burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide alarm shall be installed within the bedroom.

© 2020 Colorado Code Consulting, LLC 209

R315.4 Combination alarms Combination carbon

monoxide and smoke alarms shall be permitted to be used in lieu of carbon monoxide alarms.

© 2020 Colorado Code Consulting, LLC 210

R315.5 Power source Carbon monoxide alarms

shall receive their primary power from the building wiring where such wiring is served from a commercial source and, where primary power is interrupted, shall receive power from a battery.

Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection.

© 2020 Colorado Code Consulting, LLC 211

R315.5 Interconnectivity (2018)

When more than one requiredShall be interconnected

Exception:Interconnection of smoke alarms in existing areas shall not be required where alterations or repairs do not result in removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection without the removal of interior finishes.

© 2020 Colorado Code Consulting, LLC 212

Page 55: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 54

R315.6Power source Exceptions:

1. Carbon monoxide alarms shall be permitted to be battery operated where installed in buildings without commercial power.

2. Carbon monoxide alarms installed in accordance with Section R315.2.2 shall be permitted to be battery powered.

© 2020 Colorado Code Consulting, LLC 213

R315.7 Carbon monoxide detection systems Carbon monoxide

detection systems shall be permitted to be used in lieu of carbon monoxide alarms and shall comply with Sections R315.6.1 through R315.6.4. Listing Location Permanent fixture Combination detectors

© 2020 Colorado Code Consulting, LLC 214

R316.2 – Foam PlasticLabeling and identification Packages and containers

of foam plastic insulation and foam plastic insulation components delivered to the job site shall bear the label of an approved agency showing the manufacturer’s name, the product listing, product identification and information sufficient to determine that the end use will comply with the requirements.

© 2020 Colorado Code Consulting, LLC 215 © 2020 Colorado Code Consulting, LLC 216

R316.3 Surface burning characteristics

Unless otherwise allowed in Section R316.5 or R316.6, all foam plastic or foam plastic cores used as a component in manufactured assemblies shall have a flame spread index of not more than 75 and shall have a smoke-developed index of not more than 450 when tested in the maximum thickness intended for use in accordance with ASTM E 84 or UL 723.

Loose-fill-type foam plastic insulation shall be tested as board stock for the flame spread index and smoke-developed index.

Page 56: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 55

R316.4 Thermal barrier Unless otherwise allowed in

Section R316.5 or Section R316.6, foam plastic shall be separated from the interior of a building by an approved thermal barrier of minimum ½ inch gypsum wallboard or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.

© 2020 Colorado Code Consulting, LLC 217

R316.5.1 Masonry or concrete construction The thermal barrier is

not required in a masonry or concrete wall, floor or roof when the foam plastic insulation is separated from the interior of the building by a minimum 1-inch thickness of masonry or concrete.

© 2020 Colorado Code Consulting, LLC 218

R316.5.2 Roofing The thermal barrier is not required

when the foam plastic in a roof assembly or under a roof covering is installed in accordance with the code and the manufacturer’s installation instructions and is separated from the interior of the building by tongue-and-groove wood planks or wood structural panel sheathing not less than 15/32 inch thick bonded with exterior glue and identified as Exposure 1, with edges supported by blocking or tongue-and-groove joints or an equivalent material.

The smoke-developed index for roof applications shall not be limited.

© 2020 Colorado Code Consulting, LLC 219

R316.5.3 Attics The thermal barrier is not required where all

of the following apply:

1. Attic access is required by Section R807.1.

2. The space is entered only for purposes of repairs or maintenance.

3. The foam plastic insulation is protected against ignition using one of the following ignition barrier materials: 3.1. 1½-inch-thick mineral fiber insulation; 3.2. ¼-inch-thick wood structural panels; 3.3. 3/8-inch particleboard; 3.4. ¼-inch hardboard; 3.5. 3/8-inch gypsum board; or 3.6. Corrosion-resistant steel having a base

metal thickness of 0.016 inch; 3.7. 1 ½-inch-thick cellulose insulation.

The above ignition barrier is not required where the foam plastic insulation has been tested in accordance with Section R316.6.

© 2020 Colorado Code Consulting, LLC 220

Page 57: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 56

R316.5.4 Crawl spaces The thermal barrier is not required where all

of the following apply: 1. Crawlspace access is required by Section

R408.4 2. Entry is made only for purposes of repairs

or maintenance. 3. The foam plastic insulation is protected

against ignition using one of the following ignition barrier materials: 3.1. 1½-inch-thick mineral fiber insulation; 3.2. ¼-inch-thick wood structural panels; 3.3. 3/8-inch particleboard; 3.4. ¼-inch hardboard; 3.5. 3/8-inch gypsum board; or 3.6. Corrosion-resistant steel having a base

metal thickness of 0.016 inch.

The above ignition barrier is not required where the foam plastic insulation has been tested in accordance with Section R316.6.

© 2020 Colorado Code Consulting, LLC 221

R316.5.5 & R316.5.6Doors Foam-filled exterior

doors are exempt from the requirements of Sections R316.3 and R316.4.

Foam-filled garage doors in attached or detached garages are exempt from the requirements of Sections R316.3 and R316.4.

© 2020 Colorado Code Consulting, LLC 222

R316.5.7 Foam backer board

The thermal barrier is not required where siding backer board foam plastic insulation has a maximum thickness of 0.5 inch and a potential heat of not more than 2000 Btu per square foot when tested in accordance with NFPA 259 provided that: 1.The foam plastic insulation is

separated from the interior of the building by not less than 2 inches of mineral fiber insulation;

2.The foam plastic insulation is installed over existing exterior wall finish in conjunction with re-siding; or

3.The foam plastic insulation has been tested in accordance with Section R316.6.

© 2020 Colorado Code Consulting, LLC 223

R316.5.8 Re-siding

The thermal barrier specified in Section R316.4 is not required where the foam plastic insulation is installed over existing exterior wall finish in conjunction with re-siding provided the foam plastic has a maximum thickness of 0.5 inch and a potential heat of not more than 2000 Btu per square foot when tested in accordance with NFPA 259.

© 2020 Colorado Code Consulting, LLC 224

Page 58: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 57

R316.5.9 Interior trim The thermal barrier specified in

Section R316.4 is not required for exposed foam plastic interior trim, provided all of the following are met: 1.The minimum density is 20

pounds per cubic foot. 2.The maximum thickness of the

trim is ½ inch and the maximum width is 8 inches.

3.The interior trim shall not constitute more than 10 percent of the aggregate wall and ceiling area of any room or space.

4.The flame spread index does not exceed 75 when tested per ASTM E 84 or UL 723. The smoke-developed index is not limited.

© 2020 Colorado Code Consulting, LLC 225

R316.5.10 Interior finish Foam plastics shall be

permitted as interior finish where approved in accordance with Section R316.6

Foam plastics that are used as interior finish shall also meet the flame spread index and smoke-developed index requirements of Sections R302.9.1 and R302.9.2.

© 2020 Colorado Code Consulting, LLC 226

R316.5.11 Sill plates and headers Foam plastic shall be permitted

to be spray applied to a sill plate and header without the thermal barrier subject to all of the following: 1. The maximum thickness of the

foam plastic shall be 3¼ inches. 2. The density of the foam plastic

shall be in the range of 0.5 to 2.0 pounds per cubic foot.

3. The foam plastic shall have a flame spread index of 25 or less and an accompanying smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723.

© 2020 Colorado Code Consulting, LLC 227

R316.5.12 Sheathing

Foam plastic insulation used as sheathing shall comply with Section R316.3 and Section R316.4.

Where the foam plastic sheathing is exposed to the attic space at a gable or kneewall, the provisions of Section R316.5.3 shall apply.

© 2020 Colorado Code Consulting, LLC 228

Page 59: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 58

R316.5.13 Floors The thermal barrier is not

required to be installed on the walking surface of a structural floor system that contains foam plastic insulation when the foam plastic is covered by a minimum nominal ½-inch-thick wood structural panel or equivalent.

The thermal barrier is required on the underside of the structural floor system that contains foam plastic insulation when the underside of the structural floor system is exposed to the interior of the building.

© 2020 Colorado Code Consulting, LLC 229

R316.6 Specific approval

Foam plastic not meeting the requirements of Sections R316.3 through R316.5 shall be specifically approved on the basis of one of the following approved tests: NFPA 286 with the acceptance criteria of

Section R302.9.4, FM4880, UL 1040, or UL 1715, or fire tests related to actual end-use

configurations. Approval shall be based on the actual end

use configuration and shall be performed on the finished foam plastic assembly in the maximum thickness intended for use.

Assemblies tested shall include seams, joints and other typical details used in the installation of the assembly and shall be tested in the manner intended for use.

© 2020 Colorado Code Consulting, LLC 230

R302.9.4 Alternative test method As an alternative to having a flame spread

index of not greater than 200 and a smoke-developed index of not greater than 450 when tested in accordance with ASTM E 84 or UL 723, wall and ceiling finishes shall be permitted to be tested in accordance with NFPA 286. Materials tested in accordance with NFPA 286 shall meet the following criteria:

The interior finish shall comply with the following: 1. During the 40 kW exposure, flames shall

not spread to the ceiling. 2. The flame shall not spread to the outer

extremity of the sample on any wall or ceiling. 3. Flashover, as defined in NFPA 286, shall

not occur. 4. The peak heat release rate throughout the

test shall not exceed 800 kW. 5. The total smoke released throughout the

test shall not exceed 1,000 m2.

© 2020 Colorado Code Consulting, LLC 231 © 2020 Colorado Code Consulting, LLC 232

Protection Against DecayR317.1

Naturally durable wood or wood that has been treated is required. AWPA Standard U1 replaces the former C (commodity) standards.

Field cut ends, notches and drilled holes of preservative treated wood shall be treated in the field in accordance with AWPA M4.

Page 60: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 59

© 2020 Colorado Code Consulting, LLC 233

Protection Against DecayR317

Approved species of wood or treated lumber required if: Joists <18” to ground Beams <12” to ground Wood framing members resting on

concrete/masonry exterior walls within 8” of exposed ground

Girders entering masonry or concrete <1/2” air space

Members supporting moisture permeable floors

Furring strips on concrete without vapor barrier

R317.1Locations for Decay Protection

Wood siding, sheathing and wall framing: 6” from the ground 2” from concrete

steps and slabs and “similar horizontal surfaces”

© 2020 Colorado Code Consulting, LLC 234

© 2020 Colorado Code Consulting, LLC 235

Ground ContactR317.1.2

All wood in contact with the ground, embedded in concrete in direct

contact with the ground or embedded in concrete exposed

to the weather that supports permanent structures intended for human occupancy shall be approved pressure-preservative-treated wood suitable for ground contact use

R317.1.3 Geographical areas

In geographical areas where experience has demonstrated a specific need, approved naturally durable or pressure-preservative-treated wood shall be used for those portions of wood members that form the structural supports of buildings, balconies, porches or similar permanent building appurtenances when those members are exposed to the weather without adequate protection from a roof, eave, overhang or other covering that would prevent moisture or water accumulation on the surface or at joints between members.

© 2020 Colorado Code Consulting, LLC 236

Page 61: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 60

R317.1.3 Geographical areas Depending on local

experience, such members may include: 1. Horizontal members

such as girders, joists and decking.

2. Vertical members such as posts, poles and columns.

3. Both horizontal and vertical members.

© 2020 Colorado Code Consulting, LLC 237

R317.1.4 Wood columns Wood columns shall be approved

wood of natural decay resistance or approved pressure-preservative-treated wood. Exceptions: 1. Columns exposed to the weather or

in basements when supported by concrete piers or metal pedestals projecting 1 inch above a concrete floor or 6 inches above exposed earth and the earth is covered by an approved impervious moisture barrier.

2. Columns in enclosed crawl spaces or unexcavated areas located within the periphery of the building when supported by a concrete pier or metal pedestal at a height more than 8 inches from exposed earth and the earth is covered by an impervious moisture barrier.

© 2020 Colorado Code Consulting, LLC 238

R317.1.5 Exposed glued-laminated timbers The portions of glued-

laminated timbers that form the structural supports of a building or other structure and are exposed to weather and not properly protected by a roof, eave or similar covering shall be pressure treated with preservative, or be manufactured from naturally durable or preservative-treated wood.

© 2020 Colorado Code Consulting, LLC 239

R317.2 Quality mark Lumber and plywood required

to be pressure-preservative-treated in accordance with Section R318.1 shall bear the quality mark of an approved inspection agency that maintains continuing supervision, testing and inspection over the quality of the product and that has been approved by an accreditation body that complies with the requirements of the American Lumber Standard Committee treated wood program.

© 2020 Colorado Code Consulting, LLC 240

Page 62: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 61

R317.3.1 - Fasteners for preservative-treated wood

Fasteners, including nuts and washers, for preservative-treated wood shall be of hot-dipped, zinc-coated galvanized steel, stainless steel, silicon bronze or copper.

Coating types and weights for connectors in contact with preservative-treated wood shall be in accordance with the connector manufacturer’s recommendations.

In the absence of manufacturer’s recommendations, a minimum of ASTM A 653 type G185 zinc-coated galvanized steel, or equivalent, shall be used.

© 2020 Colorado Code Consulting, LLC 241

R317.3.1 - Fasteners for preservative-treated wood Exceptions: 1. ½-inch-diameter or greater

steel bolts. 2. Fasteners other than nails

and timber rivets shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum.

3. Plain carbon steel fasteners in SBX/DOT and zinc borate preservative-treated wood in an interior, dry environment shall be permitted.

© 2020 Colorado Code Consulting, LLC 242

R317.4 Plastic Composites

New definition Decks and

exterior structures ASTM D 7032 installed

according to the manufacturer’s instructions

© 2020 Colorado Code Consulting, LLC 243 © 2020 Colorado Code Consulting, LLC 244

Protection Against TermitesR318

In areas favorable to termite damage as established by Table R301.2(1), methods of protection shall be provided.

Page 63: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 62

R319.1 Address Numbers

4” Height ½” Stroke Contrasting background Where required by the fire code

official, address identification shall be provided in additional approvedlocations to facilitate emergency response

Address identification shall be maintained

© 2020 Colorado Code Consulting, LLC 245

R320Accessibility Where there are

four or more dwelling units or sleeping units in a single structure, the provisions of Chapter 11 of the International Building Code for Group R-3 shall apply.

© 2020 Colorado Code Consulting, LLC 246

© 2020 Colorado Code Consulting, LLC 247

R320.1.1 Guestrooms

A dwelling with guestrooms shall comply with the provisions of Chapter 11 of the International Building Code for Group R-3.

For the purpose of applying the requirements of Chapter 11 of the International Building Code, guestrooms shall be considered to be sleeping units. Exception: Owner-occupied

lodging houses with five or fewer guestrooms constructed in accordance with the International Residential Code are not required to be accessible.

© 2020 Colorado Code Consulting, LLC 248

R321 Elevators and platform lifts

Passenger elevators shall comply with ASME A17.1

Platform lifts shall comply with ASME A18.1

Elevators or platform lifts that are apart of an accessible route shall comply with ICC A117.1

Page 64: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 63

© 2020 Colorado Code Consulting, LLC 249

Flood Resistant ConstructionR322

Buildings and structures constructed in whole or in part in flood hazard areas (including A or V Zones) as established in Table R301.2(1) shall be designed and constructed in accordance with the provisions contained in this section.

Buildings and structures located in whole or in part in identified floodways shall be designed and constructed in accordance with ASCE 24.

R323Storm Shelters

This section applies to the construction of storm shelters when constructed as separate detached buildings or when constructed as safe rooms within buildings for the purpose of providing safe refuge from storms that produce high winds, such as tornados and hurricanes.

In addition to other applicable requirements in this code, storm shelters shall be constructed in accordance with ICC/NSSA-500.

© 2020 Colorado Code Consulting, LLC263

ICC 500 – Storm Shelters 2009 IRC for

construction of storm shelters.

© 2020 Colorado Code Consulting, LLC264 © 2020 Colorado Code Consulting, LLC 265

324Solar energy systems

Solar energy systems shall comply with the provisions of this section.

Page 65: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 64

© 2020 Colorado Code Consulting, LLC 266

R324.2 Solar thermal systems Solar thermal

systems shall be designed and installed in accordance with Chapter 23 and the International Fire Code.

© 2020 Colorado Code Consulting, LLC 267

R324.3 Photovoltaic systems

Photovoltaic systems shall be designed and installed in accordance with Sections R324.3.1 through R324.7.2.5 and NFPA 70. Inverters shall be listed and labeled in accordance with UL 1741.

Systems connected to the utility grid shall use inverters listed for utility interaction.

Photovoltaic panels and modules shall be listed and labeled in accordance with UL 1703.

© 2020 Colorado Code Consulting, LLC 268

R324.4 Rooftop-mounted photovoltaic systems

Rooftop-mounted photovoltaic panel systems installed on or above the roof covering shall be designed and installed in accordance with Section R907.

© 2020 Colorado Code Consulting, LLC 269

R324.4.1 Roof live load

Roof structures that provide support for photovoltaic panel systems shall be designed for applicable roof live load.

The design of roof structures need not include roof live load in the areas covered by photovoltaic panel systems.

Portions of roof structures not covered by photovoltaic panels shall be designed for roof live load.

Roof structures that provide support for photovoltaic panel systems shall be designed for live load, LR, for the load case where the photovoltaic panel system is not present.

Page 66: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 65

© 2020 Colorado Code Consulting, LLC 270

R324.5 Building-integrated photovoltaic systems

Building-integrated photovoltaic systems that serve as roof coverings shall be designed and installed in accordance with Section R905.

Photovoltaic shingles shall comply with Section R905.16.

R324.6 Roof access and pathways(2018)

Shall be providedExceptions:1. Detached non-habitable structures, carports, detached garages2. AHJ determined roof top no roof top operations3. Roof pitch 2/12 and less

© 2020 Colorado Code Consulting, LLC 271

R324.6.1 Pathways (2018)Two pathways, on separate roof planes from lowest roof edge to ridge and not less than 36 inches wideOne pathway shall be provided on the street or driveway side of the roofEach roof plane with a photovoltaic array:Pathway not less than 36 inches wide shall be provided from the lowest roof edge to ridge on the same roof plane as the photovoltaic array, on an adjacent roof plane, or straddling the same and adjacent roof planes.Pathways shall be over areas capable of supporting fire fighters accessing the roof. Pathways shall be located in areas with minimal obstructions such as vent pipes, conduit, or mechanical equipment

© 2020 Colorado Code Consulting, LLC 272 © 2020 Colorado Code Consulting, LLC 273

Page 67: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 66

R324.6.2.2 Emergency escape and rescue opening (2018)Panels and modules installed on dwellings shall not be placed on the portion of a roof that is below an emergency escape and rescue opening. A pathway not less than 36 inches wide shall be provided to the emergency escape and rescue opening

© 2020 Colorado Code Consulting, LLC 274 © 2020 Colorado Code Consulting, LLC 275

R324.7Ground-mounted photovoltaic systems

Ground-mounted photovoltaic systems shall be designed and in-stalled in accordance with Section R301.

Ground-mounted photovoltaic systems shall be subject to the fire separation distance requirements determined by the local jurisdiction.

R325.2 Mezzanines The clear height

above and below mezzanine floor construction shall be not less than 7 feet.

© 2020 Colorado Code Consulting, LLC 276

R325.3 Area limitation The aggregate area of a

mezzanine or mezzanines shall be not greater than one-third of the floor area of the room or space in which they are located.

The enclosed portion of a room shall not be included in a determination of the floor area of the room in which the mezzanine is located.

© 2020 Colorado Code Consulting, LLC 277

Page 68: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 67

R325.3 Area limitation 2018Exception: The aggregate area of a mezzanine located within a dwelling unit equipped with a fire sprinkler system in accordance with Section P2904 shall not be greater than one-half of the floor area of the room, provided that the mezzanine meets all of the following requirements:

© 2020 Colorado Code Consulting, LLC 278

1. Except for enclosed closets and bathrooms, the mezzanine is open to the room in which such mezzanine is located.2. The opening to the room is unobstructed except for walls not more than 42 inches in height, columns and posts.3. The exceptions to Section R325.5 are not applied.

R325.4 Means of egress

The means of egress for mezzanines shall comply with the applicable provisions of Section R311.

© 2020 Colorado Code Consulting, LLC 279

R325.5 Openness

Mezzanines shall be open and unobstructed to the room in which they are located except for walls not more than 36 inches in height, columns and posts. Exceptions: 1. Mezzanines or portions thereof are not

required to be open to the room in which they are located, provided that the aggregate floor area of the enclosed space is not greater than 10 percent of the mezzanine area.

2. In buildings that are not more than two stories above grade plane and equipped throughout with an automatic sprinkler system in accordance with NFPA 13R or NFPA 13D, a mezzanine having two or more means of egress shall not be required to be open to the room in which the mezzanine is located.

© 2020 Colorado Code Consulting, LLC 280

R326Swimming pools, spas and hot tubs

The design and construction of pools and spas shall comply with the International Swimming Pool and Spa Code.

© 2020 Colorado Code Consulting, LLC 281

Page 69: 2018 International Residential Code2018 International Residential Code Chapter 3 Building Planning 2 Instructor Gil Rossmiller In the construction industry for over 40 years ICC –IRC

2018 IRC Chapter 3

© 2020 Colorado Code Consulting, LLC 68

Copyright MaterialsThis presentation is protected by US and International

Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is

prohibited.© Colorado Code Consulting, LLC, 2020

© 2020 Colorado Code Consulting, LLC 282

283