2015 IPC CODE – CHAPTERS 8-9 SECTIONS 801-918.8
INDIRECT/SPECIAL WASTE Changes to the 2012 Code are highlighted in yellow. SECTION801-GENERAL
801.1Scope.
Thischaptershallgovernmattersconcerningindirectwastepipingandspecialwastes.This
chaptershallfurthercontrolmattersconcerningfood-handlingestablishments,sterilizers,
clear-waterwastes,waste,swimmingpools,methodsofprovidingairbreaksorairgaps,and
neutralizingdevicesforcorrosivewastes.
801.2Protection.
Devices,appurtenances,appliancesandapparatusintendedtoservesomespecialfunction,
suchassterilization,distillation,processing,cooling,orstorageoficeorfoods,andthat
dischargetothedrainagesystem,shallbeprovidedwithprotectionagainstbackflow,flooding,
fouling,contaminationandstoppageofthedrain.
SECTION802-INDIRECTWASTES
802.1Whererequired.
Food-handlingequipment,inotherthandwellingunits,clear-waterwaste,dishwashing
machinesandutensils,pots,pansanddishwashingsinksshalldischargethroughanindirect
wastepipeasspecifiedinSections802.1.1through802.1.8.Health-carerelatedfixtures,devices
andequipmentshalldischargetothedrainagesystemthroughanindirectwastepipebymeans
ofanairgapinaccordancewiththischapterandSection713.3.Fixturesnotrequiredbythis
sectiontobeindirectlyconnectedshallbedirectlyconnectedtotheplumbingsystemin
accordancewithChapter7.
802.1.1Foodhandling.
Equipmentandfixturesutilizedforthestorage,preparationandhandlingoffoodshall
dischargethroughanindirectwastepipebymeansofanairgap.Eachwellofamultiple-
compartmentsinkshalldischargeindependentlytoawastereceptor.
2
802.1.2Floordrainsinfoodstorageareas.
Floordrainslocatedwithinwalk-inrefrigeratorsorfreezersinfoodserviceandfood
establishmentsshallbeindirectlyconnectedtothesanitarydrainagesystembymeans
ofanairgap.Whereafloordrainislocatedwithinanareasubjecttofreezing,thewaste
lineservingthefloordrainshallnotbetrappedandshallindirectlydischargeintoa
wastereceptorlocatedoutsideoftheareasubjecttofreezing.
Exception:Whereprotectedagainstbackflowbyabackwatervalve,suchfloor
drainsshallbeindirectlyconnectedtothesanitarydrainagesystembymeansof
anairbreakoranairgap.
802.1.3Potableclear-waterwaste.
Wheredevicesandequipment,suchassterilizersandreliefvalves,dischargepotable
watertothebuildingdrainagesystem,thedischargeshallbethroughanindirectwaste
pipebymeansofanairgap.
802.1.4Swimmingpools.
Wherewastewaterfromswimmingpools,backwashfromfiltersandwaterfrompool
deckdrainsdischargetothebuildingdrainagesystem,thedischargeshallbethroughan
indirectwastepipebymeansofanairgap.
802.1.5Nonpotableclear-waterwaste.
Wheredevicesandequipmentsuchasprocesstanks,filters,dripsandboilersdischarge
nonpotablewatertothebuildingdrainagesystem,thedischargeshallbethroughan
indirectwastepipebymeansofanairbreakoranairgap.
802.1.6Domesticdishwashingmachines.
Domesticdishwashingmachinesshalldischargeindirectlythroughanairgaporairbreak
intoawastereceptorinaccordancewithSection802.2,ordischargeintoawyebranch
fittingonthetailpieceofthekitchensinkorthedishwasherconnectionofafoodwaste
disposer.Thewastelineofadomesticdishwashingmachinedischargingintoakitchen
sinktailpieceorfoodwastedisposershallconnecttoadeck-mountedairgaporthe
wastelineshallriseandbesecurelyfastenedtotheundersideofthesinkrimor
counter.
3
802.1.7Commercialdishwashingmachines.
Thedischargefromacommercialdishwashingmachineshallbethroughanairgaporair
breakintoawastereceptorinaccordancewithSection802.2.
802.1.8Foodutensils,dishes,potsandpanssinks.
Sinks,inotherthandwellingunits,usedforthewashing,rinsingorsanitizingofutensils,
dishes,pots,pansorservicewareusedinthepreparation,servingoreatingoffoodshall
dischargeindirectlythroughanairgaporanairbreaktothedrainagesystem.
802.2Installation.
Indirectwastepipingshalldischargethroughanairgaporairbreakintoawastereceptor.
Wastereceptorsshallbetrappedandventedandshallconnecttothebuildingdrainagesystem.
Indirectwastepipingthatexceeds30inches(762mm)indevelopedlengthmeasured
horizontally,or54inches(1372mm)intotaldevelopedlength,shallbetrapped.
Exception:Whereawastereceptorreceivesonlyclearwaterwasteanddoesnotdirectly
connecttoasanitarydrainagesystem,thereceptorshallnotrequireatrap.
802.2.1Airgap.
Theairgapbetweentheindirectwastepipeandthefloodlevelrimofthewaste
receptorshallbenotlessthantwicetheeffectiveopeningoftheindirectwastepipe.
802.2.2Airbreak.
Anairbreakshallbeprovidedbetweentheindirectwastepipeandthetrapsealofthe
wastereceptor.
802.3Wastereceptors.
Forotherthanhubdrainsthatreceiveonlyclear-waterwasteandstandpipes,aremovable
strainerorbasketshallcovertheoutletofwastereceptors.Wastereceptorsshallnotbe
installedinconcealedspaces.Wastereceptorsshallnotbeinstalledinplenums,crawlspaces,
attics,interstitialspacesaboveceilingsandbelowfloors.Readyaccessshallbeprovidedto
wastereceptors.
802.3.1Sizeofreceptors.
Awastereceptorshallbesizedforthemaximumdischargeofallindirectwastepipes
servedbythereceptor.Receptorsshallbeinstalledtopreventsplashingorflooding.
4
802.3.2Hubdrains.
Ahubdrainshallbeintheformofahuborapipeextendingnotlessthan1inch(25
mm)aboveawater-imperviousfloor.
802.3.3Standpipes.
Standpipesshallbeindividuallytrapped.Standpipesshallextendnotlessthan18inches
(457mm)butnotgreaterthan42inches(1066mm)abovethetrapweir.Accessshallbe
providedtostandpipesanddrainsforrodding.
SECTION803-SPECIALWASTES
803.1Neutralizingdevicerequiredforcorrosivewastes.
Corrosiveliquids,spentacidsorotherharmfulchemicalsthatdestroyorinjureadrain,sewer,
soilorwastepipe,orcreatenoxiousortoxicfumesorinterferewithsewagetreatment
processesshallnotbedischargedintotheplumbingsystemwithoutbeingthoroughlydiluted,
neutralizedortreatedbypassingthroughanapproveddilutionorneutralizingdevice.Such
devicesshallbeautomaticallyprovidedwithasufficientsupplyofdilutingwaterorneutralizing
mediumsoastomakethecontentsnoninjuriousbeforedischargeintothedrainagesystem.
Thenatureofthecorrosiveorharmfulwasteandthemethodofitstreatmentordilutionshall
beapprovedpriortoinstallation.
803.2Systemdesign.
Achemicaldrainageandventsystemshallbedesignedandinstalledinaccordancewiththis
code.Chemicaldrainageandventsystemsshallbecompletelyseparatedfromthesanitary
systems.Chemicalwasteshallnotdischargetoasanitarydrainagesystemuntilsuchwastehas
beentreatedinaccordancewithSection803.1.
SECTION804-MATERIALS,JOINTSANDCONNECTIONS
804.1General.
Thematerialsandmethodsutilizedfortheconstructionandinstallationofindirectwastepipes
andsystemsshallcomplywiththeapplicableprovisionsofChapter7.
5
2015 IPC CODE - CHAPTER 9 VENTS
SECTION901-GENERAL
901.1Scope.
Theprovisionsofthischaptershallgovernthematerials,design,constructionandinstallationof
ventsystems.
901.2Trapsealprotection.
Theplumbingsystemshallbeprovidedwithasystemofventpipingthatwillpermitthe
admissionoremissionofairsothatthesealofanyfixturetrapshallnotbesubjectedtoa
pressuredifferentialofmorethan1inchofwatercolumn(249Pa).
901.2.1Ventingrequired.
Trapsandtrappedfixturesshallbeventedinaccordancewithoneoftheventing
methodsspecifiedinthischapter.
901.3Chemicalwasteventsystems.
Theventsystemforachemicalwastesystemshallbeindependentofthesanitaryventsystem
andshallterminateseparatelythroughtherooftotheoutdoorsortoanairadmittancevalve
thatcomplieswithASSE1049.Airadmittancevalvesforchemicalwastesystemsshallbe
constructedofmaterialsapprovedinaccordancewithSection702.5andshallbetestedfor
chemicalresistanceinaccordancewithASTMF1412.
901.4Uselimitations.
Theplumbingventsystemshallnotbeutilizedforpurposesotherthantheventingofthe
plumbingsystem.
901.5Tests.
TheventsystemshallbetestedinaccordancewithSection312.
901.6Engineeredsystems.
EngineeredventingsystemsshallconformtotheprovisionsofSection919.
6
SECTION902-MATERIALS
902.1Vents.
Thematerialsandmethodsutilizedfortheconstructionandinstallationofventingsystems
shallcomplywiththeapplicableprovisionsofSection702.
902.2Sheetcopper.
SheetcopperforventpipeflashingsshallconformtoASTMB152andshallweighnotlessthan
8ouncespersquarefoot(2.5kg/m2).
902.3Sheetlead.
Sheetleadforventpipeflashingsshallweighnotlessthan3poundspersquarefoot(15kg/m2)
forfield-constructedflashingsandnotlessthan2½poundspersquarefoot(12kg/m2)for
prefabricatedflashings.
SECTION903-VENTTERMINALS
903.1Roofextension.
Openventpipesthatextendthrougharoofshallbeterminatednotlessthan[NUMBER]inches
(mm)abovetheroof.Wherearoofistobeusedforassemblyorasapromenade,observation
deck,sunbathingdeckorsimilarpurposes,openventpipesshallterminatenotlessthan7feet
(2134mm)abovetheroof.
903.2Frostclosure.
Wherethe97.5-percentvalueforoutsidedesigntemperatureis0°F(-18°C)orless,vent
extensionsthrougharooforwallshallbenotlessthan3inches(76mm)indiameter.Any
increaseinthesizeoftheventshallbemadenotlessthan1foot(305mm)insidethethermal
envelopeofthebuilding.
903.3Flashings.
Thejunctureofeachventpipewiththerooflineshallbemadewatertightbyanapproved
flashing.
903.4Prohibiteduse.
Aventterminalshallnotbeusedforanypurposeotherthanaventterminal.
7
903.5Locationofventterminal.
Anopenventterminalfromadrainagesystemshallnotbelocateddirectlybeneathanydoor,
openablewindow,orotherairintakeopeningofthebuildingorofanadjacentbuilding,and
anysuchventterminalshallnotbewithin10feet(3048mm)horizontallyofsuchanopening
unlessitis3feet(914mm)ormoreabovethetopofsuchopening.
903.6Extensionthroughthewall.
Ventterminalsextendingthroughthewallshallterminateatapointnotlessthan10feet(3048
mm)fromalotlineandnotlessthan10feet(3048mm)aboveaveragegroundlevel.Vent
terminalsshallnotterminateundertheoverhangofastructurewithsoffitvents.Sidewallvent
terminalsshallbeprotectedtopreventbirdsorrodentsfromenteringorblockingthevent
opening.
903.7Extensionoutsideastructure.
Inclimateswherethe97.5percentvalueforoutsidedesigntemperatureislessthan0°F(-18°C),
ventpipesinstalledontheexteriorofthestructureshallbeprotectedagainstfreezingby
insulation,heatorboth.
SECTION904-OUTDOORVENTEXTENSIONS
904.1Requiredventextension.
Theventsystemservingeachbuildingdrainshallhavenotlessthanoneventpipethatextends
totheoutdoors.
904.1.1Installation.
Therequiredventshallbeadryventthatconnectstothebuildingdrainoranextension
ofadrainthatconnectstothebuildingdrain.Suchventshallnotbeanislandfixture
ventasallowedbySection916.
904.1.2Size.
TherequiredventshallbesizedinaccordancewithSection906.2basedontherequired
sizeofthebuildingdrain.
8
904.2Ventstackrequired.
Aventstackshallberequiredforeverydrainagestackthathasfivebranchintervalsormore.
Exception:DrainagestacksinstalledinaccordancewithSection913.
904.3Venttermination.
Ventstacksorstackventsshallterminateoutdoorstotheopenairortoastack-typeair
admittancevalveinaccordancewithSection918.
904.4Ventconnectionatbase.
Ventstacksshallconnecttothebaseofthedrainagestack.Theventstackshallconnectator
belowthelowesthorizontalbranch.Wheretheventstackconnectstothebuildingdrain,the
connectionshallbelocateddownstreamofthedrainagestackandwithinadistanceof10times
thediameterofthedrainagestack.
904.5Ventheaders.
Stackventsandventstacksconnectedintoacommonventheaderatthetopofthestacksand
extendingtotheopenairatonepointshallbesizedinaccordancewiththerequirementsof
Section906.1.Thenumberoffixtureunitsshallbethesumofallfixtureunitsonallstacks
connectedthereto,andthedevelopedlengthshallbethelongestventlengthfromthe
intersectionatthebaseofthemostdistantstacktotheventterminalintheopenair,asa
directextensionofonestack.
SECTION905-VENTCONNECTIONSANDGRADES
905.1Connection.
Individual,branchandcircuitventsshallconnecttoaventstack,stackvent,airadmittance
valveorextendtotheopenair.
905.2Grade.
Ventandbranchventpipesshallbesogradedandconnectedastodrainbacktothedrainage
pipebygravity.
905.3Ventconnectiontodrainagesystem.
Everydryventconnectingtoahorizontaldrainshallconnectabovethecenterlineofthe
horizontaldrainpipe.
9
905.4Verticalriseofvent.
Everydryventshallriseverticallytoapointnotlessthan6inches(152mm)abovetheflood
levelrimofthehighesttraportrappedfixturebeingvented.
Exception:Ventsforinterceptorslocatedoutdoors.
905.5Heightabovefixtures.
Aconnectionbetweenaventpipeandaventstackorstackventshallbemadeatnotlessthan
6inches(152mm)abovethefloodlevelrimofthehighestfixtureservedbythevent.
Horizontalventpipesformingbranchvents,reliefventsorloopventsshallbelocatednotless
than6inches(152mm)abovethefloodlevelrimofthehighestfixtureserved.
905.6Ventforfuturefixtures.
Wherethedrainagepipinghasbeenroughed-inforfuturefixtures,arough-inconnectionfora
ventshallbeinstalled.Theventsizeshallbenotlessthanone-halfthediameteroftherough-in
draintobeserved.Theventrough-inshallconnecttotheventsystem,orshallbeventedby
othermeansasprovidedforinthischapter.Theconnectionshallbeidentifiedtoindicatethat
itisavent.
10
SECTION906-VENTPIPESIZING
906.1Sizeofstackventsandventstacks.
Theminimumrequireddiameterofstackventsandventstacksshallbedeterminedfromthe
developedlengthandthetotalofdrainagefixtureunitsconnectedtheretoinaccordancewith
Table906.1,butinnocaseshallthediameterbelessthanone-halfthediameterofthedrain
servedorlessthan1¼inches(32mm).
11
906.2Ventsotherthanstackventsorventstacks.
Thediameterofindividualvents,branchvents,circuitventsandreliefventsshallbenotless
thanone-halftherequireddiameterofthedrainserved.Therequiredsizeofthedrainshallbe
determinedinaccordancewithTable710.1(2).Ventpipesshallnotbelessthan1¼inches(32
mm)indiameter.Ventsexceeding40feet(12192mm)indevelopedlengthshallbeincreased
byonenominalpipesizefortheentiredevelopedlengthoftheventpipe.Reliefventsforsoil
andwastestacksinbuildingshavingmorethan10branchintervalsshallbesizedinaccordance
withSection908.2.
906.3Developedlength.
Thedevelopedlengthofindividual,branch,circuitandreliefventsshallbemeasuredfromthe
farthestpointofventconnectiontothedrainagesystemtothepointofconnectiontothevent
stack,stackventorterminationoutsideofthebuilding.
906.4Multiplebranchvents.
Wheremultiplebranchventsareconnectedtoacommonbranchvent,thecommonbranch
ventshallbesizedinaccordancewiththissectionbasedonthesizeofthecommonhorizontal
drainagebranchthatisorwouldberequiredtoservethetotaldrainagefixtureunitloadbeing
vented.
12
906.5Sumpvents.
SumpventsizesshallbedeterminedinaccordancewithSections906.5.1and906.5.2.
906.5.1Sewagepumpsandsewageejectorsotherthanpneumatic.
Drainagepipingbelowsewerlevelshallbeventedinthesamemannerasthatofa
gravitysystem.Buildingsumpventsizesforsumpswithsewagepumpsorsewage
ejectors,otherthanpneumatic,shallbedeterminedinaccordancewithTable906.5.1.
906.5.2Pneumaticsewageejectors.
Theairpressurereliefpipefromapneumaticsewageejectorshallbeconnectedtoan
independentventstackterminatingasrequiredforventextensionsthroughtheroof.
Thereliefpipeshallbesizedtorelieveairpressureinsidetheejectortoatmospheric
pressure,butshallbenotlessthaninches1¼inches(32mm)insize.
13
SECTION907-VENTSFORSTACKOFFSETS
907.1Ventforhorizontaloffsetofdrainagestack.
Horizontaloffsetsofdrainagestacksshallbeventedwherefiveormorebranchintervalsare
locatedabovetheoffset.Theoffsetshallbeventedbyventingtheuppersectionofthe
drainagestackandthelowersectionofthedrainagestack.
907.2Uppersection.
Theuppersectionofthedrainagestackshallbeventedasaseparatestackwithaventstack
connectioninstalledinaccordancewithSection904.4.Theoffsetshallbeconsideredthebase
ofthestack.
907.3Lowersection.
Thelowersectionofthedrainagestackshallbeventedbyayokeventconnectingbetweenthe
offsetandthenextlowerhorizontalbranch.Theyokeventconnectionshallbepermittedtobe
averticalextensionofthedrainagestack.Thesizeoftheyokeventandconnectionshallbea
minimumofthesizerequiredfortheventstackofthedrainagestack.
SECTION908-RELIEFVENTS-STACKSOFMORETHAN10BRANCHINTERVALS
908.1Whererequired.
Soilandwastestacksinbuildingshavingmorethan10branchintervalsshallbeprovidedwitha
reliefventateachtenthintervalinstalled,beginningwiththetopfloor.
908.2Sizeandconnection.
Thesizeofthereliefventshallbeequaltothesizeoftheventstacktowhichitconnects.The
lowerendofeachreliefventshallconnecttothesoilorwastestackthroughawyebelowthe
horizontalbranchservingthefloor,andtheupperendshallconnecttotheventstackthrougha
wyenotlessthan3feet(914mm)abovethefloor.
14
SECTION909-FIXTUREVENTS
909.1Distanceoftrapfromvent.
Eachfixturetrapshallhaveaprotectingventlocatedsothattheslopeandthedeveloped
lengthinthefixturedrainfromthetrapweirtotheventfittingarewithintherequirementsset
forthinTable909.1.
Exception:The
developed
lengthofthe
fixturedrain
fromthetrap
weirtothe
ventfittingfor
self-siphoning
fixtures,such
aswaterclosets,shallnotbelimited.
909.2Ventingoffixturedrains.
Thetotalfallinafixturedrainduetopipeslopeshallnotexceedthediameterofthefixture
drain,norshalltheventconnectiontoafixturedrain,exceptforwaterclosets,bebelowthe
weirofthetrap.
909.3Crownvent.
Aventshallnotbeinstalledwithintwopipediametersofthetrapweir.
SECTION910-INDIVIDUALVENT
910.1Individualventpermitted.
Eachtrapandtrappedfixtureispermittedtobeprovidedwithanindividualvent.Theindividual
ventshallconnecttothefixturedrainofthetraportrappedfixturebeingvented.
15
SECTION911-COMMONVENT
911.1Individualventascommonvent.
Anindividualventispermittedtoventtwotrapsortrappedfixturesasacommonvent.The
trapsortrappedfixturesbeingcommonventedshallbelocatedonthesamefloorlevel.
911.2Connectionatthesamelevel.
Wherethefixturedrainsbeingcommonventedconnectatthesamelevel,theventconnection
shallbeattheinterconnectionofthefixturedrainsordownstreamoftheinterconnection.
911.3Connectionatdifferentlevels.
Wherethefixturedrainsconnectatdifferentlevels,theventshallconnectasavertical
extensionoftheverticaldrain.Theverticaldrainpipeconnectingthetwofixturedrainsshallbe
consideredtheventfor
thelowerfixturedrain,
andshallbesizedin
accordancewithTable
911.3.Theupperfixture
shallnotbeawater
closet.
SECTION912-WETVENTING
912.1Horizontalwetventpermitted.
Anycombinationoffixtureswithintwobathroomgroupslocatedonthesamefloorlevelis
permittedtobeventedbyahorizontalwetvent.Thewetventshallbeconsideredtheventfor
thefixturesandshallextendfromtheconnectionofthedryventalongthedirectionoftheflow
inthedrainpipetothemostdownstreamfixturedrainconnectiontothehorizontalbranch
drain.Eachwet-ventedfixturedrainshallconnectindependentlytothehorizontalwetvent.
Onlythefixtureswithinthebathroomgroupsshallconnecttothewet-ventedhorizontalbranch
drain.Anyadditionalfixturesshalldischargedownstreamofthehorizontalwetvent.
16
912.1.1Verticalwetventpermitted.
Anycombinationoffixtureswithintwobathroomgroupslocatedonthesamefloorlevel
ispermittedtobeventedbyaverticalwetvent.Theverticalwetventshallbe
consideredtheventforthefixturesandshallextendfromtheconnectionofthedry
ventdowntothelowestfixturedrainconnection.Eachwet-ventedfixtureshallconnect
independentlytotheverticalwetvent.Waterclosetdrainsshallconnectatthesame
elevation.Otherfixturedrainsshallconnectaboveoratthesameelevationasthewater
closetfixturedrains.Thedry-ventconnectiontotheverticalwetventshallbean
individualorcommonventservingoneortwofixtures.
912.2Dryventconnection.
Therequireddry-ventconnectionforwet-ventedsystemsshallcomplywithSections912.2.1
and912.2.2.
912.2.1Horizontalwetvent.
Thedry-ventconnectionforahorizontalwet-ventsystemshallbeanindividualventora
commonventforanybathroomgroupfixture,exceptanemergencyfloordrain.Where
thedry-ventconnectstoawaterclosetfixturedrain,thedrainshallconnecthorizontally
tothehorizontalwet-ventsystem.Notmorethanonewet-ventedfixturedrainshall
dischargeupstreamofthedry-ventedfixturedrainconnection.
912.2.2Verticalwetvent.
Thedry-ventconnectionforaverticalwet-ventsystemshallbeanindividualventor
commonventforthemostupstreamfixturedrain.
912.3Size.
Thedryventservingthewetventshallbesizedbasedonthelargestrequireddiameterofpipe
withinthewet-ventsystem
servedbythedryvent.Thewet
ventshallbeofasizenotless
thanthatspecifiedinTable912.3,
basedonthefixtureunit
dischargetothewetvent.
17
SECTION913-WASTESTACKVENT
913.1Wastestackventpermitted.
Awastestackshallbeconsideredaventforallofthefixturesdischargingtothestackwhere
installedinaccordancewiththerequirementsofthissection.
913.2Stackinstallation.
Thewastestackshallbevertical,andbothhorizontalandverticaloffsetsshallbeprohibited
betweenthelowestfixturedrainconnectionandthehighestfixturedrainconnection.Fixture
drainsshallconnectseparatelytothewastestack.Thestackshallnotreceivethedischargeof
waterclosetsorurinals.
913.3Stackvent.
Astackventshallbeprovidedforthewastestack.Thesizeofthestackventshallbenotless
thanthesizeofthewastestack.Offsetsshallbepermittedinthestackvent,shallbelocatednot
lessthan6inches(152mm)abovethefloodlevelofthehighestfixtureandshallbein
accordancewithSection905.2.Thestackventshallbepermittedtoconnectwithother
stackventsandventstacksinaccordancewithSection904.5.
913.4Wastestacksize.
Thewastestackshallbesized
basedonthetotaldischargetothe
stackandthedischargewithina
branchintervalinaccordancewith
Table913.4.Thewastestackshall
bethesamesizethroughoutits
length.
SECTION914-CIRCUITVENTING
914.1Circuitventpermitted.
Amaximumofeightfixturesconnectedtoahorizontalbranchdrainshallbepermittedtobe
circuitvented.Eachfixturedrainshallconnecthorizontallytothehorizontalbranchbeing
circuitvented.Thehorizontalbranchdrainshallbeclassifiedasaventfromthemost
18
downstreamfixturedrainconnectiontothemostupstreamfixturedrainconnectiontothe
horizontalbranch.
914.1.1Multiplecircuit-ventedbranches.
Circuit-ventedhorizontalbranchdrainsarepermittedtobeconnectedtogether.Each
groupofamaximumofeightfixturesshallbeconsideredaseparatecircuitventand
shallconformtotherequirementsofthissection.
914.2Ventconnection.
Thecircuitventconnectionshallbelocatedbetweenthetwomostupstreamfixturedrains.The
ventshallconnecttothehorizontalbranchandshallbeinstalledinaccordancewithSection
905.Thecircuitventpipeshallnotreceivethedischargeofanysoilorwaste.
914.3Slopeandsizeofhorizontalbranch.
Theslopeoftheventsectionofthehorizontalbranchdrainshallbenotgreaterthanoneunit
verticalin12unitshorizontal(8.3-percentslope).Theentirelengthoftheventsectionofthe
horizontalbranchdrainshallbesizedforthetotaldrainagedischargetothebranch.
914.3.1Sizeofmultiplecircuitvent.
Eachseparatecircuit-ventedhorizontalbranchthatisinterconnectedshallbesized
independentlyinaccordancewithSection914.3.Thedownstreamcircuit-vented
horizontalbranchshallbesizedforthetotaldischargeintothebranch,includingthe
upstreambranchesandthefixtureswithinthebranch.
914.4Reliefvent.
Areliefventshallbeprovidedforcircuit-ventedhorizontalbranchesreceivingthedischargeof
fourormorewaterclosetsandconnectingtoadrainagestackthatreceivesthedischargeof
soilorwastefromupperhorizontalbranches.
914.4.1Connectionandinstallation.
Thereliefventshallconnecttothehorizontalbranchdrainbetweenthestackandthe
mostdownstreamfixturedrainofthecircuitvent.Thereliefventshallbeinstalledin
accordancewithSection905.
19
914.4.2Fixturedrainorbranch.
Thereliefventispermittedtobeafixturedrainorfixturebranchforfixtureslocated
withinthesamebranchintervalasthecircuit-ventedhorizontalbranch.Themaximum
dischargetoareliefventshallbefourfixtureunits.
914.5Additionalfixtures.
Fixtures,otherthanthecircuitventedfixtures,arepermittedtodischargetothehorizontal
branchdrain.Suchfixturesshallbelocatedonthesamefloorasthecircuit-ventedfixturesand
shallbeeitherindividuallyorcommonvented.
SECTION915-COMBINATIONWASTEANDVENTSYSTEM
915.1Typeoffixtures.
Acombinationwasteandventsystemshallnotservefixturesotherthanfloordrains,sinks,
lavatoriesanddrinkingfountains.Combinationwasteandventsystemsshallnotreceivethe
dischargefromafooddisposerorclinicalsink.
915.2Installation.
Theonlyverticalpipeofacombinationwasteandventsystemshallbetheconnectionbetween
thefixturedrainandthehorizontalcombinationwasteandventpipe.Theverticaldistanceshall
notexceed8feet(2438mm).
915.2.1Slope.
Theslopeofahorizontalcombinationwasteandventpipeshallnotexceedone-half
unitverticalin12units
horizontal(4-percent
slope)andshallnotbe
lessthanthatindicated
inTable704.1.
915.2.2Sizeandlength.
Thesizebethat
indicatedinTable
915.2.2unlimited.
20
915.2.3Connection.
Thecombinationwasteandventsystemshallbeprovidedwithadryventconnectedat
anypointwithinthesystemorthesystemshallconnecttoahorizontaldrainthatserves
ventedfixtureslocatedonthesamefloor.Combinationwasteandventsystems
connectingtobuildingdrainsreceivingonlythedischargefromoneormorestacksshall
beprovidedwithadryvent.Theventconnectiontothecombinationwasteandvent
pipeshallextendverticallytoapointnotlessthan6inches(152mm)abovetheflood
levelrimofthehighestfixturebeingventedbeforeoffsettinghorizontally.
915.2.4Ventsize.
TheventshallbesizedforthetotaldrainagefixtureunitloadinaccordancewithSection
906.2.
915.2.5Fixturebranchordrain.
Thefixturebranchorfixturedrainshallconnecttothecombinationwasteandvent
withinadistancespecifiedinTable909.1.Thecombinationwasteandventpipeshallbe
consideredtheventforthefixture.
SECTION916-ISLANDFIXTUREVENTING
916.1 Limitation.
Islandfixtureventingshallnotbepermittedforfixturesotherthansinksandlavatories.
Residentialkitchensinkswithadishwasherwasteconnection,afoodwastedisposer,orboth,
incombinationwiththekitchensinkwaste,shallbepermittedtobeventedinaccordancewith
thissection.
916.2Ventconnection.
Theislandfixtureventshallconnecttothefixturedrainasrequiredforanindividualor
commonvent.Theventshallriseverticallytoabovethedrainageoutletofthefixturebeing
ventedbeforeoffsettinghorizontallyorverticallydownward.Theventorbranchventfor
multipleislandfixtureventsshallextendtoapointnotlessthan6inches(152mm)abovethe
highestislandfixturebeingventedbeforeconnectingtotheoutsideventterminal.
21
916.3Ventinstallationbelowthefixturefloodlevelrim.
Theventlocatedbelowthefloodlevelrimofthefixturebeingventedshallbeinstalledas
requiredfordrainagepipinginaccordancewithChapter7,exceptforsizing.Theventshallbe
sizedinaccordancewithSection906.2.Thelowestpointoftheislandfixtureventshallconnect
fullsizetothedrainagesystem.Theconnectionshallbetoaverticaldrainpipeortothetop
halfofahorizontaldrainpipe.Cleanoutsshallbeprovidedintheislandfixtureventtopermit
roddingofallventpipinglocatedbelowthefloodlevelrimofthefixtures.Roddinginboth
directionsshallbepermittedthroughacleanout.
SECTION917-SINGLESTACKVENTSYSTEM
917.1Wherepermitted.
Adrainagestackshallserveasasinglestackventsystemwheresizedandinstalledin
accordancewithSections917.2through917.9.Thedrainagestackandbranchpipingshallbe
theventsforthedrainagesystem.Thedrainagestackshallhaveastackvent.
917.2Stacksize.
Drainagestacksshallbe
sizedinaccordancewith
Table917.2.Stacksshallbe
uniformlysizedbasedon
thetotalconnected
drainagefixtureunitload.
Thestackventshallbethe
samesizeasthedrainage
stack.A3-inch(76mm)stackshallservenotmorethantwowaterclosets.
917.3Branchsize.
Horizontalbranchesconnectingtoasinglestackventsystemshallbesizedinaccordancewith
Table710.1(2).Notmorethanonewaterclosetshalldischargeintoa3-inch(76mm)horizontal
branchatapointwithinadevelopedlengthof18inches(457mm)measuredhorizontallyfrom
thestack.Whereawaterclosetiswithin18inches(457mm)measuredhorizontallyfromthe
22
stackandnotmorethanonefixturewithadrainsizeofnotmorethan1½inches(38mm)
connectstoa3-inch(76mm)horizontalbranch,thebranchdrainconnectiontothestackshall
bemadewithasanitarytee.
917.4Lengthofhorizontalbranches.
ThelengthofhorizontalbranchesshallconformtotherequirementsofSections917.4.1
through917.4.3.
917.4.1Waterclosetconnection.
Waterclosetconnectionsshallbenotgreaterthan4feet(1219mm)indeveloped
lengthmeasuredhorizontallyfromthestack.
Exception:Wheretheconnectionismadewithasanitarytee,themaximum
developedlengthshallbe8feet(2438mm).
917.4.2Fixtureconnections.
Fixturesotherthanwaterclosetsshallbelocatednotgreaterthan12feet(3657mm)in
developedlength,measuredhorizontallyfromthestack.
917.4.3Verticalpipinginbranch.
Thelengthofverticalpipinginafixturedrainconnectingtoahorizontalbranchshallnot
beconsideredincomputingthefixture'sdistanceindevelopedlengthmeasured
horizontallyfromthestack.
917.5Minimumverticalpipingsizefromfixture.
Theverticalportionofpipinginafixturedraintoahorizontalbranchshallbe2inches(51mm).
Theminimumsizeoftheverticalportionofpipingforawater-suppliedurinalorstandpipeshall
be3inches(76mm).Themaximumverticaldropshallbe4feet(1219mm).Fixturedrainsthat
arenotincreasedinsize,orhaveaverticaldropinexcessof4feet(1219mm),shallbe
individuallyvented.
917.6Additionalventingrequired.
Additionalventingshallbeprovidedwheremorethanonewaterclosetdischargestoa
horizontalbranchandwherethedistancefromafixturetraptothestackexceedsthelimitsin
Section917.4.Whereadditionalventingisrequired,thefixture(s)shallbeventedbyindividual
vents,commonvents,wetvents,circuitvents,oracombinationwasteandventpipe.Thedry
23
ventextensionsfortheadditionalventingshallconnecttoabranchvent,ventstack,stackvent,
airadmittancevalve,orshallterminateoutdoors.
917.7Stackoffsets.
Wherefixturedrainsarenotconnectedbelowahorizontaloffsetinastack,ahorizontaloffset
shallnotberequiredtobevented.Wherehorizontalbranchesorfixturedrainsareconnected
belowahorizontaloffsetinastack,theoffsetshallbeventedinaccordancewithSection907.
Fixtureconnectionsshallnotbemadetoastackwithin2feet(610mm)aboveorbelowa
horizontaloffset.
917.8Prohibitedlowerconnections.
Stacksgreaterthan2branchintervalsinheightshallnotreceivethedischargeofhorizontal
branchesonthelowertwofloors.Thereshallbenoconnectionstothestackbetweenthe
lowertwofloorsandadistanceofnotlessthan10pipediametersdownstreamfromthebase
ofthesinglestackventedsystem.
917.9Sizingbuildingdrainsandsewers.
Thebuildingdrainandbuildingsewerreceivingthedischargeofasinglestackventsystemshall
besizedinaccordancewithTable710.1(1).
SECTION918-AIRADMITTANCEVALVES
918.1General.
Ventsystemsutilizingairadmittancevalvesshallcomplywiththissection.Stack-typeair
admittancevalvesshallconformtoASSE1050.Individualandbranchtypeairadmittancevalves
shallconformtoASSE1051.
918.2Installation.
Thevalvesshallbeinstalledinaccordancewiththerequirementsofthissectionandthe
manufacturer'sinstructions.AiradmittancevalvesshallbeinstalledaftertheDWVtesting
requiredbySection312.2or312.3hasbeenperformed.
918.3Wherepermitted.
Individual,branchandcircuitventsshallbepermittedtoterminatewithaconnectiontoan
individualorbranch-typeairadmittancevalveinaccordancewithSection918.3.1.Stackvents
24
andventstacksshallbepermittedtoterminatetostack-typeairadmittancevalvesin
accordancewithSection918.3.2.
918.3.1Horizontalbranches.
Individualandbranch-typeairadmittancevalvesshallventonlyfixturesthatareonthe
samefloorlevelandconnecttoahorizontalbranchdrain.Wherethehorizontalbranch
islocatedmorethanfourbranchintervalsfromthetopofthestack,thehorizontal
branchshallbeprovidedwithareliefventthatshallconnecttoaventstackorstack
vent,orextendoutdoorstotheopenair.Thereliefventshallconnecttothehorizontal
branchdrainbetweenthestackandthemostdownstreamfixturedrainconnectedto
thehorizontalbranchdrain.ThereliefventshallbesizedinaccordancewithSection
906.2andinstalledinaccordancewithSection905.Thereliefventshallbepermittedto
serveastheventforotherfixtures.
918.3.2Stack.
Stack-typeairadmittancevalvesshallbeprohibitedfromservingastheventterminal
forventstacksorstackventsthatservedrainagestackshavingmorethansixbranch
intervals.
918.4Location.
Individualandbranch-typeairadmittancevalvesshallbelocatedaminimumof4inches(102
mm)abovethehorizontalbranchdrainorfixturedrainbeingvented.Stack-typeairadmittance
valvesshallbelocatednotlessthan6inches(152mm)abovethefloodlevelrimofthehighest
fixturebeingvented.Theairadmittancevalveshallbelocatedwithinthemaximumdeveloped
lengthpermittedforthevent.Theairadmittancevalveshallbeinstallednotlessthan6inches
(152mm)aboveinsulationmaterials.
918.5Accessandventilation.
Accessshallbeprovidedtoallairadmittancevalves.Suchvalvesshallbeinstalledinalocation
thatallowsairtoenterthevalve.
918.6Size.
Theairadmittancevalveshallberatedinaccordancewiththestandardforthesizeofthevent
towhichthevalveisconnected.
25
918.7Ventrequired.
Withineachplumbingsystem,notlessthanonestackventorventstackshallextendoutdoors
totheopenair.
918.8Prohibitedinstallations.
Airadmittancevalvesshallnotbeinstalledinnonneutralizedspecialwastesystemsas
describedinChapter8exceptwheresuchvalvesareincompliancewithASSE1049,are
constructedofmaterialsapprovedinaccordancewithSection702.5andaretestedfor
chemicalresistanceinaccordancewithASTMF1412.Airadmittancevalvesshallnotbelocated
inspacesutilizedassupplyorreturnairplenums.Airadmittancevalveswithoutanengineered
designshallnotbeutilizedtoventsumpsortanksofanytype.