2013-3262-3m-0001 rev a datasheet open drain heater datasheet
DESCRIPTION
Datasheet Open Drain Heater DatasheetTRANSCRIPT
-
Page: 2 of 6
REVISION LOG
STV EXTENSION STV SOUTH
WEST PROJECT (SVSW)
EPCI FOR WHP-SVSW,
PIPELINES AND CPP
MODIFICATIONS
DATASHEET FOR OPEN DRAIN HEATER
Document No.: 2013-3262-3M-0001
Revision: A
Revision No. Section Revision Description
A ALL ISSUED FOR REVIEW
-
1 Mainufacturer: EX HEAT or Equal Area Classification: Class 1, DIV 2, Group D, T3
2 Quantity: One
3 Horizontal Vertical Fluid composition: HYDROCARBON LIQUID & WATER
4 Specific Gravity of Contents: 0.8 - 0.975
5 Code: ATEX Operating Pressure: ATM
6 Specifications: 2013-3269-3L-0011 Operating Temperature C: 60C
7 Bundle length mm; 750 ( VTC) Operating Liquid Level mm: 550
8 Flange Diameter: 6" ( VTC) ( note 12) Normal Liquid Volume ( at NLL) m3: ( Note 14)
9 Design Pressure barg: WATER FULL+ 0.05Barg
10 Vacuum Design bar: - 0.002barg Flanges: SA105N
11 Design Max. tempaerature C: VTA Baffles/ Tie Rods: 316SS
12 Design Min. tempaerature C: 0 Elements: Alloy 800 Uns No8800
13 Seismic Loads ( Horz./Vert.) g: N/A Gaskets 316SS Spiral Wound, 4.4 mm thk.
14 Wind & Transportation Load: ( Note 2)
15 Blast load bar: N/A 316SS inner & outer rings, graphite filler
16 Slug Loads barg: N/A Bolts & Nuts: ( refer A1 Pipe Class)
17 Corrosion Allowance (lnt.) mm: 3 mm PTFE COATED
18 Terminal Box: 316L SS
19 Heat Loss Duty (KW): 10KW Namplate: 316L SS
20 Total Surface area m2: VTA
21 Heat transfer coefficients W/m2.C: VTA Inspector Authority: VR
22 Mean teamperature difference C: VTA Post Weld Heat treatment: N/A
23 Radiography N/A
24 No. Active: 3 DPT: YES
25 No. Spare: 2 Ultrasonic: NO
26 Diameter mm: VTA Hydrostatic Test barg: VTA
27 Active "U" mm: VTA
28 Total Load kW: 10 External Coating: Note 3
29 No. of element per phase: VTA
30 Element Load kW: VTA Heater Bundle Weight (kg): VTA
31 Voltage V: Note-4
32 Flux W/cm2: VTA Protection: NEMA 4X/7
33 Sheath temp. C: VTA Paint: Marine
34
35
36
37
38
39
NO. QTY SIZE TYPE ORIENTATION SERVICES REMARKSFACERATING
Heater ConnectionN5 1 6" ( VTC) ANSI 150# RF WN
DESIGN DATA
HEAT TRANSFER DATA
NOZZLE SCHEDULE (Refer Pipe Class A1)
OPERATING CONDITIONS
MATERIALS ( note-8)
FABRICATION & INSPECTION
PROTECTIVE COATING
WEIGHTS
JUNCTION BOX
ELEMENT DETAILS
DATA SHEET
PROJECT NAME:
STV EXTENSION PLAN- STV SOUTH WEST (SVSW)
EPCI FOR WHP-SVSW, PIPELINES AND CPP MODIFICATIONS
Item Tag No. : HAP - 6225
Requisition No. : 2013-3200-1W-0003
Document No. : 2013-3262-3M-0001
Sheet No. : 3 of 6
Service : OPEN DRAIN HEATER
Rev. : A
-
40
41 Tag No.: TZT-6225-3 TZT-6225-4
42 Service: Heater Flange Over Temp. Heater Element Over Temp. ( Hi/Hi)
43 P&ID No.: 2013-3262-01-0015 2013-3262-01-0015
44 Line No.: NA NA
45 Line Size ( Wall Thickness, mm): NA NA
46 Quantity 1 1
47
48 Measurement Type: 3 Wire RTD, 100Ohm at 0 Deg.C 3 Wire RTD, 100Ohm at 0 Deg.C
49 Element Material: Platinum Element Platinum Element
50 Instrument Connection Thread: NA NA
51 Immersion Length: VTA VTA
52 Thermowell Connection NA NA
53
54 Thermowell Material: NA NA
55 Thermowell Immersion Leght: NA NA
56 Thermowell Lagging Length: NA NA
57 Thermowell Construction Style: NA NA
58 Thermowell Process Connection: NA NA
59 Thermowell Stem Style: NA NA
60 Thermowell Mouting: NA NA
61 Flange Type/ Rating/ Material: NA NA
62
63 Electronic/ Smart Hart Protocal: Yes/ Smart Hart Yes/ Smart Hart
64 Output Signal: 4-20mA (24VDC) 4-20mA (24VDC)
65 Power Supply: 24VDC ( Loop Powered) from ICSS 24VDC ( Loop Powered) from ICSS
66 IP Rating/ Tropicalized: NEMA 4X NEMA 4X
67 Electrical Protection: NEMA 7 NEMA 7
68 Certificate Number;
69 Hazardous Area Classification: Class I, Div. 2, Group D, T3 Class I, Div. 2, Group D, T3
70 Electrical Connection: M20 x 1.5 M20 x 1.5
71 Process Connection: NA NA
72 Housing Material: SS316 SS316
73 Housing Paint: Polyurethane Polyurethane
74 Accuracy: +/- 0.03% of span +/- 0.03% of span
75 Temperature effect: +/- 0.001% of span +/- 0.001% of span
76 Range Min/ Range Max: VTA VTA
77 Manufacturer: ROSEMOUNT or Equal ROSEMOUNT or Equal
78
SENSOR
THERMOWELL
TRANSMITTER
GENERAL TRANSMITTERS TEMPERATURE
DATA SHEET
PROJECT NAME:
STV EXTENSION PLAN- STV SOUTH WEST (SVSW)
EPCI FOR WHP-SVSW, PIPELINES AND CPP MODIFICATIONS
Item Tag No. : HAP - 6225
Requisition No. : 2013-3200-1W-0003
Document No. : 2013-3262-3M-0001
Sheet No. : 4 of 6
Service : OPEN DRAIN HEATER
Rev. : A
-
79
80 Chemical / Material:
81 Chemical Seal Diaphragm
82 Bottom Flange Material:L
83 Capillary Material / Lengh (m):
84 Integrated Indicator: Yes ( LCD Display) Yes ( LCD Display)
85 2" Pipe Mounting Bracket SS316L No No
86 Manifold: No No
87
88 Fluid: HYDROCARBON LIQUID & WATER HYDROCARBON LIQUID & WATER
89 Flow rate: Inlet / Outlet 0 0
90 Design Pressure: Water Full + 0.05barg WF + 0.05barg
91 Design Temperature: VTA VTA
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
PROCESS DATA
ACCESSORIES
DATA SHEET
PROJECT NAME:
STV EXTENSION PLAN- STV SOUTH WEST (SVSW)
EPCI FOR WHP-SVSW, PIPELINES AND CPP MODIFICATIONS
Item Tag No. : HAP - 6225
Requisition No. : 2013-3200-1W-0003
Document No. : 2013-3262-3M-0001
Sheet No. : 5 of 6
Service : OPEN DRAIN HEATER
Rev. : A
-
114 NOTED:
115 1) The immersed heater Tag no. HAP-6225 is to be mounted on Open Drain Tank Tag No. ABJ-6225
116 2) The Heater with the tank shall be designed for wind load ( 3 second wind speed) and transportation load as detail in
117 Specification for Atmospheric Tank: 2013-3200-11-0006
118 3) Painting shall be in accordance with COMPANY specification 2012-3189-61-0010-3289-6L-0010 " Specification Painting and Protective Coating"
119 4) The electric heater power supply shall be 3C 4mm XLE, 480V, 3 phase, 60Hz.
120 5) VTA = VENDOR To Advise
121 VTC = VENDOR To Confirm
122 6) The Heater assembly shall be designed to avoid excessive vibration during operation. Necessary internal support inside the tank shall be provided
123 ( by Tank Vendor). Heater Vendor to advise any such additional support required
124 7) VENDOR to confirm material selection
125 8) Heater shall be designed for full of liquid of Open Drain Tank ABJ-6225 (Tank height is 1.3m)
126 The Liquid condition as follow: Fluid (Note 14 )
127 Density 82-975
128 Viscosity 13.3CP - 0.6737CP
129 Wax Appearance Temp. 54C
130
131 9) VENDOR to advise, in their proposal, impact of mercury traces in the fluid on material selection
132 10) Minimum design temerature to be minimum ambient air temperature. VENDOR shall calculate and confirm the minimum.
133 Design metal temperature ( MDMT) for the proposed material and selected thickness with their proposal, talking into account all heater components.
134 11) VENDOR to provide, heater termination box shall have space heater with rated 240 VAC but power by 120VAC.
135 12) VENDOR to provide optional SIL-2 rated TZT's in accordance with IEC 61508
136 13) Heater duty must be enough to heat up fluid from 20 C- 60 C at 550mm
137 14) Open drain Tank is isulated to avoid heat loss. The thickness of insulation is refered on document 2013-3262-1M-0001_ Open Drain Tank Datasheet
138 15) Process datasheet shall be refered in document 2013-3262-1M-0001_ Open Drain Tank Datasheet
139 16) Insulation will be used for oil compartment
140 17) Flange Shall be conform to ASME B16.5
141 18) Vendor to provided local Stop Push Button.
142 19) Vendor to provided permanently attached ss316ss tags of Transmitters, minium thickness of 1/16"
143
144
145
146
147
148
149
150
151
DATA SHEET
PROJECT NAME:
STV EXTENSION PLAN- STV SOUTH WEST (SVSW)
EPCI FOR WHP-SVSW, PIPELINES AND CPP MODIFICATIONS
Item Tag No. : HAP - 6225
Requisition No. : 2013-3200-1W-0003
Document No. : 2013-3262-3M-0001
Sheet No. : 6 of 6
Service : OPEN DRAIN HEATER
Rev. : A
Cover -1Cover -2Sheet 1Sheet 2Sheet 3Sheet 4