2012-12 sprecon-e-p dq6 en
TRANSCRIPT
© Sprecher Automation 2012
www.sprecher-automation.com
SPRECONSPRECON--EE--P DQ6P DQ6
Transformer Differential ProtectionProtection and Combined Protection and Control Devices
2
SPRECONSPRECON--EE--P DQ6P DQ6
3
SPRECONSPRECON--EE--P DQ6P DQ6
Differential protection for:• Two- and three-winding transformer• Short line (considering the maximum current range)• Bay (for maximal three ends, considering the maximum current
range)
Differential- and full motor protection for:• Motor • amplitudes adaptation, vector groups adaptation, rotating field
adaptation and zero current correction are integrated• 4-section characteristic of biased differential protection• improved sensitivity in the case of earth faults with integrated
biased earth current differential protection (with measuring of neutral point current)
• Overexcitation- and und Inrush restraint (with 2. und 5. harmonics) • Stabilisation against current transformer saturation• Many additionally functions
4
SPRECONSPRECON--EE--P DQ6P DQ6
Designation Code:
DxQx6D … digital
2 … for two winding transformers3 … for three winding transformer
Q … Differential protection U … with Voltage- and Frequency Protection
6 … Family Range
DxQx6-1 Protection devices (Circuit-breaker control and check-back)
DxQx6-2 Protection and Control devices (Circuit-breaker- and disconnector control)
5
SCADAIEC 60870-5-101/-104 SPRECON-E Designer
SPRECON-E Service Program
SPRECON-V460HMI Workstation
IEC 61850 / IEC 60870-5-104
(LWL)
SPRECON-E-CGateway 2
(redundant)SPRECON-E-C
Gateway 1
SPRECON-E-C
SPRECON-E-P D6-2
OBS
SPRECON-E-P D6-2
OBSSPRECON-E-P D6-2
OBS (One Box Solution)
SPRECON-E-CBay unit
SPRECON-E-CBay unit
SPRECON-E-P D4
Protection device
SPRECONSPRECON--EE--P AS A PART OF P AS A PART OF ENERGY STATION AUTOMATIONENERGY STATION AUTOMATION
SPRECON-E-P ERER 3Earth fault Protector
SPRECON-E-P D6-1Protection device
6
SPRECONSPRECON--EE--P DQ6P DQ6
D2Qx6• 7I Star / Delta• 7I+1U Star / Delta + voltage input• 8I Star / Star or Star / Delta + frame leakage protection
7I 8I 8I7I+1U
7
SPRECONSPRECON--EE--P DQ6P DQ6
D3Qx6• 11I Star / Star / Delta with earth fault differential protection
orStar / Delta / Delta with frame leakage protection
• 12I Star / Star / Delta with frame leakage protection
11I11I 11I 12I
8
SPRECONSPRECON--EE--P DQ6P DQ6
D3QU6• 10I+1U Star / Delta / Delta + voltage input or
Star / Star / Star without Earth current differential protection + voltage input
• 11I+1U Star / Star / Delta with 2 x Earth current differential protection or Star / Delta / frame leakage protection leakage protection + voltage input
10I+1U 11I+1U 11I+1U10I+1U
9
SPRECONSPRECON--EE--P DQ6P DQ6
IL – measurement of the phase currents per transformer side
IE 1x – measurement of the earth current for earth current differentialprotection (REF)
IE 20x – sensitive measurement of the earth current (frame leakage protection)
U – measurement of voltage (voltage protection, frequency protection) *)
*) Protection functions in preparation (Hardware available!!!)
D2Q6 D2QU6*) D3Q6 D3QU6
*)Variants:Variant / transformer inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U
IE- sensitivity of the earth current transformer 1x
1x/1x or 1x
1x/1x or 1x/1x/
20x 1x1x/1x
or
1x/20x 1x/20x 1x/20x
10
SPRECONSPRECON--EE--P DQ6P DQ6
*) Enlargement by an optional application of the DIU10C4 module(DIU10C4: 10 DI, 4 DO)
**) optional Outputs for a direct control of engine-done switch devices (not accessibly for the protective part)
Designation of the protection modules:
D2Q6 D2QU6 D3Q6 D3QU6Variants:Variant / Transformer inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U
DI 15-25 15-25 15-25 15-25 15-25 15-25 15-25
DO *) 14-18 14-18 14-18 14-18 14-18 14-18 14-18
PowerRelais (option) **) 2 2 2 2 2 2 2
DQ6 PROT-D2Q6-IE1…………………………….. PR-281
PROT-D2Q6-2xIE1…………………………….. PR-285
PROT-D2Q6-IE1-IE20…………………………….. PR-286
PROT-D2QU6-IE1…………………………….. PR-291
PROT-D3Q6-2xIE1…………………………….. PR-2A5
PROT-D3Q6-IE1-IE20…………………………….. PR-2A6
PROT-D3Q6-2xIE1-IE20…………………………….. PR-2A8
PROT-D3QU6-IE1…………………………….. PR-2B1
PROT-D3QU6-2xIE1…………………………….. PR-2B5
PROT-D3QU6-IE1-IE20…………………………….. PR-2B6
11
SPRECONSPRECON--EE--P DQ6 FUNCTIONSP DQ6 FUNCTIONS
Reference Type
Implemented protection functionsIEEE C37.2
IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6
Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U
Neutral-Point current sensitivity 1x
1x/1x or 1x
1x/1x or 1x/1x/ 20x 1x
1x/1x or
1x/20x 1x/20x 1x/20x
Differential protection, number of ends 87T PDIF 2 2 2 3 3 3 3
Ground differential protection, number of ends 87N PDIF 1 2 1 2 2 1 2
Switch on protection (SOTF, SOP), assignable to end 50, 50N PIOC x x x x x x x
IL>DT/IDMT, three stages per end, number of ends 50, 51 PTOC 2 2 2 3 3 3 3
IE>DT/IDMT, three stages per end, number of ends
50N,51N, 51Ns PTOC 2 2 2 3 3 3 3
Inrush restraint PHAR x x x x x x x
Overload protection (2 images, assignable to end) 49, 49N PTTR x x x x x x x
Lockout, number of ends 86 PMRI 2 2 2 3 3 3 3
12
SPRECONSPRECON--EE--P DQ6 FUNCTIONSP DQ6 FUNCTIONS
Reference Type
Implemented protection functionsIEEE C37.2
IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6
Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U
Neutral-Point current sensitivity 1x1x/1x oder 1x
1x/1x oder 1x/1x/
20x 1x1x/1x oder
1x/20x 1x/20x 1x/20x
Circuit breaker failure prot. (CBF), two stages per end, number of ends 50BF RBRF 2 2 2 3 3 3 3
Circuit breaker tripping by up to 6 external signals (PTRC) x x x x x x x
Trip circuit supervision, number of ends 74TC 2 2 2 3 3 3 3
Parameter sets 4 4 4 4 4 4 4
Logic + time stages for optocoupler inputs x x x x x x x
Virtual binary inputs 15 15 15 15 15 15 15
Logic + hold time for output relays x x x x x x x
Measurands, short report x x x x x x x
Event logging, non-volatile RDRE x x x x x x x
Disturbance data recording, non-volatile RADR,RBDR x x x x x x x
Statistics x x x x x x x
Measurand checks, self supervision x x x x x x x
Assistance for test and putting into operation x x x x x x x
13
SPRECONSPRECON--EE--P DQ6P DQ6FUNCTIONS IN PREPARATIONFUNCTIONS IN PREPARATION
Reference Type
Implemented protection functionsIEEE C37.2
IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6
Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U
Neutral-Point current sensitivity 1x1x/1x oder 1x
1x/1x oder 1x/1x/
20x 1x1x/1x oder
1x/20x 1x/20x 1x/20x
*) Functions in preparation
Overvoltage protection (U>), two stages (*)
59 PTOV x x x
Undervoltage protection (U<), two stages (*)
27 PTUV x x x
Frequency protection (four stages f<, two stages f>) (*)
81 PTUF,PTOF x x x
Negative sequence protection Ineg>, three stages, assignable to end (*)
46 PTOC 2 2 2 3 3 3 3
Starting protection, locked rotor protection (motor protection), assignable to end (*)
49R, 66, 48,
51LRPMRI/PMSS x x x x x x x
Underload protection (motor protection) (*)
37 PTUC x x x x x x x
Circuit breaker failure prot. (CBF), two stages per end, number of ends
50BF RBRF 2 2 2 3 3 3 3
Current annunciation stages, (3x IL>an, 3x IE>an), assignable to end (*) x x x x x x x
14
Characteristic of the biased transformer differential protection
SPRECONSPRECON--EE--P DQ6 P DQ6
15
SPRECONSPRECON--EE--P DQ6 P DQ6
Characteristic of the biased transformer earth current differential protection
16
SPRECONSPRECON--E COMME COMM--3 3 –– ENGINEERING ENGINEERING TOOL FOR PROTECTIONTOOL FOR PROTECTION One Tool for all phases….
• Engineering (Protection Adjusting) • Operating (Documentation / Archiving of all Settings, Measurands,
Events and Disturbance records)• Commissioning and Testing of the Protection (export of the
settings as XML- file for the numerical testing device, Evaluation / Analysis of the network faults, also graphical Analysis by using of COMTRADE- Viewer)
17
PARAMETRISATION WITH COMMPARAMETRISATION WITH COMM--33
18
THANK YOU FOR THANK YOU FOR YOUR ATTENTION !YOUR ATTENTION !
Any liability regarding the correctness and completeness of any information and/or specifications in the presentation is excluded. All rights are reserved to alter specifications, make modifications, or terminate models without prior notice. The specifications of a model may vary from country to country.