2002 IS Catalog 116 Pepperl+Fuchs ® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607 E-mail: [email protected] • www.am.pepperl-fuchs.com Introduction ............................................................................................................................. 117 Rotation Speed Limit Alarm KFD2-DWB-Ex1.D (24 VDC) ............................................................................................................... 118 KFA5-DWB-Ex1.D (120 VAC) .............................................................................................................. 119 KFA6-DWB-Ex1.D (240 VAC) .............................................................................................................. 120 Rotation Speed Converter (Digital to analog converter) KFU8-FSSP-1.D (24 VDC, 120 or 240 VAC) ...................................................................................... 121 KFD2-UFC-Ex1 (24 VDC without display) .......................................................................................... 122 KFD2-UFC-Ex1.D (24 VDC with display) ............................................................................................. 123 KFU8-UFC-Ex1 (24 VDC, 120 or 240 VAC without display) ............................................................... 124 KFU8-UFC-Ex1.D (24 VDC, 120 or 240 VAC with display) ................................................................ 125 Universal Logic Controls KFD2-UFT-Ex2.D (24 VDC) ................................................................................................................. 126 KFU8-UFT-Ex2.D (24 VDC, 120 or 240 VAC) ...................................................................................... 127 Timer KFD2-DU-Ex1.D (24 VDC) ................................................................................................................... 128 KFA5-DU-Ex1.D (120 VAC) ................................................................................................................. 129 KFA6-DU-Ex1.D (240 VAC) ................................................................................................................. 130 KFD2-CRG-Ex1.D (24 VDC) ................................................................................................... 131 KFU8-CRG-Ex1.D (24 VDC, 120 or 240 VAC) ........................................................................ 132 Latching Relay KFA5-SR2-Ex2.W.IR (120 VAC) .............................................................................................. 133 KFA6-SR2-Ex2.W.IR (240 VAC) .............................................................................................. 134 Universal Limit Alarm (Voltage, current, RTD, T/C) KFD2-GU-Ex1 (24 VDC Intrinsic safety applications) .......................................................................... 135 Page

Upload: lamnhu

Post on 18-Aug-2018

218 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

2002 IS Catalog

116 Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Introduction ............................................................................................................................. 117Rotation Speed Limit Alarm

KFD2-DWB-Ex1.D (24 VDC) ............................................................................................................... 118KFA5-DWB-Ex1.D (120 VAC) .............................................................................................................. 119KFA6-DWB-Ex1.D (240 VAC) .............................................................................................................. 120

Rotation Speed Converter (Digital to analog converter)KFU8-FSSP-1.D (24 VDC, 120 or 240 VAC) ...................................................................................... 121KFD2-UFC-Ex1 (24 VDC without display) .......................................................................................... 122KFD2-UFC-Ex1.D (24 VDC with display) ............................................................................................. 123KFU8-UFC-Ex1 (24 VDC, 120 or 240 VAC without display) ............................................................... 124KFU8-UFC-Ex1.D (24 VDC, 120 or 240 VAC with display) ................................................................ 125

Universal Logic ControlsKFD2-UFT-Ex2.D (24 VDC) ................................................................................................................. 126KFU8-UFT-Ex2.D (24 VDC, 120 or 240 VAC) ...................................................................................... 127

TimerKFD2-DU-Ex1.D (24 VDC) ................................................................................................................... 128KFA5-DU-Ex1.D (120 VAC) ................................................................................................................. 129KFA6-DU-Ex1.D (240 VAC) ................................................................................................................. 130KFD2-CRG-Ex1.D (24 VDC) ................................................................................................... 131KFU8-CRG-Ex1.D (24 VDC, 120 or 240 VAC) ........................................................................ 132

Latching RelayKFA5-SR2-Ex2.W.IR (120 VAC) .............................................................................................. 133KFA6-SR2-Ex2.W.IR (240 VAC) .............................................................................................. 134

Universal Limit Alarm (Voltage, current, RTD, T/C)KFD2-GU-Ex1 (24 VDC Intrinsic safety applications) .......................................................................... 135

Page

Page 2: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

2002 IS Catalog

117Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Logic controls typically convert analog voltage or current inputs to signals that monitor for speed,direction, frequency or time. Some logic controls feature relay outputs that can be used to selectminimum and maximum values. These versatile modules can be used for level control, for poweringtransmitters, or for a multitude of general-purpose and intrinsically safe applications.

When combined with P+F N3 output sensors, the following switch isolators act as logic controlsand can be used to detect the direction of moving targets:

• KFD2-SR2-Ex2.W (see page 11)• KFD2-SR2-Ex2.2S (see page 12)• KFA5-SR2-Ex2.W (see page 15)• KFA6-SR2-Ex2.W (see page 16)• KFD2-SOT2-Ex2 (see page 21)• KFA5-SOT2-Ex2 (see page 24)• KFA6-SOT2-Ex2 (see page 25)• KFD2-ST2-Ex2 (see page 26)

To be used as direction detection, these logic controls must be connected to a bistable, N3 outputsensors found in the 2002 P+F Sensor Catalog. These sensors have outputs that latch when atarget passes through the ring and do not unlatch until the target passes in the opposite direction.For more information about these switch isolators, refer to the pages indicated above. For assistancewith direction detection applications, contact a GreenTeam representative at (330) 486-0002 or e-mail usat [email protected].

Introduction

Direction Detection with Special P+F NAMUR Sensors

Page 3: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

118

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

KFD2-DWB-Ex1.D

Logic ControlsRotational SpeedLimit Alarm

The KFD2-DWB-Ex1.D monitors foroverspeed or underspeed conditions bycomparing the input frequency to the user-programmed reference frequency. Thereference frequency is easily programed bypush buttons mounted on the front panel.An overspeed or underspeed condition issignaled via the relay outputs. Leadbreakage and short circuits in the sensorare indicated by a red LED and throughthe collective error output via Power Rail.The start-up override feature sets relayoutputs to default conditions programmedby the user, for up to 1,000 seconds.

24 VDC supply

Operating range 0.06-300,000RPM (0.001-5,000 Hz)

Relay outputs

Push-button programmable

Collective error messaging

LCD display

Lead breakage (LB) and shortcircuit (SC) monitoring

17

1618

111012

13

14

23

24

Output 1

Output 2

Start Up Override

Supply 24 VDC

KFD2-DWB-Ex1.D

Collective Error Messaging

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2 W

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2 A

Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms/ ≈20 ms

Entity ParametersFM control drawing no. 116-0200

Transfer CharacteristicsFrequency range 0.001-5,000 Hz

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 4: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

119

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Logic ControlsRotational SpeedLimit Alarm

The KFA5-DWB-Ex1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.

120 VAC supply

Operating range 0.06-300,000RPM (0.001-5,000 Hz)

Relay outputs

Push-button programmable

Start-up override

LCD display

Lead breakage (LB) and shortcircuit (SC) monitoring

KFA5-DWB-Ex1.D

17

1618

111012

13

14

23

24

Output 1

Output 2

Start Up Override

Supply 120 VAC

KFA5-DWB-Ex1.D

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24Nominal voltage 120 VACPower consumption 2 VA

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Relay output 2 (SPDT) Terminals 16, 17, 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A

Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms

Entity ParametersFM control drawing no. 116-0200

Transfer CharacteristicsFrequency range 0.001-5,000 Hz

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 5: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

120

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Logic ControlsRotational SpeedLimit Alarm

The KFA6-DWB-Ex1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.

KFA6-DWB-Ex1.D

240 VAC supply

Operating range 0.06-300,000RPM (0.001-5,000 kHz)

Relay outputs

Push-button programmable

Start-up override

LCD display

Lead breakage (LB) and shortcircuit (SC) monitoring

17

1618

111012

13

14

23

24

Output 1

Output 2

Start Up Override

Supply 240 VAC

KFA6-DWB-Ex1.D

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24Nominal voltage 240 VACPower consumption 2 VA

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A

Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms

Transfer CharacteristicsFrequency range 0.001-5,000 Hz

Entity ParametersFM control drawing number 116-0200

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 6: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

121

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Digital to AnalogConverter

The KFU8-FSSP-1.D converts a digitalinput signal into an analog output signalfor connection to standard current orvoltage input devices. A scaleable digitalpulse output is provided to isolate andtransfer the digital signal. The inputfrequency range is easily programmed withthe push buttons on the front panel.Alternatively, the unit can be programmedto record the input frequency range. Thesame unit can be powered from 24 VDC,120 VAC or 240 VAC.

KFU8-FSSP-1.D

24 VDC, 120 or 240 VAC supply

Operating range 0.06-599,940RPM (0.001-9,999 kHz)

Analog current and voltage output

Push-button programmable

LED display

KFU8-FSSP-1.D

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power SupplyNominal voltage 240 VAC, < 5 VA, terminals 16, 18

120 VAC, < 5 VA, terminals 17, 1824 VDC, < 5 W, terminals 11, 12

Inputs (not intrinsically safe)Nominal data NAMUR, 2-, 3- or 4- wire DCInput pulse length / interval ≥ 40 µs / ≥ 40 µs

Output (not intrinsically safe)Nominal voltage term. 5, 6: 0-10/2-10 VDC, resolution 10 mVNominal current term. 4, 5: 0-20 / 4-20 mA, resolution 20 µA,Measurement accuracy ≤ 0.2 % of the final valueTemperature drift ≤ 0.005 % / ºC of the final value

MechanicalHousing Type B4 (see page 387)Dimensions (mm) 107 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Page 7: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

122

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

24 VDC supply

Operating range 0.06-300,000RPM (0.001-5,000 kHz)

Analog and digital outputs

PC programmable

Lead breakage (LB) and shortcircuit (SC) monitoring

10

171618192087

1314

Output 1

Output 2

Output 3

Output 4 0/4-20 mA

Start Up Override

KFD2-UFC-Ex1

Programming JackGND

TxDRxD

Collective Error Messaging

12

11

2324

Supply 24 VDC

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Universal FrequencyConverter

This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programmedto actuate at desired frequencies. The unitis programmable with a PC and thePACTware configuration software. Adebounce filter eliminates extraneoussignals from relay bounce.

Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.

KFD2-UFC-Ex1

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2.2 W

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)

Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mA

Load ≤ 650 Ω

Entity ParametersFM control drawing no. 116-0200

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 8: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

123

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Universal FrequencyConverter withDisplay

This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programedto actuate at desired frequencies. Theunits is programmable with a PC andthe PACTware configuration software. Adebounce circuit eliminates extraneoussignals from relay bounce.

Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.

KFD2-UFC-Ex1.D

24 VDC supply

Operating range 0.06-300,000RPM (0.001-5,000 kHz)

Analog and digital outputs

Push-button and PCprogrammable

LCD display

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2.2 W

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈20 ms

Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)

Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω

Entity parametersFM control drawing no. 116-0200

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

10

171618192087

1314

Output 1

Output 2

Output 3

Output 4 0/4-20 mA

Start Up Override

KFD2-UFC-Ex1.D

Programming JackGND

TxDRxD

Collective Error Messaging

12

11

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

2324

Supply 24 VDC

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 9: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

124

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Universal FrequencyConverter

This universal frequency converterconverts a digital input signal into ananalog output signal for connection tostandard current input devices. A passivetransistor output isolates and transfers thedigital signal. Two relay outputs can beprogrammed to actuate at desiredfrequencies. The unit is programmable witha PC and the PACTware configurationsoftware. A debounce circuit eliminatesextraneous signals from relay bounce. Thesame unit can be powered from 24 VDC,120 VAC or 240 VAC.

Lead breakage and short circuits in thesensor are indicated by a red LED.

KFU8-UFC-Ex1

Can supply 24 VDC, 120 or240 VAC

Operating range 0.06-300,000RPM (0.001-5,000 kHz)

Analog and digital outputs

PC programmable

Lead breakage (LB) and shortcircuit (SC) monitoring

10

171618192087

1314

Output 1

Output 2

Output 3

Output 4 0/4-20 mA

Start Up Override

KFU8-UFC-Ex1

Programming JackGND

TxDRxD

12

11

23

24

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Supply 24 VDC 120 VAC 240 VAC

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24Nominal voltage 20-90 VDC; 48-250 VACPower consumption 2.2 W; 3 VA

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC/2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)

Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale ≤3.6 mA, upscale≥22mALoad ≤ 650 Ω

Entity ParametersFM control drawing no. 116-0200

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 10: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

125

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Universal FrequencyConverter withDisplay

KFU8-UFC-Ex1.D

This universal frequency converterconverts a digital input signal into ananalog output signal for connection tostandard current input devices. A passivetransistor output isolates and transfers thedigital signal. Two relay outputs can beprogrammed to actuate at desiredfrequencies. The unit is programmable byusing push buttons on the front panel, orwith a PC and the PACTware configurationsoftware. A debounce circuit eliminatesextraneous signals from relay bounce. Thesame unit can be powered from 24 VDC, 120VAC or 240 VAC.

Lead breakage and short circuits in thesensor are indicated by a red LED.

Can supply 24 VDC, 120 or240 VAC

Operating range 0.06-300,000RPM (0.001-5,000 kHz)

Analog and digital outputs

Push-button and PCprogrammable

LCD display

Lead breakage (LB) and shortcircuit (SC) monitoring

10

171618192087

1314

Output 1

Output 2

Output 3

Output 4 0/4-20 mA

Start Up Override

KFU8-UFC-Ex1.D

Programming JackGND

TxDRxD

12

11

23

24

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Supply 24 VDC 120 VAC 240 VAC

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24Nominal voltage 20-90 VDC ; 48-250 VACPower consumption 2.2 W; 3 VA

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)

Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale ≤ 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω

Entity ParametersFM control drawing no. 116-0200

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 11: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

126

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24 or Power RailNominal voltage 20-30 VDCPower consumption 2.5 W

Input (intrinsically safe) Terminals 1+, 3-; 4+,6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output 3, 4 (passive transistor) Terminals 19+ and 20- and 21+Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output swiched off (leakage ≤ 10 µA)

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

KFD2-UFT-Ex2.D

Direction /SynchronizationMonitor

The KFD2-UFT-Ex2.D can function as a rotationdirection indicator or synchronization monitor.Programming is simple with the PACTwareconfiguration software or with the on-boarddisplay and buttons. PACTware is available atwww.am.pepperl-fuchs.com.

The input and output circuits are galvanicallyisolated allowing connection to intrinsically safefield devices in hazardous areas.

Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.

Dual input

0.001 Hz - 5 kHz input frequency

Two relay outputs

Two isolated electronic outputs

PC or push-buttonprogrammable

Programmable output functions

Lead breakage (LB) and shortcircuit (SC) monitoring

Start-up override

Page 12: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

127

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Class I, Div 1, Group A-G:Class I, Zone 0, II C

KFU8-UFT-Ex2.D

Direction /SynchronizationMonitor

The KFU8-UFT-Ex2.D can function as arotation direction indicator or synchronizationmonitor. Programming is simple with thePACTware configuration software or with theon-board display and buttons. PACTware isavailable at www.am.pepperl-fuchs.com.

The input and output circuits are galvanicallyisolated allowing connection to intrinsicallysafe field devices in hazardous areas.

Lead breakage and short circuits in thesensor are indicated by a red LED.

Dual input

24 VDC, 120 VAC or 240 VACsupply

0.001 Hz - 5 kHz input frequency

Two relay outputs

Two isolated electronic outputs

PC or push-buttonprogrammable

Programmable output functions

Lead breakage (LB) and shortcircuit (SC) monitoring

Start-up override

Supply 24 VDC 120 VAC 240 VAC

KFU8-UFT-Ex2.D

Input 2

Input 1

LB/SCLB/SC LB

R2

R1R1

R2

R1R1

2324

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Power Supply Terminals 23, 24Nominal voltage 20-90 VDC ; 48-253 VACPower consumption 2.5 W; 4 VA

Input (intrinsically safe) Terminals 1+, 3-; 4+,6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output 3, 4 (passive transistor) Terminals 19+ and 20- and 21+Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Page 13: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

128

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Timer With Display

This highly configurable timer is commonlyused in applications requiring an on-delay, off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it is anintrinsic safety barrier so equipment insidehazardous locations can be connected.

Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.

KFD2-DU-Ex1.D

24 VDC supply

Input frequency up to 100 Hz

Relay output and transistoroutput

Push-button programmable

Lead breakage (LB) and shortcircuit (SC) monitoring

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

111012

1314

2324

Output 1

Output 2

Reset

Supply 24 VDC

KFD2-DU-Ex1.D

Collective Error Messaging

19

20

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Power Supply Terminals 23, 24 or Power RailNominal voltage 20-30 VDCPower consumption 1.8 W

Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms.Time delay 0-3600 s

Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected

Transfer CharacteristicsFrequency range 0.001-100 Hz

MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 14: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

129

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Timer With Display

This highly configurable timer is commonlyused in applications requiring an on-delay,off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it isintrinsically safe so equipment insidehazardous locations can be connected.

Lead breakage and short circuits in thesensor are indicated by a red LED.

KFA5-DU-Ex1.D

120 VAC supply

Input frequency up to 100 Hz

Relay output and transistoroutput

Push-button programmable

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 23, 24Nominal voltage 120 VACPower consumption 2 VA

Inputs (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay Output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msTime delay 0-3600 s

Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected

Transfer CharacteristicsFrequency range 0.001-100 Hz

MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

111012

1314

2324

Output 1

Output 2

Reset

Supply 120 VAC

KFA5-DU-Ex1.D

19

20

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 15: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

130

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Timer With Display

This highly configurable timer is commonlyused in applications requiring an on-delay,off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it is anintrinsic safety barrier, so equipment insidehazardous locations can be connected.

Lead breakage and short circuits in thesensor are indicated by a red LED.

KFA6-DU-Ex1.D

240 VAC supply

Input frequency up to 100 Hz

Relay output and transistoroutput

Push-button programmable

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 23, 24Nominal voltage 240 VACPower consumption 2 VA

Input (intrinsically safe) Terminals 1+,3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs

Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 A

Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms.Time delay 0-3600 s

Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected

Transfer CharacteristicsFrequency range 0.001-100 Hz

MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

111012

1314

2324

Output 1

Output 2

Reset

Supply 240 VAC

KFA6-DU-Ex1.D

19

20

1

3

Input 1

LB/SCLB/SC LB

R2

R1R1

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 16: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

131

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

KFD2-CRG-Ex1.D

TransmitterPower Supply

The KFD2-CRG-Ex1.D is suited for a variety ofmeasuring tasks. 2- and 3-wire transmittersas well as active power supplies with 0/4-20mA signals can be connected.

Two relays and an active 0/4-20 mA currentoutput are available.

The current output is freely scalable. The inputhas a lead breakage and short circuitmonitoring function.

The device is operated by means of PCsoftware (PACTware) or via the push-buttonson the front panel.

Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.

24 VDC supply

Analog input 0/4 -20 mA

Analog output 0/4-20 mA

Two relay outputs

Each output individuallyprogrammable as high or lowalarm or error message output

Push-button or PCprogrammable

Lead breakage (LB) and shortcircuit (SC) monitoring

8

7

Output 1

Output 2

Supply 24 VDC

KFD2-CRG-Ex1.D

11

1012

Collective Error Messaging

17

16

18

23

24

0/4-20mA Output

I

(+) 1

3 3 3

2

(+) 1

2

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Power Supply Terminals 23+, 24-Nominal voltage 20-30 VDCPower consumption 2.5 W

Input (intrinsically safe) Terminals 1, 2, ,3Input signal 0/4-20 mAAvailable voltage > 15 V at 20 mAInput resistance 45 Ω

Outputs (not intrinsically safe)Relay output I (SPDT) Terminals 10, 11 and 12Relay output II (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output III Terminals 8+, 7-Current range 0/4-20 mALoad ≤ 650 ΩFault signal downscale I ≤ 3.6mA, upscale I ≥ 21mA

Transfer CharacteristicsMeasuring time ≥ 100 msTemperature current measurement: 0.003% / ºC

current output: 0.005% / ºCcurrent measurement & output:0.006% / ºC

MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Page 17: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

132

Technical Data

Connection Diagram

Model Number

2002 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Timer With Display

KFU8-CRG-Ex1.D

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

8

7

Output 1

Output 2

KFU8-CRG-Ex1.D

11

1012

17

16

18

23

24

0/4-20mA Output

I

(+) 1

3 3 3

2

(+) 1

2

Supply 24 VDC 120 VAC 240 VAC

Class I, Div 1, Group A-G:Class I, Zone 0, II C

The KFD2-CRG-Ex1.D is suited for a varietyof measuring tasks. 2- and 3-wiretransmitters as well as active power supplieswith 0/4-20 mA signals can be connected.

Two relays and an active 0/4-20 mA currentoutput are available.

The current output is freely scalable. Theinput has a lead breakage and short circuitmonitoring function.

The device is operated by means of PCsoftware (PACTware) or via the push-buttonson the front panel.

Lead breakage and short circuits in thesensor are indicated by a red LED.

24 VDC, 120 or 240 VAC supply

Analog input 0/4 -20 mA

Analog output 0/4-20 mA

Two relay outputs

Each output individuallyprogrammable as high or lowalarm or error message output

Push-button or PCprogrammable

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 23+, 24-Nominal voltage 20-90 VDC or 48-253 VACPower consumption 2.2 W / 4 VA

Input (intrinsically safe) Terminals 1, 2, ,3Input signal 0/4-20 mAAvailable voltage > 15 V at 20 mAInput resistance 45 Ω

Outputs (not intrinsically safe)Relay output I (SPDT) Terminals 10, 11 and 12Relay output II (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Output III Terminals 8+, 7-Current range 0/4-20 mALoad ≤ 650 ΩFault signal downscale I ≤ 3.6mA, upscale I ≥ 21mA

Transfer CharacteristicsMeasuring time ≥ 100 msTemperature current measurement: 0.003% / ºC

current output: 0.005% / ºCcurrent measurement & output:0.006% / ºC

MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Page 18: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

133

Technical Data

Connection Diagram

Model Number

2001 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Latching RelaySwitch Isolator

This isolator is a galvanically isolatedintrinsic safety barrier with a latching relayfor level control, pump up/pump down, orother switch/logic applications. The leadbreakage feature of this barrier requires aconnection of a 10 kΩ resistor in parallelwith the contact when using a mechanicalswitch. NAMUR proximity sensors,however, are designed with the LBfunction and make external resistorsunnecessary. If an LB fault occurs, thesignal output relay reverts to the de-energized state. The output de-energizesif the unit loses power. When power isrestored, the output relay returns to thesame state it held before the interruption.

KFA5-SR2-Ex2.W.IR

Dual-channel

120 VAC supply

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 14, 15Nominal voltage 120 VACPower consumption 1.5 W

Inputs (intrinsically safe) Terminals 1+, 3-; 4+, 6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 10 ms / ≥ 10 ms

Output (Not intrinsically safe)Relay Output (2 SPDT) Terminals 7, 8, 9 ; 10, 11, 12Contact load 250 VAC / 4 A / cos ø > 0.7; 40 VDC/4AMechanical life ≥107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Transfer CharacteristicsSwitching frequency ≤ 10 Hz

MechanicalHousing Type C (See page 387)Dimensions (mm) 110 x 20 x 70Weight 150 g (5.3 oz.)

Ambient Temperature -20ºC to +60ºC (0ºF to +140ºF)

KFA5-SR2-Ex2.W.IR

8

7

9

14

Output 1

Output 2

Supply 120 VAC15

11

10

12

Input 2

Input 1

LB/SCLB/SC LB

R2

R1 R1

R2

R1 R1

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 19: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

134

Technical Data

Connection Diagram

Model Number

2001 IS CatalogLogic

Contr

ols

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Input 2

Input 1

LB/SCLB/SC LB

R2

R1 R1

R2

R1 R1

KFA6-SR2-Ex2.W.IR

Supply 240 VAC

Latching RelaySwitch Isolator

This isolator is a galvanically isolated,intrinsic safety barrier with a latching relayfor level control, pump up/pump down, orother switch/logic applications. The leadbreakage feature of this barrier requires aconnection of a 10 kΩ resistor in parallelwith the contact when using a mechanicalswitch. NAMUR proximity sensors;however, are designed with the LBfunction and make external resistorsunnecessary. If an LB fault occurs, thesignal output relay reverts to the de-energizedstate. The output de-energizes if the unitloses power. When power is restored, theoutput relay returns to the same state itheld before the interruption.

KFA6-SR2-Ex2.W.IR

Dual-channel

240 VAC supply

Lead breakage (LB) and shortcircuit (SC) monitoring

Power Supply Terminals 14, 15Nominal voltage 240 VACPower consumption ≤ 1.5 W

Inputs (intrinsically safe) Terminals 1+, 3-; 4+, 6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 10 ms / ≥ 10 ms

Output (Not intrinsically safe)Relay output (2 SPDT) Terminals 7, 8, 9; 10, 11, 12Contact load 250 VAC / 4 A / cos ø ≥ 0.7; 40 VDC 4AMechanical life ≥107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms

Transfer CharacteristicsSwitching frequency ≤ 10 Hz

MechanicalHousing Type C (See page 387)Dimensions (mm) 110 x 20 x 70Weight 150 g (5.3 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Class I, Div 1, Group A-G:Class I, Zone 0, II C

Page 20: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

135

Technical Data

Connection Diagram

Model Number

2001 IS CatalogLogic

Contro

ls

Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

The KFD2-GU-Ex1 accepts a varietyof inputs and provides a relay tripwhenever it reaches a user-programmedset point. This unit is configuredwith a K-ADP1 adapter, PACTwaresoftware and a PC. Terminal K-CJC isavailable for thermocouples when internalcompensation is desired. K-ADP1,PACTware and K-CJC are sold separately.

KFD2-GU-Ex1

24 VDC supply

T/C, RTD, current and voltageinputs

2 programmable trip points

Lead breakage monitoring

8

79

14

31

1

Output 1

Output 2

Supply 24 VDC

KFD2-GU-Ex1

3

Hazardous Area

2

5

4

6

15

11

10122 wire

Input for RTDs 3 wire

wire2 4

312

2

2

5

6

Input for voltage supply

Input for voltage supply

Cold junction compensation on

Input for thermocouples

0V-20 mA 4V-20 mA

0V-10V 2V-10V

Programming JackGND

TxDRxD

Power Supply Terminals 14+ , 15- or Power RailNominal voltage 20-30 VDCPower consumption ≈ 1.5 W

Inputs (intrinsically safe)Thermocouple (terminals 1,2) B,E,J,K,L,N,R,S or TRTD (terminals 1, 2, 3, 4) 2-, 3+, or 4-wide (N;100 or P+100)Voltage (terminals 2-, 6+) 0/2-10VDC wireCurrent (terminals 2-, 5+) 0/4-20mA

Outputs (not intrinsically safe)Relay Output 1 (SPDT) Terminals 7, 8 and 9Relay Output 2 (SPDT) Terminals 10, 11 and 12Contact load 250 VAC / 2 A / cos ø ≥ 0.6

Transfer characteristicsCalibrated accuracy PT100: 0.01% + 0.2ºC (4-wire)

T/C: 0.05% + 1.2ºCVoltage (0-10 V): 0.02% + 500µVCurrent (0-20 mA): 0.02% + 1 µA

Temperature Drift PT100: (0.0015% + 0.01ºC) / ºCT/C: (0.004% + 0.01ºC) / ºCVoltage: 0.007% / ºCCurrent: 0.0055% / ºC

MechanicalHousing Type C (See page 387)Dimensions (mm) 115 x 20 x 118Weight 150 g (5.3 oz.)

Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)

Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com

Class I, Div 1, Group A-G,Zone 0, IIC

I.S. AnalogLimit Alarm LogicControls

Page 21: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

2002 IS Catalog

136 Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com

Page 22: 2002 IS Catalog - Steven Engineeringstevenengineering.com/Tech_Support/PDFs/32ILOGIC.pdf · 2002 IS Catalog Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607

2002 IS Catalog

137Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com