Installation manualFor professional installer
to be kept by user for f u r the r re fe rence
" Manual for installation of 2 zone kit. " Kit is required for the installation of an underfloor heating circuit. " For installation and parametering refer to the installation manual 1485.
78
3
2 Zone Kitcode 074012
For Hybrid Gas Heat Pump
Document n° 1503-3 ~ 18/09/2012
Société Industrielle de ChauffageBP 64 - 59660 MERVILLE - FRANCE
FR EN IT ES PT
EN DE
Content
Description 3Packing . . . . . . . . . . . . . . . . . . . . . . . . 3Application . . . . . . . . . . . . . . . . . . . . . . . 3General data . . . . . . . . . . . . . . . . . . . . . . 3
Instruction for the installer 4Hydraulic schematics . . . . . . . . . . . . . . . . . 4Hydraulic connections . . . . . . . . . . . . . . . . . 5Extension card assembly . . . . . . . . . . . . . . . 6Electric connections . . . . . . . . . . . . . . . . . . 6
Modem . . . . . . . . . . . . . . . . . . . . . 7Parameters . . . . . . . . . . . . . . . . . . . . . . 7
1 single underfloor heating circuit . . . . . . . . 72 heating circuits . . . . . . . . . . . . . . . . 7
Checking and commissioning . . . . . . . . . . . . . 7Heating installation with 1 single underfloor heating circuit . . . . . . . . 7
Speed adjustments of the heating cicuit pump CC1 . . . . . . . . . . . . 8
Spare parts 9
Installation manual "1503 - EN"
2 Zone Kit code 074012
- 2 -
1 Description
1 1 Packing1 package : 2 circuit kit .
On reception and before starting assembly check the received goods and look for possible damage during transport .
1 2 ApplicationManagement of an underfloor heating circuit or of 2 heating circuits requires the installation of this kit
figure 1 - Dimensions in mm
199
647
1800 30
49,3
832794
1229
1729
1828
273179
598
55271,5163
130268
199
Flow (CC1 et CC2)
Return mixing circuit (CC1)
Return direct circuit (CC2)
1 3 General data
Absorbed power 75 WMax operating pressure 3 barSupply voltage 230V - 50HzØ flow / return (male) 26 x 34 mmWeight 5,2 kg
Servomotor: - Range: 90° . - Time to open or close the valve completely : 4 min .
3-way valve: - Nominal: 26x34 mm . - Kv type: 6 .
figure 2 - Pressure and flow volume available ( indoor unit + 2 circuit kit )
1
ext. in
2
4
6 7
4
2
3
ext. in
2
4
6 7
4
2
2
ext. in
2
4
6 7
4
2
4
ext. in
2
4
6 7
4
2
Settings of circulating pump CC1
Mixing circuit (CC1)
0
100
200
300
400
500
600
mbar 1 mbar = 10 mmCE = 100 Pa
m /h3
1
3
4
1 1,5 2 2,50,50
CC mélangéDonnées notices
V4PVV6PVV7PC - extrap.
0
100
200
300
400
500
600
mbar
0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2m3/h
1
23
1mbar = 10 mmCE = 100 Pa
Direct circuit (CC2)
Installation manual "1503 - EN" - 3 -
2 zone kit code 074012
Legend :
CAR - Non-return valve
C -Circulating pump ( DHW and direct circuit CC2 )
CC1 - Mixing circuit (CC1)
Cd Condenser
CEG Circulating pump gas burner chamber
CPr Pressure sensor
EG Gas burner chamber
PC - Underfloor heating circuit
Pg - Degasser
R - Radiators
SA1 - Room sensor mixing circuit CC1 (optional)
SA2 - Room sensor direct circuit CC2 ( optional)
SDp - Flow sensor mixing circuit
SD Flow sensor
SDEG Flow sensor gas chamber exchanger
SR Return sensor
SREG Return sensor gas chamber exchanger
SP - Security thermostat underfloor circuit (not supplied)
SSu - Safety valve
UE Outdoor unit
VD - 3-way valve
VE - Expansion vessel
VM - 3-way valve mixing circuit CC1
2 Instruction for the installer
2 1 Hydraulic schematics
UE
VE
VD
Cd
Pg
Pg
SSu
SD
C
CARCPr
EG
CEG
SREG
SDEG
SR
M
VM SDp
SPCC1
SA1PC
CAR
• Layout 10 : 1 single underfloor heating circuit.
UE
VE
VD
Cd
Pg
Pg
SSu
SD
C
CARCPr
EG
CEG
SREG
SDEG
SR
SA2
M
VM SDp
SPCC1
SA1
RCART
PC
CAR
• Layout 10 : 2 heating circuits
Installation manual "1503 - EN"
2 Zone Kit code 074012
- 4 -
figure 3 - Connections for 1 underfloor circuit
Flow mixing circuit CC1)
Plug moved
Return mixing circuit CC1
figure 4 - Connections for 2 heating circuits
Flow of mixing circuit CC1 and direct circuit
CC2)
Plug removed
Return mixing circuit (CC1)
Return direct circuit (CC2)
10
0
1
2
3
figure 5 - Installing the mixing valve
A
B
2 2 Hydraulic connections
Connections have to be executed according to local regulations .• Assembly of the hydraulic kit - For a 2 circuit layout: Assemble the T on the flow tube - Respect the assembly direction of the valve:
1: flow heat pump.2: flow mixing circuit CC1.3: return mixing circuit CC1 .
A - Set the 3-way valve on 5 B - Assemble the motor on the valve . Refer to the manual supplied with the motor .
" When the motor rotates anti-clockwise the 3-way valve is opened ( i e increase temperature )
- The circulating pump can be fitted directly to 2 using the supplied tubing. Consider the direction of the flow and the orientation . (figure 6) . - For a 2 circuit layout : assemble the non-return valves : on the flow CC2 and on the return CC1 considering the direction of circulation . - For a single underfloor circuit : close the return CC2 with the plug fitted in factory on return CC1 (figure 3) . - assemble the non-return valve on the return CC1 considering the direction of circulation . - Assemble the flow sensor. Position the flow temperature sensor with a halter on the mixing circuit flow tube CC1.
Make sure to have a correct contact between sensor and tube . The contact surface must be clean of paint and rust . The halter must be tightened .
figure 6 - Allowed positions of circulating pump
Installation manual "1503 - EN" - 5 -
2 zone kit code 074012
2 3 Extension card assemblyBefore assembly make sure that the power supply is disconnected . - To access the electric parts take off the front cover . - Fit the PCB AVS 55 with the support on the PCB RVS 21 .
figure 7 - Extension card
Heat Pump Regulation PCB (RVS)
Extension PCB (AVS)
2 .4 Electric connections
Electric installation has to be made with respect to local security norms ( i .e . VDE 0100 or similar ) .The electric connections are made only after completion of all other assembly operations .Connect as follows :• 1 - Circulating pump mixing circuit CC1• 2 - 3-way valve• 3 - Flow sensor .• 4 - Shunt on ‘M’• 5 - Connection RVS/AVS. • 6 - Power supply AVS . Connect the cable harness to
the heat pump supply connector .• 7 - Room sensor or room controller ( optional ) .• 8 - Modem .• 9 - If underfloor heating connect the security cut-
out on the connector of the underfloor circulating pump (X110) .
figure 8 - Electric connections on AVS 55
M
X10
X110
X112
X152
X150
X153
X154
X100
Ou/Or
B2MB1321
BKBNBUBNBUC.C
M
L
N
Power supply AVSShunt
Room sensor or
room controller mixing circuit CC13-way valve
Pump Mixingcircuit CC1
Overheat protection underfloor circuit
Flow sensor mixing circuit CC1
Connection RVS/AVS
Extension card AVS 55
2
6
19 3
7
8
5
4
Colour codes
BK Black BN Brown BU Blue
Modem
M
4
Installation manual "1503 - EN"
2 Zone Kit code 074012
- 6 -
TEL110
6 A
CRT
figure 9 - Modem
2 4 1 ModemYou can initiate the frost protection function of the heat pump through a modem . - Connect the telephone contact on connector X 152 - Setting : menu ‘configuration’, lines 6420 and 6421. Refer to heat pump manual .
The activated telephone contact changes the heat pump to Frost Protection programm .According to the settings all heat demand from heating circuits and DHW are ignored .The heat pump and /or the room controller must not be set to Frost Protection .
" Attention ! The use of modem contact excludes the installation of a pool kit
2 5 Parameters
2 5 1 Single underfloor circuit - Menu ‘configuration’
5710 = On5715 = Off
- Set then the parameters of the circuit CC1 (refer to the heat pump manual : temperature setting, heating curve) .
2 5 2 2 heating circuits - Menu ‘configuration’
5710 = On5715 = Off
- Set then the parameters of the circuits CC1 and CC2 (refer to the heat pump manual : temperature setting, heating curve)
2 6 Checking and commissioningFor checking and commissioning , - Refer to the heat pump manual .
2 6 1 Installation with 1 single underfloor heating circuit.to control combustion ( when changing gas or during maintenance ) you can start-up the gas heat generator without the heat pump (see heat pump manual, § Operation of the gas heat generator) .
" Close manually the 3-way valve of the underfloor circuit
The supplied heat during this setting operation must be evacuated through the DHW circuit: draw-off hot DHW to lower the temperature of the DHW tank ( < 35°C) .• The 3-way valve lever must be in low position (position
DHW . Activate the DHW function if required) (figure 11) .For the further operation s refer to the heat pump manual point 3 of § Operation of the gas heat generator
figure 10 - Non-return valve
figure 11 - 3-way valve in position DHW
Valve disengaged (position for filling or purge)
Valve disengaged (position for filling or
purge)
Valve closed (normal working
position)
Valve closed (normal working position)
• lever in low position ( DHW )
Installation manual "1503 - EN" - 7 -
2 zone kit code 074012
2 7 Speed selection of mixing circuit pump CC1
ext. in
2
4
6 7
4
2
Do not use this zone
ext. in
2
4
6 7
4
2
The circulating pump adjusts the pressure depending on the flow volume .
Recommended for a radiator installation (especially all systems with thermostatic valves or with electric valve) .
ext. in
2
4
6 7
4
2
The circulating pump maintains the pressure whatever the flow volume.
Recommended for an installation with constant pressure drop i .e . underfloor heating .
Blocking of the circulating pump :If the motor is blocked a start-up sequence is triggered .If the motor remains blocked it will be stopped .
" Cut the power supply of the circulating pump during 30 sec to unlock and to allow another start-up sequence
ext. in
2
4
6 7
4
2
ext. in
2
4
6 7
4
2
figure 12 - Setting of the circulating pump
Direction of flow
Installation manual "1503 - EN"
2 Zone Kit code 074012
- 8 -
3 Spare parts
For every spare parts order indicate: model and code, product nae and code of the part .Qty = total quantity in the device .
N° Code Description Type Qty1 109957 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . .012 110869 Connector . . . . . . . . . . . . . . . . . 5 plots . . . . . . .013 150307 Motor . . . . . . . . . . . . . . . . . . . .ARA 671 . . . . . . .014 188174 3-way valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . .015 142735 Seal . . . . . . . . . . . . . . . . . . . . . . .26x34 . . . . . . .076 184094 Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .017 149001 Connector . . . . . . . . . . . . . . . . . .1" MM . . . . . . .028 177545 T part . . . . . . . . . . . . . . . . . . . . . FFF 1" . . . . . . .019 175062 PCB holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0110 165341 Extension card . . . . . . . . . . . . . . . . AVS . . . . . . .0111 133116 Cable harness . . . . . . . . . . . 2ème circuit . . . . . . .0112 198746 Flow sensor . . . . . . . . . . . . QAD36/101 . . . . . . .0113 109517 Sensor harness . . . . . . . . . . . . . . . . . . . . . . . . . .0114 110870 Connector . . . . . . . . . . . . . . . . . 2 plots . . . . . . .0115 110047 Non-return valve . . . . . . . . . . . . . . . . . . . . . . . . .0216 110867 Connector . . . . . . . . . . . . . . . . . 6 plots . . . . . . .0117 110865 Connector . . . . . . . . . . . . . . . . . 2 plots . . . . . . .0118 153018 Harness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0119 199910 Fuse . . . . . . . . . . . . . . . . . 250v - 6 .3A T . . . . . . .01
2
1
3
6
9
14
1911 10
5
55
4
5
5
16
17
18
13
12
15
15
5
5
77
8
figure 13 - Spare parts 2 circuit kit
Installation manual "1503 - EN" - 9 -
2 zone kit code 074012
Installation manual "1503 - EN"
2 Zone Kit code 074012
- 10 -
Installation manual "1503 - EN" - 11 -
2 zone kit code 074012
Date of installation :
Contact of your heating technician or your after-sales service.
Complies with: - Low voltage directive 2006/95/EC, under standard EN 60335-1. - Electromagnetic compatibility Diretive 2004/108/EC.
Cet appareil est identifié par ce symbole. Il signifie que tous les produits électriques et électroniques doivent être impérativement séparés des déchets ménagers. Un circuit spécifique de récupération pour ce type de produits est mis en place dans les pays de l’Union Européenne (*), en Norvège, Islande et au Liechtenstein. N’essayez pas de démonter ce produit vous-même. Cela peut avoir des effets nocifs sur votre santé et sur l’environnement. Le retraitement du liquide réfrigérant, de l’huile et des autres pièces doit être réalisé par un installateur qualifié conformément aux législations locales et nationales en vigueur. Pour son recyclage, cet appareil doit être pris en charge par un service spécialisé et ne doit être en aucun cas jeté avec les ordures ménagères, avec les encombrants ou dans une décharge. Veuillez contacter votre installateur ou le représentant local pour plus d’informations.
* En fonction des règlements nationaux de chaque état membre.
Mat
eria
l sub
ject
to c
hang
es w
ithou
t not
ice
- Non
con
tract
ual d
ocum
ent.
atlantic-comfort.com
Société Industrielle de ChauffageSATC - BP 64 - 59660 MERVILLE - FRANCE
RC
Dun
kerq
ue -
Sire
n 44
0 55
5 88
6