2. considerations in choosing directional...

43
Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Technical Report to the Line Protection Subcommittee of the PES, Power Systems Relaying Committee Presented by Working Group D-3 Line Protection Subcommittee

Upload: others

Post on 11-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in

Line Protection Applications

Technical Report to the Line Protection Subcommittee of the PES, Power Systems

Relaying Committee

Presented by Working Group D-3 Line Protection Subcommittee

Page 2: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in

Line Protection Applications

Working Group D-3 Members:

John Appleyard, Jeffrey Barsch, Gabriel Benmouyal, Art Buanno, Randy Crellin, Randy Cunico, Normann Fischer, Michael Fleck, Robert Frye, Charles Henville, Meyer Kao (Chair), Shoukat Khan, Gary Kobet, Alex Lee, Don Lukach, Walter McCannon, Joe Mooney, Jim O’brien, Cristian Paduraru, Suhag Patel, Russell

Patterson, Frank Plumptre, Elmo Price (Vice-chair), Ryland Revelle, Sinan Saygin, Mark Schroeder, Steve Turner

Page 3: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

What is Polarization

The process of comparing a reference phasor, voltage or current, to line current phasor to determine the direction to a fault

The reference phasor is generally referred to as the polarizing quantity

Basis for design of directional elements

Page 4: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Why Use It for Ground Overcurrent Application

In a network transmission system, ground overcurrent elements can be very difficult to coordinate

Ground directional elements are used to supervise ground overcurrent elements so that they only operate for faults in a desired direction

Page 5: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Sequence Network for Ground Faults

AV V

VV

Page 6: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Sequence Network for Ground Faults, Cont.

ZG0 ZTH0

Zero

ZL0 ZH0

X A-G

G H

RELAY

I0

LINE

IP

V2, V0

I1, I2, I0

IP

V0

*

*Tertiary not loaded

ZTM0

ZTL0

Page 7: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Polarizing Methods for Ground Directional Elements

Zero sequence voltage Negative sequence voltage Zero sequence current Dual Polarizing, combination of zero sequence

voltage and zero sequence current Negative sequence and zero sequence

impedance Virtual polarizing Voltage compensation

Page 8: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

System Vectors, Balanced and During a Single Line to Ground (SLG) Fault

Page 9: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Zero and Negative Sequence Voltage Polarizing Source

Sequence voltages are obtained from the three phase to neutral voltages, or

-3V0 obtained from broken delta connection

Page 10: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Zero and Negative Sequence Voltage Directional Operating Characteristics

Page 11: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Zero Sequence Current (Current Polarizing) Polarizing Source

P+

+ P

+P

(a) Υ − ∆ (b) Υ – ∆ − Υ

(c) Zig-zag

+

(d) Auto – with ∆ tertiary

P

RMRH

RM

RN

+ PVirtually always OK

OK at times

Page 12: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Zero Sequence Current (Current Polarizing) Directional Operating Characteristics

Transformer Zero Sequence Current Polarized Directional Ground Fault Function

Forward Operating

Region

Reverse Operating

Region

Operating Sensitivity Minimum Levels

3I0 (Operating)

Ipol (Polarizing)

Non-operating Region

Page 13: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Dual Polarizing, Combination of Zero Seq. Voltage and Zero Seq. Current

Page 14: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Dual Polarizing, Multiple Directional Element Designs

Electromechanical Designs Separate voltage polarized and current polarized

units with their forward (closing torque) operating contacts arranged in parallel so that either unit may indicate forward ground fault direction

A single directional unit that has both polarizing elements acting simultaneously on the same unit, so that a single contact that operates on the sum of the torque is developed by the two methods

Page 15: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Dual Polarizing, Multiple Directional Element Designs, Cont.

Numerical Relay Designs Paralleling (OR gate) of the appropriate outputs of the

two methods, however, the voltage polarizing unit is blocked if polarizing current is available. The voltage unit will only operate if polarizing current is not available.

Page 16: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Dual Polarizing, Multiple Directional Element Designs, Cont.

Numerical Relay Designs, Cont. Dual polarization by summing the polarizing voltage

phasor, –3V0, and the polarizing current phasor rotated by the angle α, the arg(V0/I0) for a strong forward fault.

Page 17: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Other Methods

Negative and zero sequence impedance Negative sequence Impedance:

𝑍𝑍2 =𝑅𝑅𝑅𝑅 𝑉𝑉2 � ∠𝜃𝜃2 � 𝐼𝐼2 ∗

𝐼𝐼2 2

Zero sequence Impedance:

𝑍𝑍0 =𝑅𝑅𝑅𝑅 𝑉𝑉0 � ∠𝜃𝜃0 � 𝐼𝐼0 ∗

𝐼𝐼0 2

Page 18: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Other Methods, Cont.

Virtual polarization Based on phase selector has identified the faulted

phase

Phase Selector Pickup Virtual Residual, VN polarizing A Phase Fault VB + VC

B Phase Fault VA + VC

C Phase Fault VA + VB

No selection VA + VB + VC

Page 19: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Other Methods, Cont.

Voltage Compensation Either negative or zero sequence voltage compensation Long line and resistive fault applications; low operating

current and strong source with low source impedance Vpol = -V0A+ I0R* K*e jRCA ; care when choosing K so

that the direction is not forward for a reverse fault

Z0LZ0A

REL A

Z0B

V0A = - I0AZ0A

REL B

I0BI0R = I0A

I0A

V0K = - I0A(Z0A+K)

K

Page 20: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Application Consideration of Different Methods

Zero sequence mutually coupled lines Line and source impedance consideration Mismatch of polarization methods on line

terminals in communication assisted trip scheme Other considerations

Page 21: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Zero Sequence Mutually Coupled Lines: Application Example (Zero Seq. Voltage and Zero Seq. Current Polarized)

500kVStation 1 Station 2

R R

161kV

Station 3

57mi

27mi Z0=0.25pu

Z0=0.044pu

Z0M=0.04pu

40%

85%Other linesOther

lines

Page 22: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Fault on 500kV Bus at Station 1 (Neglect Mutual Coupling)

500kVStation 1 Station 2

R R

161kV

Station 3

57mi

27mi Z0=0.25pu

Z0=0.044pu

X3I0=2510A

3I0=480A

Other linesOther

lines

100AWithout mutual coupling

-3Vo

Forward fault

3Io-3Vo

3Io

Reverse fault

Page 23: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Fault on 500kV Bus at Station 1, Partial Zero Seq. Network (Neglect Mutual Coupling)

Station 3

69kV

Station 1500kV

MidPt MidPt

To positive sequence network

To n

egat

ive

sequ

ence

ne

twor

k

Station 2R

R

V0

Z0LX

2510A

480A

100A

Page 24: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Fault on 500kV Bus at Station 1(With Mutual Coupling)At Station 3, forward direction asserted for both zero sequence voltage and current polarizing elements

500kVStation 1 Station 2

R R

161kV

Station 3

57mi

27mi Z0=0.25pu

Z0=0.044pu

Z0M=0.04pu

40%

85%

X3I0=2740A

3I0=470A

Other linesOther

lines

70AWith mutual coupling

-3Vo

3IoForward fault-3Vo

3Io

Forward fault

Page 25: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Fault on 500kV Bus at Station 1, Partial Zero Seq. Network (With Mutual Coupling)

Station 3

69kV

Station 1500kV

MidPt MidPt

To positive sequence network

To n

egat

ive

sequ

ence

ne

twor

k

Station 2R

R

V0

Z0LXZ0M

1:1

2740A

470A

70A

Page 26: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

Page 27: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Simplified Sequence Network at the Fault Location

Z1S Z1L

Z2S Z2L

Z0S Z0L

VA1

VA2

VA0

Phase-to-ground

VA1

VA2

VA0

Phase-to-phase-to-ground

Z1 = Z1S+Z1L

Z2 = Z2S+Z2L ≅ Z1

Z0 = Z0S+Z0L

Page 28: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Magnitude of Sequence Voltages Vary with Fault Type and the Z0/Z1 Ratio, As Viewed from the Fault Point

𝑉𝑉𝐴𝐴0 =⁄𝑍𝑍0 𝑍𝑍1

⁄𝑍𝑍0 𝑍𝑍1 + 2

Single Line-to-Ground (SLG)

𝑉𝑉𝐴𝐴2 =1

⁄𝑍𝑍0 𝑍𝑍1 + 2

𝑉𝑉𝐴𝐴0 = 𝑉𝑉𝐴𝐴2 =⁄𝑍𝑍0 𝑍𝑍1⁄2𝑍𝑍0 𝑍𝑍1 + 1

Line-to-Line-to-Ground (LLG)

Page 29: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

Observations: If the system is homogeneous, that is if the

ratios of source to line impedances are similar in the zero and negative sequence networks then the ratios of voltages at the relay will be the same as at the fault. Because line zero sequence impedance is roughly three times that of positive/negative sequence impedance, zero sequence voltage polarizing is superior.

Page 30: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

Observations (Cont.): Where the system is not homogeneous, the

relative zero and negative sequence voltages at the relay can be easily estimated for ground fault at any point on the line

𝑉𝑉𝐴𝐴0𝑅𝑅𝑉𝑉𝐴𝐴𝐴𝑅𝑅

= 𝑍𝑍0𝑍𝑍𝐴� 1+ ⁄𝑛𝑛�𝑍𝑍1𝐿𝐿 𝑍𝑍1𝑆𝑆

1+ ⁄𝑛𝑛�𝑍𝑍0𝐿𝐿 𝑍𝑍0𝑆𝑆SLG

𝑉𝑉𝐴𝐴0𝑅𝑅𝑉𝑉𝐴𝐴𝐴𝑅𝑅

= 1+ ⁄𝑛𝑛�𝑍𝑍1𝐿𝐿 𝑍𝑍1𝑆𝑆1+ ⁄𝑛𝑛�𝑍𝑍0𝐿𝐿 𝑍𝑍0𝑆𝑆

LLG

Page 31: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

Observations (Cont.): The magnitude of the negative- or zero-

sequence voltages are directly proportional to the current and the source impedance behind the relay location. Therefore, it can be seen that given a long line with a strong source behind the relay (Z2L >> Z2S or Z0L >> Z0S) the negative or zero-sequence voltage at the relay location can be relatively small.

Page 32: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

Observations (Cont.): To evaluate the choice of the sequence

voltages at the relay, the magnitude of zero and negative sequence voltages at the relay can be estimated for ground fault at end of the line

𝑉𝑉𝐴𝐴2𝐴𝐴 = 1⁄𝑍𝑍0 𝑍𝑍1+2

� 1⁄𝑍𝑍𝐴𝐿𝐿 𝑍𝑍𝐴𝑆𝑆+1

per unit

𝑉𝑉𝐴𝐴0𝐴𝐴 = ⁄𝑍𝑍0 𝑍𝑍1⁄𝑍𝑍0 𝑍𝑍1+2

� 1⁄𝑍𝑍0𝐿𝐿 𝑍𝑍0𝑆𝑆+1

per unit

Page 33: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Inadequate Negative Sequence Voltage Example

161kVStation 1 Station 2

R

96mi Z+=0.3pu

Z0=0.74pu

ZS+=0.01pu

ZS0=0.02pu

XPhase-to-ground line-end fault3I0=760A

V2=590VI2=250A

240/1

1400/1 Breaker trips by ground instantaneous

NOTE: All quantities at Station 1 are after the breaker at Station 2 has tripped

Page 34: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Sources of Error in calculating V2 and V0 –Untransposed Lines

Normally Expected Phase and Sequence Fault Voltages, A Phase SLG

VA

VBVC

VA VA

VC

VB

a2Vb

aVC

3V0 3V2

Compute 3V2Compute 3V0

Page 35: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Sources of Error in calculating V2 and V0 –Untransposed Lines, Cont.

Phase and Sequence Fault Voltages Showing Reversal of 3V0, A Phase SLG

VA VA VA

VC

VC

VB

VB

a2Vb

aVC

3V0

3V2

Compute 3V2Compute 3V0

Page 36: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Sources of Error in calculating V2 and V0 –Untransposed Lines, Cont.

Phase and Sequence Fault Voltages Showing Reversal of 3V2, A Phase SLG

VA VA VA

VCVC

VB

VB

a2Vb

aVC

3V0

3V2

Compute 3V2Compute 3V0

Page 37: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Mismatch of polarization methods on line terminals in communication assisted trip scheme

Bus F, relay system K: Zero sequence voltage and current polarized

Bus H, relay system M: Negative sequence voltage polarized

Page 38: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont.

Page 39: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont.

Sequence Currents (IFH2 and IFH0) in Per Unit of If on Line FH for Different Fault Locations on Line FG m Distance from Bus F

Page 40: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont.

The negative and zero sequence currents will flow in opposite directions on line FH for faults between 0.45 and 0.835 p.u. of line FG length as measured from Bus F

m 0 .1 0.2 0.3 0.4 0.45 0.5 0.6 0.7 0.8 0.835 0.9 1.0

IFH2 -.196 -.173 -.149 -.125 -.102 - -.078 -.055 -.031 -.007 0 .016 .039

IFH0 -.078 -.061 -.043 -.026 -.009 0 .009 .026 .043 .061 - .078 .096

Page 41: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Other Considerations

Single pole open affecting an adjacent line Series compensated lines or lines near series

compensated lines and static var compensator Inherently directional; strong source impedance

behind and weak forward source impedance Current polarizing at stations with more than one

transformer and split low-sides Modeling of ground directional element in

software

Page 42: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Recommendation on Choosing Appropriate Method

* - OK, but study recommendedNR - Not recommendedSR - Study required** - special compensation may be required or inherent directionality may

make directional control unnecessary

Configuration: Significant Zero Sequence Mutual Coupling

Negative Sequence Voltage

Zero Sequence (Voltage, Current, or Dual)

Short and medium length lines (SIR > 0.5)

No OK* OK*

Yes OK* NR

Long lines** (SIR ≤ 0.5)

No SR OK*

Yes SR NR

DCB or POTT Relay at the remote terminal with zero sequence polarizing

No NR OK*

Yes NR SR

Page 43: 2. Considerations in Choosing Directional …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2...Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent

Summary:

Choice of polarizing method for directional ground elements is an important decision that should not be overlooked or reduced to a “cookie-cutter” approach.

Each application should be carefully evaluated for adequacy.

Manufacturer recommendations and/or traditional utility practices should never be used in lieu of thorough study of the particular relay in question on the protected line.