1_per unit
TRANSCRIPT
-
8/13/2019 1_Per Unit
1/28
-
8/13/2019 1_Per Unit
2/28
Course OverviewCourse OverviewSynopsis:
The subject deals with topics related to the-
system, power flow analysis, analysis of balanced
and unbalanced faults, power system stability and, ,protection, differential protection and application,distance protection and application. Overall, this
the protection schemes for power systemnetwork.
2
-
8/13/2019 1_Per Unit
3/28
Course Outcome
should be able to:
and unbalanced faults techniques. (PLO4-
CTPS-C4)2. Demonstrate power flow analysis using related
software. (PLO3-CS-P4)
. on power system requirement. (PLO11-SD-A3)
3
-
8/13/2019 1_Per Unit
4/28
Lecture Plan
WEEKS CONTENTS
1 Per-Unit System
2 Power Flow Analysis
3 Analysis of Balanced Fault
4 Analysis of Unbalanced Fault
6 Application of Power System Stability
7 Load Frequency and Automatic Generation Controls
8 Reactive Power and Voltage Controls
9 Non-Directional Overcurrent and Earth Fault Protection
4
-
8/13/2019 1_Per Unit
5/28
ec ure an
WEEK CONTENTS
10 Directional Overcurrent and Earth Fault Relay
11 Differential Protection Scheme
12 Differential Protection Application
13 Distance Protection Scheme
14 Distance Protection Application
Syllabusdetails
5
-
8/13/2019 1_Per Unit
6/28
-
8/13/2019 1_Per Unit
7/28
CHAPTER CONTENTS
1 Per-Unit System (3 Hours)
Introduction
Vectors
Operators
Convention Used for Voltage Direction ase uan es an er- n ys em
Transferring Per-Unit Quantities from One Set
of Base Values
7
-
8/13/2019 1_Per Unit
8/28
Representation of Electric Power System
One-Line Diagram (OLD)
Definition:A diagram showing the interconnection of
-
power system by standard symbols on a single
phase basis.
Y
B
=
8
- -
-
8/13/2019 1_Per Unit
9/28
Advantages of OLD
Simplicity
1- represents all 3-s of the balanced system
by their standard symbols
The completion of the circuit through the neutral is
omitted
9
-
8/13/2019 1_Per Unit
10/28
Symbols for One-Line Diagram
2-winding power transformerOr
3-winding power transformerOr
LoadOr
(oil/liquid) (OCB)
Air CB (ACB)
10
skip next page
-
8/13/2019 1_Per Unit
11/28
Busbar 3-phase, 3-wire
Transmission line
3-phase wye,
Fuse
3-phase wye,
A
Current
transformer
(CT)
Vor Potential
transformer
PT or VT
Voltmeter
11
-
8/13/2019 1_Per Unit
12/28
Impedance (Z) and Reactance (X) Diagram
Impedance (Z = R + jX) diagram is converted fromOLD showing the equivalent circuit of eachcomponen o e sys em. s nee e o ca cu a e e
performance of a system under normal and abnormalconditions i.e. load conditions (Load Flow (LF) studies)or upon e occurrence o a au s or c rcu auanalysis studies).
Reactance (jX) diagram is further simplified from Zdiagram by omitting all static loads, all Rs, themagnetizing I (Im) of each transformer, and thecapacitance (C) of the transmission line. It is applied
only to fault calculations, and not to LF studies.Z and X diagrams sometimes called the Positive-
se uence dia ram.
12
-
8/13/2019 1_Per Unit
13/28
Z and X Diagrams
Example: OLD of an EPS
T2T1
Load A
WITH WISDOM WE EXPLORE 13
-
8/13/2019 1_Per Unit
14/28
Z dia ram corres ondin to the OLD
E1 E2 E3
Gen.3
LoadB
TransformerT2
TransmissionLine
TransformerT1
LoadA
Generators1 and 2
14
-
8/13/2019 1_Per Unit
15/28
X diagram corresponding to the OLD
E1 E2 E1
Generators
1 and 2
Transmission
LineTransformer
T2
Gen.
3Transformer
T1
15
-
8/13/2019 1_Per Unit
16/28
Per - unit (P.U) Representation
Common quantities used in power system analysis (PSA) are
voltage (V) (in kV), current (I) (in kA), voltamperes (in kVA or
MVA), and impedance (in ). It is very cumbersome to convert
s o eren vo age eve s n a av ng wo or more
levels. P.U. representation is introduced in such a way that the various
p ys ca quan es are expresse as a ec ma rac on or
multiples of base quantities and is defined as:
actual quantityQuantity in per-unit
base value quantity
Example:
For instance, if a base voltage of 275 kV is chosen, actual
16
. , , . . ,
1.00, and 1.05 per-unit.
-
8/13/2019 1_Per Unit
17/28
For 1- systems: The formula relates the various quantities
for 1- system:
(1- )
( )
base kVA (in kVA)Base I (in A)
base V (in kV)LN
LN
1
kVvoltage,base
kVAbaseAcurrent,Base
( )
2
base V (in V)
Base Z (in ohms) base I (in A)
(base V ) (in kV)
LN
LN
LN
Acurrent,base
,impedanceBase
2
LN )kVvoltage,(base
(1- )
(1- ) (1- )
ase n o msbase MVA (in MVA)
Base power (in kW) base kVA (
in kVA)
1MVAbase
Base P, MW1= Base MVA1(3- ) (1- ) ase , = ase
2.)(
base
base
base
upVVAZ
ZactuaZZ
-
8/13/2019 1_Per Unit
18/28
or - sys ems:The formula relates the various quantities for 3- system:
(3- )base kVABase I (in A)
3 X base V (in kV)LL
LL
3
kVvoltage,baseX3
kVAbaseAcurrent,Base
2
( )
(3- )
(base V ) (in kV)Base Z (in ohms)
base MVA
LL
3
2
LL
MVAbase
)kVvoltage,(baseimpedanceBase
(3- ) (3- )
(3- ) (3- )
Base power (in MW) base MVA
33
33
MVAbaseMWpower,Base
kVAbasekWpower,Base
)( baseVAZactualZ
Z
18
.
basebase VZ
-
8/13/2019 1_Per Unit
19/28
Example:
The base impedance and base voltage for a given
power system are 10 and 400V, respectively.
Solution:
400
rom ms aw,
Base current =10
X40040=
19
1000
19
-
8/13/2019 1_Per Unit
20/28
-
8/13/2019 1_Per Unit
21/28
Example:
A 3-, Y-connected system is rated at 100 MVA and 132 kV.
Express 80 MVA of 3- apparent power (S) as a p.u. value
referred to:
(a) the 3- system MVA as base and
(b) the 1- system MVA as base.
(a) For the3- base,
Base MVA = 100 MVA = 1 p.u.
and Base kV = 132 kV = 1 p.u.
so p.u. MVA = 80/100 = 0.8 p.u.
(b) For the1- base,
Base MVA = 100/3 MVA = 33.33 MVA = 1 p.u.
21
. . .
so p.u. MVA = (1/3)*(80/33.333) = 0.8 p.u.
-
8/13/2019 1_Per Unit
22/28
Changing the Base of P.U. Quantities
The Z of individualgeneratorsandtransformersare
generally in terms of%orp.u.quantities based on
.
For PSA, all Zs must be expressed in p.u. on acommon system base. Thus, it is necessary to
convert the p.u. Zs from one base to another
(common base, for example: 100 MVA).
P.U. Z of a circuit
element2
(actual Z in ) * (base MVA)
(base V) in kV
The equation shows that p.u. Z is directly proportional
to the base MVA and inversely proportional to the
22
square of the base V.
-
8/13/2019 1_Per Unit
23/28
Therefore to chan e from old base .u. Z to newbase p.u. Z, the following equation applies:
old newnew old
new old
base kV base MVAP.U. Z P.U. Z base kV base MVA
Example 1:
The reactance X of a generator is given as0.20 p.u. based on the generators nameplate
rating of 13.2 kV, 30 MVA. The base for
new base.
2
23
.x" 0.20 0.306 p.u.
13.8 30
-
8/13/2019 1_Per Unit
24/28
-
8/13/2019 1_Per Unit
25/28
Analysis of PS problems are greatly simplified by
using single-line Z diagram in which systemparameters are expressed in p.u. The steps to
. .
Step 1: Select a common volt-ampere base for
the entire power system and a voltage base for one.
Step 2:Compute voltage bases for all partsof thePS by correlating the transformation ratios of the
transformer banks.
25
-
8/13/2019 1_Per Unit
26/28
nameplate of the equipment) to the common systemvolt-ampere base and the applicable voltage base. In
values, compute base Z for the part of the PS in whichthe equipment is connected and calculate the p.u..
Step 4:Draw a single-line diagramof the PS indicating. .
PS.
.
26
-
8/13/2019 1_Per Unit
27/28
Example 4:
Draw the reactance diagram of system shown
below. Assume reactance for the transmission line is
the generator circuit
6.6/66 kV
27
-
8/13/2019 1_Per Unit
28/28
A 30 MVA 13.8 kV 3-generator has a sub-transient
reactance (Xd) of 15%. The generator supplies two
.
ends, as shown in OLD below. The motors have rated
inputs of 20 MVA and 10 MVA, both 12.5 kV with x =
20%. The 3-transformer T1 is rated 35 MVA 13.2/116
(/Y) kV with leakage reactance (Xl) of 10%. 3-
transformer T2 is rated at 10 MVA, 116/12.5 (Y/) kV
with Xl of 10%. Series X of the tr. line is 80 . Draw theX diagram with all Xs marked in p.u. Select the
generator rating as base in the generator circuit.
28