- 1 -
1.1 List of 10CHA01 generator protection function:
Code /ModelANSI
Codesetting value function
Setting value
AddressRemarks
F10
7UT6355-6EB92-1AA0-LOD
87G-TGenerator-Transformer
differential protection1201~1263
F11
7UM6225-6EB92-0CA0-LOD
87G Generator differential protection 2001~2063A
21 Impedance protection 3301~3317A
59 Overvoltage protection 4101~4107A
59N interturn protection 5501~5504
27 undervoltage protection 4001~4006A
81 Frequency protection 4201~4215
46 Neg.Seq O/C protection 1701~1707
49 Overload protection 1601~1616A
40 Loss-of-Field protection 3001~3014A
32F Low Forward-power protection 3201~3206A
32R2 Reverse Power protection 3101~3105A
24 Overexcitation protection 4301~4314
78 Out-of-Step protection 3501~3512
50/27 Inadvertent energizing Protection 7101~7105
60 VT1 fuse failure 8001
F12
7UM6115-5EB92-0AA0-LOD
32R1 Reverse Power protection 3101~3105A
64G1 90% Stator earth fault protection 5001~5005
60 VT2 fuse failure 8001