Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 COVER
TECHNICAL SPECIFICATION NO. E0021 FOR 198KV LIGHTNING ARRESTERS
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 INDEX
SPECIFICATION FOR 198 KV LIGHTNING ARRESTERS C O N T E N T S SECTION D E S C R I P T I O N PAGE NO. 1.00.00 INTENT OF SPECIFICATION E0021:1 2.00.00 SCOPE OF WORK E0021:1 3.00.00 GENERAL REQUIREMENTS E0021:1 4.00.00 DESIGN CRITERIA E0021:2 5.00.00 SPECIFIC REQUIREMENTS E0021:3 6.00.00 T E S T S E0021:4 7.00.00 DRAWINGS, DATA & MANUALS E0021:5 ATTACHMENTS ANNEXURE-A RATINGS AND REQUIREMENTS E0021:7 ANNEXURE-B FITTINGS AND ACCESSORIES E0021:10 ANNEXURE-C MANDATORY SPARES E0021:11
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 1 of 11
SPECIFICATION FOR 198 KV LIGHTNING ARRESTERS 1.00.00 INTENT OF SPECIFICATION 1.01.00 This Specification is intended to cover the design, manufacture, assembly,
testing at manufacturer's works, supply & delivery, properly packed for transport F.O.R. site of 198 KV LIGHTNING ARRESTERS complete with all materials and accessories for efficient and trouble-free operation.
1.02.00 In the event of any discrepancy with listed documents, the stipulation of this
specification shall govern. 1.03.00 This specification shall be read and construed in conjunction with other sections
of the bidding document. 2.00.00 SCOPE OF WORK 2.01.00 Scope of Supply Type and rating of the equipment listed below are further detailed in the
annexures. The ratings indicated are minimum values. Bidder shall check the same with respect to insulation coordination.
2.01.01 Each lighting arrester shall be furnished complete with accessories as listed in
the annexure. 2.01.02 All relevant drawings, data and manuals sufficient to operate, maintain & repair
main equipment and auxiliary system. 2.01.03 Commissioning spares and recommended spare parts for three (3) years
operation. 3.00.00 GENERAL REQUIREMENTS 3.01.00 Codes and Standards 3.01.01 All equipment and materials shall be designed, manufactured and tested in
accordance with the latest applicable IEC/IS except where modified and/or supplemented by this specification.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 2 of 11
3.01.02 Equipment and materials conforming to any other standard which ensures equal or better quality may be accepted. In such case, copies of the English version of the standard adopted shall be submitted along with the bid.
3.02.00 Annexures 3.02.01 All annexures appended to this specification shall form part of this specification
and supplement the requirements specified herein. 3.02.02 This specification shall be read and construed in conjunction with the
annexures to determine the scope of work. 4.00.00 DESIGN CRITERIA 4.01.00 The equipment will be used in 220KV switchyard of DCR TPP at
Yamunanagar. The electrical system data are as listed in the annexure. 4.02.00 The equipment will be installed outdoor in a hot, humid and tropical atmosphere
with heavy pollution. 4.03.00 All equipment, accessories and wiring shall have tropical protection, involving
special treatment of metal and insulation against fungus, insects and corrosion. 4.04.00 The maximum temperature in any part of the equipment at specified rating shall
not exceed the permissible limits as stipulated in the relevant standards. 4.05.00 The equipment shall be capable of withstanding the dynamic and thermal
stresses of listed short circuit current without any damage or deterioration. 4.06.00 There shall be no radio interference when the equipment is operated at
maximum service voltage. 4.07.00 The safety clearances of all live parts of the equipment shall be as per relevant
standards. 4.08.00 Arresters shall be designed with sufficient cantilever strength to meet with
stress due to wind pressure and short circuit forces arising from rated short time current.
4.09.00 The lightning arrester shall be installed as close to the equipment as possible
and also on the line entrance.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 3 of 11
5.00.00 SPECIFIC REQUIREMENTS 5.01.00 Type and Rating 5.01.01 Lightning arrester shall be station class, heavy duty, metal oxide gapless type
with ratings as detailed in the annexure. 5.01.02 The arrester shall have adequate thermal discharge capacity for severe
switching surges, long duration surges and multiple strokes. 5.02.00 Constructional Features 5.02.01 The arrester shall be single pole, hermetically sealed with non-linear blocks of
sintered metal oxide material so as to obtain a robust construction with excellent electrical, thermal and mechanical characteristics even after repeated operation.
5.02.02 Insulator shall be wet process porcelain, brown glazed and free from
imperfections. All metal parts and hardware shall be hot dip galvanised. 5.02.03 Creepage distance shall correspond to heavily polluted atmosphere. Grading
ring, if required, shall be provided to maintain voltage gradient within permissible limit.
5.02.04 The arrester shall be provided with pressure relief device to prevent shattering
of porcelain in case excessive gas pressure builds up. 5.03.00 Accessories 5.03.01 Lightning arrester shall be furnished complete with insulating base, arrester
disconnector, surge counter, leakage current monitor, insulated Cu. cable and anchoring hardware for mounting on steel structure.
5.03.02 The surge counter shall be suitably enclosed for outdoor duty and be mounted
at a convenient height for reading. Counter terminals shall be such as to permit connections with minimum possible bends. No auxiliary power supply or battery shall be required for operation of counter.
5.03.03 A leakage current detector shall be furnished with the counter as an integral
part. This is for monitoring the leakage to indicate any possible breakdown. Readings of milli-ammeter and counter shall be visible through inspection glass panel.
5.03.04 A suitably sized by-pass shunt along with necessary terminals shall be
furnished for bypassing the discharge counter if required. 5.03.05 Grading ring/corona ring as applicable for the particular voltage class of
arrester shall be provided.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 4 of 11
5.04.00 Terminals 5.04.01 All connection terminals shall be of corrosion resistant material and complete
connection hardware. 5.04.02 All ground terminals shall have provision of connection to G.I. flat of approved
size. 6.00.00 TESTS 6.01.00 Routine Tests 6.01.01 During manufacture and on completion, all equipment shall be subjected to the
Routine Tests as laid down in latest revision of IEC/IS. 6.02.00 Acceptance & Type Tests 6.02.01 Acceptance & type tests to be carried out on lightning arresters according to
latest revision of IEC/IS. Acceptance tests, whenever possible shall be conducted on the complete
arrestor unit. Each metal oxide block of surge arrester shall be tested for the guaranteed
specific energy capability in addition to the routine/acceptance test as per IEC/IS.
6.03.00 Special Tests 6.03.01 Special thermal stability tests to be conducted on lightning arresters according
to IEC, as an acceptance test. 6.03.02 Temperature cycle test on the porcelain housing of the arrester to be
conducted as per IS/IEC. 6.03.03 The artificial pollution test shall be carried out as per applicable standards. 6.03.04 The galvanisation test on metal parts shall be carried out as acceptance test. 6.03.05 The functional (operational) acceptance tests shall be carried out on the surge counter.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 5 of 11
6.04.00 Test Witness Tests shall be performed in presence of Purchaser's representative if so
desired by the Purchaser. The Contractor shall give at least thirty (30) days' advance notice of the date when the tests are to be carried out.
6.05.00 Test Certificates 6.05.01 Certified reports of all the tests carried out at the works shall be furnished in
requisite no. of copies for approval of the Purchaser. 6.05.02 The equipment shall be despatched from works only after receipt of
Purchaser's written approval of the test reports. 6.05.03 Type test certificate of any associated equipment, if so desired by the
Purchaser, shall be furnished. Otherwise, the equipment shall have to be type tested, free of charge, to prove the design.
6.05.04 The test report shall furnish complete identification of the equipment such as
serial no., rating, equipment designation and date of test. 7.00.00 DRAWINGS, DATA & MANUALS 7.01.00 Drawings, Data and Manuals shall be submitted with the bid and in quantities
and procedures as specified in General Conditions of Contract and/or elsewhere in this specification for approval and subsequent distribution after the issue of Letter of Award.
7.02.00 To be submitted with each copy of the Bid. 7.02.01 Typical general arrangement drawing showing constructional features and
disposition of various accessories. 7.02.02 Technical leaflets. 7.02.03 Type test certificate on similar equipment. 7.03.00 To be submitted for Approval and Distribution 7.03.01 Dimensioned general arrangement drawing showing disposition of various
accessories and safety clearances. 7.03.02 Transport/Shipping dimensions with weight. 7.03.03 Foundation plan and loading.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 6 of 11
7.03.04 Assembly drawing for erection at site with part numbers and schedule of
materials. 7.03.05 Characteristic curves for insulation coordination. 7.03.06 Any other relevant drawing or data necessary for satisfactory installation,
operation and maintenance. 7.03.07 Instruction manuals on the equipment and its various accessories. The manual shall clearly indicate method of installation, check-ups and tests to
be carried out before commissioning of the equipment.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 7 of 11
ANNEXURE-A RATINGS & REQUIREMENTS LIGHTNING ARRESTER 1.0 Reference Standard : IEC 99-4 / IS 3070 2.0 Type : Station class, Metal oxide gapless 3.0 Service : Outdoor, heavily polluted atmosphere. 4.0 System Details 4.1 Voltage (Nom/Max.)... KV : 220/245 4.2 Nos. of phases : 3 4.3 Frequency : 50 Hz ±5% 4.4 System Neutral : Effectively earthed 4.5 3-Phase Symmetrical Fault level : 40 KA for 1 second 4.6 Insulation level of the equipment to be protected (lightning)..KVP a) Transformer : ±950 b) CB/Isolator : ±1050 c) Instrument Transformer : ±1050 d) Across open contacts : ±1200 5.0 Arrester Duty 5.1 Type of equipment being protected : Transformer/C.B./Isolator/CT/CVT
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 8 of 11
ANNEXURE-A 6.0 L.A. Rating 6.1 Rated Voltage : 198 KV 6.2 Nominal discharge current : 10 KA 6.3 Long duration Discharge class : Class 3 6.4 Maximum continuous operating voltage (kV rms) : 168 7.0 Insulation Level of Arrester housing 7.1 1-minute 50 Hz withstand (dry & wet) : 380 7.2 Lightning Impulse withstand : 650 8.0 Maximum Lightning Impulse Residual voltage at 8/20 µs current wave (KV peak) 8.1 At 5KA : 450 8.2 At 10 KA : 481 9.0 Switching Impulse Residual Voltage (KVP) 9.1 Maximum at 1 KAp : 409 10.0 High Current impulse withstand value (4/10 micro sec.impulse) .. KA : 100 KA 11.0 Creepage......mm (mimimum) : 6125 12.0 Mounting : Steel Structure
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 9 of 11
ANNEXURE-A
13.0 Pressure relief current : 40KA 14.0 Pressure relief class : A 15.0 Continuous current 15.1 Resistive component of : 1000 continuous current (Max) ...microamp 15.2 Capacitive component of : 1500 continuous current (Max) ...microamp 16.0 Minimum energy handling : 4.5KJ/KV capacity
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 10 of 11
ANNEXURE-B FITTINGS AND ACCESSORIES Each Lightning Arrester shall be furnished complete with the accessories as listed below : 1. Insulating Base with anchoring bolts, nuts etc. for fixing the equipment on to structure. 2. Surge counter with integral leakage current monitor. 3. By-pass shunt with connection provision. 4. Ground terminals. 5. Clamp type bimetallic terminal connectors to suit Twin Moose 6. Grading ring, if necessary. 7. Arrester disconnector. 8. Other standard accessories, which are not specifically mentioned but are usually
provided with Lightning Arrester of such type and rating for efficient and trouble-free operation.
Specification for
220 kV Switchyard HPGC : 2 x 300 MW Deenbandhu Chhotu Ram TPP, Yamuna Nagar
DOCUMENT NO. REL-DCRTP-CEE-201-P-501 E0021 Page 11 of 11
ANNEXURE-C MANDATORY SPARES Bidder shall quote for the mandatory spares indicated below. In case any item is not considered by the bidder, same shall be supplied free of cost, if found applicable during detailed engineering as per approved scheme, equipment requirement, etc
Sl. No. Description Unit Qty.
1.0 Complete surge arrester with insulating base, surge monitor and terminal connector No. 3